Actuator / valve · Modbus register map
Rotork Modbus RTU Mk3 option card (IQ3, SI3/SI4, CK, CVA, CMA, K-range) Modbus register map
Updated 19 November 2026
The Mk3 Modbus module puts a Rotork electric valve actuator on an RS-485 Modbus RTU highway (single, dual or repeater versions). Open, close, stop, ESD and partial stroke can be sent as coils or as one register value, and position control uses a 0-100.0 % set-point register. Status bits, torque and valve position can be read as discrete inputs, input registers or holding registers, and holding registers 7-31 hold the positioner, comms-loss and network settings.
This page lists 98 Modbus registers for the Rotork Modbus RTU Mk3 option card (IQ3, SI3/SI4, CK, CVA, CMA, K-range) — 36 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Rotork’s own free documentation (linked below) and checked against it.
- Manufacturer
- Rotork
- Model
- Modbus RTU Mk3 option card (IQ3, SI3/SI4, CK, CVA, CMA, K-range)
- Equipment type
- Actuator / valve
- Registers
- 98 (36 writable)
- Transport
- Modbus RTU
- Default unit ID
- 247
- Default serial
- 9600 baud, 8N1
- Documented addressing
- 0-based (the number printed is the address on the wire)
- 32-bit word order
- CDAB low word first (word-swapped)
- Firmware
- Modbus module firmware V104 or later
- Also known as
- IQ3 Modbus, Rotork MFU Mk3, Modbus Mk3 module, SI3 Modbus, SI4 Modbus, CK Modbus, CVA Modbus, CMA Modbus, K-range Modbus
Integration notes: Rotork Modbus RTU Mk3 option card (IQ3, SI3/SI4, CK, CVA, CMA, K-range)
Read input registers 0-4 (status bits, torque, position) with function 04 or 03. Command the valve by writing register 5 (0 stop, 1 close, 2 open, 3 ESD) or send a position in 0.1 % to register 6. The actuator selector must be in Remote.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 0 | Status word 1 | BITMAP16 | Status: limits, moving, remote/local, alarms | Read |
| IR 1 | Status word 2 | BITMAP16 | Status: interlocks, DIs, general alarm | Read |
| IR 3 | Valve position | UINT16 | Valve position, 0.1 % | Read |
| IR 2 | Actuator instantaneous torque | UINT16 | Instantaneous torque, % | Read |
| HR 5 | Actuator digital control | UINT16 | Digital control command | Read/write |
| HR 6 | Actuator position DV (desired value) | UINT16 | Position set-point, 0.1 % | Read/write |
| HR 7 | Action on loss of comms | UINT16 | Action on loss of comms | Read/write |
Enable Modbus control & writes
Set the module address (register 22, default 247), baud (23) and parity (24) with a Modbus tool or the Rotork setting tool over IR/Bluetooth. Turn the actuator's local/remote selector to Remote. Keep register 80 at 0.
Communication loss & watchdog
If no network traffic is seen for the comms fault timer (register 21, default 10 s), the actuator does what register 7 says: nothing (default), open, close, stop, or move to the comms lost position in register 13.
Byte order & addressing
- Addresses are already 0-based: holding register 5 is 40006 in 1-based host software.
- Writing 0 % or 100 % to the position register runs to the tight shut-off or full open limit unless limited-range positioning is set.
- Only register 5 values 0 (stop) and 3 (ESD), and coils 0 and 3, accept broadcast (address 0).
Network setup
- RS-485 two-wire half duplex, 300 to 115200 baud, 8 data bits, odd/even/none parity, 1 or 2 stop bits.
- Switch on module termination (register 25) only on the last device of a segment; use network biasing somewhere on the highway.
- Replies can take up to 190 ms; a segment takes up to 32 nodes, more with repeaters.
Watch out for
- Every new module ships at address 247, which the manual says should never stay in use on a live system; readdress each actuator before adding the next.
