- Home
- Modbus register maps
- Vaisala
- HMP Series (HMP1-HMP9) with MMP8 and TMP1 probes (Modbus RTU)
Sensor (humidity and temperature probe) · Modbus register map
Vaisala HMP Series (HMP1-HMP9) with MMP8 and TMP1 probes (Modbus RTU) Modbus register map
Updated 19 November 2026
The HMP Series are Vaisala HUMICAP humidity and temperature probes for industrial use (MMP8 measures moisture in oil, TMP1 is temperature only). Each probe is a Modbus RTU slave on RS-485. This map covers all measured and calculated humidity parameters, measurement and device status, compensation, purge and filtering settings, serial settings and test registers.
This page lists 67 Modbus registers for the Vaisala HMP Series (HMP1-HMP9) with MMP8 and TMP1 probes (Modbus RTU) — 14 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Vaisala’s own free documentation (linked below) and checked against it.
- Manufacturer
- Vaisala
- Model
- HMP Series (HMP1-HMP9) with MMP8 and TMP1 probes (Modbus RTU)
- Equipment type
- Sensor (humidity and temperature probe)
- Registers
- 67 (14 writable)
- Transport
- Modbus RTU
- Default unit ID
- 240
- Default serial
- 19200 baud, 8N2
- Documented addressing
- 1-based (subtract 1 for the wire address)
- 32-bit word order
- CDAB low word first (word-swapped)
- Also known as
- HMP1, HMP3, HMP4, HMP5, HMP7, HMP8, HMP9, TMP1, MMP8
Integration notes: Vaisala HMP Series (HMP1-HMP9) with MMP8 and TMP1 probes (Modbus RTU)
Read holding registers 1-4 for RH and temperature (CDAB floats), plus any calculated parameter you need from 7-66. Write the process pressure to 769 for correct calculated values.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 0 | Relative humidity | FLOAT32 CDAB | Relative humidity | Read |
| HR 2 | Temperature | FLOAT32 CDAB | Temperature | Read |
| HR 8 | Dew/frost point temperature | FLOAT32 CDAB | Dew/frost point | Read |
| HR 522 | Device status | BITMAP16 | Device status | Read |
| HR 515 | Error code | INT32 CDAB | Error code | Read |
| HR 768 | Pressure compensation setpoint | FLOAT32 CDAB | Pressure compensation | Read/write |
Enable Modbus control & writes
The probes talk Modbus RTU over RS-485 as standalone devices; no separate enable step is described. Vaisala Insight PC software exposes the same configuration settings.
Byte order & addressing
- Floats are low word first (CDAB); pick "word-swapped" float in masters that default to high word first.
- Read or write each 32-bit value in one transaction.
Network setup
- Defaults: address 240, 19200 baud, no parity, 8 data bits, 2 stop bits.
- Up to ten probes can share one RS-485 line, each with its own address (register 1537).
- Change serial settings with registers 1538-1540; register 1542 restarts the probe.
Watch out for
- Use the test registers (7937 on) to confirm float format and addressing before trusting readings.
- When condensation prevention warming is on, RH-dependent outputs are unavailable unless you write the real air temperature to register 821.
