Sensor transmitter (host for Vaisala probes) · Modbus register map
Vaisala Indigo510 / Indigo520 transmitters (Modbus TCP) Modbus register map
Updated 19 November 2026
Indigo510 and Indigo520 are Vaisala transmitters that host one or two smart probes (humidity, CO2, dew point, H2O2 and others) and expose them over Modbus TCP, analog outputs and relays. This map covers the transmitter itself at unit ID 240: optional barometer and analog input, analog output and relay configuration, network and clock settings.
This page lists 65 Modbus registers for the Vaisala Indigo510 / Indigo520 transmitters (Modbus TCP) — 49 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Vaisala’s own free documentation (linked below) and checked against it.
- Manufacturer
- Vaisala
- Model
- Indigo510 / Indigo520 transmitters (Modbus TCP)
- Equipment type
- Sensor transmitter (host for Vaisala probes)
- Registers
- 65 (49 writable)
- Transport
- Modbus TCP
- Default unit ID
- 240
- TCP port
- 502
- Documented addressing
- 1-based (subtract 1 for the wire address)
- 32-bit word order
- CDAB low word first (word-swapped)
- Also known as
- Indigo510, Indigo520, Indigo500 series
Integration notes: Vaisala Indigo510 / Indigo520 transmitters (Modbus TCP)
Enable Modbus TCP read (and write if needed) on the transmitter, then poll unit ID 240 for these registers and 241/242 for the connected probes.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 42 | Barometric pressure | FLOAT32 CDAB | Barometric pressure (if fitted) | Read |
| HR 54 | Analog input level (validated) | FLOAT32 CDAB | Validated analog input | Read |
| HR 1808 | AOUT1 output level | FLOAT32 CDAB | AOUT1 output level | Read |
| HR 3081 | Relay 1 output state | INT16 | Relay 1 state | Read |
| HR 514 | Barometer error flags | BITMAP16 | Barometer errors | Read |
Enable Modbus control & writes
Turn on Modbus TCP/IP read and, if needed, write in the touchscreen or web interface (both are off by default).
Byte order & addressing
- Floats are low word first (CDAB); pick "word-swapped" float in masters that default to high word first.
- Read or write each 32-bit value in one transaction.
Network setup
- Unit ID 240 = transmitter, 241 = probe on terminal 1, 242 = probe on terminal 2; Modbus TCP port 502.
- Set DHCP or a static IP with registers 1537-1561 (write 1 to 1578 to apply) or on the touchscreen/web interface.
Watch out for
- Use only one Modbus TCP client at a time and one transaction at a time; nested requests are not handled reliably.
- Response time is about 2 s; raise the client timeout if requests time out.
- Vaisala warns not to leave Modbus write enabled on an open network; turn it off when not needed.
Vaisala Indigo510 / Indigo520 transmitters (Modbus TCP) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 42doc 43 | Barometric pressure | Optional barometer module. | FLOAT32 | CDAB | hPa | Read | ||
| HR | 48doc 49 | Height-corrected pressure | FLOAT32 | CDAB | hPa | Read | |||
| HR | 52doc 53 | Analog input level (actual) | FLOAT32 | CDAB | mA | Read | |||
| HR | 54doc 55 | Analog input level (validated) | NaN outside 3.8-20.5 mA. | FLOAT32 | CDAB | mA | Read | ||
| HR | 277doc 278 | Barometric pressure (integer) | INT16 | × 0.1 | hPa | Read | |||
