Sensor (pressure transmitter) · Modbus register map

KELLER X-Line digital pressure transmitters, Series 30 / 40 (Modbus RTU) Modbus register map

Updated 19 November 2026

Short answer

KELLER X-Line digital pressure transmitters (Series 30 and 40) speak both the KELLER bus protocol and Modbus RTU on the same RS-485 line. This map covers the Modbus process values (pressure P1/P2, temperatures and the calculated CH0 channel) as floats, x100 integers and 32-bit integers, the conductivity values of 5.21 devices, and the main configuration and status registers.

This page lists 40 Modbus registers for the KELLER X-Line digital pressure transmitters, Series 30 / 40 (Modbus RTU) — 6 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from KELLER’s own free documentation (linked below) and checked against it.

Manufacturer
KELLER
Model
X-Line digital pressure transmitters, Series 30 / 40 (Modbus RTU)
Equipment type
Sensor (pressure transmitter)
Registers
40 (6 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
9600 baud, 8N1
Documented addressing
hexadecimal, 0-based
32-bit word order
ABCD high word first (big-endian)
Firmware
Class.Group 5.20-10.40 and later, 5.21-xx.xx, 5.24-xx.xx (older 5.20-5.50 only supports the floats at 0x0000-0x000A and the 16-bit integers)
Also known as
Series 30X, Series 33X, Series 35X, Series 36X, Series 46X, PAA-33X, PR-33X, PA-36XW, Class.Group 5.20, Class.Group 5.21, Class.Group 5.24
Source document
Description of the Communication protocol for X-Line Pressure Transmitters from KELLER (Class.Group 5.20, 5.21, 5.24) · Version 3.7 · rev. 2020-11
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: KELLER X-Line digital pressure transmitters, Series 30 / 40 (Modbus RTU)

Integration in brief

Read 4 registers from 0x0100 (function 03) for P1 and its temperature as ABCD floats, or 0x0002-0x000B for all process values. Use the x100 integers at 0x0010 if your master has no float support.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 2P1 pressureFLOAT32 ABCDPressure P1 (bar)Read
HR 8TOB1 sensor 1 temperatureFLOAT32 ABCDSensor temperatureRead
HR 256P1 pressure (block 2)FLOAT32 ABCDP1 + TOB1 in one readRead
HR 524Device statusBITMAP16Channel error bitsRead
HR 17P1 (integer x100)INT16P1 as x100 integerRead

Enable Modbus control & writes

Modbus is always active alongside the KELLER protocol; no initialisation command is needed.

Byte order & addressing

Network setup

Watch out for

KELLER X-Line digital pressure transmitters, Series 30 / 40 (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