Vaisala HMP Series (HMP1-HMP9) with MMP8 and TMP1 probes (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 1 | Relative humidity | FLOAT32 | CDAB | %RH | Read | |||
| HR | 2doc 3 | Temperature | FLOAT32 | CDAB | °C | Read | |||
| HR | 6doc 7 | Dew point temperature | FLOAT32 | CDAB | °C | Read | |||
| HR | 8doc 9 | Dew/frost point temperature | FLOAT32 | CDAB | °C | Read | |||
| HR | 10doc 11 | Dew/frost point at 1 atm | FLOAT32 | CDAB | °C | Read | |||
| HR | 12doc 13 | Dew point at 1 atm | FLOAT32 | CDAB | °C | Read | |||
| HR | 14doc 15 | Absolute humidity | FLOAT32 | CDAB | g/m3 | Read | |||
| HR | 16doc 17 | Mixing ratio | FLOAT32 | CDAB | g/kg | Read | |||
| HR | 18doc 19 | Wet-bulb temperature | FLOAT32 | CDAB | °C | Read | |||
| HR | 20doc 21 | Water concentration | FLOAT32 | CDAB | ppmv | Read | |||
| HR | 22doc 23 | Water vapor pressure | FLOAT32 | CDAB | hPa | Read | |||
| HR | 24doc 25 | Water vapor saturation pressure | FLOAT32 | CDAB | hPa | Read | |||
| HR | 26doc 27 | Enthalpy | FLOAT32 | CDAB | kJ/kg | Read | |||
| HR | 28doc 29 | Water activity | FLOAT32 | CDAB | Read | ||||
| HR | 30doc 31 | Dew/frost point depression | FLOAT32 | CDAB | °C | Read | |||
| HR | 32doc 33 | Absolute humidity at NTP | FLOAT32 | CDAB | g/m3 | Read | |||
| HR | 34doc 35 | Water concentration in oil | FLOAT32 | CDAB | ppmw | Read | |||
| HR | 40doc 41 | Relative saturation | FLOAT32 | CDAB | %RS | Read | |||
| HR | 42doc 43 | Water concentration (wet basis) | FLOAT32 | CDAB | vol-% | Read | |||
| HR | 44doc 45 | Relative humidity (dew/frost) | FLOAT32 | CDAB | %RH | Read | |||
| HR | 64doc 65 | Water mass fraction | FLOAT32 | CDAB | ppmw | Read | |||
| HR | 256doc 257 | Relative humidity (integer) | INT16 | × 0.01 | %RH | Read | |||
| HR | 257doc 258 | Temperature (integer) | INT16 | × 0.01 | °C | Read | |||
| HR | 259doc 260 | Dew point (integer) | INT16 | × 0.01 | °C | Read | |||
| HR | 260doc 261 | Dew/frost point (integer) | INT16 | × 0.01 | °C | Read | |||
| HR | 261doc 262 | Dew/frost point at 1 atm (integer) | INT16 | × 0.01 | °C | Read | |||
| HR | 262doc 263 | Dew point at 1 atm (integer) | INT16 | × 0.01 | °C | Read | |||
| HR | 263doc 264 | Absolute humidity (integer) | INT16 | × 0.01 | g/m3 | Read | |||
| HR | 264doc 265 | Mixing ratio (integer) | INT16 | × 0.01 | g/kg | Read | |||
| HR | 265doc 266 | Wet-bulb temperature (integer) | INT16 | × 0.01 | °C | Read | |||
| HR | 266doc 267 | Water concentration (integer) | INT16 | ppmv | Read | ||||
| HR | 267doc 268 | Water vapor pressure (integer) | INT16 | × 0.1 | hPa | Read | |||
| HR | 268doc 269 | Water vapor saturation pressure (integer) | INT16 | × 0.1 | hPa | Read | |||
| HR | 269doc 270 | Enthalpy (integer) | INT16 | × 0.01 | kJ/kg | Read | |||
| HR | 270doc 271 | Water activity (integer) | INT16 | × 0.0001 | Read | ||||
| HR | 271doc 272 | Dew/frost point depression (integer) | INT16 | × 0.1 | °C | Read | |||
| HR | 272doc 273 | Absolute humidity at NTP (integer) | INT16 | × 0.01 | g/m3 | Read | |||
| HR | 273doc 274 | Water concentration in oil (integer) | INT16 | ppmw | Read | ||||
| HR | 276doc 277 | Relative saturation (integer) | INT16 | × 0.01 | %RS | Read | |||
| HR | 277doc 278 | Water concentration wet basis (integer) | INT16 | × 0.01 | vol-% | Read | |||
| HR | 278doc 279 | RH dew/frost (integer) | INT16 | × 0.01 | %RH | Read | |||
