Teracom TCW210-TH temperature and humidity data logger Modbus register map
Updated 19 November 2026
The TCW210-TH is a Teracom Ethernet data logger for up to eight temperature or temperature/humidity sensors on 1-Wire or Modbus RTU. Over Modbus TCP it serves each sensor's values, raw values, limits, trim settings and alarm flags as holding registers.
This page lists 239 Modbus registers for the Teracom TCW210-TH temperature and humidity data logger — 132 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Teracom’s own free documentation (linked below) and checked against it.
- Manufacturer
- Teracom
- Model
- TCW210-TH temperature and humidity data logger
- Equipment type
- Sensor (temperature / humidity data logger)
- Registers
- 239 (132 writable)
- Transport
- Modbus TCP
- Default unit ID
- Not stated
- TCP port
- 502
- Documented addressing
- 0-based (the number printed is the address on the wire)
- 32-bit word order
- ABCD high word first (big-endian)
- Firmware
- V2.012 or later
- Also known as
- TCW210-TH, TCW210
- Source document
- TCW210-TH User manual · Revision R1.26 · rev. 2026-10
Integration notes: Teracom TCW210-TH temperature and humidity data logger
Enable Modbus TCP, then read sensor values as floats from holding registers 19800 onward (two registers per value) with function 03.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 19800 | Sensor 1, S11 value | FLOAT32 ABCD | Sensor 1 first value | Read |
| HR 19802 | Sensor 1, S12 value | FLOAT32 ABCD | Sensor 1 second value | Read |
| HR 20000 | Sensor 1, S11 alarm status | UINT16 | Sensor 1 first value alarm | Read |
| HR 50002 | Temperature unit | UINT16 | Temperature unit | Read/write |
| HR 50003 | HW error | UINT16 | Hardware error | Read/write |
Enable Modbus control & writes
Modbus TCP/IP is disabled by default. Enable it on the services page of the web interface (standard port 502).
Byte order & addressing
- Floats are high word first (ABCD).
- PDU 50000 reports whether settings are saved (0 = unsaved, 1 = saved).
Network setup
- The factory IP is 192.168.1.2; change it in the network settings, then enable Modbus TCP/IP.
Teracom TCW210-TH temperature and humidity data logger Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 18100 | Sensor 1 description | User label text, UTF-8, zero padded. | STRING[64] | Read/write | ||||
| HR | 18132 | Sensor 2 description | User label text, UTF-8, zero padded. | STRING[64] | Read/write | ||||
| HR | 18164 | Sensor 3 description | User label text, UTF-8, zero padded. | STRING[64] | Read/write | ||||
| HR | 18196 | Sensor 4 description | User label text, UTF-8, zero padded. | STRING[64] | Read/write | ||||
| HR | 18228 | Sensor 5 description | User label text, UTF-8, zero padded. | STRING[64] | Read/write | ||||
| HR | 18260 | Sensor 6 description | User label text, UTF-8, zero padded. | STRING[64] | Read/write | ||||
| HR | 18292 | Sensor 7 description | User label text, UTF-8, zero padded. | STRING[64] | Read/write | ||||
| HR | 18324 | Sensor 8 description | User label text, UTF-8, zero padded. | STRING[64] | Read/write | ||||
| HR | 18400 | Sensor 1, S11 dimension | Unit text for this value, UTF-8. | STRING[64] | Read | ||||
| HR | 18432 | Sensor 1, S12 dimension | Unit text for this value, UTF-8. | STRING[64] | Read | ||||
| HR | 18464 | Sensor 1, S13 dimension | Unit text for this value, UTF-8. | STRING[64] | Read | ||||
| HR | 18496 | Sensor 2, S21 dimension | Unit text for this value, UTF-8. | STRING[64] | Read | ||||
| HR | 18528 | Sensor 2, S22 dimension | Unit text for this value, UTF-8. | STRING[64] | Read | ||||
| HR | 18560 | Sensor 2, S23 dimension | Unit text for this value, UTF-8. | STRING[64] | Read | ||||
| HR | 18592 | Sensor 3, S31 dimension | Unit text for this value, UTF-8. | STRING[64] | Read | ||||
| HR | 18624 | Sensor 3, S32 dimension | Unit text for this value, UTF-8. | STRING[64] | Read | ||||
| HR | 18656 | Sensor 3, S33 dimension | Unit text for this value, UTF-8. | STRING[64] | Read | ||||
| HR | 18688 | Sensor 4, S41 dimension | Unit text for this value, UTF-8. | STRING[64] | Read | ||||
| HR | 18720 | Sensor 4, S42 dimension | Unit text for this value, UTF-8. | STRING[64] | Read | ||||
