Sensor · Modbus register map
VTS RH+T-SENS-D-MODRTU humidity and temperature transducer Modbus register map
Updated 17 November 2026
A duct humidity and temperature transducer from VTS with a 0-5/0-10 V humidity output and an RS-485 Modbus RTU port. Humidity, temperature, a fixed test value and sensor status are plain 16-bit holding registers; address, baud rate, parity and stop bits are changed by writing a password, command and parameter.
This page lists 9 Modbus registers for the VTS RH+T-SENS-D-MODRTU humidity and temperature transducer — 3 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from VTS’s own free documentation (linked below) and checked against it.
- Manufacturer
- VTS
- Model
- RH+T-SENS-D-MODRTU humidity and temperature transducer
- Equipment type
- Sensor
- Registers
- 9 (3 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 19200 baud, 8N1
- Documented addressing
- hexadecimal, 0-based
- Also known as
- RH&T-SENS-D-MODRTU, VTS duct humidity sensor
Integration notes: VTS RH+T-SENS-D-MODRTU humidity and temperature transducer
Read holding registers 0-2 with FC03: humidity in 0.1 %RH, temperature in 0.01 °C (signed) and the 1000 test value; check STATUS_REG (0x000A) for a sensor fault.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 0 | RH_REG (relative humidity) | UINT16 | Relative humidity | Read |
| HR 1 | TEMP_REG (temperature) | INT16 | Temperature | Read |
| HR 2 | TEST_VAL_REG | UINT16 | Link test value | Read |
| HR 10 | STATUS_REG | UINT16 | Sensor status | Read |
Enable Modbus control & writes
Modbus RTU is always on. Set the address on the right DIP switch (binary, 1-247) or by command; left DIP switches 3-6 pick fixed parity/baud or 'use software settings'.
Byte order & addressing
- Configuration only runs when the password register is written with 1234.
- Fixed parity choice 'no parity, 2 stop bits' exists on the DIP switch.
Network setup
- Switch on the built-in 120 ohm terminator (left DIP 1) at the line ends.
- Restart the transducer after changing DIP switches.
Watch out for
- The analogue output only carries humidity; temperature is Modbus only.
VTS RH+T-SENS-D-MODRTU humidity and temperature transducer Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 0x0000 | RH_REG (relative humidity) | 0-100.0 %RH. | UINT16 | × 0.1 | %RH | Read | ||
| HR | 1doc 0x0001 | TEMP_REG (temperature) | Signed, -40.00 to 123.80 °C. | INT16 | × 0.01 | °C | Read | ||
| HR | 2doc 0x0002 | TEST_VAL_REG | Always reads 1000 (0x03E8); use it to check the link. | UINT16 | Read | ||||
| HR | 3doc 0x0003 | PASS_REG (password) | Writing 1234 (0x04D2) runs the command in COMMAND_REG/PARAM_REG. | UINT16 | Read/write | ||||
| HR | 4doc 0x0004 | COMMAND_REG | Command number; set to 0xEEEE after a bad parameter. | UINT16 | Read/write | 1 = Set device address; 2 = Set baud rate; 3 = Set parity; 4 = Set stop bits; 6 = Device reset | |||
| HR | 5doc 0x0005 | PARAM_REG | Parameter for the command (see notes). | UINT16 | Read/write | ||||
| HR | 10doc 0x000A | STATUS_REG | UINT16 | Read | 0 = No sensor; 1 = Sensor OK; 2 = Error | ||||
| HR | 11doc 0x000B | DEV_ID_REG (device identification) | Bits 11-15 device family, 9-10 hardware version, 4-8 type, 0-1 duct/room. | UINT16 | Read | ||||
| HR | 12doc 0x000C | SOFT_VER_REG (software version) | Four nibbles N.AB + revision letter (0x3210 = 3.21a). | UINT16 | Read |
Notes on this map
- All registers are 16-bit; there are no 32-bit values.
- Command parameters: 1 = address 1-247 (default 1); 2 = baud code 24/48/96/192/384/576/1152 for 2400-115200 bit/s (default 192 = 19200); 3 = parity 0 none (default), 1 even, 2 odd; 4 = stop bits 1 (default) or 2; 6 = 1 software reset of the device, 2 reset of the sensor module.
- Commands can be sent as one FC16 write of password + command + parameter, or as single writes with the password written last.
- Reserved registers 0x0006-0x0009 read 0 and are not listed. Reading an address outside the map returns exception 02.
- The DIP switches can override baud rate, parity and address; they are read only at power-up or after RESET.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the VTS RH+T-SENS-D-MODRTU humidity and temperature transducer
What Modbus registers does the VTS RH+T-SENS-D-MODRTU humidity and temperature transducer have?
