Rotork Modbus RTU Mk3 option card (IQ3, SI3/SI4, CK, CVA, CMA, K-range) Modbus register map

Updated 19 November 2026

Short answer

The Mk3 Modbus module puts a Rotork electric valve actuator on an RS-485 Modbus RTU highway (single, dual or repeater versions). Open, close, stop, ESD and partial stroke can be sent as coils or as one register value, and position control uses a 0-100.0 % set-point register. Status bits, torque and valve position can be read as discrete inputs, input registers or holding registers, and holding registers 7-31 hold the positioner, comms-loss and network settings.

This page lists 98 Modbus registers for the Rotork Modbus RTU Mk3 option card (IQ3, SI3/SI4, CK, CVA, CMA, K-range) — 36 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Rotork’s own free documentation (linked below) and checked against it.

Manufacturer
Rotork
Model
Modbus RTU Mk3 option card (IQ3, SI3/SI4, CK, CVA, CMA, K-range)
Equipment type
Actuator / valve
Registers
98 (36 writable)
Transport
Modbus RTU
Default unit ID
247
Default serial
9600 baud, 8N1
Documented addressing
0-based (the number printed is the address on the wire)
32-bit word order
CDAB low word first (word-swapped)
Firmware
Modbus module firmware V104 or later
Also known as
IQ3 Modbus, Rotork MFU Mk3, Modbus Mk3 module, SI3 Modbus, SI4 Modbus, CK Modbus, CVA Modbus, CMA Modbus, K-range Modbus
Source document
Modbus RTU Mk3 Option Technical Manual · PUB091-004-00 Issue 08/25 · rev. 2025-08
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Rotork Modbus RTU Mk3 option card (IQ3, SI3/SI4, CK, CVA, CMA, K-range)

Integration in brief

Read input registers 0-4 (status bits, torque, position) with function 04 or 03. Command the valve by writing register 5 (0 stop, 1 close, 2 open, 3 ESD) or send a position in 0.1 % to register 6. The actuator selector must be in Remote.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 0Status word 1BITMAP16Status: limits, moving, remote/local, alarmsRead
IR 1Status word 2BITMAP16Status: interlocks, DIs, general alarmRead
IR 3Valve positionUINT16Valve position, 0.1 %Read
IR 2Actuator instantaneous torqueUINT16Instantaneous torque, %Read
HR 5Actuator digital controlUINT16Digital control commandRead/write
HR 6Actuator position DV (desired value)UINT16Position set-point, 0.1 %Read/write
HR 7Action on loss of commsUINT16Action on loss of commsRead/write

Enable Modbus control & writes

Set the module address (register 22, default 247), baud (23) and parity (24) with a Modbus tool or the Rotork setting tool over IR/Bluetooth. Turn the actuator's local/remote selector to Remote. Keep register 80 at 0.

Communication loss & watchdog

If no network traffic is seen for the comms fault timer (register 21, default 10 s), the actuator does what register 7 says: nothing (default), open, close, stop, or move to the comms lost position in register 13.

Byte order & addressing

Network setup

Watch out for

Rotork Modbus RTU Mk3 option card (IQ3, SI3/SI4, CK, CVA, CMA, K-range) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