| HR | 18752 | Sensor 4, S43 dimension | Unit text for this value, UTF-8. | STRING[64] | Read | ||||
| HR | 18784 | Sensor 5, S51 dimension | Unit text for this value, UTF-8. | STRING[64] | Read | ||||
| HR | 18816 | Sensor 5, S52 dimension | Unit text for this value, UTF-8. | STRING[64] | Read | ||||
| HR | 18848 | Sensor 5, S53 dimension | Unit text for this value, UTF-8. | STRING[64] | Read | ||||
| HR | 18880 | Sensor 6, S61 dimension | Unit text for this value, UTF-8. | STRING[64] | Read | ||||
| HR | 18912 | Sensor 6, S62 dimension | Unit text for this value, UTF-8. | STRING[64] | Read | ||||
| HR | 18944 | Sensor 6, S63 dimension | Unit text for this value, UTF-8. | STRING[64] | Read | ||||
| HR | 18976 | Sensor 7, S71 dimension | Unit text for this value, UTF-8. | STRING[64] | Read | ||||
| HR | 19008 | Sensor 7, S72 dimension | Unit text for this value, UTF-8. | STRING[64] | Read | ||||
| HR | 19040 | Sensor 7, S73 dimension | Unit text for this value, UTF-8. | STRING[64] | Read | ||||
| HR | 19072 | Sensor 8, S81 dimension | Unit text for this value, UTF-8. | STRING[64] | Read | ||||
| HR | 19104 | Sensor 8, S82 dimension | Unit text for this value, UTF-8. | STRING[64] | Read | ||||
| HR | 19136 | Sensor 8, S83 dimension | Unit text for this value, UTF-8. | STRING[64] | Read | ||||
| HR | 19200 | Sensor 1, S11 max | Upper alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19202 | Sensor 1, S12 max | Upper alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19204 | Sensor 1, S13 max | Upper alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19206 | Sensor 2, S21 max | Upper alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19208 | Sensor 2, S22 max | Upper alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19210 | Sensor 2, S23 max | Upper alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19212 | Sensor 3, S31 max | Upper alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19214 | Sensor 3, S32 max | Upper alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19216 | Sensor 3, S33 max | Upper alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19218 | Sensor 4, S41 max | Upper alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19220 | Sensor 4, S42 max | Upper alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19222 | Sensor 4, S43 max | Upper alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19224 | Sensor 5, S51 max | Upper alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19226 | Sensor 5, S52 max | Upper alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19228 | Sensor 5, S53 max | Upper alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19230 | Sensor 6, S61 max | Upper alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19232 | Sensor 6, S62 max | Upper alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19234 | Sensor 6, S63 max | Upper alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19236 | Sensor 7, S71 max | Upper alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19238 | Sensor 7, S72 max | Upper alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19240 | Sensor 7, S73 max | Upper alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19242 | Sensor 8, S81 max | Upper alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19244 | Sensor 8, S82 max | Upper alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19246 | Sensor 8, S83 max | Upper alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19300 | Sensor 1, S11 min | Lower alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19302 | Sensor 1, S12 min | Lower alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19304 | Sensor 1, S13 min | Lower alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19306 | Sensor 2, S21 min | Lower alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19308 | Sensor 2, S22 min | Lower alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19310 | Sensor 2, S23 min | Lower alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19312 | Sensor 3, S31 min | Lower alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19314 | Sensor 3, S32 min | Lower alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19316 | Sensor 3, S33 min | Lower alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19318 | Sensor 4, S41 min | Lower alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19320 | Sensor 4, S42 min | Lower alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19322 | Sensor 4, S43 min | Lower alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19324 | Sensor 5, S51 min | Lower alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19326 | Sensor 5, S52 min | Lower alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19328 | Sensor 5, S53 min | Lower alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19330 | Sensor 6, S61 min | Lower alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19332 | Sensor 6, S62 min | Lower alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19334 | Sensor 6, S63 min | Lower alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19336 | Sensor 7, S71 min | Lower alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19338 | Sensor 7, S72 min | Lower alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19340 | Sensor 7, S73 min | Lower alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19342 | Sensor 8, S81 min | Lower alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19344 | Sensor 8, S82 min | Lower alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19346 | Sensor 8, S83 min | Lower alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19400 | Sensor 1, S11 hysteresis | Alarm hysteresis. | FLOAT32 | ABCD | Read/write | |||
| HR | 19402 | Sensor 1, S12 hysteresis | Alarm hysteresis. | FLOAT32 | ABCD | Read/write | |||
| HR | 19404 | Sensor 1, S13 hysteresis | Alarm hysteresis. | FLOAT32 | ABCD | Read/write | |||
| HR | 19406 | Sensor 2, S21 hysteresis | Alarm hysteresis. | FLOAT32 | ABCD | Read/write | |||
| HR | 19408 | Sensor 2, S22 hysteresis | Alarm hysteresis. | FLOAT32 | ABCD | Read/write | |||
| HR | 19410 | Sensor 2, S23 hysteresis | Alarm hysteresis. | FLOAT32 | ABCD | Read/write | |||
| HR | 19412 | Sensor 3, S31 hysteresis | Alarm hysteresis. | FLOAT32 | ABCD | Read/write | |||
| HR | 19414 | Sensor 3, S32 hysteresis | Alarm hysteresis. | FLOAT32 | ABCD | Read/write | |||
| HR | 19416 | Sensor 3, S33 hysteresis | Alarm hysteresis. | FLOAT32 | ABCD | Read/write | |||
| HR | 19418 | Sensor 4, S41 hysteresis | Alarm hysteresis. | FLOAT32 | ABCD | Read/write | |||
| HR | 19420 | Sensor 4, S42 hysteresis | Alarm hysteresis. | FLOAT32 | ABCD | Read/write | |||
| HR | 19422 | Sensor 4, S43 hysteresis | Alarm hysteresis. | FLOAT32 | ABCD | Read/write | |||
| HR | 19424 | Sensor 5, S51 hysteresis | Alarm hysteresis. | FLOAT32 | ABCD | Read/write | |||
| HR | 19426 | Sensor 5, S52 hysteresis | Alarm hysteresis. | FLOAT32 | ABCD | Read/write | |||
| HR | 19428 | Sensor 5, S53 hysteresis | Alarm hysteresis. | FLOAT32 | ABCD | Read/write | |||
| HR | 19430 | Sensor 6, S61 hysteresis | Alarm hysteresis. | FLOAT32 | ABCD | Read/write | |||
| HR | 19432 | Sensor 6, S62 hysteresis | Alarm hysteresis. | FLOAT32 | ABCD | Read/write | |||
| HR | 19434 | Sensor 6, S63 hysteresis | Alarm hysteresis. | FLOAT32 | ABCD | Read/write | |||
| HR | 19436 | Sensor 7, S71 hysteresis | Alarm hysteresis. | FLOAT32 | ABCD | Read/write | |||
| HR | 19438 | Sensor 7, S72 hysteresis | Alarm hysteresis. | FLOAT32 | ABCD | Read/write | |||
| HR | 19440 | Sensor 7, S73 hysteresis | Alarm hysteresis. | FLOAT32 | ABCD | Read/write | |||
| HR | 19442 | Sensor 8, S81 hysteresis | Alarm hysteresis. | FLOAT32 | ABCD | Read/write | |||
| HR | 19444 | Sensor 8, S82 hysteresis | Alarm hysteresis. | FLOAT32 | ABCD | Read/write | |||
| HR | 19446 | Sensor 8, S83 hysteresis | Alarm hysteresis. | FLOAT32 | ABCD | Read/write | |||
| HR | 19500 | Sensor 1, S11 multiplier | Scaling multiplier applied to the reading. | FLOAT32 | ABCD | Read/write | |||
| HR | 19502 | Sensor 1, S12 multiplier | Scaling multiplier applied to the reading. | FLOAT32 | ABCD | Read/write | |||
| HR | 19504 | Sensor 1, S13 multiplier | Scaling multiplier applied to the reading. | FLOAT32 | ABCD | Read/write | |||
| HR | 19506 | Sensor 2, S21 multiplier | Scaling multiplier applied to the reading. | FLOAT32 | ABCD | Read/write | |||
| HR | 19508 | Sensor 2, S22 multiplier | Scaling multiplier applied to the reading. | FLOAT32 | ABCD | Read/write | |||
| HR | 19510 | Sensor 2, S23 multiplier | Scaling multiplier applied to the reading. | FLOAT32 | ABCD | Read/write | |||
