- TLB4 four-channel weight transmitter (Modbus RTU / Modbus TCP)
Sensor (load-cell weight transmitter) · Modbus register map
Laumas TLB4 four-channel weight transmitter (Modbus RTU / Modbus TCP) Modbus register map
Updated 17 November 2026
The TLB4 is a DIN-rail weight transmitter for up to four load cells. Over Modbus RTU (or the Modbus/TCP version, which uses the same register list) it exposes gross, net and peak weight, a status word, digital I/O, setpoints and calibration values as holding registers, and takes commands (tare, zero, save) through a single command register. This map lists the directly addressed registers; settings reached through the exchange registers are left out.
This page lists 25 Modbus registers for the Laumas TLB4 four-channel weight transmitter (Modbus RTU / Modbus TCP) — 12 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Laumas’s own free documentation (linked below) and checked against it.
- Manufacturer
- Laumas
- Model
- TLB4 four-channel weight transmitter (Modbus RTU / Modbus TCP)
- Equipment type
- Sensor (load-cell weight transmitter)
- Registers
- 25 (12 writable)
- Transport
- Modbus RTU, Modbus TCP
- Default unit ID
- Not stated
- TCP port
- 502
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- TLB4, TLB4 MODBUS, TLB4 Modbus/TCP
Integration notes: Laumas TLB4 four-channel weight transmitter (Modbus RTU / Modbus TCP)
Read 40007-40013 in one FC3 request: status word, then gross, net and peak weight as 32-bit H/L pairs. Apply the sign bits from the status word and the decimals from the division index. Write 7 / 9 / 8 to the command register 40006 for tare on, tare off and zero.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 6 | Status register (SR1) | BITMAP16 | Status: stability, sign and load-cell errors | Read |
| HR 7 | Gross weight (GW) | UINT32 ABCD | Gross weight | Read |
| HR 9 | Net weight (NW) | UINT32 ABCD | Net weight | Read |
| HR 13 | Divisions and units of measure (DU) | UINT16 | Division index for the implied decimals | Read |
| HR 5 | Command register (CMDR) | UINT16 | Command register for tare / zero | Read/write |
| HR 16 | Digital inputs (INS) | BITMAP16 | Digital inputs | Read |
Enable Modbus control & writes
Select Modbus RTU in the instrument's serial communication menu and set address, baud, parity and stop bits there. The Modbus/TCP version gets its IP address from the Lantronix DeviceInstaller tool and listens on port 502.
Byte order & addressing
- Only FC3 and FC16 are supported; use FC16 even for a single register (the manual's examples write with FC16).
- At most 32 registers per request.
- Weights carry no sign: check SR1 bits 7 (gross), 8 (net), 9 (peak).
- Setpoints and some values are written to EEPROM (limited to about 100000 writes); setpoints themselves stay in RAM until command 99.
Network setup
- Set the RS-485 address (1-99), baud rate, parity and stop bits in the instrument's serial communication setting menu.
- For Modbus/TCP use port 502; the register set is identical to RTU.
Watch out for
- Broadcast (address 0) writes are executed with no reply; broadcast reads are ignored.
- Setpoints and hysteresis values are set to zero if the calibration is changed significantly.
Laumas TLB4 four-channel weight transmitter (Modbus RTU / Modbus TCP) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 40001 | Firmware version | UINT16 | Read | |||||
| HR | 1doc 40002 | Instrument type | UINT16 | Read | |||||
| HR | 2doc 40003 | Year of manufacture | UINT16 | Read | |||||
| HR | 3doc 40004 | Serial number | UINT16 | Read | |||||
| HR | 4doc 40005 | Program type | BASE or LOAD program; some registers apply to one program only. | UINT16 | Read | ||||
| HR | 5doc 40006 | Command register (CMDR) | Write a command code to run it; see notes for the codes. | UINT16 | Read/write | 7 = Semi-automatic tare on (net weight); 8 = Semi-automatic zero; 9 = Tare off (back to gross); 99 = Save setpoints to EEPROM; 100 = Tare weight zero setting (calibration zero); 101 = Acquire single calibration point (sample weight in CALW); 104 = Cancel real calibration; 106 = Acquire one of multiple calibration points; 130 = Activate preset tare (value in PT) | |||