98 of 98 shown
Rotork Modbus RTU Mk3 option card (IQ3, SI3/SI4, CK, CVA, CMA, K-range) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
CO0Stop commandBITRead/write
CO1Close commandBITRead/write
CO2Open commandBITRead/write
CO3ESD commandBITRead/write
CO4DO-1 (extra relay S5)Needs the extra relay / DIO board.BITRead/write
CO5DO-2 (extra relay S6)Needs the extra relay / DIO board.BITRead/write
CO6DO-3 (extra relay S7)Needs the extra relay / DIO board.BITRead/write
CO7DO-4 (extra relay S8)Needs the extra relay / DIO board.BITRead/write
CO8Partial stroke testBITRead/write
CO9DO-5 (actuator relay S1, IQ3 only)BITRead/write
CO10DO-6 (actuator relay S2, IQ3 only)BITRead/write
CO11DO-7 (actuator relay S3, IQ3 only)BITRead/write
CO12DO-8 (actuator relay S4, IQ3 only)BITRead/write
DI0Actuator movingBITRead
DI1Closed position limitBITRead
DI2Open position limitBITRead
DI3Running closedBITRead
DI4Running openBITRead
DI5Remote selectedBITRead
DI6Local Stop selectedBITRead
DI7Local selectedBITRead
DI8Thermostat trippedBITRead
DI9Monitor relayBITRead
DI10Valve obstructedBITRead
DI11Valve jammedBITRead
DI12Valve moving by handBITRead
DI13Moving inhibited by MITBITRead
DI14Position control enabledBITRead
DI16Battery lowBITRead
DI17Open interlock activeBITRead
DI18Close interlock activeBITRead
DI19DI-1BITRead
DI20DI-2BITRead
DI21DI-3BITRead
DI22DI-4BITRead
DI26Control contentionBITRead
DI27Partial stroke test in progressBITRead
DI28Partial stroke test errorBITRead
DI29General alarmBattery, valve, actuator or control alarm, jam/obstruction or monitor relay.BITRead
IR0Status word 1Same bits as discrete inputs 0-14; bit 15 left out (see notes).BITMAP16Readbit 0 = Actuator moving; bit 1 = Closed position limit; bit 2 = Open position limit; bit 3 = Running closed; bit 4 = Running open; bit 5 = Remote selected; bit 6 = Local Stop selected; bit 7 = Local selected; bit 8 = Thermostat tripped; bit 9 = Monitor relay; bit 10 = Valve obstructed; bit 11 = Valve jammed; bit 12 = Valve moving by hand; bit 13 = Moving inhibited by MIT; bit 14 = Position control enabled
IR1Status word 2Same bits as discrete inputs 16-29.BITMAP16Readbit 0 = Battery low; bit 1 = Open interlock active; bit 2 = Close interlock active; bit 3 = DI-1; bit 4 = DI-2; bit 5 = DI-3; bit 6 = DI-4; bit 10 = Control contention; bit 11 = Partial stroke test in progress; bit 12 = Partial stroke test error; bit 13 = General alarm
IR2Actuator instantaneous torque0-0x78 = 0-120 %.UINT16%Read
IR3Valve position0-0x3E8 = 0.0-100.0 %.UINT16× 0.1%Read
IR4Analogue inputOptional analogue card (IQ3); 0-0x3E8 = 0.0-100.0 %.UINT16× 0.1%Read
HR0Status word 1Same bits as discrete inputs 0-14; bit 15 left out (see notes).BITMAP16Readbit 0 = Actuator moving; bit 1 = Closed position limit; bit 2 = Open position limit; bit 3 = Running closed; bit 4 = Running open; bit 5 = Remote selected; bit 6 = Local Stop selected; bit 7 = Local selected; bit 8 = Thermostat tripped; bit 9 = Monitor relay; bit 10 = Valve obstructed; bit 11 = Valve jammed; bit 12 = Valve moving by hand; bit 13 = Moving inhibited by MIT; bit 14 = Position control enabled
HR1Status word 2Same bits as discrete inputs 16-29.BITMAP16Readbit 0 = Battery low; bit 1 = Open interlock active; bit 2 = Close interlock active; bit 3 = DI-1; bit 4 = DI-2; bit 5 = DI-3; bit 6 = DI-4; bit 10 = Control contention; bit 11 = Partial stroke test in progress; bit 12 = Partial stroke test error; bit 13 = General alarm
HR2Actuator instantaneous torque0-0x78 = 0-120 %.UINT16%Read
HR3Valve position0-0x3E8 = 0.0-100.0 %.UINT16× 0.1%Read
HR4Analogue inputOptional analogue card (IQ3); 0-0x3E8 = 0.0-100.0 %.UINT16× 0.1%Read
HR5Actuator digital controlWrite one command value; broadcast allowed for 0 and 3.UINT16Read/write0 = Stop; 1 = Close; 2 = Open; 3 = ESD; 4 = Partial stroke test
HR6Actuator position DV (desired value)0-0x3E8 = 0.0-100.0 %; 0 and 100 % drive to the tight-shut / full-open limits.UINT16× 0.1%Read/write
HR7Action on loss of commsTaken after the comms fault timer (register 21) expires.UINT16Read/write0 = Nothing (default); 1 = Open; 3 = Close; 5 = Stop; 7 = Go to comms lost position (register 13)