- Dual-channel modules share one baud/parity setting; leave an 11-byte idle gap on port 1 so port 2 messages are answered.
- Setting the deadband below the hysteresis forces the hysteresis to 0.1 %.
Rotork Modbus RTU Mk3 option card (IQ3, SI3/SI4, CK, CVA, CMA, K-range) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 0 | Stop command | BIT | Read/write | |||||
| CO | 1 | Close command | BIT | Read/write | |||||
| CO | 2 | Open command | BIT | Read/write | |||||
| CO | 3 | ESD command | BIT | Read/write | |||||
| CO | 4 | DO-1 (extra relay S5) | Needs the extra relay / DIO board. | BIT | Read/write | ||||
| CO | 5 | DO-2 (extra relay S6) | Needs the extra relay / DIO board. | BIT | Read/write | ||||
| CO | 6 | DO-3 (extra relay S7) | Needs the extra relay / DIO board. | BIT | Read/write | ||||
| CO | 7 | DO-4 (extra relay S8) | Needs the extra relay / DIO board. | BIT | Read/write | ||||
| CO | 8 | Partial stroke test | BIT | Read/write | |||||
| CO | 9 | DO-5 (actuator relay S1, IQ3 only) | BIT | Read/write | |||||
| CO | 10 | DO-6 (actuator relay S2, IQ3 only) | BIT | Read/write | |||||
| CO | 11 | DO-7 (actuator relay S3, IQ3 only) | BIT | Read/write | |||||
| CO | 12 | DO-8 (actuator relay S4, IQ3 only) | BIT | Read/write | |||||
| DI | 0 | Actuator moving | BIT | Read | |||||
| DI | 1 | Closed position limit | BIT | Read | |||||
| DI | 2 | Open position limit | BIT | Read | |||||
| DI | 3 | Running closed | BIT | Read | |||||
| DI | 4 | Running open | BIT | Read | |||||
| DI | 5 | Remote selected | BIT | Read | |||||
| DI | 6 | Local Stop selected | BIT | Read | |||||
| DI | 7 | Local selected | BIT | Read | |||||
| DI | 8 | Thermostat tripped | BIT | Read | |||||
| DI | 9 | Monitor relay | BIT | Read | |||||
| DI | 10 | Valve obstructed | BIT | Read | |||||
| DI | 11 | Valve jammed | BIT | Read | |||||
| DI | 12 | Valve moving by hand | BIT | Read | |||||
| DI | 13 | Moving inhibited by MIT | BIT | Read | |||||
| DI | 14 | Position control enabled | BIT | Read | |||||
| DI | 16 | Battery low | BIT | Read | |||||
| DI | 17 | Open interlock active | BIT | Read | |||||
| DI | 18 | Close interlock active | BIT | Read | |||||
| DI | 19 | DI-1 | BIT | Read | |||||
| DI | 20 | DI-2 | BIT | Read | |||||
| DI | 21 | DI-3 | BIT | Read | |||||
| DI | 22 | DI-4 | BIT | Read | |||||
| DI | 26 | Control contention | BIT | Read | |||||
| DI | 27 | Partial stroke test in progress | BIT | Read | |||||
| DI | 28 | Partial stroke test error | BIT | Read | |||||
| DI | 29 | General alarm | Battery, valve, actuator or control alarm, jam/obstruction or monitor relay. | BIT | Read | ||||
| IR | 0 | Status word 1 | Same bits as discrete inputs 0-14; bit 15 left out (see notes). | BITMAP16 | Read | bit 0 = Actuator moving; bit 1 = Closed position limit; bit 2 = Open position limit; bit 3 = Running closed; bit 4 = Running open; bit 5 = Remote selected; bit 6 = Local Stop selected; bit 7 = Local selected; bit 8 = Thermostat tripped; bit 9 = Monitor relay; bit 10 = Valve obstructed; bit 11 = Valve jammed; bit 12 = Valve moving by hand; bit 13 = Moving inhibited by MIT; bit 14 = Position control enabled | |||