| HR | 19512 | Sensor 3, S31 multiplier | Scaling multiplier applied to the reading. | FLOAT32 | ABCD | Read/write | |||
| HR | 19514 | Sensor 3, S32 multiplier | Scaling multiplier applied to the reading. | FLOAT32 | ABCD | Read/write | |||
| HR | 19516 | Sensor 3, S33 multiplier | Scaling multiplier applied to the reading. | FLOAT32 | ABCD | Read/write | |||
| HR | 19518 | Sensor 4, S41 multiplier | Scaling multiplier applied to the reading. | FLOAT32 | ABCD | Read/write | |||
| HR | 19520 | Sensor 4, S42 multiplier | Scaling multiplier applied to the reading. | FLOAT32 | ABCD | Read/write | |||
| HR | 19522 | Sensor 4, S43 multiplier | Scaling multiplier applied to the reading. | FLOAT32 | ABCD | Read/write | |||
| HR | 19524 | Sensor 5, S51 multiplier | Scaling multiplier applied to the reading. | FLOAT32 | ABCD | Read/write | |||
| HR | 19526 | Sensor 5, S52 multiplier | Scaling multiplier applied to the reading. | FLOAT32 | ABCD | Read/write | |||
| HR | 19528 | Sensor 5, S53 multiplier | Scaling multiplier applied to the reading. | FLOAT32 | ABCD | Read/write | |||
| HR | 19530 | Sensor 6, S61 multiplier | Scaling multiplier applied to the reading. | FLOAT32 | ABCD | Read/write | |||
| HR | 19532 | Sensor 6, S62 multiplier | Scaling multiplier applied to the reading. | FLOAT32 | ABCD | Read/write | |||
| HR | 19534 | Sensor 6, S63 multiplier | Scaling multiplier applied to the reading. | FLOAT32 | ABCD | Read/write | |||
| HR | 19536 | Sensor 7, S71 multiplier | Scaling multiplier applied to the reading. | FLOAT32 | ABCD | Read/write | |||
| HR | 19538 | Sensor 7, S72 multiplier | Scaling multiplier applied to the reading. | FLOAT32 | ABCD | Read/write | |||
| HR | 19540 | Sensor 7, S73 multiplier | Scaling multiplier applied to the reading. | FLOAT32 | ABCD | Read/write | |||
| HR | 19542 | Sensor 8, S81 multiplier | Scaling multiplier applied to the reading. | FLOAT32 | ABCD | Read/write | |||
| HR | 19544 | Sensor 8, S82 multiplier | Scaling multiplier applied to the reading. | FLOAT32 | ABCD | Read/write | |||
| HR | 19546 | Sensor 8, S83 multiplier | Scaling multiplier applied to the reading. | FLOAT32 | ABCD | Read/write | |||
| HR | 19600 | Sensor 1, S11 offset | Offset added after the multiplier. | FLOAT32 | ABCD | Read/write | |||
| HR | 19602 | Sensor 1, S12 offset | Offset added after the multiplier. | FLOAT32 | ABCD | Read/write | |||
| HR | 19604 | Sensor 1, S13 offset | Offset added after the multiplier. | FLOAT32 | ABCD | Read/write | |||
| HR | 19606 | Sensor 2, S21 offset | Offset added after the multiplier. | FLOAT32 | ABCD | Read/write | |||
| HR | 19608 | Sensor 2, S22 offset | Offset added after the multiplier. | FLOAT32 | ABCD | Read/write | |||
| HR | 19610 | Sensor 2, S23 offset | Offset added after the multiplier. | FLOAT32 | ABCD | Read/write | |||
| HR | 19612 | Sensor 3, S31 offset | Offset added after the multiplier. | FLOAT32 | ABCD | Read/write | |||
| HR | 19614 | Sensor 3, S32 offset | Offset added after the multiplier. | FLOAT32 | ABCD | Read/write | |||
| HR | 19616 | Sensor 3, S33 offset | Offset added after the multiplier. | FLOAT32 | ABCD | Read/write | |||
| HR | 19618 | Sensor 4, S41 offset | Offset added after the multiplier. | FLOAT32 | ABCD | Read/write | |||
| HR | 19620 | Sensor 4, S42 offset | Offset added after the multiplier. | FLOAT32 | ABCD | Read/write | |||
| HR | 19622 | Sensor 4, S43 offset | Offset added after the multiplier. | FLOAT32 | ABCD | Read/write | |||
| HR | 19624 | Sensor 5, S51 offset | Offset added after the multiplier. | FLOAT32 | ABCD | Read/write | |||
| HR | 19626 | Sensor 5, S52 offset | Offset added after the multiplier. | FLOAT32 | ABCD | Read/write | |||
| HR | 19628 | Sensor 5, S53 offset | Offset added after the multiplier. | FLOAT32 | ABCD | Read/write | |||
| HR | 19630 | Sensor 6, S61 offset | Offset added after the multiplier. | FLOAT32 | ABCD | Read/write | |||
| HR | 19632 | Sensor 6, S62 offset | Offset added after the multiplier. | FLOAT32 | ABCD | Read/write | |||
| HR | 19634 | Sensor 6, S63 offset | Offset added after the multiplier. | FLOAT32 | ABCD | Read/write | |||
| HR | 19636 | Sensor 7, S71 offset | Offset added after the multiplier. | FLOAT32 | ABCD | Read/write | |||
