Easy Modbus
  1. Home
  2. Modbus register maps
  3. Teracom
  4. TCW210-TH temperature and humidity data logger

Sensor (temperature / humidity data logger) · Modbus register map

Teracom TCW210-TH temperature and humidity data logger Modbus register map

Updated 19 November 2026

Short answer

The TCW210-TH is a Teracom Ethernet data logger for up to eight temperature or temperature/humidity sensors on 1-Wire or Modbus RTU. Over Modbus TCP it serves each sensor's values, raw values, limits, trim settings and alarm flags as holding registers.

This page lists 239 Modbus registers for the Teracom TCW210-TH temperature and humidity data logger — 132 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Teracom’s own free documentation (linked below) and checked against it.

Manufacturer
Teracom
Model
TCW210-TH temperature and humidity data logger
Equipment type
Sensor (temperature / humidity data logger)
Registers
239 (132 writable)
Transport
Modbus TCP
Default unit ID
Not stated
TCP port
502
Documented addressing
0-based (the number printed is the address on the wire)
32-bit word order
ABCD high word first (big-endian)
Firmware
V2.012 or later
Also known as
TCW210-TH, TCW210
Source document
TCW210-TH User manual · Revision R1.26 · rev. 2026-10
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Teracom TCW210-TH temperature and humidity data logger

Integration in brief

Enable Modbus TCP, then read sensor values as floats from holding registers 19800 onward (two registers per value) with function 03.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 19800Sensor 1, S11 valueFLOAT32 ABCDSensor 1 first valueRead
HR 19802Sensor 1, S12 valueFLOAT32 ABCDSensor 1 second valueRead
HR 20000Sensor 1, S11 alarm statusUINT16Sensor 1 first value alarmRead
HR 50002Temperature unitUINT16Temperature unitRead/write
HR 50003HW errorUINT16Hardware errorRead/write

Enable Modbus control & writes

Modbus TCP/IP is disabled by default. Enable it on the services page of the web interface (standard port 502).

Byte order & addressing

Network setup

Teracom TCW210-TH temperature and humidity data logger Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