| HR | 6doc 40007 | Status register (SR1) | Weight sign, stability and error flags. | BITMAP16 | Read | bit 0 = Load cell error; bit 1 = AD converter malfunction; bit 2 = Maximum weight exceeded by 9 divisions; bit 3 = Gross weight over 110% of full scale; bit 4 = Gross weight over 999999 or under -999999; bit 5 = Net weight over 999999 or under -999999; bit 7 = Gross weight negative sign; bit 8 = Net weight negative sign; bit 9 = Peak weight negative sign; bit 10 = Net display mode; bit 11 = Weight stable; bit 12 = Weight within +/- 1/4 division of zero; bit 15 = Load cell references not connected | |||
| HR | 7doc 40008 | Gross weight (GW) | Magnitude without decimal point; sign is SR1 bit 7. | UINT32 | ABCD | Read | |||
| HR | 9doc 40010 | Net weight (NW) | Magnitude without decimal point; sign is SR1 bit 8. | UINT32 | ABCD | Read | |||
| HR | 11doc 40012 | Peak weight (PW) | Magnitude without decimal point; sign is SR1 bit 9. BASE program. | UINT32 | ABCD | Read | |||
| HR | 13doc 40014 | Divisions and units of measure (DU) | High byte = unit index, low byte = division index (decimals). | UINT16 | Read | ||||
| HR | 14doc 40015 | Display coefficient (COF) | Coefficient x 10000 (BASE program). | UINT32 | ABCD | × 0.0001 | Read | ||
| HR | 16doc 40017 | Digital inputs (INS) | BITMAP16 | Read | bit 0 = Input 1 high; bit 1 = Input 2 high | ||||
| HR | 17doc 40018 | Digital outputs (OUTS) | BITMAP16 | Read/write | bit 0 = Output 1 closed; bit 1 = Output 2 closed; bit 2 = Output 3 closed | ||||
| HR | 18doc 40019 | Setpoint 1 (SP1) | Weight value without decimal point. RAM only until command 99. | INT32 | ABCD | Read/write | |||
| HR | 20doc 40021 | Setpoint 2 (SP2) | Weight value without decimal point. RAM only until command 99. | INT32 | ABCD | Read/write | |||
| HR | 22doc 40023 | Setpoint 3 (SP3) | Weight value without decimal point. RAM only until command 99. | INT32 | ABCD | Read/write | |||
| HR | 38doc 40039 | Hysteresis 1 (HYS1) | Weight value without decimal point. | INT32 | ABCD | Read/write | |||
| HR | 40doc 40041 | Hysteresis 2 (HYS2) | Weight value without decimal point. | INT32 | ABCD | Read/write | |||
| HR | 42doc 40043 | Hysteresis 3 (HYS3) | Weight value without decimal point. | INT32 | ABCD | Read/write | |||
| HR | 49doc 40050 | Instrument status (IS) | LOAD program only: batching state code. | UINT16 | Read | 0 = Idle (weight display); 1 = Formulas display; 2 = Batching constants display; 3 = Consumption display; 4 = System parameters display; 5 = Setting formula number and cycles; 6 = Batching; 12 = Batching waiting phase; 13 = Batching paused; 14 = Batching cycle end phase; 20 = Weight not stable | |||
| HR | 64doc 40065 | Sample weight for calibration (CALW) | Write the loaded test weight, then command 101 or 106; reads back 0 when OK. | INT32 | ABCD | Read/write | |||
| HR | 66doc 40067 | Analog output zero weight (ANA0) | Weight giving analog zero; saved to EEPROM. | INT32 | ABCD | Read/write | |||
| HR | 68doc 40069 | Analog output full-scale weight (ANAFS) | Weight giving analog full scale; saved to EEPROM. | INT32 | ABCD | Read/write | |||
| HR | 72doc 40073 | Preset tare (PT) | Write the tare, then command 130 to apply it. | INT32 | ABCD | Read/write |
Notes on this map
- Host: this copy is hosted by AutomationDirect, not by Laumas; a short search did not find the same protocols manual as a direct download on laumas.com.
- Word order: every 32-bit value is an H/L register pair with the high word at the lower address. The manual's read example returns gross weight 4000 as 0x0000 0x0FA0 at 40008-40009, so ABCD is documented.
- Weights (GW, NW, PW) are positive magnitudes with the decimals implied by the division setting (DU low byte); the sign comes from SR1 bits 7-9. The manual says the calibration weight CALW is a signed 32-bit number (two's complement for negatives). It does not state signedness for setpoints, hysteresis, analog weights or preset tare; they are typed INT32 here, which only matters for negative values.
- Left out: exchange registers 40051-40064 (R1/W1, EXC, AEXC). The list prints them as fourteen single registers while the other fieldbuses describe R1/W1 and EXC/AEXC as 4-byte values, and the exact register split for Modbus is not stated.
- Parameters such as filter, sensitivity, full scale and zero tracking are reached by writing W1 and sending a 65xx command to CMDR; they are not listed because they go through the exchange registers.
- Program type matters: peak weight, display coefficient, setpoints and CMDOUT are BASE program features; instrument status IS is LOAD program only.