This map lists 9 registers: 9 holding registers. 3 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the VTS RH+T-SENS-D-MODRTU humidity and temperature transducer Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The register map prints hex addresses starting at 0x0000, and the DEV_ID and SOFT_VER sections give 'addr=11=0x000B' and 'addr=12=0x000C', so the printed value is the wire address.
What are the minimum Modbus registers to integrate the VTS RH+T-SENS-D-MODRTU humidity and temperature transducer?
Start with HR 0 RH_REG (relative humidity) (Relative humidity); HR 1 TEMP_REG (temperature) (Temperature); HR 2 TEST_VAL_REG (Link test value); HR 10 STATUS_REG (Sensor status).
How do I enable Modbus control of the VTS RH+T-SENS-D-MODRTU humidity and temperature transducer?
Modbus RTU is always on. Set the address on the right DIP switch (binary, 1-247) or by command; left DIP switches 3-6 pick fixed parity/baud or 'use software settings'.
Where is the official VTS RH+T-SENS-D-MODRTU humidity and temperature transducer Modbus documentation?
The source is Humidity Transducer RH+T-SENS-D-MODRTU (ver. 2.0), revision 2021-11, published free by VTS at https://vtsgroup.com/files/document-files/3433/HUMID_EN_2.0.pdf.
More VTS Modbus register maps
- Sensor
VTS CO2-SENS-D-MODRTU
VTS CO2-SENS-D-MODRTU duct CO2 transducer (MH-Z19B sensing module), manual ver. 2.0 (11.2021).
Also known as: CO2 transducer CO2-SENS-D-MODRTU, VTS duct CO2 sensor - Thermostat (fan heater controller)
VTS HMI-VOLCANO EC controller for VOLCANO air heaters
VTS HMI-VOLCANO EC wall controller with Modbus RTU, device integration manual version 1.1.
Also known as: HMI VOLCANO EC, VOLCANO EC controller
Other valves, actuators & sensors register maps
- Sensor (duct averaging temperature)
ACI (Automation Components Inc.) Averaging Series BACnet/Modbus duct averaging temperature sensor
ACI Averaging Series copper and flexible duct averaging temperature sensors with the BACnet MS/TP / Modbus RTU interface (guide I0000932).
Also known as: Copper Averaging, Flexible Averaging, Averaging Series BACnet Modbus - Actuator / valve (damper and valve actuator)
Belimo Air/water actuators with Modbus RTU (..24A-MOD)
Belimo ..M(C)24A-MOD, ..R24A-MOD, ..V(K)24A-MOD, ..F24A-MOD, ..RF24A-MOD and ..H24A-MOD air/water actuators, per Modbus interface description edition 2026-05 / V3.08.
Also known as: LM24A-MOD, NM24A-MOD, SM24A-MOD, GM24A-MOD, LMC24A-MOD, NMC24A-MOD, NR24A-MOD, LR24A-MOD, NV24A-MOD, NVK24A-MOD, LF24A-MOD, NF24A-MOD, NRF24A-MOD, LRF24A-MOD, LH24A-MOD, SH24A-MOD - Sensor
Johnson Controls GS3000 indoor Modbus carbon monoxide transmitter
Johnson Controls GS3000 / GS3001 electrochemical CO transmitters with RS-485 Modbus RTU, per installation guide 24-11484-00021 (2020-10-01).
Also known as: GS3000, GS3001, 24-11484-00021 - Sensor (load-cell weight transmitter)
Laumas TLS weight transmitter with analog output (Modbus RTU)
Laumas TLS weight transmitter / indicator with RS-485, installation and user manual version 1.19.
Also known as: TLS, TLS 4-20mA, TLS 0-10V, CASTLTASTATEX - Sensor (load cell / strain gauge converter)
Seneca R-SG3 Ethernet load cell converter
R-SG3 in the Series R I/O manual MI-00604-29-EN.
Also known as: RSG3, R-SG3, Seneca R series strain gauge - Sensor (duct humidity / temperature / CO2 / VOC)
Siemens QFM9150/MO and QPM9152/MO duct sensors (Modbus RTU)
Siemens QFM9150/MO duct humidity/temperature sensor and QPM9152/MO duct air quality (CO2, VOC, humidity, temperature) sensor, basic documentation edition a (2022-12).
Also known as: QFM9150/MO, QPM9152/MO, S55720-S584, S55720-S585
All valves, actuators & sensors Modbus register maps →
Source: Humidity Transducer RH+T-SENS-D-MODRTU · ver. 2.0 · rev. 2021-11. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.