- Home
- Modbus register maps
- Teledyne Gas and Flame Detection
- Spyglass SG50-F flame detector (Modbus RTU)
Sensor (flame detector) · Modbus register map
Teledyne Gas and Flame Detection Spyglass SG50-F flame detector (Modbus RTU) Modbus register map
Updated 17 November 2026
The Spyglass SG50-F is a family of optical flame detectors (multi-IR, UV/IR and hydrogen-flame types, some with HD video). Its RS-485 port speaks Modbus RTU: input registers carry alarm, fault, built-in-test flags and the detector type, and holding registers set sensitivity, delays, latching, heater, video and the clock. This map covers every register the manual defines except the 32-bit and IP fields.
This page lists 19 Modbus registers for the Teledyne Gas and Flame Detection Spyglass SG50-F flame detector (Modbus RTU) — 14 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Teledyne Gas and Flame Detection’s own free documentation (linked below) and checked against it.
- Manufacturer
- Teledyne Gas and Flame Detection
- Model
- Spyglass SG50-F flame detector (Modbus RTU)
- Equipment type
- Sensor (flame detector)
- Registers
- 19 (14 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 9600 baud, 8N1
- Documented addressing
- hexadecimal, 0-based
- Also known as
- SG50-F, Spyglass SG50-F, IR3-HD, UV-IR, IR3, UV-IR-HD, IR3-H2-HD, IR3-H2, UV-IR-F, UV-IR-F-HD
Integration notes: Teledyne Gas and Flame Detection Spyglass SG50-F flame detector (Modbus RTU)
Set a unique address per detector, wire RS-485 at 9600 8N1 and poll input registers 0-2 (alarm, fault, BIT flags) with function 04.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 0 | Alarm relay | UINT16 | Fire alarm | Read |
| IR 1 | Fault relay | UINT16 | Fault | Read |
| IR 2 | BIT status | BITMAP16 | Maintenance flags | Read |
| IR 27 | Detector type | UINT16 | Detector type | Read |
| HR 1 | Sensitivity | UINT16 | Sensitivity | Read/write |
| HR 32 | Detector Modbus address | UINT16 | Modbus address | Read/write |
Enable Modbus control & writes
Modbus RTU is available on the RS-485 terminals of all SG50-F detectors; the address is register 0x0020 (1-247).
Byte order & addressing
- Addresses are printed in hex and are the wire addresses.
- Clock registers pack two fields per register (high byte, low byte).
Network setup
- 9600 baud, 8N1, half duplex 2-wire, no echo.
- Terminate the line with 120 ohm.
Watch out for
- Video and analog-video registers only work on HD models.
Teledyne Gas and Flame Detection Spyglass SG50-F flame detector (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 0doc 0x0000 | Alarm relay | Fire alarm state. | UINT16 | Read | 0 = No alarm; 1 = Alarm | |||
| IR | 1doc 0x0001 | Fault relay | UINT16 | Read | 0 = No fault; 1 = Fault | ||||
| IR | 2doc 0x0002 | BIT status | Built-in-test flags needing maintenance. | BITMAP16 | Read | bit 0 = Dirty window fault; bit 1 = 24 V power supply fault | |||
| IR | 16doc 0x0010 | FGD detector identifier | Always ASCII "FG" for this product family. | UINT16 | Read | ||||
| IR | 27doc 0x001B | Detector type | UINT16 | Read | 101 = IR3-HD; 110 = UV-IR (small); 120 = IR3 (small); 130 = UV-IR-HD; 140 = IR3-H2-HD; 150 = IR3-H2; 160 = UV-IR-F; 170 = UV-IR-F-HD | ||||
| HR | 1doc 0x0001 | Sensitivity | Detection sensitivity level. | UINT16 | Read/write | 0 = Low; 1 = Medium; 2 = High; 3 = Extreme | |||
| HR | 2doc 0x0002 | Ultra-fast detection | UINT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 3doc 0x0003 | Alarm delay | UINT16 | Read/write | 0 = 0 s; 1 = 5 s; 2 = 10 s; 3 = 20 s; 4 = 30 s | ||||
| HR | 4doc 0x0004 | Alarm latch | UINT16 | Read/write | 0 = No latch; 1 = Latch | ||||
| HR | 5doc 0x0005 | Window heater | UINT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 6doc 0x0006 | Video enable | HD models only. | UINT16 | Read/write | 0 = Disabled; 1 = Enabled | |||
| HR | 7doc 0x0007 | Post-alarm video recording duration | HD models only, 1-3. | UINT16 | min | Read/write | |||
| HR | 8doc 0x0008 | Analog video output | HD models only. | UINT16 | Read/write | 0 = Disabled; 2 = NTSC; 3 = PAL | |||
| HR | 9doc 0x0009 | Manual BIT alarm output test | UINT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 32doc 0x0020 | Detector Modbus address | 1-247. | UINT16 | Read/write | ||||
| HR | 33doc 0x0021 | Manual BIT | Write 1 to start a manual built-in test. | UINT16 | Read/write | ||||
| HR | 64doc 0x0040 | Time: hour and minute | Hour in high byte, minutes in low byte. | UINT16 | Read/write | ||||
| HR | 65doc 0x0041 | Time: second and year | Seconds in high byte, year in low byte. | UINT16 | Read/write | ||||
| HR | 66doc 0x0042 | Date: month and day | Month in high byte, day in low byte. | UINT16 | Read/write |
Notes on this map
- Left out: 0-20 mA output value (input 0x0004-0x0005), Ethernet IP address (0x0006-0x0007, HD only) and detector serial ID (u32 at 0x0019-0x001A): the manual does not give their word order or encoding.