| HR | 288doc 289 | Water vapor mass fraction (integer) | INT16 | ppmw | Read | ||||
| HR | 512doc 513 | Error status | UINT16 | Read | 0 = One or more errors active; 1 = No errors | ||||
| HR | 513doc 514 | Online status | UINT16 | Read | 0 = Output locked; 1 = Online data available | ||||
| HR | 515doc 516 | Error code | Sum of active error codes. | INT32 | CDAB | Read | bit 0 = Temperature measurement error; bit 1 = Humidity measurement error; bit 2 = Humidity sensor failure; bit 3 = Capacitance reference error; bit 4 = Ambient temperature out of range; bit 23 = Sensor heater failure (warning) | ||
| HR | 517doc 518 | Security hash | Changes whenever settings or adjustments change. | INT32 | CDAB | Read | |||
| HR | 519doc 520 | RH measurement status | BITMAP16 | Read | bit 0 = Not available; bit 1 = Not reliable; bit 2 = Under range; bit 3 = Over range; bit 5 = Value locked; bit 7 = Sensor failure; bit 8 = Not ready | ||||
| HR | 520doc 521 | T measurement status | Bit list not printed separately; 0 = OK. | INT16 | Read | ||||
| HR | 521doc 522 | Td/f measurement status | Bit list not printed separately; 0 = OK. | INT16 | Read | ||||
| HR | 522doc 523 | Device status | 0 = OK. | BITMAP16 | Read | bit 0 = Critical error, maintenance needed; bit 1 = Error, may recover automatically; bit 2 = Warning; bit 3 = Notification; bit 4 = Calibration mode active | |||
| HR | 768doc 769 | Pressure compensation setpoint | Persistent; default 1013.25 hPa. | FLOAT32 | CDAB | hPa | Read/write | ||
| HR | 772doc 773 | Sensor purge interval | 10-14400 min. | FLOAT32 | CDAB | min | Read/write | ||
| HR | 794doc 795 | Measurement filtering factor | 0-1; 1 = no filtering (default). | FLOAT32 | CDAB | Read/write | |||
| HR | 820doc 821 | Temperature compensation setpoint | When written, used instead of own temperature; cleared at reset. | FLOAT32 | CDAB | °C | Read/write | ||
| HR | 1281doc 1282 | User filtering on/off | Uses the factor in register 795. | UINT16 | Read/write | 0 = Off; 1 = On | |||
| HR | 1282doc 1283 | Interval purge on/off | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 1283doc 1284 | Startup purge on/off | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 1284doc 1285 | Start sensor purge | Write 1 to start; reads 0-100 progress. | INT16 | Read/write | ||||
| HR | 1286doc 1287 | Condensation prevention on/off | Warming needs external T in 821 for RH outputs. | UINT16 | Read/write | 0 = Off; 1 = On | |||
| HR | 1536doc 1537 | Modbus address | 1-247, default 240. | INT16 | Read/write | ||||
| HR | 1537doc 1538 | Bit rate | UINT16 | Read/write | 0 = 300; 1 = 600; 2 = 1200; 3 = 2400; 4 = 4800; 5 = 9600; 6 = 19200; 7 = 38400; 8 = 57600; 9 = 115200 | ||||
| HR | 1538doc 1539 | Parity, data, stop bits | Default 1 (None, 8, 2). | UINT16 | Read/write | 0 = None, 8, 1; 1 = None, 8, 2; 2 = Even, 8, 1; 3 = Even, 8, 2; 4 = Odd, 8, 1; 5 = Odd, 8, 2 | |||
| HR | 1539doc 1540 | Response delay | 0-1000 ms. | INT16 | ms | Read/write | |||
| HR | 1541doc 1542 | Restart device | Write 1 to restart. | INT16 | Write | ||||
| HR | 7936doc 7937 | Signed integer test | Always reads -12345. | INT16 | Read | ||||
| HR | 7937doc 7938 | Floating point test | Always reads -123.45. | FLOAT32 | CDAB | Read | |||
| HR | 7939doc 7940 | Text string test | Reads the text "-123.45". | STRING[8] | Read |
Notes on this map
- All registers are holding registers: read with function 03, write with function 16.