| HR | 280doc 281 | Height-corrected pressure (integer) | INT16 | × 0.1 | hPa | Read | |||
| HR | 282doc 283 | Analog input level (integer) | INT16 | × 0.001 | mA | Read | |||
| HR | 283doc 284 | Analog input validated (integer) | -32768 outside 3.8-20.5 mA. | INT16 | × 0.001 | mA | Read | ||
| HR | 513doc 514 | Barometer status | 0 = OK. | BITMAP16 | Read | bit 5 = Value locked; bit 7 = Sensor failure | |||
| HR | 514doc 515 | Barometer error flags | 0 = OK; flags add up. | BITMAP16 | Read | bit 2 = Pressure out of range; bit 3 = Pressure measurement error; bit 4 = Manufactory error; bit 5 = Module type not defined; bit 8 = F measurement; bit 10 = Temperature measurement; bit 11 = Info 2nd bank checksum; bit 12 = Info 1st bank checksum; bit 13 = Checksum error of current settings; bit 14 = User setting bank checksum; bit 15 = Factory bank setting checksum | |||
| HR | 784doc 785 | HCP height | Height correction, -30...+30 m. | FLOAT32 | CDAB | m | Read/write | ||
| HR | 1024doc 1025 | Date/time mode | INT16 | Read/write | 1 = NTP; 2 = Manual | ||||
| HR | 1058doc 1059 | Year | INT16 | Read/write | |||||
| HR | 1059doc 1060 | Month | INT16 | Read/write | |||||
| HR | 1060doc 1061 | Day | INT16 | Read/write | |||||
| HR | 1061doc 1062 | Hour | INT16 | Read/write | |||||
| HR | 1062doc 1063 | Minute | INT16 | Read/write | |||||
| HR | 1063doc 1064 | Second | INT16 | Read/write | |||||
| HR | 1536doc 1537 | IP setting type | INT16 | Read/write | 1 = DHCP; 2 = Static IP | ||||
| HR | 1537doc 1538 | IP address | 15-character ASCII text. | STRING[16] | Read/write | ||||
| HR | 1545doc 1546 | Gateway | 15-character ASCII text. | STRING[16] | Read/write | ||||
| HR | 1553doc 1554 | Subnet mask | 15-character ASCII text. | STRING[16] | Read/write | ||||
| HR | 1577doc 1578 | Apply network settings | Write 1 to apply. | INT16 | Write | ||||
| HR | 1792doc 1793 | AOUT1 output mode | INT16 | Read/write | 0 = Off; 1 = 0-20 mA; 2 = 4-20 mA; 3 = 0-1 V; 4 = 0-5 V; 5 = 0-10 V | ||||
| HR | 1793doc 1794 | AOUT1 output parameter | Register (unit 240 space) that drives the output. | INT16 | Read/write | ||||
| HR | 1794doc 1795 | AOUT1 scale low end | NaN if not set. | FLOAT32 | CDAB | Read/write | |||
| HR | 1796doc 1797 | AOUT1 scale high end | NaN if not set. | FLOAT32 | CDAB | Read/write | |||
| HR | 1798doc 1799 | AOUT1 error output | NaN if not set. | FLOAT32 | CDAB | Read/write | |||
| HR | 1808doc 1809 | AOUT1 output level | FLOAT32 | CDAB | Read | ||||
| HR | 1810doc 1811 | AOUT1 force output level | NaN = not forced. | FLOAT32 | CDAB | Read/write | |||
| HR | 2048doc 2049 | AOUT2 output mode | INT16 | Read/write | 0 = Off; 1 = 0-20 mA; 2 = 4-20 mA; 3 = 0-1 V; 4 = 0-5 V; 5 = 0-10 V | ||||
| HR | 2049doc 2050 | AOUT2 output parameter | Register (unit 240 space) that drives the output. | INT16 | Read/write | ||||
| HR | 2050doc 2051 | AOUT2 scale low end | NaN if not set. | FLOAT32 | CDAB | Read/write | |||
| HR | 2052doc 2053 | AOUT2 scale high end | NaN if not set. | FLOAT32 | CDAB | Read/write | |||
| HR | 2054doc 2055 | AOUT2 error output | NaN if not set. | FLOAT32 | CDAB | Read/write | |||
| HR | 2064doc 2065 | AOUT2 output level | FLOAT32 | CDAB | Read | ||||