- Input registers and holding registers are separate tables, so input 0x0001 (fault relay) and holding 0x0001 (sensitivity) are different values.
- The factory default Modbus address is not stated in this manual.
- Up to 32 detectors per segment; up to 247 with repeaters. 120 ohm end-of-line resistor required.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Teledyne Gas and Flame Detection Spyglass SG50-F flame detector (Modbus RTU)
What Modbus registers does the Teledyne Gas and Flame Detection Spyglass SG50-F flame detector (Modbus RTU) have?
This map lists 19 registers: 5 input registers, 14 holding registers. 14 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Teledyne Gas and Flame Detection Spyglass SG50-F flame detector (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual prints register addresses in hex starting at 0x0000 (alarm relay), so the hex value is the wire address: 0x0010 = address 16.
What are the minimum Modbus registers to integrate the Teledyne Gas and Flame Detection Spyglass SG50-F flame detector (Modbus RTU)?
Start with IR 0 Alarm relay (Fire alarm); IR 1 Fault relay (Fault); IR 2 BIT status (Maintenance flags); IR 27 Detector type (Detector type); HR 1 Sensitivity (Sensitivity); HR 32 Detector Modbus address (Modbus address).
How do I enable Modbus control of the Teledyne Gas and Flame Detection Spyglass SG50-F flame detector (Modbus RTU)?
Modbus RTU is available on the RS-485 terminals of all SG50-F detectors; the address is register 0x0020 (1-247).
Where is the official Teledyne Gas and Flame Detection Spyglass SG50-F flame detector (Modbus RTU) Modbus documentation?
The source is Spyglass SG50-F Modbus Communication Manual (SG50FMODBUS-EN Revision 1.0), revision 2023-02, published free by Teledyne Gas and Flame Detection at https://www.teledynegasandflamedetection.com/en-us/Products/docs/fixedflame-spyglass-sg50-f-modbus-communication-manual-english.pdf.
More Teledyne Gas and Flame Detection Modbus register maps
Other valves, actuators & sensors register maps
- Sensor (CO2 / humidity / temperature / pressure)
Teracom TSM400-4-CPTH Modbus CO2, humidity, temperature and pressure multi-sensor
TSM400-4-CPTH per the Teracom TSM400-4-CPTH user manual TSM400-4-CPTH-R1.9.
Also known as: TSM400-4-CPTH - Sensor (dew point transmitter)
Vaisala DMT153 dew point transmitter (Modbus RTU)
DMT153 trace-moisture dew point transmitter, Modbus RTU interface (user guide M213149EN-B).
Also known as: DMT153, DRYCAP DMT153 - Sensor (humidity and temperature probe)
Vaisala HMP Series (HMP1-HMP9) with MMP8 and TMP1 probes (Modbus RTU)
Vaisala HMP1/3/4/5/7/8/9, TMP1 and MMP8 probes with the Modbus RTU interface (user guide M212022EN-M).
Also known as: HMP1, HMP3, HMP4, HMP5, HMP7, HMP8, HMP9, TMP1, MMP8 - Sensor (moisture in oil transmitter)
Vaisala MMT143 moisture in oil transmitter (Modbus RTU)
MMT143 moisture-in-oil transmitter ordered with the Modbus RTU option (user guide M213308EN-B).
Also known as: MMT143 - Sensor
VTS RH+T-SENS-D-MODRTU humidity and temperature transducer
VTS RH+T-SENS-D-MODRTU duct humidity and temperature transducer (Sensirion SHT31-DIS-B), manual ver. 2.0 (11.2021).
Also known as: RH&T-SENS-D-MODRTU, VTS duct humidity sensor - Sensor (duct averaging temperature)
ACI (Automation Components Inc.) Averaging Series BACnet/Modbus duct averaging temperature sensor
ACI Averaging Series copper and flexible duct averaging temperature sensors with the BACnet MS/TP / Modbus RTU interface (guide I0000932).
Also known as: Copper Averaging, Flexible Averaging, Averaging Series BACnet Modbus
All valves, actuators & sensors Modbus register maps →
Source: Spyglass SG50-F Modbus Communication Manual · SG50FMODBUS-EN Revision 1.0 · rev. 2023-02. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.