| HR | 19638 | Sensor 7, S72 offset | Offset added after the multiplier. | FLOAT32 | ABCD | Read/write | |||
| HR | 19640 | Sensor 7, S73 offset | Offset added after the multiplier. | FLOAT32 | ABCD | Read/write | |||
| HR | 19642 | Sensor 8, S81 offset | Offset added after the multiplier. | FLOAT32 | ABCD | Read/write | |||
| HR | 19644 | Sensor 8, S82 offset | Offset added after the multiplier. | FLOAT32 | ABCD | Read/write | |||
| HR | 19646 | Sensor 8, S83 offset | Offset added after the multiplier. | FLOAT32 | ABCD | Read/write | |||
| HR | 19700 | Sensor 1 ID | Sensor ROM ID as text. | STRING[16] | Read | ||||
| HR | 19708 | Sensor 2 ID | Sensor ROM ID as text. | STRING[16] | Read | ||||
| HR | 19716 | Sensor 3 ID | Sensor ROM ID as text. | STRING[16] | Read | ||||
| HR | 19724 | Sensor 4 ID | Sensor ROM ID as text. | STRING[16] | Read | ||||
| HR | 19732 | Sensor 5 ID | Sensor ROM ID as text. | STRING[16] | Read | ||||
| HR | 19740 | Sensor 6 ID | Sensor ROM ID as text. | STRING[16] | Read | ||||
| HR | 19748 | Sensor 7 ID | Sensor ROM ID as text. | STRING[16] | Read | ||||
| HR | 19756 | Sensor 8 ID | Sensor ROM ID as text. | STRING[16] | Read | ||||
| HR | 19800 | Sensor 1, S11 value | Sensor reading after multiplier and offset; unit per its dimension string. | FLOAT32 | ABCD | Read | |||
| HR | 19802 | Sensor 1, S12 value | Sensor reading after multiplier and offset; unit per its dimension string. | FLOAT32 | ABCD | Read | |||
| HR | 19804 | Sensor 1, S13 value | Sensor reading after multiplier and offset; unit per its dimension string. | FLOAT32 | ABCD | Read | |||
| HR | 19806 | Sensor 2, S21 value | Sensor reading after multiplier and offset; unit per its dimension string. | FLOAT32 | ABCD | Read | |||
| HR | 19808 | Sensor 2, S22 value | Sensor reading after multiplier and offset; unit per its dimension string. | FLOAT32 | ABCD | Read | |||
| HR | 19810 | Sensor 2, S23 value | Sensor reading after multiplier and offset; unit per its dimension string. | FLOAT32 | ABCD | Read | |||
| HR | 19812 | Sensor 3, S31 value | Sensor reading after multiplier and offset; unit per its dimension string. | FLOAT32 | ABCD | Read | |||
| HR | 19814 | Sensor 3, S32 value | Sensor reading after multiplier and offset; unit per its dimension string. | FLOAT32 | ABCD | Read | |||
| HR | 19816 | Sensor 3, S33 value | Sensor reading after multiplier and offset; unit per its dimension string. | FLOAT32 | ABCD | Read | |||
| HR | 19818 | Sensor 4, S41 value | Sensor reading after multiplier and offset; unit per its dimension string. | FLOAT32 | ABCD | Read | |||
| HR | 19820 | Sensor 4, S42 value | Sensor reading after multiplier and offset; unit per its dimension string. | FLOAT32 | ABCD | Read | |||
| HR | 19822 | Sensor 4, S43 value | Sensor reading after multiplier and offset; unit per its dimension string. | FLOAT32 | ABCD | Read | |||
| HR | 19824 | Sensor 5, S51 value | Sensor reading after multiplier and offset; unit per its dimension string. | FLOAT32 | ABCD | Read | |||
| HR | 19826 | Sensor 5, S52 value | Sensor reading after multiplier and offset; unit per its dimension string. | FLOAT32 | ABCD | Read | |||
| HR | 19828 | Sensor 5, S53 value | Sensor reading after multiplier and offset; unit per its dimension string. | FLOAT32 | ABCD | Read | |||
| HR | 19830 | Sensor 6, S61 value | Sensor reading after multiplier and offset; unit per its dimension string. | FLOAT32 | ABCD | Read | |||
| HR | 19832 | Sensor 6, S62 value | Sensor reading after multiplier and offset; unit per its dimension string. | FLOAT32 | ABCD | Read | |||
| HR | 19834 | Sensor 6, S63 value | Sensor reading after multiplier and offset; unit per its dimension string. | FLOAT32 | ABCD | Read | |||
| HR | 19836 | Sensor 7, S71 value | Sensor reading after multiplier and offset; unit per its dimension string. | FLOAT32 | ABCD | Read | |||
| HR | 19838 | Sensor 7, S72 value | Sensor reading after multiplier and offset; unit per its dimension string. | FLOAT32 | ABCD | Read | |||
| HR | 19840 | Sensor 7, S73 value | Sensor reading after multiplier and offset; unit per its dimension string. | FLOAT32 | ABCD | Read | |||