- 32-bit floats and 32-bit integers put the least significant word at the listed register (CDAB). The guide's data-encoding section covers both formats and its worked read and write examples confirm the order.
- Unavailable data reads as quiet NaN (float) or 0x8000 (16-bit integer) rather than an exception.
- Which parameters return data depends on the probe: TMP1 is a temperature probe, and MMP8 measures moisture in oil (water activity and ppm).
- Integer registers use the scale listed per register (for example raw x 0.01 for RH and temperature).
- Register 513 reads 0 when an error is active and 1 when there is none, as printed in the guide.
- Error code register 516 is listed as a 32-bit signed integer; it is a sum of the error bits shown.
- The T and Td/f measurement status registers (521, 522) share a table cell with the RH status bit list in the guide, so their bits are not repeated here.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Vaisala HMP Series (HMP1-HMP9) with MMP8 and TMP1 probes (Modbus RTU)
What Modbus registers does the Vaisala HMP Series (HMP1-HMP9) with MMP8 and TMP1 probes (Modbus RTU) have?
This map lists 67 registers: 67 holding registers. 14 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Vaisala HMP Series (HMP1-HMP9) with MMP8 and TMP1 probes (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide numbers registers in decimal starting at 1 and also prints the 0-based hex address used in the request; register number 1 is address 0x0000 on the wire.
What byte order does the Vaisala HMP Series (HMP1-HMP9) with MMP8 and TMP1 probes (Modbus RTU) use for 32-bit values?
Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Vaisala HMP Series (HMP1-HMP9) with MMP8 and TMP1 probes (Modbus RTU)?
Start with HR 0 Relative humidity (Relative humidity); HR 2 Temperature (Temperature); HR 8 Dew/frost point temperature (Dew/frost point); HR 522 Device status (Device status); HR 515 Error code (Error code); HR 768 Pressure compensation setpoint (Pressure compensation).
How do I enable Modbus control of the Vaisala HMP Series (HMP1-HMP9) with MMP8 and TMP1 probes (Modbus RTU)?
The probes talk Modbus RTU over RS-485 as standalone devices; no separate enable step is described. Vaisala Insight PC software exposes the same configuration settings.
Where is the official Vaisala HMP Series (HMP1-HMP9) with MMP8 and TMP1 probes (Modbus RTU) Modbus documentation?
The source is HMP Series with MMP8 and TMP1 User Guide (M212022EN-M), revision 2025-08, published free by Vaisala at https://docs.vaisala.com/r/M212022EN-M/en-US.
More Vaisala Modbus register maps
- Sensor (dew point probe)
Vaisala DMP Series dew point probes (DMP5, DMP6, DMP7, DMP8) (Modbus RTU)
Vaisala DMP5, DMP6, DMP7 and DMP8 dew point and temperature probes, Modbus RTU interface (user guide M212357EN-F).
Also known as: DMP5, DMP6, DMP7, DMP8, DRYCAP DMP series - Sensor (dew point transmitter)
Vaisala DMT143 miniature dew point transmitter (Modbus RTU)
DMT143 dew point transmitters ordered with the Modbus RTU option (user guide M211435EN-L).
Also known as: DMT143, DRYCAP DMT143 - Sensor (dew point transmitter)
Vaisala DMT153 dew point transmitter (Modbus RTU)
DMT153 trace-moisture dew point transmitter, Modbus RTU interface (user guide M213149EN-B).
Also known as: DMT153, DRYCAP DMT153 - Sensor (CO2 duct transmitter)
Vaisala GMD110 duct CO2 transmitter (Modbus RTU)
GMD110 duct-mount CO2 transmitter, Modbus RTU interface (user guide M212885EN-B).
Also known as: GMD110, CARBOCAP GMD110 - Sensor (CO2 probe)
Vaisala GMP251 CARBOCAP carbon dioxide probe (Modbus RTU)
GMP251 probe in Modbus RTU mode, user guide M211799EN-N.
