- X-Line digital pressure transmitters, Series 30 / 40 (Modbus RTU)
Sensor (pressure transmitter) · Modbus register map
KELLER X-Line digital pressure transmitters, Series 30 / 40 (Modbus RTU) Modbus register map
Updated 19 November 2026
KELLER X-Line digital pressure transmitters (Series 30 and 40) speak both the KELLER bus protocol and Modbus RTU on the same RS-485 line. This map covers the Modbus process values (pressure P1/P2, temperatures and the calculated CH0 channel) as floats, x100 integers and 32-bit integers, the conductivity values of 5.21 devices, and the main configuration and status registers.
This page lists 40 Modbus registers for the KELLER X-Line digital pressure transmitters, Series 30 / 40 (Modbus RTU) — 6 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from KELLER’s own free documentation (linked below) and checked against it.
- Manufacturer
- KELLER
- Model
- X-Line digital pressure transmitters, Series 30 / 40 (Modbus RTU)
- Equipment type
- Sensor (pressure transmitter)
- Registers
- 40 (6 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 9600 baud, 8N1
- Documented addressing
- hexadecimal, 0-based
- 32-bit word order
- ABCD high word first (big-endian)
- Firmware
- Class.Group 5.20-10.40 and later, 5.21-xx.xx, 5.24-xx.xx (older 5.20-5.50 only supports the floats at 0x0000-0x000A and the 16-bit integers)
- Also known as
- Series 30X, Series 33X, Series 35X, Series 36X, Series 46X, PAA-33X, PR-33X, PA-36XW, Class.Group 5.20, Class.Group 5.21, Class.Group 5.24
Integration notes: KELLER X-Line digital pressure transmitters, Series 30 / 40 (Modbus RTU)
Read 4 registers from 0x0100 (function 03) for P1 and its temperature as ABCD floats, or 0x0002-0x000B for all process values. Use the x100 integers at 0x0010 if your master has no float support.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 2 | P1 pressure | FLOAT32 ABCD | Pressure P1 (bar) | Read |
| HR 8 | TOB1 sensor 1 temperature | FLOAT32 ABCD | Sensor temperature | Read |
| HR 256 | P1 pressure (block 2) | FLOAT32 ABCD | P1 + TOB1 in one read | Read |
| HR 524 | Device status | BITMAP16 | Channel error bits | Read |
| HR 17 | P1 (integer x100) | INT16 | P1 as x100 integer | Read |
Enable Modbus control & writes
Modbus is always active alongside the KELLER protocol; no initialisation command is needed.
Byte order & addressing
- Modbus CRC is sent low byte first; the KELLER protocol sends it high byte first.
- Address 250 reaches any device regardless of its address (point-to-point use only).
- Older firmware limits a read to 2 or 4 registers per request.
Network setup
- Defaults: address 1, 9600 baud, 8N1. 115200 baud, parity and 2 stop bits are set in register 0x0200.
Watch out for
- Single-register writes (function 06) are refused in the 0x03xx and 0xFFxx ranges and on float registers; use function 16.
KELLER X-Line digital pressure transmitters, Series 30 / 40 (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 0x0000 | CH0 calculated value | Customer-specific calculated channel. | FLOAT32 | ABCD | Read | |||
| HR | 2doc 0x0002 | P1 pressure | FLOAT32 | ABCD | bar | Read | |||
| HR | 4doc 0x0004 | P2 pressure | Second pressure sensor, if fitted. | FLOAT32 | ABCD | bar | Read | ||
| HR | 6doc 0x0006 | T temperature | FLOAT32 | ABCD | °C | Read | |||
| HR | 8doc 0x0008 | TOB1 sensor 1 temperature | FLOAT32 | ABCD | °C | Read | |||
| HR | 10doc 0x000A | TOB2 sensor 2 temperature | FLOAT32 | ABCD | °C | Read | |||
| HR | 16doc 0x0010 | CH0 (integer x100) | 32767 = error/overflow. | INT16 | × 0.01 | Read | |||
| HR | 17doc 0x0011 | P1 (integer x100) | Range +/-327 bar. | INT16 | × 0.01 | bar | Read | ||
| HR | 18doc 0x0012 | P2 (integer x100) | INT16 | × 0.01 | bar | Read | |||
| HR | 19doc 0x0013 | T (integer x100) | INT16 | × 0.01 | °C | Read | |||