| HR | 19842 | Sensor 8, S81 value | Sensor reading after multiplier and offset; unit per its dimension string. | FLOAT32 | ABCD | Read | |||
| HR | 19844 | Sensor 8, S82 value | Sensor reading after multiplier and offset; unit per its dimension string. | FLOAT32 | ABCD | Read | |||
| HR | 19846 | Sensor 8, S83 value | Sensor reading after multiplier and offset; unit per its dimension string. | FLOAT32 | ABCD | Read | |||
| HR | 19900 | Sensor 1, S11 row value | FLOAT32 | ABCD | Read | ||||
| HR | 19902 | Sensor 1, S12 row value | FLOAT32 | ABCD | Read | ||||
| HR | 19904 | Sensor 1, S13 row value | FLOAT32 | ABCD | Read | ||||
| HR | 19906 | Sensor 2, S21 row value | FLOAT32 | ABCD | Read | ||||
| HR | 19908 | Sensor 2, S22 row value | FLOAT32 | ABCD | Read | ||||
| HR | 19910 | Sensor 2, S23 row value | FLOAT32 | ABCD | Read | ||||
| HR | 19912 | Sensor 3, S31 row value | FLOAT32 | ABCD | Read | ||||
| HR | 19914 | Sensor 3, S32 row value | FLOAT32 | ABCD | Read | ||||
| HR | 19916 | Sensor 3, S33 row value | FLOAT32 | ABCD | Read | ||||
| HR | 19918 | Sensor 4, S41 row value | FLOAT32 | ABCD | Read | ||||
| HR | 19920 | Sensor 4, S42 row value | FLOAT32 | ABCD | Read | ||||
| HR | 19922 | Sensor 4, S43 row value | FLOAT32 | ABCD | Read | ||||
| HR | 19924 | Sensor 5, S51 row value | FLOAT32 | ABCD | Read | ||||
| HR | 19926 | Sensor 5, S52 row value | FLOAT32 | ABCD | Read | ||||
| HR | 19928 | Sensor 5, S53 row value | FLOAT32 | ABCD | Read | ||||
| HR | 19930 | Sensor 6, S61 row value | FLOAT32 | ABCD | Read | ||||
| HR | 19932 | Sensor 6, S62 row value | FLOAT32 | ABCD | Read | ||||
| HR | 19934 | Sensor 6, S63 row value | FLOAT32 | ABCD | Read | ||||
| HR | 19936 | Sensor 7, S71 row value | FLOAT32 | ABCD | Read | ||||
| HR | 19938 | Sensor 7, S72 row value | FLOAT32 | ABCD | Read | ||||
| HR | 19940 | Sensor 7, S73 row value | FLOAT32 | ABCD | Read | ||||
| HR | 19942 | Sensor 8, S81 row value | FLOAT32 | ABCD | Read | ||||
| HR | 19944 | Sensor 8, S82 row value | FLOAT32 | ABCD | Read | ||||
| HR | 19946 | Sensor 8, S83 row value | FLOAT32 | ABCD | Read | ||||
| HR | 20000 | Sensor 1, S11 alarm status | Alarm flag for this value. | UINT16 | Read | 0 = normal; 1 = alarm | |||
| HR | 20001 | Sensor 1, S12 alarm status | Alarm flag for this value. | UINT16 | Read | 0 = normal; 1 = alarm | |||
| HR | 20002 | Sensor 1, S13 alarm status | Alarm flag for this value. | UINT16 | Read | 0 = normal; 1 = alarm | |||
| HR | 20003 | Sensor 2, S21 alarm status | Alarm flag for this value. | UINT16 | Read | 0 = normal; 1 = alarm | |||
| HR | 20004 | Sensor 2, S22 alarm status | Alarm flag for this value. | UINT16 | Read | 0 = normal; 1 = alarm | |||
| HR | 20005 | Sensor 2, S23 alarm status | Alarm flag for this value. | UINT16 | Read | 0 = normal; 1 = alarm | |||
| HR | 20006 | Sensor 3, S31 alarm status | Alarm flag for this value. | UINT16 | Read | 0 = normal; 1 = alarm | |||
| HR | 20007 | Sensor 3, S32 alarm status | Alarm flag for this value. | UINT16 | Read | 0 = normal; 1 = alarm | |||
| HR | 20008 | Sensor 3, S33 alarm status | Alarm flag for this value. | UINT16 | Read | 0 = normal; 1 = alarm | |||
| HR | 20009 | Sensor 4, S41 alarm status | Alarm flag for this value. | UINT16 | Read | 0 = normal; 1 = alarm | |||
| HR | 20010 | Sensor 4, S42 alarm status | Alarm flag for this value. | UINT16 | Read | 0 = normal; 1 = alarm | |||
| HR | 20011 | Sensor 4, S43 alarm status | Alarm flag for this value. | UINT16 | Read | 0 = normal; 1 = alarm | |||
| HR | 20012 | Sensor 5, S51 alarm status | Alarm flag for this value. | UINT16 | Read | 0 = normal; 1 = alarm | |||
| HR | 20013 | Sensor 5, S52 alarm status | Alarm flag for this value. | UINT16 | Read | 0 = normal; 1 = alarm | |||
| HR | 20014 | Sensor 5, S53 alarm status | Alarm flag for this value. | UINT16 | Read | 0 = normal; 1 = alarm | |||
| HR | 20015 | Sensor 6, S61 alarm status | Alarm flag for this value. | UINT16 | Read | 0 = normal; 1 = alarm | |||
| HR | 20016 | Sensor 6, S62 alarm status | Alarm flag for this value. | UINT16 | Read | 0 = normal; 1 = alarm | |||
| HR | 20017 | Sensor 6, S63 alarm status | Alarm flag for this value. | UINT16 | Read | 0 = normal; 1 = alarm | |||
| HR | 20018 | Sensor 7, S71 alarm status | Alarm flag for this value. | UINT16 | Read | 0 = normal; 1 = alarm | |||