40 of 40 shown
KELLER X-Line digital pressure transmitters, Series 30 / 40 (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 0x0000CH0 calculated valueCustomer-specific calculated channel.FLOAT32ABCDRead
HR2doc 0x0002P1 pressureFLOAT32ABCDbarRead
HR4doc 0x0004P2 pressureSecond pressure sensor, if fitted.FLOAT32ABCDbarRead
HR6doc 0x0006T temperatureFLOAT32ABCD°CRead
HR8doc 0x0008TOB1 sensor 1 temperatureFLOAT32ABCD°CRead
HR10doc 0x000ATOB2 sensor 2 temperatureFLOAT32ABCD°CRead
HR16doc 0x0010CH0 (integer x100)32767 = error/overflow.INT16× 0.01Read
HR17doc 0x0011P1 (integer x100)Range +/-327 bar.INT16× 0.01barRead
HR18doc 0x0012P2 (integer x100)INT16× 0.01barRead
HR19doc 0x0013T (integer x100)INT16× 0.01°CRead
HR20doc 0x0014TOB1 (integer x100)INT16× 0.01°CRead
HR21doc 0x0015TOB2 (integer x100)INT16× 0.01°CRead
HR32doc 0x0020CH0 (32-bit integer)INT32ABCD× 0.00001Read
HR34doc 0x0022P1 (32-bit integer)Pascal (1e-5 bar).INT32ABCDPaRead
HR36doc 0x0024P2 (32-bit integer)INT32ABCDPaRead
HR38doc 0x0026T (32-bit integer)INT32ABCD× 0.01°CRead
HR40doc 0x0028TOB1 (32-bit integer)INT32ABCD× 0.01°CRead
HR42doc 0x002ATOB2 (32-bit integer)INT32ABCD× 0.01°CRead
HR256doc 0x0100P1 pressure (block 2)Same as 0x0002, regrouped for one-shot reads.FLOAT32ABCDbarRead
HR258doc 0x0102TOB1 temperature (block 2)FLOAT32ABCD°CRead
HR260doc 0x0104P2 pressure (block 2)FLOAT32ABCDbarRead
HR262doc 0x0106TOB2 temperature (block 2)FLOAT32ABCD°CRead
HR264doc 0x0108P1 pressure (block 2, copy)Class.Group 5.21 / 5.24.FLOAT32ABCDbarRead
HR266doc 0x010AT temperature (block 2)Class.Group 5.21 / 5.24.FLOAT32ABCD°CRead
HR268doc 0x010CConductivity, temperature compensated5.21 devices with conductivity only.FLOAT32ABCDmS/cmRead
HR270doc 0x010EConductivity, raw5.21 devices with conductivity only.FLOAT32ABCDmS/cmRead
HR512doc 0x0200UART settingsBits 0-3 baud (0 = 9600, 1 = 115200).BITMAP16Read/writebit 4 = Parity enabled; bit 5 = Even parity (0 = odd); bit 6 = 2 stop bits (5.21/5.24)
HR514doc 0x0202Serial number high wordUINT16Read
HR515doc 0x0203Serial number low wordUINT16Read
HR516doc 0x0204Active pressure channelsBITMAP16Readbit 1 = P1; bit 2 = P2
HR517doc 0x0205Active temperature channelsBITMAP16Readbit 3 = T; bit 4 = TOB1; bit 5 = TOB2; bit 7 = Conductivity (5.21)
HR518doc 0x0206CH0 calculation modeRestart needed after change.UINT16Read/write0 = Inactive; 1 = P1-P2; 2 = P2-P1; 3 = sqrt(P1); 4 = sqrt(P2); 5 = sqrt(P1-P2); 6 = sqrt(P2-P1); 11 = abs(P1); 12 = abs(P1-P2); 13 = Line-pressure compensated dP (factory); 14 = Straight-line fit of P1; 15 = PT1000 temperature
HR521doc 0x0209Sensor type (P-Mode)Low nibble P1, high nibble P2: 0 = PR relative, 1 = PA absolute, 2 = PAA absolute.UINT16Read
HR522doc 0x020AFilter controlBITMAP16Read/writebit 0 = Adaptive filter P1/P2 on; bit 1 = Low-pass filter T/TOB1/TOB2 on
HR524doc 0x020CDevice statusSet bit = error in that channel.BITMAP16Readbit 0 = CH0 error; bit 1 = P1 error; bit 2 = P2 error; bit 3 = T error; bit 4 = TOB1 error; bit 5 = TOB2 error; bit 6 = ERR2 analog output computation error; bit 7 = /STD power-up mode
HR525doc 0x020DDevice address1-247, default 1; 250 = transparent.UINT16Read/write
HR526doc 0x020EFirmware Class.GroupUINT16Read
HR527doc 0x020FFirmware Year.WeekUINT16Read
HR533doc 0x0215Inter-frame time at 9600 baudDefault 35 (3.5 ms); 5.21-16.50+ and 5.24.UINT16× 0.1msRead/write
HR534doc 0x0216Inter-frame time at 115200 baudDefault 18 (1.8 ms).UINT16× 0.1msRead/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the KELLER X-Line digital pressure transmitters, Series 30 / 40 (Modbus RTU)

What Modbus registers does the KELLER X-Line digital pressure transmitters, Series 30 / 40 (Modbus RTU) have?

This map lists 40 registers: 40 holding registers. 6 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the KELLER X-Line digital pressure transmitters, Series 30 / 40 (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The document gives the start address (StAdd) in hex exactly as it goes into the request; its example reads P1 with start address 0x0002.

What byte order does the KELLER X-Line digital pressure transmitters, Series 30 / 40 (Modbus RTU) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the KELLER X-Line digital pressure transmitters, Series 30 / 40 (Modbus RTU)?

Start with HR 2 P1 pressure (Pressure P1 (bar)); HR 8 TOB1 sensor 1 temperature (Sensor temperature); HR 256 P1 pressure (block 2) (P1 + TOB1 in one read); HR 524 Device status (Channel error bits); HR 17 P1 (integer x100) (P1 as x100 integer).

How do I enable Modbus control of the KELLER X-Line digital pressure transmitters, Series 30 / 40 (Modbus RTU)?

Modbus is always active alongside the KELLER protocol; no initialisation command is needed.

Where is the official KELLER X-Line digital pressure transmitters, Series 30 / 40 (Modbus RTU) Modbus documentation?

The source is Description of the Communication protocol for X-Line Pressure Transmitters from KELLER (Class.Group 5.20, 5.21, 5.24) (Version 3.7), revision 2020-11, published free by KELLER at https://us.keller-pressure.com/file-cache/website_component/5e2f29419d8b1060a188c377/manuals/1625167998276.

Other valves, actuators & sensors register maps

All valves, actuators & sensors Modbus register maps →

Source: Description of the Communication protocol for X-Line Pressure Transmitters from KELLER (Class.Group 5.20, 5.21, 5.24) · Version 3.7 · rev. 2020-11. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.