| IR | 1 | Status word 2 | Same bits as discrete inputs 16-29. | BITMAP16 | Read | bit 0 = Battery low; bit 1 = Open interlock active; bit 2 = Close interlock active; bit 3 = DI-1; bit 4 = DI-2; bit 5 = DI-3; bit 6 = DI-4; bit 10 = Control contention; bit 11 = Partial stroke test in progress; bit 12 = Partial stroke test error; bit 13 = General alarm | |||
| IR | 2 | Actuator instantaneous torque | 0-0x78 = 0-120 %. | UINT16 | % | Read | |||
| IR | 3 | Valve position | 0-0x3E8 = 0.0-100.0 %. | UINT16 | × 0.1 | % | Read | ||
| IR | 4 | Analogue input | Optional analogue card (IQ3); 0-0x3E8 = 0.0-100.0 %. | UINT16 | × 0.1 | % | Read | ||
| HR | 0 | Status word 1 | Same bits as discrete inputs 0-14; bit 15 left out (see notes). | BITMAP16 | Read | bit 0 = Actuator moving; bit 1 = Closed position limit; bit 2 = Open position limit; bit 3 = Running closed; bit 4 = Running open; bit 5 = Remote selected; bit 6 = Local Stop selected; bit 7 = Local selected; bit 8 = Thermostat tripped; bit 9 = Monitor relay; bit 10 = Valve obstructed; bit 11 = Valve jammed; bit 12 = Valve moving by hand; bit 13 = Moving inhibited by MIT; bit 14 = Position control enabled | |||
| HR | 1 | Status word 2 | Same bits as discrete inputs 16-29. | BITMAP16 | Read | bit 0 = Battery low; bit 1 = Open interlock active; bit 2 = Close interlock active; bit 3 = DI-1; bit 4 = DI-2; bit 5 = DI-3; bit 6 = DI-4; bit 10 = Control contention; bit 11 = Partial stroke test in progress; bit 12 = Partial stroke test error; bit 13 = General alarm | |||
| HR | 2 | Actuator instantaneous torque | 0-0x78 = 0-120 %. | UINT16 | % | Read | |||
| HR | 3 | Valve position | 0-0x3E8 = 0.0-100.0 %. | UINT16 | × 0.1 | % | Read | ||
| HR | 4 | Analogue input | Optional analogue card (IQ3); 0-0x3E8 = 0.0-100.0 %. | UINT16 | × 0.1 | % | Read | ||
| HR | 5 | Actuator digital control | Write one command value; broadcast allowed for 0 and 3. | UINT16 | Read/write | 0 = Stop; 1 = Close; 2 = Open; 3 = ESD; 4 = Partial stroke test | |||
| HR | 6 | Actuator position DV (desired value) | 0-0x3E8 = 0.0-100.0 %; 0 and 100 % drive to the tight-shut / full-open limits. | UINT16 | × 0.1 | % | Read/write | ||
| HR | 7 | Action on loss of comms | Taken after the comms fault timer (register 21) expires. | UINT16 | Read/write | 0 = Nothing (default); 1 = Open; 3 = Close; 5 = Stop; 7 = Go to comms lost position (register 13) | |||
| HR | 8 | Limited range position minimum | 0-100 %, default 0. | UINT16 | % | Read/write | |||
| HR | 9 | Limited range position maximum | 0-100 %, default 100. | UINT16 | % | Read/write | |||
| HR | 10 | Deadband | 0-25.5 %, default 5.0 % (0x32). | UINT16 | × 0.1 | % | Read/write | ||
| HR | 11 | Motion inhibit time | Minimum idle time between positioning starts, 0-255 s, default 5. | UINT16 | s | Read/write | |||
| HR | 12 | Aux input mask | High nibble enables inputs as commands, low nibble sets contact sense; default 15. | BITMAP16 | Read/write | bit 0 = Open input: closed contact reports 1; bit 1 = Close input: closed contact reports 1; bit 2 = Stop/Maintain input: closed contact reports 1; bit 3 = ESD input: closed contact reports 1; bit 4 = Enable Open input as command; bit 5 = Enable Close input as command; bit 6 = Enable Stop/Maintain input as command; bit 7 = Enable ESD input as command | |||