- Serial settings (baud, parity, address 1-99) are set from the instrument's own menu; the protocols manual does not give factory values.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Laumas TLB4 four-channel weight transmitter (Modbus RTU / Modbus TCP)
What Modbus registers does the Laumas TLB4 four-channel weight transmitter (Modbus RTU / Modbus TCP) have?
This map lists 25 registers: 25 holding registers. 12 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Laumas TLB4 four-channel weight transmitter (Modbus RTU / Modbus TCP) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are printed 40001-40074. Laumas says to subtract 40001 for a 0-based client (40028 -> 27). The manual's read example asks for start address 0x0007 to read gross weight at 40008, confirming the offset.
What byte order does the Laumas TLB4 four-channel weight transmitter (Modbus RTU / Modbus TCP) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Laumas TLB4 four-channel weight transmitter (Modbus RTU / Modbus TCP)?
Start with HR 6 Status register (SR1) (Status: stability, sign and load-cell errors); HR 7 Gross weight (GW) (Gross weight); HR 9 Net weight (NW) (Net weight); HR 13 Divisions and units of measure (DU) (Division index for the implied decimals); HR 5 Command register (CMDR) (Command register for tare / zero); HR 16 Digital inputs (INS) (Digital inputs).
How do I enable Modbus control of the Laumas TLB4 four-channel weight transmitter (Modbus RTU / Modbus TCP)?
Select Modbus RTU in the instrument's serial communication menu and set address, baud, parity and stop bits there. The Modbus/TCP version gets its IP address from the Lantronix DeviceInstaller tool and listens on port 502.
Where is the official Laumas TLB4 four-channel weight transmitter (Modbus RTU / Modbus TCP) Modbus documentation?
The source is TLB4 User Manual - Communication Protocols (version 1.12). Laumas doesn't publish it on its own website, so this map was re-typed from a free copy at https://cdn.automationdirect.com/static/manuals/laumas/tlb4protocolsmanualen.pdf. It may be an older revision, so check it against the live unit.
More Laumas Modbus register maps
- Sensor (load-cell weight transmitter)
Laumas TLS weight transmitter with analog output (Modbus RTU)
Laumas TLS weight transmitter / indicator with RS-485, installation and user manual version 1.19.
Also known as: TLS, TLS 4-20mA, TLS 0-10V, CASTLTASTATEX - Sensor (load-cell weight indicator)
Laumas WLIGHT weight indicator / transmitter (Modbus RTU)
Laumas WLIGHT, installation and user manual version 1.03.
Also known as: WLIGHT, W LIGHT
Other valves, actuators & sensors register maps
- Actuator / valve
Rotork Modbus RTU Mk3 option card (IQ3, SI3/SI4, CK, CVA, CMA, K-range)
Rotork Modbus RTU Mk3 option module (MFU) in IQ3, SI3, SI4, CK, CVA (firmware CVA1.14 or later), CMA and K-range actuators, using the default Rotork database (register 80 = 0), per PUB091-004-00 issue 08/25.
Also known as: IQ3 Modbus, Rotork MFU Mk3, Modbus Mk3 module, SI3 Modbus, SI4 Modbus, CK Modbus, CVA Modbus, CMA Modbus, K-range Modbus - Sensor (room humidity / temperature)
Siemens QFA3150/MO room humidity and temperature sensor (Modbus RTU)
Siemens QFA3150/MO room relative humidity and temperature sensor, basic documentation edition a (2021-01).
Also known as: QFA3150/MO, S55720-S535 - Sensor (temperature / humidity data logger)
Teracom TCW210-TH temperature and humidity data logger
TCW210-TH per the Teracom TCW210-TH user manual Revision R1.26, firmware V2.012 or later.
Also known as: TCW210-TH, TCW210 - Sensor (humidity / temperature)
Teracom TSM400-4-TH Modbus humidity and temperature sensor
TSM400-4-TH per the Teracom TSM400-4-TH user manual TSM400-4-TH-R1.10.
Also known as: TSM400-4-TH - Sensor (CO2 duct transmitter)
Vaisala GMD110 duct CO2 transmitter (Modbus RTU)
GMD110 duct-mount CO2 transmitter, Modbus RTU interface (user guide M212885EN-B).
Also known as: GMD110, CARBOCAP GMD110 - Sensor (humidity and temperature probe)
Vaisala HMP60 / HMP110 series humidity and temperature probes (Modbus RTU)
HMP60/HMP110-series probes ordered with the Modbus RTU option (user guide M211060EN-N).
Also known as: HMP110, HMP113, HMP115, TMP115, HMP60, HMP63, HUMICAP HMP110, HMP110T, HMP63T, HMP115T
All valves, actuators & sensors Modbus register maps →
Source: TLB4 User Manual - Communication Protocols · version 1.12 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.