| HR | 2066doc 2067 | AOUT2 force output level | NaN = not forced. | FLOAT32 | CDAB | Read/write | |||
| HR | 2304doc 2305 | AOUT3 output mode | INT16 | Read/write | 0 = Off; 1 = 0-20 mA; 2 = 4-20 mA; 3 = 0-1 V; 4 = 0-5 V; 5 = 0-10 V | ||||
| HR | 2305doc 2306 | AOUT3 output parameter | Register (unit 240 space) that drives the output. | INT16 | Read/write | ||||
| HR | 2306doc 2307 | AOUT3 scale low end | NaN if not set. | FLOAT32 | CDAB | Read/write | |||
| HR | 2308doc 2309 | AOUT3 scale high end | NaN if not set. | FLOAT32 | CDAB | Read/write | |||
| HR | 2310doc 2311 | AOUT3 error output | NaN if not set. | FLOAT32 | CDAB | Read/write | |||
| HR | 2320doc 2321 | AOUT3 output level | FLOAT32 | CDAB | Read | ||||
| HR | 2322doc 2323 | AOUT3 force output level | NaN = not forced. | FLOAT32 | CDAB | Read/write | |||
| HR | 2560doc 2561 | AOUT4 output mode | INT16 | Read/write | 0 = Off; 1 = 0-20 mA; 2 = 4-20 mA; 3 = 0-1 V; 4 = 0-5 V; 5 = 0-10 V | ||||
| HR | 2561doc 2562 | AOUT4 output parameter | Register (unit 240 space) that drives the output. | INT16 | Read/write | ||||
| HR | 2562doc 2563 | AOUT4 scale low end | NaN if not set. | FLOAT32 | CDAB | Read/write | |||
| HR | 2564doc 2565 | AOUT4 scale high end | NaN if not set. | FLOAT32 | CDAB | Read/write | |||
| HR | 2566doc 2567 | AOUT4 error output | NaN if not set. | FLOAT32 | CDAB | Read/write | |||
| HR | 2576doc 2577 | AOUT4 output level | FLOAT32 | CDAB | Read | ||||
| HR | 2578doc 2579 | AOUT4 force output level | NaN = not forced. | FLOAT32 | CDAB | Read/write | |||
| HR | 3072doc 3073 | Relay 1 mode | INT16 | Read/write | 0 = Off; 1 = Above setpoint; 2 = Below setpoint | ||||
| HR | 3073doc 3074 | Relay 1 parameter | Register (unit 240 space) that drives the relay. | INT16 | Read/write | ||||
| HR | 3074doc 3075 | Relay 1 active above | NaN if not set. | FLOAT32 | CDAB | Read/write | |||
| HR | 3076doc 3077 | Relay 1 active below | NaN if not set. | FLOAT32 | CDAB | Read/write | |||
| HR | 3078doc 3079 | Relay 1 hysteresis | NaN if not set. | FLOAT32 | CDAB | Read/write | |||
| HR | 3081doc 3082 | Relay 1 output state | INT16 | Read | 0 = Disabled; 1 = Active; 2 = Inactive | ||||
| HR | 3082doc 3083 | Relay 1 force output | INT16 | Read/write | 0 = Normal mode; 1 = Force active; 2 = Force inactive | ||||
| HR | 3328doc 3329 | Relay 2 mode | INT16 | Read/write | 0 = Off; 1 = Above setpoint; 2 = Below setpoint | ||||
| HR | 3329doc 3330 | Relay 2 parameter | Register (unit 240 space) that drives the relay. | INT16 | Read/write | ||||
| HR | 3330doc 3331 | Relay 2 active above | NaN if not set. | FLOAT32 | CDAB | Read/write | |||
| HR | 3332doc 3333 | Relay 2 active below | NaN if not set. | FLOAT32 | CDAB | Read/write | |||
| HR | 3334doc 3335 | Relay 2 hysteresis | NaN if not set. | FLOAT32 | CDAB | Read/write | |||
| HR | 3337doc 3338 | Relay 2 output state | INT16 | Read | 0 = Disabled; 1 = Active; 2 = Inactive | ||||
| HR | 3338doc 3339 | Relay 2 force output | INT16 | Read/write | 0 = Normal mode; 1 = Force active; 2 = Force inactive |
Notes on this map
- Transmitter registers are holding registers on unit ID 240: read with function 03, write with function 16.