Also known as: GMP251, CARBOCAP GMP251, Vaisala GMP251 - Sensor (CO2 probe)
Vaisala GMP252 CARBOCAP carbon dioxide probe (Modbus RTU)
GMP252 probe in Modbus RTU mode, user guide M211897EN-G.
Also known as: GMP252, CARBOCAP GMP252, Vaisala GMP252 - Sensor (CO2 wall transmitter)
Vaisala GMW87 CO2 and temperature wall transmitter (Modbus RTU)
GMW87, the RS-485 Modbus RTU model of the GMW80 series (user guide M211748EN-H).
Also known as: GMW87, GMW80 series Modbus - Sensor (humidity and temperature transmitter)
Vaisala HMDW110 series humidity and temperature transmitters with TMI110 (Modbus RTU)
HMDW110-series duct, wall and outdoor transmitters and TMI110 ordered with the Modbus RTU option (user guide M211726EN-L).
Also known as: HMD110, HMD112, HMW110, HMW112, HMW112D, HMS110, HMS112, TMW110, TMW112, TMW112D, TMI110 - Sensor (humidity and temperature module)
Vaisala HMM170 humidity module (Modbus RTU)
HMM170 OEM humidity and temperature module with the Modbus RTU interface (user guide M212259EN-D).
Also known as: HMM170, HUMICAP HMM170 - Sensor (humidity and temperature probe)
Vaisala HMP60 / HMP110 series humidity and temperature probes (Modbus RTU)
HMP60/HMP110-series probes ordered with the Modbus RTU option (user guide M211060EN-N).
Also known as: HMP110, HMP113, HMP115, TMP115, HMP60, HMP63, HUMICAP HMP110, HMP110T, HMP63T, HMP115T - Sensor (humidity and temperature transmitter)
Vaisala HMW87 / HMW87D wall humidity and temperature transmitters (Modbus RTU)
HMW87 and HMW87D wall transmitters of the HMDW80 series (the Modbus models in user guide M211510EN-J).
Also known as: HMW87, HMW87D, HMDW80 Modbus - Sensor (H2O2 probe)
Vaisala HPP271 hydrogen peroxide probe (Modbus RTU)
HPP271 vaporized hydrogen peroxide probe, Modbus RTU interface (user guide M211888EN-E).
Also known as: HPP271, PEROXCAP HPP271 - Sensor (H2O2 / humidity probe)
Vaisala HPP272 hydrogen peroxide, humidity and temperature probe (Modbus RTU)
HPP272 vaporized hydrogen peroxide probe, Modbus RTU interface (user guide M211972EN-G).
Also known as: HPP272, PEROXCAP HPP272 - Sensor transmitter (host for Vaisala probes)
Vaisala Indigo510 / Indigo520 transmitters (Modbus TCP)
Indigo510 and Indigo520 transmitter registers (unit ID 240) over Modbus TCP (user guide M212287EN-AJ).
Also known as: Indigo510, Indigo520, Indigo500 series - Sensor (transformer oil monitor)
Vaisala MHT410 moisture, hydrogen and temperature transmitter for transformer oil (Modbus RTU)
MHT410 transformer oil monitor, Modbus RTU on the RS-485 screw terminals (user guide M211737EN-J).
Also known as: MHT410 - Sensor (moisture in oil transmitter)
Vaisala MMT143 moisture in oil transmitter (Modbus RTU)
MMT143 moisture-in-oil transmitter ordered with the Modbus RTU option (user guide M213308EN-B).
Also known as: MMT143 - Sensor (HVAC humidity, temperature and CO2 transmitter)
Vaisala Origo10 transmitters for HVAC (Origo10A, Modbus RTU)
Origo10A duct and wall transmitters ordered with the Modbus RTU output (user guide M213293EN-B). Origo10L has no Modbus.