| HR | 13 | Comms lost position | 0-100 %, default 0; used when register 7 = 7. | UINT16 | % | Read/write | |||
| HR | 14 | Hysteresis | 0-25.5 %, default 2.0 % (0x14). | UINT16 | × 0.1 | % | Read/write | ||
| HR | 15 | Slow mode range | 0-100 %, default 5. | UINT16 | % | Read/write | |||
| HR | 16 | Valve jammed time | 0-255 s, default 5. | UINT16 | s | Read/write | |||
| HR | 17 | Manual movement travel | 0-100 %, default 10. | UINT16 | % | Read/write | |||
| HR | 18 | Watchdog timeout | 0-255 s, default 10. | UINT16 | s | Read/write | |||
| HR | 19 | ESD DI-4 / net disable | IQ3: what the ESD/DI-4 remote input does. | UINT16 | Read/write | 0 = DI-4 is ESD (default); 1 = DI-4 is network disable | |||
| HR | 20 | Analogue input max/min | Calibration: write 1 with max input applied, then 2 with min applied. | UINT16 | Read/write | ||||
| HR | 21 | Comms fault timer | Seconds without traffic before register 7 acts; default 10. | UINT16 | s | Read/write | |||
| HR | 22 | Modbus address | 1-247, default 247. | UINT16 | Read/write | ||||
| HR | 23 | Baud rate | UINT16 | Read/write | 1 = 300; 2 = 600; 3 = 1200; 4 = 2400; 5 = 4800; 6 = 9600 (default); 7 = 19200; 8 = 38400; 9 = 57600; 10 = 115200 | ||||
| HR | 24 | Parity / stop bits | UINT16 | Read/write | 0 = No parity, 1 stop bit (default); 1 = No parity, 2 stop bits; 2 = Even, 1 stop bit; 3 = Even, 2 stop bits; 4 = Odd, 1 stop bit; 5 = Odd, 2 stop bits | ||||
| HR | 25 | Network termination | Switch on only at the last device of a segment. | UINT16 | Read/write | 0 = Off (default); 1 = On | |||
| HR | 26 | Actuator tag name | 12 ASCII characters, one per byte, registers 26-31. | STRING[12] | Read/write | ||||
| HR | 32 | Close torque set | 0-0x78 = 0-120 %. | UINT16 | % | Read | |||
| HR | 33 | Open torque set | 0-0x78 = 0-120 %. | UINT16 | % | Read | |||
| HR | 34 | Torque at 0% - open direction | Data logger, 0-120 %. | UINT16 | % | Read | |||
| HR | 35 | Torque at 10% - open direction | Data logger, 0-120 %. | UINT16 | % | Read | |||
| HR | 36 | Torque at 20% - open direction | Data logger, 0-120 %. | UINT16 | % | Read | |||
| HR | 37 | Torque at 30% - open direction | Data logger, 0-120 %. | UINT16 | % | Read | |||
| HR | 38 | Torque at 40% - open direction | Data logger, 0-120 %. | UINT16 | % | Read | |||
| HR | 39 | Torque at 50% - open direction | Data logger, 0-120 %. | UINT16 | % | Read | |||
| HR | 40 | Torque at 60% - open direction | Data logger, 0-120 %. | UINT16 | % | Read | |||
| HR | 41 | Torque at 70% - open direction | Data logger, 0-120 %. | UINT16 | % | Read | |||
| HR | 42 | Torque at 80% - open direction | Data logger, 0-120 %. | UINT16 | % | Read | |||
| HR | 43 | Torque at 90% - open direction | Data logger, 0-120 %. | UINT16 | % | Read | |||
| HR | 44 | Torque at 100% - open direction | Data logger, 0-120 %. | UINT16 | % | Read | |||
| HR | 45 | Torque at 0% - close direction | Data logger, 0-120 %. | UINT16 | % | Read | |||
| HR | 46 | Torque at 10% - close direction | Data logger, 0-120 %. | UINT16 | % | Read | |||
| HR | 47 | Torque at 20% - close direction | Data logger, 0-120 %. | UINT16 | % | Read | |||
| HR | 48 | Torque at 30% - close direction | Data logger, 0-120 %. | UINT16 | % | Read | |||