| HR | 20doc 0x0014 | TOB1 (integer x100) | INT16 | × 0.01 | °C | Read | |||
| HR | 21doc 0x0015 | TOB2 (integer x100) | INT16 | × 0.01 | °C | Read | |||
| HR | 32doc 0x0020 | CH0 (32-bit integer) | INT32 | ABCD | × 0.00001 | Read | |||
| HR | 34doc 0x0022 | P1 (32-bit integer) | Pascal (1e-5 bar). | INT32 | ABCD | Pa | Read | ||
| HR | 36doc 0x0024 | P2 (32-bit integer) | INT32 | ABCD | Pa | Read | |||
| HR | 38doc 0x0026 | T (32-bit integer) | INT32 | ABCD | × 0.01 | °C | Read | ||
| HR | 40doc 0x0028 | TOB1 (32-bit integer) | INT32 | ABCD | × 0.01 | °C | Read | ||
| HR | 42doc 0x002A | TOB2 (32-bit integer) | INT32 | ABCD | × 0.01 | °C | Read | ||
| HR | 256doc 0x0100 | P1 pressure (block 2) | Same as 0x0002, regrouped for one-shot reads. | FLOAT32 | ABCD | bar | Read | ||
| HR | 258doc 0x0102 | TOB1 temperature (block 2) | FLOAT32 | ABCD | °C | Read | |||
| HR | 260doc 0x0104 | P2 pressure (block 2) | FLOAT32 | ABCD | bar | Read | |||
| HR | 262doc 0x0106 | TOB2 temperature (block 2) | FLOAT32 | ABCD | °C | Read | |||
| HR | 264doc 0x0108 | P1 pressure (block 2, copy) | Class.Group 5.21 / 5.24. | FLOAT32 | ABCD | bar | Read | ||
| HR | 266doc 0x010A | T temperature (block 2) | Class.Group 5.21 / 5.24. | FLOAT32 | ABCD | °C | Read | ||
| HR | 268doc 0x010C | Conductivity, temperature compensated | 5.21 devices with conductivity only. | FLOAT32 | ABCD | mS/cm | Read | ||
| HR | 270doc 0x010E | Conductivity, raw | 5.21 devices with conductivity only. | FLOAT32 | ABCD | mS/cm | Read | ||
| HR | 512doc 0x0200 | UART settings | Bits 0-3 baud (0 = 9600, 1 = 115200). | BITMAP16 | Read/write | bit 4 = Parity enabled; bit 5 = Even parity (0 = odd); bit 6 = 2 stop bits (5.21/5.24) | |||
| HR | 514doc 0x0202 | Serial number high word | UINT16 | Read | |||||
| HR | 515doc 0x0203 | Serial number low word | UINT16 | Read | |||||
| HR | 516doc 0x0204 | Active pressure channels | BITMAP16 | Read | bit 1 = P1; bit 2 = P2 | ||||
| HR | 517doc 0x0205 | Active temperature channels | BITMAP16 | Read | bit 3 = T; bit 4 = TOB1; bit 5 = TOB2; bit 7 = Conductivity (5.21) | ||||
| HR | 518doc 0x0206 | CH0 calculation mode | Restart needed after change. | UINT16 | Read/write | 0 = Inactive; 1 = P1-P2; 2 = P2-P1; 3 = sqrt(P1); 4 = sqrt(P2); 5 = sqrt(P1-P2); 6 = sqrt(P2-P1); 11 = abs(P1); 12 = abs(P1-P2); 13 = Line-pressure compensated dP (factory); 14 = Straight-line fit of P1; 15 = PT1000 temperature | |||
| HR | 521doc 0x0209 | Sensor type (P-Mode) | Low nibble P1, high nibble P2: 0 = PR relative, 1 = PA absolute, 2 = PAA absolute. | UINT16 | Read | ||||
| HR | 522doc 0x020A | Filter control | BITMAP16 | Read/write | bit 0 = Adaptive filter P1/P2 on; bit 1 = Low-pass filter T/TOB1/TOB2 on | ||||
| HR | 524doc 0x020C | Device status | Set bit = error in that channel. | BITMAP16 | Read | bit 0 = CH0 error; bit 1 = P1 error; bit 2 = P2 error; bit 3 = T error; bit 4 = TOB1 error; bit 5 = TOB2 error; bit 6 = ERR2 analog output computation error; bit 7 = /STD power-up mode | |||
| HR | 525doc 0x020D | Device address | 1-247, default 1; 250 = transparent. | UINT16 | Read/write | ||||
| HR | 526doc 0x020E | Firmware Class.Group | UINT16 | Read | |||||
| HR | 527doc 0x020F | Firmware Year.Week | UINT16 | Read | |||||
| HR | 533doc 0x0215 | Inter-frame time at 9600 baud | Default 35 (3.5 ms); 5.21-16.50+ and 5.24. | UINT16 | × 0.1 | ms | Read/write | ||
| HR | 534doc 0x0216 | Inter-frame time at 115200 baud | Default 18 (1.8 ms). | UINT16 | × 0.1 | ms | Read/write |
Notes on this map
- Floats and 32-bit integers are high word first (ABCD): the register map labels the first register HWord, the float chapter puts the exponent byte in register 0, and the worked P1 read returns 3F 75 F0 7B = 0.9607 bar.
- Each channel must be read in one request starting on an even address; an odd start returns exception 2.