Also known as: Origo10, Origo10A, Origo 10, Vaisala Origo10 duct transmitter, Vaisala Origo10 wall transmitter - Sensor (precipitation)
Vaisala RM60 PRECICAP radar precipitation sensor (Modbus RTU)
RM60 sensors ordered with communication option 1 (RS-485 Modbus RTU) or switched to Modbus, per user guide M213218EN-B.
Also known as: RM60, PRECICAP RM60, Vaisala RM60 - Sensor (ultrasonic wind)
Vaisala WM80 ultrasonic wind sensor (Modbus RTU)
WM80 sensors with RS-485 in Modbus mode (e.g. ordering option C), per user guide M212995EN-F.
Also known as: WM80, Vaisala WM80, Ultrasonic Wind Sensor WM80 - Sensor (weather transmitter)
Vaisala WXT530 series weather transmitters (Modbus RTU)
WXT531-WXT536 weather transmitters with firmware 3.85 or later in Modbus RTU mode (user guide M211840EN-G).
Also known as: WXT531, WXT532, WXT533, WXT534, WXT535, WXT536 - Sensor (humidity and temperature probe)
Vaisala XMP10 humidity and temperature probe (Modbus RTU)
XMP10 probes ordered with (or switched to) Modbus RTU output, user guide M213279EN-A.
Also known as: XMP10, HUMICAP XMP10, Vaisala XMP10 - Sensor (CO2/humidity wall transmitter)
Vaisala XMW85 CO2, humidity and temperature wall transmitter (Modbus RTU)
XMW85 wall transmitter, Modbus RTU interface (user guide M213257EN-B).
Also known as: XMW85
Other valves, actuators & sensors register maps
- Sensor
VTS RH+T-SENS-D-MODRTU humidity and temperature transducer
VTS RH+T-SENS-D-MODRTU duct humidity and temperature transducer (Sensirion SHT31-DIS-B), manual ver. 2.0 (11.2021).
Also known as: RH&T-SENS-D-MODRTU, VTS duct humidity sensor - Sensor (duct averaging temperature)
ACI (Automation Components Inc.) Averaging Series BACnet/Modbus duct averaging temperature sensor
ACI Averaging Series copper and flexible duct averaging temperature sensors with the BACnet MS/TP / Modbus RTU interface (guide I0000932).
Also known as: Copper Averaging, Flexible Averaging, Averaging Series BACnet Modbus - Actuator / valve (damper and valve actuator)
Belimo Air/water actuators with Modbus RTU (..24A-MOD)
Belimo ..M(C)24A-MOD, ..R24A-MOD, ..V(K)24A-MOD, ..F24A-MOD, ..RF24A-MOD and ..H24A-MOD air/water actuators, per Modbus interface description edition 2026-05 / V3.08.
Also known as: LM24A-MOD, NM24A-MOD, SM24A-MOD, GM24A-MOD, LMC24A-MOD, NMC24A-MOD, NR24A-MOD, LR24A-MOD, NV24A-MOD, NVK24A-MOD, LF24A-MOD, NF24A-MOD, NRF24A-MOD, LRF24A-MOD, LH24A-MOD, SH24A-MOD - Sensor
Johnson Controls GS3000 indoor Modbus carbon monoxide transmitter
Johnson Controls GS3000 / GS3001 electrochemical CO transmitters with RS-485 Modbus RTU, per installation guide 24-11484-00021 (2020-10-01).
Also known as: GS3000, GS3001, 24-11484-00021 - Sensor (load-cell weight transmitter)
Laumas TLS weight transmitter with analog output (Modbus RTU)
Laumas TLS weight transmitter / indicator with RS-485, installation and user manual version 1.19.
Also known as: TLS, TLS 4-20mA, TLS 0-10V, CASTLTASTATEX - Sensor (load cell / strain gauge converter)
Seneca R-SG3 Ethernet load cell converter
R-SG3 in the Series R I/O manual MI-00604-29-EN.
Also known as: RSG3, R-SG3, Seneca R series strain gauge
All valves, actuators & sensors Modbus register maps →
Source: HMP Series with MMP8 and TMP1 User Guide · M212022EN-M · rev. 2025-08. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.