Sensor (flame detector) · Modbus register map

Teledyne Gas and Flame Detection Spyglass SG50-F flame detector (Modbus RTU) Modbus register map

Updated 17 November 2026

Short answer

The Spyglass SG50-F is a family of optical flame detectors (multi-IR, UV/IR and hydrogen-flame types, some with HD video). Its RS-485 port speaks Modbus RTU: input registers carry alarm, fault, built-in-test flags and the detector type, and holding registers set sensitivity, delays, latching, heater, video and the clock. This map covers every register the manual defines except the 32-bit and IP fields.

This page lists 19 Modbus registers for the Teledyne Gas and Flame Detection Spyglass SG50-F flame detector (Modbus RTU) — 14 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Teledyne Gas and Flame Detection’s own free documentation (linked below) and checked against it.

Manufacturer
Teledyne Gas and Flame Detection
Model
Spyglass SG50-F flame detector (Modbus RTU)
Equipment type
Sensor (flame detector)
Registers
19 (14 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
9600 baud, 8N1
Documented addressing
hexadecimal, 0-based
Also known as
SG50-F, Spyglass SG50-F, IR3-HD, UV-IR, IR3, UV-IR-HD, IR3-H2-HD, IR3-H2, UV-IR-F, UV-IR-F-HD
Source document
Spyglass SG50-F Modbus Communication Manual · SG50FMODBUS-EN Revision 1.0 · rev. 2023-02
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Teledyne Gas and Flame Detection Spyglass SG50-F flame detector (Modbus RTU)

Integration in brief

Set a unique address per detector, wire RS-485 at 9600 8N1 and poll input registers 0-2 (alarm, fault, BIT flags) with function 04.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 0Alarm relayUINT16Fire alarmRead
IR 1Fault relayUINT16FaultRead
IR 2BIT statusBITMAP16Maintenance flagsRead
IR 27Detector typeUINT16Detector typeRead
HR 1SensitivityUINT16SensitivityRead/write
HR 32Detector Modbus addressUINT16Modbus addressRead/write

Enable Modbus control & writes

Modbus RTU is available on the RS-485 terminals of all SG50-F detectors; the address is register 0x0020 (1-247).

Byte order & addressing

Network setup

Watch out for

Teledyne Gas and Flame Detection Spyglass SG50-F flame detector (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

19 of 19 shown
Teledyne Gas and Flame Detection Spyglass SG50-F flame detector (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR0doc 0x0000Alarm relayFire alarm state.UINT16Read0 = No alarm; 1 = Alarm
IR1doc 0x0001Fault relayUINT16Read0 = No fault; 1 = Fault
IR2doc 0x0002BIT statusBuilt-in-test flags needing maintenance.BITMAP16Readbit 0 = Dirty window fault; bit 1 = 24 V power supply fault
IR16doc 0x0010FGD detector identifierAlways ASCII "FG" for this product family.UINT16Read
IR27doc 0x001BDetector typeUINT16Read101 = IR3-HD; 110 = UV-IR (small); 120 = IR3 (small); 130 = UV-IR-HD; 140 = IR3-H2-HD; 150 = IR3-H2; 160 = UV-IR-F; 170 = UV-IR-F-HD
HR1doc 0x0001SensitivityDetection sensitivity level.UINT16Read/write0 = Low; 1 = Medium; 2 = High; 3 = Extreme
HR2doc 0x0002Ultra-fast detectionUINT16Read/write0 = Disabled; 1 = Enabled
HR3doc 0x0003Alarm delayUINT16Read/write0 = 0 s; 1 = 5 s; 2 = 10 s; 3 = 20 s; 4 = 30 s
HR4doc 0x0004Alarm latchUINT16Read/write0 = No latch; 1 = Latch
HR5doc 0x0005Window heaterUINT16Read/write0 = Disabled; 1 = Enabled
HR6doc 0x0006Video enableHD models only.UINT16Read/write0 = Disabled; 1 = Enabled
HR7doc 0x0007Post-alarm video recording durationHD models only, 1-3.UINT16minRead/write
HR8doc 0x0008Analog video outputHD models only.UINT16Read/write0 = Disabled; 2 = NTSC; 3 = PAL
HR9doc 0x0009Manual BIT alarm output testUINT16Read/write0 = Disabled; 1 = Enabled
HR32doc 0x0020Detector Modbus address1-247.UINT16Read/write
HR33doc 0x0021Manual BITWrite 1 to start a manual built-in test.UINT16Read/write
HR64doc 0x0040Time: hour and minuteHour in high byte, minutes in low byte.UINT16Read/write
HR65doc 0x0041Time: second and yearSeconds in high byte, year in low byte.UINT16Read/write
HR66doc 0x0042Date: month and dayMonth in high byte, day in low byte.UINT16Read/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Teledyne Gas and Flame Detection Spyglass SG50-F flame detector (Modbus RTU)

What Modbus registers does the Teledyne Gas and Flame Detection Spyglass SG50-F flame detector (Modbus RTU) have?

This map lists 19 registers: 5 input registers, 14 holding registers. 14 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Teledyne Gas and Flame Detection Spyglass SG50-F flame detector (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual prints register addresses in hex starting at 0x0000 (alarm relay), so the hex value is the wire address: 0x0010 = address 16.

What are the minimum Modbus registers to integrate the Teledyne Gas and Flame Detection Spyglass SG50-F flame detector (Modbus RTU)?

Start with IR 0 Alarm relay (Fire alarm); IR 1 Fault relay (Fault); IR 2 BIT status (Maintenance flags); IR 27 Detector type (Detector type); HR 1 Sensitivity (Sensitivity); HR 32 Detector Modbus address (Modbus address).

How do I enable Modbus control of the Teledyne Gas and Flame Detection Spyglass SG50-F flame detector (Modbus RTU)?

Modbus RTU is available on the RS-485 terminals of all SG50-F detectors; the address is register 0x0020 (1-247).

Where is the official Teledyne Gas and Flame Detection Spyglass SG50-F flame detector (Modbus RTU) Modbus documentation?

The source is Spyglass SG50-F Modbus Communication Manual (SG50FMODBUS-EN Revision 1.0), revision 2023-02, published free by Teledyne Gas and Flame Detection at https://www.teledynegasandflamedetection.com/en-us/Products/docs/fixedflame-spyglass-sg50-f-modbus-communication-manual-english.pdf.

More Teledyne Gas and Flame Detection Modbus register maps

Other valves, actuators & sensors register maps

All valves, actuators & sensors Modbus register maps →

Source: Spyglass SG50-F Modbus Communication Manual · SG50FMODBUS-EN Revision 1.0 · rev. 2023-02. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.