- 32-bit floats put the least significant word at the listed register (CDAB). The guide states this, and its worked example (30.56 %RH read from a probe at unit ID 241) confirms it.
- Unavailable data reads as quiet NaN (float) or 0x8000 (16-bit integer) rather than an exception.
- Probe readings are not in this map: read the probe on unit ID 241 (terminal 1) or 242 (terminal 2) using that probe's own register map.
- Modbus TCP read and write access are both disabled by default and must be enabled on the touchscreen or web interface.
- Indigo510 has 2 analog outputs; Indigo520 has 4 analog outputs, an analog input and 2 relays (the analog input, outputs and relays are not available on PoE-powered Indigo520 units). Registers for hardware a unit lacks are not useful on it.
- Left out: analog output clipping limits, NTP address and DNS server strings, the time-zone enum (91 values) and the test registers.
- Network strings occupy 8 registers for up to 15 characters.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Vaisala Indigo510 / Indigo520 transmitters (Modbus TCP)
What Modbus registers does the Vaisala Indigo510 / Indigo520 transmitters (Modbus TCP) have?
This map lists 65 registers: 65 holding registers. 49 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Vaisala Indigo510 / Indigo520 transmitters (Modbus TCP) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide numbers registers in decimal starting at 1 and also prints the 0-based hex address used in the request; register number 1 is address 0x0000 on the wire.
What byte order does the Vaisala Indigo510 / Indigo520 transmitters (Modbus TCP) use for 32-bit values?
Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Vaisala Indigo510 / Indigo520 transmitters (Modbus TCP)?
Start with HR 42 Barometric pressure (Barometric pressure (if fitted)); HR 54 Analog input level (validated) (Validated analog input); HR 1808 AOUT1 output level (AOUT1 output level); HR 3081 Relay 1 output state (Relay 1 state); HR 514 Barometer error flags (Barometer errors).
How do I enable Modbus control of the Vaisala Indigo510 / Indigo520 transmitters (Modbus TCP)?
Turn on Modbus TCP/IP read and, if needed, write in the touchscreen or web interface (both are off by default).
Where is the official Vaisala Indigo510 / Indigo520 transmitters (Modbus TCP) Modbus documentation?
The source is Indigo510, Indigo520 User Guide (M212287EN-AJ), revision 2026-10, published free by Vaisala at https://docs.vaisala.com/r/M212287EN-AJ/en-US.
More Vaisala Modbus register maps
- Sensor (dew point probe)
Vaisala DMP Series dew point probes (DMP5, DMP6, DMP7, DMP8) (Modbus RTU)
Vaisala DMP5, DMP6, DMP7 and DMP8 dew point and temperature probes, Modbus RTU interface (user guide M212357EN-F).
Also known as: DMP5, DMP6, DMP7, DMP8, DRYCAP DMP series - Sensor (dew point transmitter)
Vaisala DMT143 miniature dew point transmitter (Modbus RTU)
DMT143 dew point transmitters ordered with the Modbus RTU option (user guide M211435EN-L).
Also known as: DMT143, DRYCAP DMT143 - Sensor (dew point transmitter)
Vaisala DMT153 dew point transmitter (Modbus RTU)
DMT153 trace-moisture dew point transmitter, Modbus RTU interface (user guide M213149EN-B).
Also known as: DMT153, DRYCAP DMT153 - Sensor (CO2 duct transmitter)
Vaisala GMD110 duct CO2 transmitter (Modbus RTU)
GMD110 duct-mount CO2 transmitter, Modbus RTU interface (user guide M212885EN-B).
Also known as: GMD110, CARBOCAP GMD110 - Sensor (CO2 probe)
Vaisala GMP251 CARBOCAP carbon dioxide probe (Modbus RTU)
GMP251 probe in Modbus RTU mode, user guide M211799EN-N.
