VTS RH+T-SENS-D-MODRTU humidity and temperature transducer Modbus register map

Updated 17 November 2026

Short answer

A duct humidity and temperature transducer from VTS with a 0-5/0-10 V humidity output and an RS-485 Modbus RTU port. Humidity, temperature, a fixed test value and sensor status are plain 16-bit holding registers; address, baud rate, parity and stop bits are changed by writing a password, command and parameter.

This page lists 9 Modbus registers for the VTS RH+T-SENS-D-MODRTU humidity and temperature transducer — 3 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from VTS’s own free documentation (linked below) and checked against it.

Manufacturer
VTS
Model
RH+T-SENS-D-MODRTU humidity and temperature transducer
Equipment type
Sensor
Registers
9 (3 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
19200 baud, 8N1
Documented addressing
hexadecimal, 0-based
Also known as
RH&T-SENS-D-MODRTU, VTS duct humidity sensor
Source document
Humidity Transducer RH+T-SENS-D-MODRTU · ver. 2.0 · rev. 2021-11
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: VTS RH+T-SENS-D-MODRTU humidity and temperature transducer

Integration in brief

Read holding registers 0-2 with FC03: humidity in 0.1 %RH, temperature in 0.01 °C (signed) and the 1000 test value; check STATUS_REG (0x000A) for a sensor fault.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 0RH_REG (relative humidity)UINT16Relative humidityRead
HR 1TEMP_REG (temperature)INT16TemperatureRead
HR 2TEST_VAL_REGUINT16Link test valueRead
HR 10STATUS_REGUINT16Sensor statusRead

Enable Modbus control & writes

Modbus RTU is always on. Set the address on the right DIP switch (binary, 1-247) or by command; left DIP switches 3-6 pick fixed parity/baud or 'use software settings'.

Byte order & addressing

Network setup

Watch out for

VTS RH+T-SENS-D-MODRTU humidity and temperature transducer Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

9 of 9 shown
VTS RH+T-SENS-D-MODRTU humidity and temperature transducer Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 0x0000RH_REG (relative humidity)0-100.0 %RH.UINT16× 0.1%RHRead
HR1doc 0x0001TEMP_REG (temperature)Signed, -40.00 to 123.80 °C.INT16× 0.01°CRead
HR2doc 0x0002TEST_VAL_REGAlways reads 1000 (0x03E8); use it to check the link.UINT16Read
HR3doc 0x0003PASS_REG (password)Writing 1234 (0x04D2) runs the command in COMMAND_REG/PARAM_REG.UINT16Read/write
HR4doc 0x0004COMMAND_REGCommand number; set to 0xEEEE after a bad parameter.UINT16Read/write1 = Set device address; 2 = Set baud rate; 3 = Set parity; 4 = Set stop bits; 6 = Device reset
HR5doc 0x0005PARAM_REGParameter for the command (see notes).UINT16Read/write
HR10doc 0x000ASTATUS_REGUINT16Read0 = No sensor; 1 = Sensor OK; 2 = Error
HR11doc 0x000BDEV_ID_REG (device identification)Bits 11-15 device family, 9-10 hardware version, 4-8 type, 0-1 duct/room.UINT16Read
HR12doc 0x000CSOFT_VER_REG (software version)Four nibbles N.AB + revision letter (0x3210 = 3.21a).UINT16Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the VTS RH+T-SENS-D-MODRTU humidity and temperature transducer

What Modbus registers does the VTS RH+T-SENS-D-MODRTU humidity and temperature transducer have?

This map lists 9 registers: 9 holding registers. 3 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the VTS RH+T-SENS-D-MODRTU humidity and temperature transducer Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The register map prints hex addresses starting at 0x0000, and the DEV_ID and SOFT_VER sections give 'addr=11=0x000B' and 'addr=12=0x000C', so the printed value is the wire address.

What are the minimum Modbus registers to integrate the VTS RH+T-SENS-D-MODRTU humidity and temperature transducer?

Start with HR 0 RH_REG (relative humidity) (Relative humidity); HR 1 TEMP_REG (temperature) (Temperature); HR 2 TEST_VAL_REG (Link test value); HR 10 STATUS_REG (Sensor status).

How do I enable Modbus control of the VTS RH+T-SENS-D-MODRTU humidity and temperature transducer?

Modbus RTU is always on. Set the address on the right DIP switch (binary, 1-247) or by command; left DIP switches 3-6 pick fixed parity/baud or 'use software settings'.

Where is the official VTS RH+T-SENS-D-MODRTU humidity and temperature transducer Modbus documentation?

The source is Humidity Transducer RH+T-SENS-D-MODRTU (ver. 2.0), revision 2021-11, published free by VTS at https://vtsgroup.com/files/document-files/3433/HUMID_EN_2.0.pdf.

More VTS Modbus register maps

Other valves, actuators & sensors register maps

All valves, actuators & sensors Modbus register maps →

Source: Humidity Transducer RH+T-SENS-D-MODRTU · ver. 2.0 · rev. 2021-11. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.