| HR | 20019 | Sensor 7, S72 alarm status | Alarm flag for this value. | UINT16 | Read | 0 = normal; 1 = alarm | |||
| HR | 20020 | Sensor 7, S73 alarm status | Alarm flag for this value. | UINT16 | Read | 0 = normal; 1 = alarm | |||
| HR | 20021 | Sensor 8, S81 alarm status | Alarm flag for this value. | UINT16 | Read | 0 = normal; 1 = alarm | |||
| HR | 20022 | Sensor 8, S82 alarm status | Alarm flag for this value. | UINT16 | Read | 0 = normal; 1 = alarm | |||
| HR | 20023 | Sensor 8, S83 alarm status | Alarm flag for this value. | UINT16 | Read | 0 = normal; 1 = alarm | |||
| HR | 50000 | Save configuration | Shows or triggers saving of the configuration. | UINT16 | Read/write | 0 = unsaved; 1 = saved | |||
| HR | 50001 | Restart device | Write 1 to restart the module. | UINT16 | Read/write | 0 = cancel; 1 = restart | |||
| HR | 50002 | Temperature unit | Unit used for temperature values. | UINT16 | Read/write | 0 = Celsius; 1 = Fahrenheit | |||
| HR | 50003 | HW error | UINT16 | Read/write | 0 = noErr; 1 = hwErr | ||||
| HR | 50100 | Device ID | Sensor ROM ID as text. | STRING[18] | Read | ||||
| HR | 50200 | Hostname | STRING[16] | Read | |||||
| HR | 50300 | Device IP | STRING[16] | Read |
Notes on this map
- Word order: the manual says float registers are sent big-endian and its example response 41BD 0655 decodes to 23.628, i.e. high word first (ABCD).
- Strings are fixed-length UTF-8, zero padded; 64-byte fields span 32 registers.
- Each of the 8 sensors has three value slots (Sx1..Sx3), each with dimension, limits, multiplier, offset, value, raw value and alarm status.
- Left out: 'Number of installed sensors' (PDU 18000), listed only as '16-bit Integer' without saying signed or unsigned.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Teracom TCW210-TH temperature and humidity data logger
What Modbus registers does the Teracom TCW210-TH temperature and humidity data logger have?
This map lists 239 registers: 239 holding registers. 132 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Teracom TCW210-TH temperature and humidity data logger Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The address table prints PDU (wire) addresses in decimal. The manual's example frame reads register 19800 as 0x4D58 on the wire, so no offset is applied.
What byte order does the Teracom TCW210-TH temperature and humidity data logger use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Teracom TCW210-TH temperature and humidity data logger?
Start with HR 19800 Sensor 1, S11 value (Sensor 1 first value); HR 19802 Sensor 1, S12 value (Sensor 1 second value); HR 20000 Sensor 1, S11 alarm status (Sensor 1 first value alarm); HR 50002 Temperature unit (Temperature unit); HR 50003 HW error (Hardware error).
How do I enable Modbus control of the Teracom TCW210-TH temperature and humidity data logger?
Modbus TCP/IP is disabled by default. Enable it on the services page of the web interface (standard port 502).
Where is the official Teracom TCW210-TH temperature and humidity data logger Modbus documentation?
The source is TCW210-TH User manual (Revision R1.26), revision 2026-10, published free by Teracom at https://www.teracomsystems.com/download/temperature-humidity-data-logger-tcw210-th-user-manual/.
More Teracom Modbus register maps
- Sensor (Ethernet data logger / I/O module)
Teracom TCW220 Ethernet data logger
TCW220 per the Teracom TCW220 user manual Revision R4.24, firmware V2.012 or later.
Also known as: TCW220 - Sensor (Ethernet I/O module)
Teracom TCW241 Ethernet I/O module
TCW241 per the Teracom TCW241 user manual Revision R4.30, firmware v2.012 or later.
Also known as: TCW241 - Energy meter (Ethernet energy monitoring / data logger)
Teracom TCW260 Ethernet energy monitoring module
TCW260 per the Teracom TCW260 user manual Revision R1.19, firmware V3.009 or later.
Also known as: TCW260 - Sensor (Ethernet analog / digital output module)
Teracom TCW280 Ethernet analog output module
TCW280 per the Teracom TCW280 user manual TCW280_R1.8.
Also known as: TCW280 - Sensor (1-Wire to Modbus gateway)
Teracom TCW320x-WMG 1-Wire to Modbus gateway
TCW320E-WMG (Ethernet) and TCW320W-WMG (Wi-Fi) per the user manual Revision R1.0; both share one fixed register map.