Also known as: GMP251, CARBOCAP GMP251, Vaisala GMP251 - Sensor (CO2 probe)
Vaisala GMP252 CARBOCAP carbon dioxide probe (Modbus RTU)
GMP252 probe in Modbus RTU mode, user guide M211897EN-G.
Also known as: GMP252, CARBOCAP GMP252, Vaisala GMP252 - Sensor (CO2 wall transmitter)
Vaisala GMW87 CO2 and temperature wall transmitter (Modbus RTU)
GMW87, the RS-485 Modbus RTU model of the GMW80 series (user guide M211748EN-H).
Also known as: GMW87, GMW80 series Modbus - Sensor (humidity and temperature transmitter)
Vaisala HMDW110 series humidity and temperature transmitters with TMI110 (Modbus RTU)
HMDW110-series duct, wall and outdoor transmitters and TMI110 ordered with the Modbus RTU option (user guide M211726EN-L).
Also known as: HMD110, HMD112, HMW110, HMW112, HMW112D, HMS110, HMS112, TMW110, TMW112, TMW112D, TMI110 - Sensor (humidity and temperature module)
Vaisala HMM170 humidity module (Modbus RTU)
HMM170 OEM humidity and temperature module with the Modbus RTU interface (user guide M212259EN-D).
Also known as: HMM170, HUMICAP HMM170 - Sensor (humidity and temperature probe)
Vaisala HMP Series (HMP1-HMP9) with MMP8 and TMP1 probes (Modbus RTU)
Vaisala HMP1/3/4/5/7/8/9, TMP1 and MMP8 probes with the Modbus RTU interface (user guide M212022EN-M).
Also known as: HMP1, HMP3, HMP4, HMP5, HMP7, HMP8, HMP9, TMP1, MMP8 - Sensor (humidity and temperature probe)
Vaisala HMP60 / HMP110 series humidity and temperature probes (Modbus RTU)
HMP60/HMP110-series probes ordered with the Modbus RTU option (user guide M211060EN-N).
Also known as: HMP110, HMP113, HMP115, TMP115, HMP60, HMP63, HUMICAP HMP110, HMP110T, HMP63T, HMP115T - Sensor (humidity and temperature transmitter)
Vaisala HMW87 / HMW87D wall humidity and temperature transmitters (Modbus RTU)
HMW87 and HMW87D wall transmitters of the HMDW80 series (the Modbus models in user guide M211510EN-J).
Also known as: HMW87, HMW87D, HMDW80 Modbus - Sensor (H2O2 probe)
Vaisala HPP271 hydrogen peroxide probe (Modbus RTU)
HPP271 vaporized hydrogen peroxide probe, Modbus RTU interface (user guide M211888EN-E).
Also known as: HPP271, PEROXCAP HPP271 - Sensor (H2O2 / humidity probe)
Vaisala HPP272 hydrogen peroxide, humidity and temperature probe (Modbus RTU)
HPP272 vaporized hydrogen peroxide probe, Modbus RTU interface (user guide M211972EN-G).
Also known as: HPP272, PEROXCAP HPP272 - Sensor (transformer oil monitor)
Vaisala MHT410 moisture, hydrogen and temperature transmitter for transformer oil (Modbus RTU)
MHT410 transformer oil monitor, Modbus RTU on the RS-485 screw terminals (user guide M211737EN-J).
Also known as: MHT410 - Sensor (moisture in oil transmitter)
Vaisala MMT143 moisture in oil transmitter (Modbus RTU)
MMT143 moisture-in-oil transmitter ordered with the Modbus RTU option (user guide M213308EN-B).
Also known as: MMT143 - Sensor (HVAC humidity, temperature and CO2 transmitter)
Vaisala Origo10 transmitters for HVAC (Origo10A, Modbus RTU)
Origo10A duct and wall transmitters ordered with the Modbus RTU output (user guide M213293EN-B). Origo10L has no Modbus.
Also known as: Origo10, Origo10A, Origo 10, Vaisala Origo10 duct transmitter, Vaisala Origo10 wall transmitter - Sensor (precipitation)
Vaisala RM60 PRECICAP radar precipitation sensor (Modbus RTU)
RM60 sensors ordered with communication option 1 (RS-485 Modbus RTU) or switched to Modbus, per user guide M213218EN-B.