HR8Limited range position minimum0-100 %, default 0.UINT16%Read/write
HR9Limited range position maximum0-100 %, default 100.UINT16%Read/write
HR10Deadband0-25.5 %, default 5.0 % (0x32).UINT16× 0.1%Read/write
HR11Motion inhibit timeMinimum idle time between positioning starts, 0-255 s, default 5.UINT16sRead/write
HR12Aux input maskHigh nibble enables inputs as commands, low nibble sets contact sense; default 15.BITMAP16Read/writebit 0 = Open input: closed contact reports 1; bit 1 = Close input: closed contact reports 1; bit 2 = Stop/Maintain input: closed contact reports 1; bit 3 = ESD input: closed contact reports 1; bit 4 = Enable Open input as command; bit 5 = Enable Close input as command; bit 6 = Enable Stop/Maintain input as command; bit 7 = Enable ESD input as command
HR13Comms lost position0-100 %, default 0; used when register 7 = 7.UINT16%Read/write
HR14Hysteresis0-25.5 %, default 2.0 % (0x14).UINT16× 0.1%Read/write
HR15Slow mode range0-100 %, default 5.UINT16%Read/write
HR16Valve jammed time0-255 s, default 5.UINT16sRead/write
HR17Manual movement travel0-100 %, default 10.UINT16%Read/write
HR18Watchdog timeout0-255 s, default 10.UINT16sRead/write
HR19ESD DI-4 / net disableIQ3: what the ESD/DI-4 remote input does.UINT16Read/write0 = DI-4 is ESD (default); 1 = DI-4 is network disable
HR20Analogue input max/minCalibration: write 1 with max input applied, then 2 with min applied.UINT16Read/write
HR21Comms fault timerSeconds without traffic before register 7 acts; default 10.UINT16sRead/write
HR22Modbus address1-247, default 247.UINT16Read/write
HR23Baud rateUINT16Read/write1 = 300; 2 = 600; 3 = 1200; 4 = 2400; 5 = 4800; 6 = 9600 (default); 7 = 19200; 8 = 38400; 9 = 57600; 10 = 115200
HR24Parity / stop bitsUINT16Read/write0 = No parity, 1 stop bit (default); 1 = No parity, 2 stop bits; 2 = Even, 1 stop bit; 3 = Even, 2 stop bits; 4 = Odd, 1 stop bit; 5 = Odd, 2 stop bits
HR25Network terminationSwitch on only at the last device of a segment.UINT16Read/write0 = Off (default); 1 = On
HR26Actuator tag name12 ASCII characters, one per byte, registers 26-31.STRING[12]Read/write
HR32Close torque set0-0x78 = 0-120 %.UINT16%Read
HR33Open torque set0-0x78 = 0-120 %.UINT16%Read
HR34Torque at 0% - open directionData logger, 0-120 %.UINT16%Read
HR35Torque at 10% - open directionData logger, 0-120 %.UINT16%Read
HR36Torque at 20% - open directionData logger, 0-120 %.UINT16%Read
HR37Torque at 30% - open directionData logger, 0-120 %.UINT16%Read
HR38Torque at 40% - open directionData logger, 0-120 %.UINT16%Read
HR39Torque at 50% - open directionData logger, 0-120 %.UINT16%Read
HR40Torque at 60% - open directionData logger, 0-120 %.UINT16%Read
HR41Torque at 70% - open directionData logger, 0-120 %.UINT16%Read
HR42Torque at 80% - open directionData logger, 0-120 %.UINT16%Read
HR43Torque at 90% - open directionData logger, 0-120 %.UINT16%Read
HR44Torque at 100% - open directionData logger, 0-120 %.UINT16%Read
HR45Torque at 0% - close directionData logger, 0-120 %.UINT16%Read
HR46Torque at 10% - close directionData logger, 0-120 %.UINT16%Read
HR47Torque at 20% - close directionData logger, 0-120 %.UINT16%Read
HR48Torque at 30% - close directionData logger, 0-120 %.UINT16%Read
HR49Torque at 40% - close directionData logger, 0-120 %.UINT16%Read
HR50Torque at 50% - close directionData logger, 0-120 %.UINT16%Read
HR51Torque at 60% - close directionData logger, 0-120 %.UINT16%Read
HR52Torque at 70% - close directionData logger, 0-120 %.UINT16%Read
HR53Torque at 80% - close directionData logger, 0-120 %.UINT16%Read
HR54Torque at 90% - close directionData logger, 0-120 %.UINT16%Read
HR55Torque at 100% - close directionData logger, 0-120 %.UINT16%Read
HR56Close motor startsLow word at 56, high at 57. On CVA, 56 and 57 are separate contactor counts.UINT32CDABRead
HR58Open motor startsLow word at 58, high at 59. On CVA, 58 is total distance; 59 unused.UINT32CDABRead
HR80Database typeLeave at 0; 1 selects Custom Database A1.UINT16Read/write0 = Rotork (default); 1 = Custom Database A1

