Vaisala Indigo510 / Indigo520 transmitters (Modbus TCP) Modbus register map

Updated 19 November 2026

Short answer

Indigo510 and Indigo520 are Vaisala transmitters that host one or two smart probes (humidity, CO2, dew point, H2O2 and others) and expose them over Modbus TCP, analog outputs and relays. This map covers the transmitter itself at unit ID 240: optional barometer and analog input, analog output and relay configuration, network and clock settings.

This page lists 65 Modbus registers for the Vaisala Indigo510 / Indigo520 transmitters (Modbus TCP) — 49 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Vaisala’s own free documentation (linked below) and checked against it.

Manufacturer
Vaisala
Model
Indigo510 / Indigo520 transmitters (Modbus TCP)
Equipment type
Sensor transmitter (host for Vaisala probes)
Registers
65 (49 writable)
Transport
Modbus TCP
Default unit ID
240
TCP port
502
Documented addressing
1-based (subtract 1 for the wire address)
32-bit word order
CDAB low word first (word-swapped)
Also known as
Indigo510, Indigo520, Indigo500 series
Source document
Indigo510, Indigo520 User Guide · M212287EN-AJ · rev. 2026-10
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Vaisala Indigo510 / Indigo520 transmitters (Modbus TCP)

Integration in brief

Enable Modbus TCP read (and write if needed) on the transmitter, then poll unit ID 240 for these registers and 241/242 for the connected probes.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 42Barometric pressureFLOAT32 CDABBarometric pressure (if fitted)Read
HR 54Analog input level (validated)FLOAT32 CDABValidated analog inputRead
HR 1808AOUT1 output levelFLOAT32 CDABAOUT1 output levelRead
HR 3081Relay 1 output stateINT16Relay 1 stateRead
HR 514Barometer error flagsBITMAP16Barometer errorsRead

Enable Modbus control & writes

Turn on Modbus TCP/IP read and, if needed, write in the touchscreen or web interface (both are off by default).

Byte order & addressing

Network setup

Watch out for

Vaisala Indigo510 / Indigo520 transmitters (Modbus TCP) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