| HR | 49 | Torque at 40% - close direction | Data logger, 0-120 %. | UINT16 | % | Read | |||
| HR | 50 | Torque at 50% - close direction | Data logger, 0-120 %. | UINT16 | % | Read | |||
| HR | 51 | Torque at 60% - close direction | Data logger, 0-120 %. | UINT16 | % | Read | |||
| HR | 52 | Torque at 70% - close direction | Data logger, 0-120 %. | UINT16 | % | Read | |||
| HR | 53 | Torque at 80% - close direction | Data logger, 0-120 %. | UINT16 | % | Read | |||
| HR | 54 | Torque at 90% - close direction | Data logger, 0-120 %. | UINT16 | % | Read | |||
| HR | 55 | Torque at 100% - close direction | Data logger, 0-120 %. | UINT16 | % | Read | |||
| HR | 56 | Close motor starts | Low word at 56, high at 57. On CVA, 56 and 57 are separate contactor counts. | UINT32 | CDAB | Read | |||
| HR | 58 | Open motor starts | Low word at 58, high at 59. On CVA, 58 is total distance; 59 unused. | UINT32 | CDAB | Read | |||
| HR | 80 | Database type | Leave at 0; 1 selects Custom Database A1. | UINT16 | Read/write | 0 = Rotork (default); 1 = Custom Database A1 |
Notes on this map
- Only two 32-bit values exist (motor start counts); the manual labels the low order word at the lower register and the high order word at the next one, so they are CDAB.
- Holding registers 0-4 and input registers 0-4 carry the same data; registers 0 and 1 pack the same bits as discrete inputs 0-29 (bit 0/15 excepted, see below).
- Ranges are printed in hex: torque 0-0x78 (0-120 %), position 0-0x3E8 (0.0-100.0 %).
- Data logger registers 32-59 update a short time after the actuator stops in Remote and can lag by up to two minutes. On ELB units registers 32-49 hold pressure and alarm data instead; the ELB-only tables are not included here.
- The comms fault timer (register 21) is given as 0-255 s in the table but 0-65 s in the text, and the Comms Lost Position text refers to 'Fault Mode (Register 1)' where the table uses register 7. Check on site.
- Not every actuator range supports every location (e.g. DO-5 to DO-8 are IQ3 only); see the manual's database summary table.
- Also supported: function 07 (exception status byte), 08 (loopback, sub-codes 00 and 02) and 17 (report slave ID: name, software version and tag).
- Status bit 0/15 (discrete input 15) is left out: the data tables call it EEPROM checksum failure, but the database summary and the signal descriptions call it Watchdog Recovery.
- Register 80 is marked read-only in the data logger table but writable (06) in the configuration register table; it is kept as RW.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Rotork Modbus RTU Mk3 option card (IQ3, SI3/SI4, CK, CVA, CMA, K-range)
What Modbus registers does the Rotork Modbus RTU Mk3 option card (IQ3, SI3/SI4, CK, CVA, CMA, K-range) have?
This map lists 98 registers: 13 coils, 26 discrete inputs, 5 input registers, 54 holding registers. 36 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Rotork Modbus RTU Mk3 option card (IQ3, SI3/SI4, CK, CVA, CMA, K-range) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual says every coil, discrete and register location is numbered from 0 with no offset, exactly as sent on the wire. Hosts that use 1/10001/30001/40001 numbering must add those offsets themselves.