Also known as: RM60, PRECICAP RM60, Vaisala RM60 - Sensor (ultrasonic wind)
Vaisala WM80 ultrasonic wind sensor (Modbus RTU)
WM80 sensors with RS-485 in Modbus mode (e.g. ordering option C), per user guide M212995EN-F.
Also known as: WM80, Vaisala WM80, Ultrasonic Wind Sensor WM80 - Sensor (weather transmitter)
Vaisala WXT530 series weather transmitters (Modbus RTU)
WXT531-WXT536 weather transmitters with firmware 3.85 or later in Modbus RTU mode (user guide M211840EN-G).
Also known as: WXT531, WXT532, WXT533, WXT534, WXT535, WXT536 - Sensor (humidity and temperature probe)
Vaisala XMP10 humidity and temperature probe (Modbus RTU)
XMP10 probes ordered with (or switched to) Modbus RTU output, user guide M213279EN-A.
Also known as: XMP10, HUMICAP XMP10, Vaisala XMP10 - Sensor (CO2/humidity wall transmitter)
Vaisala XMW85 CO2, humidity and temperature wall transmitter (Modbus RTU)
XMW85 wall transmitter, Modbus RTU interface (user guide M213257EN-B).
Also known as: XMW85
Other valves, actuators & sensors register maps
- Sensor (digital indicator with alarms)
Yokogawa UTAdvanced UM33A digital indicator with alarms
Yokogawa UM33A indicators with RS-485 (Modbus RTU/ASCII); process monitoring D registers from IM 05P07A01-01EN chapter 10.
Also known as: UM33A - Actuator / valve (pressure-independent characterised control valve)
Belimo 2-way EPIV DN 15-50 (Version 4.2) Modbus RTU
Belimo 2-way EPIV DN 15-50 Version 4 (EP..R2+(K)BAC) on Modbus RTU, per interface description edition 2025-09 / V4.2.
Also known as: EP..R2+BAC, EP..R2+KBAC, Electronic pressure-independent valve - Sensor (water analysis transmitter)
Endress+Hauser Liquiline CM44x multichannel transmitter (Modbus RS485 / TCP)
Liquiline CM44x with the Modbus RS485 or Modbus TCP option, software 1.11.00 and later (SD01189C/07/EN/07.22). The CSFxx sampler and CA80xx analyzer blocks of the same guide are not included.
Also known as: CM442, CM444, CM448, CM44P, CM44R, Liquiline CM442, Liquiline CM444, Liquiline CM448 - Sensor (pressure transmitter)
KELLER X-Line digital pressure transmitters, Series 30 / 40 (Modbus RTU)
KELLER X-Line transmitters with RS-485, Class.Group firmware 5.20-10.40 or later, 5.21 and 5.24 (protocol document version 3.7).
Also known as: Series 30X, Series 33X, Series 35X, Series 36X, Series 46X, PAA-33X, PR-33X, PA-36XW, Class.Group 5.20, Class.Group 5.21, Class.Group 5.24 - Sensor (leak detection controller)
RLE Technologies LD5200 leak detection controller (Modbus RTU / Modbus TCP slave)
RLE LD5200 distance-read leak detection controller, user guide version 04.22 (firmware 2.3.1).
Also known as: LD5200 - Sensor (signal conditioner)
Shinko Technos SGxL signal conditioner series (Modbus RTU)
Shinko SGxL signal conditioners (SGBL, SGCL, SGDL, SGIL, SGLL, SGML, SGPL, SGRL, SGSL, SGTL, SGUL); SGFL and SGJL are not covered. Manual No.SGxL1CE3.
Also known as: SGBL, SGCL, SGDL, SGIL, SGLL, SGML, SGPL, SGRL, SGSL, SGTL, SGUL
All valves, actuators & sensors Modbus register maps →
Source: Indigo510, Indigo520 User Guide · M212287EN-AJ · rev. 2026-10. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.