65 of 65 shown
Vaisala Indigo510 / Indigo520 transmitters (Modbus TCP) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR42doc 43Barometric pressureOptional barometer module.FLOAT32CDABhPaRead
HR48doc 49Height-corrected pressureFLOAT32CDABhPaRead
HR52doc 53Analog input level (actual)FLOAT32CDABmARead
HR54doc 55Analog input level (validated)NaN outside 3.8-20.5 mA.FLOAT32CDABmARead
HR277doc 278Barometric pressure (integer)INT16× 0.1hPaRead
HR280doc 281Height-corrected pressure (integer)INT16× 0.1hPaRead
HR282doc 283Analog input level (integer)INT16× 0.001mARead
HR283doc 284Analog input validated (integer)-32768 outside 3.8-20.5 mA.INT16× 0.001mARead
HR513doc 514Barometer status0 = OK.BITMAP16Readbit 5 = Value locked; bit 7 = Sensor failure
HR514doc 515Barometer error flags0 = OK; flags add up.BITMAP16Readbit 2 = Pressure out of range; bit 3 = Pressure measurement error; bit 4 = Manufactory error; bit 5 = Module type not defined; bit 8 = F measurement; bit 10 = Temperature measurement; bit 11 = Info 2nd bank checksum; bit 12 = Info 1st bank checksum; bit 13 = Checksum error of current settings; bit 14 = User setting bank checksum; bit 15 = Factory bank setting checksum
HR784doc 785HCP heightHeight correction, -30...+30 m.FLOAT32CDABmRead/write
HR1024doc 1025Date/time modeINT16Read/write1 = NTP; 2 = Manual
HR1058doc 1059YearINT16Read/write
HR1059doc 1060MonthINT16Read/write
HR1060doc 1061DayINT16Read/write
HR1061doc 1062HourINT16Read/write
HR1062doc 1063MinuteINT16Read/write
HR1063doc 1064SecondINT16Read/write
HR1536doc 1537IP setting typeINT16Read/write1 = DHCP; 2 = Static IP
HR1537doc 1538IP address15-character ASCII text.STRING[16]Read/write
HR1545doc 1546Gateway15-character ASCII text.STRING[16]Read/write
HR1553doc 1554Subnet mask15-character ASCII text.STRING[16]Read/write
HR1577doc 1578Apply network settingsWrite 1 to apply.INT16Write
HR1792doc 1793AOUT1 output modeINT16Read/write0 = Off; 1 = 0-20 mA; 2 = 4-20 mA; 3 = 0-1 V; 4 = 0-5 V; 5 = 0-10 V
HR1793doc 1794AOUT1 output parameterRegister (unit 240 space) that drives the output.INT16Read/write
HR1794doc 1795AOUT1 scale low endNaN if not set.FLOAT32CDABRead/write
HR1796doc 1797AOUT1 scale high endNaN if not set.FLOAT32CDABRead/write
HR1798doc 1799AOUT1 error outputNaN if not set.FLOAT32CDABRead/write
HR1808doc 1809AOUT1 output levelFLOAT32CDABRead
HR1810doc 1811AOUT1 force output levelNaN = not forced.FLOAT32CDABRead/write
HR2048doc 2049AOUT2 output modeINT16Read/write0 = Off; 1 = 0-20 mA; 2 = 4-20 mA; 3 = 0-1 V; 4 = 0-5 V; 5 = 0-10 V
HR2049doc 2050AOUT2 output parameterRegister (unit 240 space) that drives the output.INT16Read/write
HR2050doc 2051AOUT2 scale low endNaN if not set.FLOAT32CDABRead/write
HR2052doc 2053AOUT2 scale high endNaN if not set.FLOAT32CDABRead/write
HR2054doc 2055AOUT2 error outputNaN if not set.FLOAT32CDABRead/write
HR2064doc 2065AOUT2 output levelFLOAT32CDABRead
HR2066doc 2067AOUT2 force output levelNaN = not forced.FLOAT32CDABRead/write
HR2304doc 2305AOUT3 output modeINT16Read/write0 = Off; 1 = 0-20 mA; 2 = 4-20 mA; 3 = 0-1 V; 4 = 0-5 V; 5 = 0-10 V
HR2305doc 2306AOUT3 output parameterRegister (unit 240 space) that drives the output.INT16Read/write
HR2306doc 2307AOUT3 scale low endNaN if not set.FLOAT32CDABRead/write
HR2308doc 2309AOUT3 scale high endNaN if not set.FLOAT32CDABRead/write
HR2310doc 2311AOUT3 error outputNaN if not set.FLOAT32CDABRead/write
HR2320doc 2321AOUT3 output levelFLOAT32CDABRead
HR2322doc 2323AOUT3 force output levelNaN = not forced.FLOAT32CDABRead/write
HR2560doc 2561AOUT4 output modeINT16Read/write0 = Off; 1 = 0-20 mA; 2 = 4-20 mA; 3 = 0-1 V; 4 = 0-5 V; 5 = 0-10 V
HR2561doc 2562AOUT4 output parameterRegister (unit 240 space) that drives the output.INT16Read/write
HR2562doc 2563AOUT4 scale low endNaN if not set.FLOAT32CDABRead/write
HR2564doc 2565AOUT4 scale high endNaN if not set.FLOAT32CDABRead/write
HR2566doc 2567AOUT4 error outputNaN if not set.FLOAT32CDABRead/write
HR2576doc 2577AOUT4 output levelFLOAT32CDABRead
HR2578doc 2579AOUT4 force output levelNaN = not forced.FLOAT32CDABRead/write
HR3072doc 3073Relay 1 modeINT16Read/write0 = Off; 1 = Above setpoint; 2 = Below setpoint
HR3073doc 3074Relay 1 parameterRegister (unit 240 space) that drives the relay.INT16Read/write
HR3074doc 3075Relay 1 active aboveNaN if not set.FLOAT32CDABRead/write
HR3076doc 3077Relay 1 active belowNaN if not set.FLOAT32CDABRead/write
HR3078doc 3079Relay 1 hysteresisNaN if not set.FLOAT32CDABRead/write
HR3081doc 3082Relay 1 output stateINT16Read0 = Disabled; 1 = Active; 2 = Inactive
HR3082doc 3083Relay 1 force outputINT16Read/write0 = Normal mode; 1 = Force active; 2 = Force inactive
HR3328doc 3329Relay 2 modeINT16Read/write0 = Off; 1 = Above setpoint; 2 = Below setpoint
HR3329doc 3330Relay 2 parameterRegister (unit 240 space) that drives the relay.INT16Read/write
HR3330doc 3331Relay 2 active aboveNaN if not set.FLOAT32CDABRead/write
HR3332doc 3333Relay 2 active belowNaN if not set.FLOAT32CDABRead/write
HR3334doc 3335Relay 2 hysteresisNaN if not set.FLOAT32CDABRead/write
HR3337doc 3338Relay 2 output stateINT16Read0 = Disabled; 1 = Active; 2 = Inactive
HR3338doc 3339Relay 2 force outputINT16Read/write0 = Normal mode; 1 = Force active; 2 = Force inactive

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Vaisala Indigo510 / Indigo520 transmitters (Modbus TCP)

What Modbus registers does the Vaisala Indigo510 / Indigo520 transmitters (Modbus TCP) have?

This map lists 65 registers: 65 holding registers. 49 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Vaisala Indigo510 / Indigo520 transmitters (Modbus TCP) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide numbers registers in decimal starting at 1 and also prints the 0-based hex address used in the request; register number 1 is address 0x0000 on the wire.

What byte order does the Vaisala Indigo510 / Indigo520 transmitters (Modbus TCP) use for 32-bit values?

Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Vaisala Indigo510 / Indigo520 transmitters (Modbus TCP)?

Start with HR 42 Barometric pressure (Barometric pressure (if fitted)); HR 54 Analog input level (validated) (Validated analog input); HR 1808 AOUT1 output level (AOUT1 output level); HR 3081 Relay 1 output state (Relay 1 state); HR 514 Barometer error flags (Barometer errors).

How do I enable Modbus control of the Vaisala Indigo510 / Indigo520 transmitters (Modbus TCP)?

Turn on Modbus TCP/IP read and, if needed, write in the touchscreen or web interface (both are off by default).

Where is the official Vaisala Indigo510 / Indigo520 transmitters (Modbus TCP) Modbus documentation?