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Rotork Modbus RTU Mk3 option card (IQ3, SI3/SI4, CK, CVA, CMA, K-range)

What Modbus registers does the Rotork Modbus RTU Mk3 option card (IQ3, SI3/SI4, CK, CVA, CMA, K-range) have?

This map lists 98 registers: 13 coils, 26 discrete inputs, 5 input registers, 54 holding registers. 36 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Rotork Modbus RTU Mk3 option card (IQ3, SI3/SI4, CK, CVA, CMA, K-range) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual says every coil, discrete and register location is numbered from 0 with no offset, exactly as sent on the wire. Hosts that use 1/10001/30001/40001 numbering must add those offsets themselves.

What byte order does the Rotork Modbus RTU Mk3 option card (IQ3, SI3/SI4, CK, CVA, CMA, K-range) use for 32-bit values?

Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Rotork Modbus RTU Mk3 option card (IQ3, SI3/SI4, CK, CVA, CMA, K-range)?

Start with IR 0 Status word 1 (Status: limits, moving, remote/local, alarms); IR 1 Status word 2 (Status: interlocks, DIs, general alarm); IR 3 Valve position (Valve position, 0.1 %); IR 2 Actuator instantaneous torque (Instantaneous torque, %); HR 5 Actuator digital control (Digital control command); HR 6 Actuator position DV (desired value) (Position set-point, 0.1 %); HR 7 Action on loss of comms (Action on loss of comms).

How do I enable Modbus control of the Rotork Modbus RTU Mk3 option card (IQ3, SI3/SI4, CK, CVA, CMA, K-range)?

Set the module address (register 22, default 247), baud (23) and parity (24) with a Modbus tool or the Rotork setting tool over IR/Bluetooth. Turn the actuator's local/remote selector to Remote. Keep register 80 at 0.

What happens when the Rotork Modbus RTU Mk3 option card (IQ3, SI3/SI4, CK, CVA, CMA, K-range) loses Modbus communication?

If no network traffic is seen for the comms fault timer (register 21, default 10 s), the actuator does what register 7 says: nothing (default), open, close, stop, or move to the comms lost position in register 13.

Where is the official Rotork Modbus RTU Mk3 option card (IQ3, SI3/SI4, CK, CVA, CMA, K-range) Modbus documentation?

The source is Modbus RTU Mk3 Option Technical Manual (PUB091-004-00 Issue 08/25), revision 2025-08, published free by Rotork at https://media.rotork.com/api/public/content/pub091-004-000414-pdf-rtkimportasseteb0d51.pdf.

Other valves, actuators & sensors register maps

All valves, actuators & sensors Modbus register maps →

Source: Modbus RTU Mk3 Option Technical Manual · PUB091-004-00 Issue 08/25 · rev. 2025-08. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.