What byte order does the Rotork Modbus RTU Mk3 option card (IQ3, SI3/SI4, CK, CVA, CMA, K-range) use for 32-bit values?
Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Rotork Modbus RTU Mk3 option card (IQ3, SI3/SI4, CK, CVA, CMA, K-range)?
Start with IR 0 Status word 1 (Status: limits, moving, remote/local, alarms); IR 1 Status word 2 (Status: interlocks, DIs, general alarm); IR 3 Valve position (Valve position, 0.1 %); IR 2 Actuator instantaneous torque (Instantaneous torque, %); HR 5 Actuator digital control (Digital control command); HR 6 Actuator position DV (desired value) (Position set-point, 0.1 %); HR 7 Action on loss of comms (Action on loss of comms).
How do I enable Modbus control of the Rotork Modbus RTU Mk3 option card (IQ3, SI3/SI4, CK, CVA, CMA, K-range)?
Set the module address (register 22, default 247), baud (23) and parity (24) with a Modbus tool or the Rotork setting tool over IR/Bluetooth. Turn the actuator's local/remote selector to Remote. Keep register 80 at 0.
What happens when the Rotork Modbus RTU Mk3 option card (IQ3, SI3/SI4, CK, CVA, CMA, K-range) loses Modbus communication?
If no network traffic is seen for the comms fault timer (register 21, default 10 s), the actuator does what register 7 says: nothing (default), open, close, stop, or move to the comms lost position in register 13.
Where is the official Rotork Modbus RTU Mk3 option card (IQ3, SI3/SI4, CK, CVA, CMA, K-range) Modbus documentation?
The source is Modbus RTU Mk3 Option Technical Manual (PUB091-004-00 Issue 08/25), revision 2025-08, published free by Rotork at https://media.rotork.com/api/public/content/pub091-004-000414-pdf-rtkimportasseteb0d51.pdf.
Other valves, actuators & sensors register maps
- Sensor (room humidity / temperature)
Siemens QFA3150/MO room humidity and temperature sensor (Modbus RTU)
Siemens QFA3150/MO room relative humidity and temperature sensor, basic documentation edition a (2021-01).
Also known as: QFA3150/MO, S55720-S535 - Sensor (temperature / humidity data logger)
Teracom TCW210-TH temperature and humidity data logger
TCW210-TH per the Teracom TCW210-TH user manual Revision R1.26, firmware V2.012 or later.
Also known as: TCW210-TH, TCW210 - Sensor (humidity / temperature)
Teracom TSM400-4-TH Modbus humidity and temperature sensor
TSM400-4-TH per the Teracom TSM400-4-TH user manual TSM400-4-TH-R1.10.
Also known as: TSM400-4-TH - Sensor (CO2 duct transmitter)
Vaisala GMD110 duct CO2 transmitter (Modbus RTU)
GMD110 duct-mount CO2 transmitter, Modbus RTU interface (user guide M212885EN-B).
Also known as: GMD110, CARBOCAP GMD110 - Sensor (humidity and temperature probe)
Vaisala HMP60 / HMP110 series humidity and temperature probes (Modbus RTU)
HMP60/HMP110-series probes ordered with the Modbus RTU option (user guide M211060EN-N).
Also known as: HMP110, HMP113, HMP115, TMP115, HMP60, HMP63, HUMICAP HMP110, HMP110T, HMP63T, HMP115T - Sensor (precipitation)
Vaisala RM60 PRECICAP radar precipitation sensor (Modbus RTU)
RM60 sensors ordered with communication option 1 (RS-485 Modbus RTU) or switched to Modbus, per user guide M213218EN-B.
Also known as: RM60, PRECICAP RM60, Vaisala RM60
All valves, actuators & sensors Modbus register maps →
Source: Modbus RTU Mk3 Option Technical Manual · PUB091-004-00 Issue 08/25 · rev. 2025-08. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.