Sensor · Modbus register map
VTS CO2-SENS-D-MODRTU Modbus register map
Updated 17 November 2026
A duct-mounted CO2 transducer from VTS with a 0-5/0-10 V output and an RS-485 Modbus RTU interface. The measurement, sensor status and a fixed test value sit in the first three holding registers; configuration is done by writing a password, command and parameter into three registers. All registers are plain 16-bit values read with function 03.
This page lists 8 Modbus registers for the VTS CO2-SENS-D-MODRTU — 3 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from VTS’s own free documentation (linked below) and checked against it.
- Manufacturer
- VTS
- Model
- CO2-SENS-D-MODRTU
- Equipment type
- Sensor
- Registers
- 8 (3 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 19200 baud, 8N1
- Documented addressing
- hexadecimal, 0-based
- Also known as
- CO2 transducer CO2-SENS-D-MODRTU, VTS duct CO2 sensor
- Source document
- CO2 Transducer CO2-SENS-D-MODRTU · ver. 2.0 · rev. 2021-11
Integration notes: VTS CO2-SENS-D-MODRTU
Read three holding registers from 0x0000 with function 03: CO2 in ppm, status, and the 1000 test value. Check status is 1 before trusting the reading.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 0 | VALUE_REG (CO2 concentration) | UINT16 | CO2 concentration in ppm | Read |
| HR 1 | STATUS_REG | UINT16 | Sensor status / warm-up | Read |
| HR 2 | TEST_VAL_REG | UINT16 | Fixed 1000 test value for comms check | Read |
| HR 11 | DEV_ID_REG (device identification) | BITMAP16 | Device identification | Read |
Enable Modbus control & writes
Modbus RTU is always active. To change settings write password 1234, command and parameter to 0x0003-0x0005 in one function 16 write, or write command and parameter first and the password last.
Byte order & addressing
- An invalid or out-of-range parameter makes COMMAND_REG read 0xEEEE instead of executing.
- Status reads 3 (warm up) for the first 3 minutes after power-on.
Network setup
- Left DIP switch: switch 1 = 120 ohm termination, 2 = analogue range 0-5 V or 0-10 V, 3-4 = parity/stop bits or 'use software settings', 5-6 = baud 2400-19200.
- Right DIP switch sets the address in binary (switch 1 = +1 ... switch 8 = +128).
- DIP switch changes are read only at start-up: press RESET or cycle power after changing them.
Watch out for
- The DIP switches only offer 2400-19200 baud; 38400-115200 can only be set through the command registers.
VTS CO2-SENS-D-MODRTU Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 0x0000 | VALUE_REG (CO2 concentration) | CO2 concentration, 0-2000 ppm. | UINT16 | ppm | Read | |||
| HR | 1doc 0x0001 | STATUS_REG | Sensor state. | UINT16 | Read | 0 = Sensor missing; 1 = Correct operation; 2 = Sensor error; 3 = Warm up (first 3 minutes after start) | |||
| HR | 2doc 0x0002 | TEST_VAL_REG | Always 1000 (0x03E8); use it to check reads are correct. | UINT16 | Read | ||||
| HR | 3doc 0x0003 | PASS_REG (password) | Write 1234 (0x04D2) to execute the command in COMMAND_REG/PARAM_REG. | UINT16 | Read/write | ||||
| HR | 4doc 0x0004 | COMMAND_REG | Command number; reads 0xEEEE after an invalid parameter. | UINT16 | Read/write | 1 = Set device address; 2 = Set baud rate; 3 = Set parity; 4 = Set stop bits; 5 = ABClogic on/off; 6 = Device reset | |||
| HR | 5doc 0x0005 | PARAM_REG | Parameter for the command; see notes for the value list per command. | UINT16 | Read/write | ||||
| HR | 11doc 0x000B | DEV_ID_REG (device identification) | Basic duct CO2 version reads 0xC100. | BITMAP16 | Read | bit 0-1 = T: type (0 duct, 1 room); bit 2-3 = Always 0; bit 4-8 = OPTIONS: device type (b10000 = CO2 transducer with MH-Z19B); bit 9-10 = HV: hardware version; bit 11-15 = DEV: b11000 = air parameter sensor | |||
| HR | 12doc 0x000C | SOFT_VER_REG (software version) | Four nibbles N.AB + revision letter, e.g. 0x3210 = 3.21a. | BITMAP16 | Read | bit 0-3 = REV: revision letter (0 = a ... 9 = j); bit 4-7 = B digit; bit 8-11 = A digit; bit 12-15 = N digit |
Notes on this map
- All registers are 16-bit; there are no 32-bit values in this map.
- Command parameters: 1 = address 1-247 (default 1); 2 = baud code 24/48/96/192/384/576/1152 for 2400-115200 bit/s (default 192 = 19200); 3 = parity 0 none (default), 1 even, 2 odd; 4 = stop bits 1 (default) or 2; 5 = ABClogic 0 off (default) / 1 on; 6 = 1 software reset of device, 2 reset of sensor module.