Also known as: TCW320E-WMG, TCW320W-WMG - Energy meter (S0 pulse counter / digital input module)
Teracom TDI340 4-channel S0 pulse counter with Modbus RTU
TDI340 per the Teracom TDI340 user manual Revision R1.11, firmware V1.06 or later.
Also known as: TDI340 - Sensor (relay output module)
Teracom TDO340 4-channel Modbus RTU relay output module
TDO340 per the Teracom TDO340 user manual Revision R1.2, firmware V1.03 or later.
Also known as: TDO340 - Sensor (water leak detector)
Teracom TSF400-4 water-leak detector with Modbus RTU
TSF400-4 per the Teracom TSF400-4 user manual Revision R1.2.
Also known as: TSF400-4 - Sensor (humidity / temperature)
Teracom TSH300v3 RS-485 humidity and temperature sensor
TSH300v3 per the Teracom TSH300v3 user manual Revision R1.17.
Also known as: TSH300, TSH300v3 - Sensor (humidity / temperature)
Teracom TSH331 IP54 Modbus RTU humidity and temperature sensor
TSH331 per the Teracom TSH331 user manual Rev. 1.5, firmware v1.08 or later.
Also known as: TSH331 - Sensor (CO2 / pressure)
Teracom TSM400-4-CP Modbus CO2 and barometric pressure sensor
TSM400-4-CP per the Teracom TSM400-4-CP user manual TSM400-4-CP-R1.9.
Also known as: TSM400-4-CP - Sensor (CO2 / humidity / temperature / pressure)
Teracom TSM400-4-CPTH Modbus CO2, humidity, temperature and pressure multi-sensor
TSM400-4-CPTH per the Teracom TSM400-4-CPTH user manual TSM400-4-CPTH-R1.9.
Also known as: TSM400-4-CPTH - Sensor (humidity / temperature)
Teracom TSM400-4-TH Modbus humidity and temperature sensor
TSM400-4-TH per the Teracom TSM400-4-TH user manual TSM400-4-TH-R1.10.
Also known as: TSM400-4-TH - Sensor (temperature)
Teracom TST300v3 / TST300v4 RS-485 precision temperature sensor
TST300v3/v4 per the Teracom TST300v3/v4 user manual Revision R1.19.
Also known as: TST300, TST300v3, TST300v4 - Sensor (thermocouple input module)
Teracom TST320 2-channel thermocouple module with Modbus RTU
TST320 per the Teracom TST320 user manual Revision R1.6.
Also known as: TST320 - Sensor (AC/DC voltage transducer)
Teracom TSV300 AC/DC voltage transducer with Modbus RTU
TSV300 per the Teracom TSV300 user manual Revision R1.4, firmware V1.06 or later.
Also known as: TSV300
Other valves, actuators & sensors register maps
- Sensor (CO2 duct transmitter)
Vaisala GMD110 duct CO2 transmitter (Modbus RTU)
GMD110 duct-mount CO2 transmitter, Modbus RTU interface (user guide M212885EN-B).
Also known as: GMD110, CARBOCAP GMD110 - Sensor (humidity and temperature probe)
Vaisala HMP60 / HMP110 series humidity and temperature probes (Modbus RTU)
HMP60/HMP110-series probes ordered with the Modbus RTU option (user guide M211060EN-N).
Also known as: HMP110, HMP113, HMP115, TMP115, HMP60, HMP63, HUMICAP HMP110, HMP110T, HMP63T, HMP115T - Sensor (precipitation)
Vaisala RM60 PRECICAP radar precipitation sensor (Modbus RTU)
RM60 sensors ordered with communication option 1 (RS-485 Modbus RTU) or switched to Modbus, per user guide M213218EN-B.
Also known as: RM60, PRECICAP RM60, Vaisala RM60 - Water treatment controller (Sensor / controller)
Walchem W600 water treatment controller (Modbus/TCP)
Walchem W600 controllers (software 3.01 and up) with the Modbus/TCP feature, per Modbus manual 180676.K. W900, Intuition-6 and Intuition-9 use the same type maps but different block start addresses.
Also known as: W600 series - Sensor (room temperature / humidity)
ACI (Automation Components Inc.) Wall Plate Series BACnet/Modbus temperature/RH sensor
ACI Wall Plate Series stainless wall-plate temperature, RH and temperature/RH sensors with the BACnet MS/TP / Modbus RTU interface (guide I0000931).
Also known as: A/RH-BM wall plate, Wall Plate Series BACnet Modbus - Sensor (particulate matter)
DFRobot SEN0662 Gravity BMV080 PM2.5 air quality sensor (UART Modbus RTU)
DFRobot SEN0662 Gravity BMV080 module with its DIP switch set to UART, firmware V1.0.0 / register map version 4, per the DFRobot wiki register page.
Also known as: SEN0662, Gravity BMV080, BMV080 PM2.5 sensor, DFRobot BMV080
All valves, actuators & sensors Modbus register maps →
Source: TCW210-TH User manual · Revision R1.26 · rev. 2026-10. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.