- Inactive channels read NaN (float), 32767 (16-bit) or 2147483647 (32-bit); over/underflow reads +/- infinity in the float range.
- Which ranges exist depends on firmware: 32-bit integers need 5.20-12.28 or later; 16-bit integers work on 5.20-5.50 and on 5.20-12.28 or later but not on 5.20-10.40; the 0x0100 block and the 0x02xx configuration range need 5.20-10.40 or later.
- Left out: the coefficient ranges (0x03xx, 0x3xxx, 0x40xx), command registers above 0xFF00, conductivity range/compensation settings and the ASCII serial number.
- The KELLER bus protocol (functions 30-100) runs on the same line; this map covers only the Modbus functions 3, 6, 8 and 16.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the KELLER X-Line digital pressure transmitters, Series 30 / 40 (Modbus RTU)
What Modbus registers does the KELLER X-Line digital pressure transmitters, Series 30 / 40 (Modbus RTU) have?
This map lists 40 registers: 40 holding registers. 6 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the KELLER X-Line digital pressure transmitters, Series 30 / 40 (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The document gives the start address (StAdd) in hex exactly as it goes into the request; its example reads P1 with start address 0x0002.
What byte order does the KELLER X-Line digital pressure transmitters, Series 30 / 40 (Modbus RTU) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the KELLER X-Line digital pressure transmitters, Series 30 / 40 (Modbus RTU)?
Start with HR 2 P1 pressure (Pressure P1 (bar)); HR 8 TOB1 sensor 1 temperature (Sensor temperature); HR 256 P1 pressure (block 2) (P1 + TOB1 in one read); HR 524 Device status (Channel error bits); HR 17 P1 (integer x100) (P1 as x100 integer).
How do I enable Modbus control of the KELLER X-Line digital pressure transmitters, Series 30 / 40 (Modbus RTU)?
Modbus is always active alongside the KELLER protocol; no initialisation command is needed.
Where is the official KELLER X-Line digital pressure transmitters, Series 30 / 40 (Modbus RTU) Modbus documentation?
The source is Description of the Communication protocol for X-Line Pressure Transmitters from KELLER (Class.Group 5.20, 5.21, 5.24) (Version 3.7), revision 2020-11, published free by KELLER at https://us.keller-pressure.com/file-cache/website_component/5e2f29419d8b1060a188c377/manuals/1625167998276.
Other valves, actuators & sensors register maps
- Sensor (leak detection controller)
RLE Technologies LD5200 leak detection controller (Modbus RTU / Modbus TCP slave)
RLE LD5200 distance-read leak detection controller, user guide version 04.22 (firmware 2.3.1).
Also known as: LD5200 - Sensor (signal conditioner)
Shinko Technos SGxL signal conditioner series (Modbus RTU)
Shinko SGxL signal conditioners (SGBL, SGCL, SGDL, SGIL, SGLL, SGML, SGPL, SGRL, SGSL, SGTL, SGUL); SGFL and SGJL are not covered. Manual No.SGxL1CE3.
Also known as: SGBL, SGCL, SGDL, SGIL, SGLL, SGML, SGPL, SGRL, SGSL, SGTL, SGUL - Sensor (flame detector)
Teledyne Gas and Flame Detection Spyglass SG50-F flame detector (Modbus RTU)
Teledyne Spyglass SG50-F optical flame detectors (IR3, UV-IR, IR3-H2 and HD video variants) with RS-485 Modbus RTU, communication manual SG50FMODBUS-EN rev 1.0.
Also known as: SG50-F, Spyglass SG50-F, IR3-HD, UV-IR, IR3, UV-IR-HD, IR3-H2-HD, IR3-H2, UV-IR-F, UV-IR-F-HD - Sensor (CO2 / humidity / temperature / pressure)
Teracom TSM400-4-CPTH Modbus CO2, humidity, temperature and pressure multi-sensor
TSM400-4-CPTH per the Teracom TSM400-4-CPTH user manual TSM400-4-CPTH-R1.9.
Also known as: TSM400-4-CPTH - Sensor (dew point transmitter)
Vaisala DMT153 dew point transmitter (Modbus RTU)
DMT153 trace-moisture dew point transmitter, Modbus RTU interface (user guide M213149EN-B).
Also known as: DMT153, DRYCAP DMT153 - Sensor (humidity and temperature probe)
Vaisala HMP Series (HMP1-HMP9) with MMP8 and TMP1 probes (Modbus RTU)
Vaisala HMP1/3/4/5/7/8/9, TMP1 and MMP8 probes with the Modbus RTU interface (user guide M212022EN-M).
Also known as: HMP1, HMP3, HMP4, HMP5, HMP7, HMP8, HMP9, TMP1, MMP8
All valves, actuators & sensors Modbus register maps →
Source: Description of the Communication protocol for X-Line Pressure Transmitters from KELLER (Class.Group 5.20, 5.21, 5.24) · Version 3.7 · rev. 2020-11. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.