- The defaults above are the software-configuration defaults from the command table. The DIP switches can override baud rate, parity and address; their factory positions are marked in bold in the manual and could not be confirmed from the text.
- Reserved registers 0x0006-0x000A read 0 and are not listed. Reading any address not in the map returns exception 02.
- The manual lists functions 03, 06 and 16 only; use function 03 (read holding registers) for all reads.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the VTS CO2-SENS-D-MODRTU
What Modbus registers does the VTS CO2-SENS-D-MODRTU have?
This map lists 8 registers: 8 holding registers. 3 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the VTS CO2-SENS-D-MODRTU Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The register map lists addresses in hex from 0x0000, and the DEV_ID description gives 'addr=11=0x000B', so the printed value is the wire address.
What are the minimum Modbus registers to integrate the VTS CO2-SENS-D-MODRTU?
Start with HR 0 VALUE_REG (CO2 concentration) (CO2 concentration in ppm); HR 1 STATUS_REG (Sensor status / warm-up); HR 2 TEST_VAL_REG (Fixed 1000 test value for comms check); HR 11 DEV_ID_REG (device identification) (Device identification).
How do I enable Modbus control of the VTS CO2-SENS-D-MODRTU?
Modbus RTU is always active. To change settings write password 1234, command and parameter to 0x0003-0x0005 in one function 16 write, or write command and parameter first and the password last.
Where is the official VTS CO2-SENS-D-MODRTU Modbus documentation?
The source is CO2 Transducer CO2-SENS-D-MODRTU (ver. 2.0), revision 2021-11, published free by VTS at https://www.vtsgroup.com/files/document-files/3430/CO2_EN_2.0.pdf.
More VTS Modbus register maps
- Thermostat (fan heater controller)
VTS HMI-VOLCANO EC controller for VOLCANO air heaters
VTS HMI-VOLCANO EC wall controller with Modbus RTU, device integration manual version 1.1.
Also known as: HMI VOLCANO EC, VOLCANO EC controller - Sensor
VTS RH+T-SENS-D-MODRTU humidity and temperature transducer
VTS RH+T-SENS-D-MODRTU duct humidity and temperature transducer (Sensirion SHT31-DIS-B), manual ver. 2.0 (11.2021).
Also known as: RH&T-SENS-D-MODRTU, VTS duct humidity sensor
Other valves, actuators & sensors register maps
- Sensor (limit controller)
Yokogawa UTAdvanced UT35A-L limit controller
Yokogawa UT35A-L limit controllers with RS-485 (Modbus RTU/ASCII); process monitoring D registers from IM 05P07A01-01EN chapter 12.
Also known as: UT35A-L - Actuator / valve (6-way pressure-independent change-over valve)
Belimo 6-way EPIV Modbus RTU (EP..R-R6+BAC)
Belimo 6-way EPIV EP..R-R6+BAC on Modbus RTU, per 6-way EPIV Modbus Register en-gb 2024-01 (general notes dated 16.12.2019).
Also known as: EP..R-R6+BAC, 6-way pressure-independent valve - Sensor
Fronius Fronius Sensor Card via Datamanager (SunSpec 302/303/307)
A Fronius Sensor Card connected to a Fronius Datamanager over Solar Net and republished by it as a SunSpec device; the same layout is used for the float and int+SF settings.
Also known as: Fronius Sensor Card, IG Sensor Card - Sensor (load-cell weight transmitter)
Laumas TLB4 four-channel weight transmitter (Modbus RTU / Modbus TCP)
Laumas TLB4 with the Modbus RTU port or the Modbus/TCP option; communication protocols manual version 1.12. Direct registers only.
Also known as: TLB4, TLB4 MODBUS, TLB4 Modbus/TCP - Actuator / valve
Rotork Modbus RTU Mk3 option card (IQ3, SI3/SI4, CK, CVA, CMA, K-range)
Rotork Modbus RTU Mk3 option module (MFU) in IQ3, SI3, SI4, CK, CVA (firmware CVA1.14 or later), CMA and K-range actuators, using the default Rotork database (register 80 = 0), per PUB091-004-00 issue 08/25.
Also known as: IQ3 Modbus, Rotork MFU Mk3, Modbus Mk3 module, SI3 Modbus, SI4 Modbus, CK Modbus, CVA Modbus, CMA Modbus, K-range Modbus - Sensor (room humidity / temperature)
Siemens QFA3150/MO room humidity and temperature sensor (Modbus RTU)
Siemens QFA3150/MO room relative humidity and temperature sensor, basic documentation edition a (2021-01).
Also known as: QFA3150/MO, S55720-S535
All valves, actuators & sensors Modbus register maps →
Source: CO2 Transducer CO2-SENS-D-MODRTU · ver. 2.0 · rev. 2021-11. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.