239 of 239 shown
Teracom TCW210-TH temperature and humidity data logger Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR18100Sensor 1 descriptionUser label text, UTF-8, zero padded.STRING[64]Read/write
HR18132Sensor 2 descriptionUser label text, UTF-8, zero padded.STRING[64]Read/write
HR18164Sensor 3 descriptionUser label text, UTF-8, zero padded.STRING[64]Read/write
HR18196Sensor 4 descriptionUser label text, UTF-8, zero padded.STRING[64]Read/write
HR18228Sensor 5 descriptionUser label text, UTF-8, zero padded.STRING[64]Read/write
HR18260Sensor 6 descriptionUser label text, UTF-8, zero padded.STRING[64]Read/write
HR18292Sensor 7 descriptionUser label text, UTF-8, zero padded.STRING[64]Read/write
HR18324Sensor 8 descriptionUser label text, UTF-8, zero padded.STRING[64]Read/write
HR18400Sensor 1, S11 dimensionUnit text for this value, UTF-8.STRING[64]Read
HR18432Sensor 1, S12 dimensionUnit text for this value, UTF-8.STRING[64]Read
HR18464Sensor 1, S13 dimensionUnit text for this value, UTF-8.STRING[64]Read
HR18496Sensor 2, S21 dimensionUnit text for this value, UTF-8.STRING[64]Read
HR18528Sensor 2, S22 dimensionUnit text for this value, UTF-8.STRING[64]Read
HR18560Sensor 2, S23 dimensionUnit text for this value, UTF-8.STRING[64]Read
HR18592Sensor 3, S31 dimensionUnit text for this value, UTF-8.STRING[64]Read
HR18624Sensor 3, S32 dimensionUnit text for this value, UTF-8.STRING[64]Read
HR18656Sensor 3, S33 dimensionUnit text for this value, UTF-8.STRING[64]Read
HR18688Sensor 4, S41 dimensionUnit text for this value, UTF-8.STRING[64]Read
HR18720Sensor 4, S42 dimensionUnit text for this value, UTF-8.STRING[64]Read
HR18752Sensor 4, S43 dimensionUnit text for this value, UTF-8.STRING[64]Read
HR18784Sensor 5, S51 dimensionUnit text for this value, UTF-8.STRING[64]Read
HR18816Sensor 5, S52 dimensionUnit text for this value, UTF-8.STRING[64]Read
HR18848Sensor 5, S53 dimensionUnit text for this value, UTF-8.STRING[64]Read
HR18880Sensor 6, S61 dimensionUnit text for this value, UTF-8.STRING[64]Read
HR18912Sensor 6, S62 dimensionUnit text for this value, UTF-8.STRING[64]Read
HR18944Sensor 6, S63 dimensionUnit text for this value, UTF-8.STRING[64]Read
HR18976Sensor 7, S71 dimensionUnit text for this value, UTF-8.STRING[64]Read
HR19008Sensor 7, S72 dimensionUnit text for this value, UTF-8.STRING[64]Read
HR19040Sensor 7, S73 dimensionUnit text for this value, UTF-8.STRING[64]Read
HR19072Sensor 8, S81 dimensionUnit text for this value, UTF-8.STRING[64]Read
HR19104Sensor 8, S82 dimensionUnit text for this value, UTF-8.STRING[64]Read
HR19136Sensor 8, S83 dimensionUnit text for this value, UTF-8.STRING[64]Read
HR19200Sensor 1, S11 maxUpper alarm limit.FLOAT32ABCDRead/write
HR19202Sensor 1, S12 maxUpper alarm limit.FLOAT32ABCDRead/write
HR19204Sensor 1, S13 maxUpper alarm limit.FLOAT32ABCDRead/write
HR19206Sensor 2, S21 maxUpper alarm limit.FLOAT32ABCDRead/write
HR19208Sensor 2, S22 maxUpper alarm limit.FLOAT32ABCDRead/write
HR19210Sensor 2, S23 maxUpper alarm limit.FLOAT32ABCDRead/write
HR19212Sensor 3, S31 maxUpper alarm limit.FLOAT32ABCDRead/write
HR19214Sensor 3, S32 maxUpper alarm limit.FLOAT32ABCDRead/write
HR19216Sensor 3, S33 maxUpper alarm limit.FLOAT32ABCDRead/write
HR19218Sensor 4, S41 maxUpper alarm limit.FLOAT32ABCDRead/write
HR19220Sensor 4, S42 maxUpper alarm limit.FLOAT32ABCDRead/write
HR19222Sensor 4, S43 maxUpper alarm limit.FLOAT32ABCDRead/write
HR19224Sensor 5, S51 maxUpper alarm limit.FLOAT32ABCDRead/write
HR19226Sensor 5, S52 maxUpper alarm limit.FLOAT32ABCDRead/write
HR19228Sensor 5, S53 maxUpper alarm limit.FLOAT32ABCDRead/write
HR19230Sensor 6, S61 maxUpper alarm limit.FLOAT32ABCDRead/write
HR19232Sensor 6, S62 maxUpper alarm limit.FLOAT32ABCDRead/write
HR19234Sensor 6, S63 maxUpper alarm limit.FLOAT32ABCDRead/write
HR19236Sensor 7, S71 maxUpper alarm limit.FLOAT32ABCDRead/write
HR19238Sensor 7, S72 maxUpper alarm limit.FLOAT32ABCDRead/write
HR19240Sensor 7, S73 maxUpper alarm limit.FLOAT32ABCDRead/write
HR19242Sensor 8, S81 maxUpper alarm limit.FLOAT32ABCDRead/write
HR19244Sensor 8, S82 maxUpper alarm limit.FLOAT32ABCDRead/write
HR19246Sensor 8, S83 maxUpper alarm limit.FLOAT32ABCDRead/write
HR19300Sensor 1, S11 minLower alarm limit.FLOAT32ABCDRead/write
HR19302Sensor 1, S12 minLower alarm limit.FLOAT32ABCDRead/write
HR19304Sensor 1, S13 minLower alarm limit.FLOAT32ABCDRead/write
HR19306Sensor 2, S21 minLower alarm limit.FLOAT32ABCDRead/write
HR19308Sensor 2, S22 minLower alarm limit.FLOAT32ABCDRead/write
HR19310Sensor 2, S23 minLower alarm limit.FLOAT32ABCDRead/write
HR19312Sensor 3, S31 minLower alarm limit.FLOAT32ABCDRead/write
HR19314Sensor 3, S32 minLower alarm limit.FLOAT32ABCDRead/write
HR19316Sensor 3, S33 minLower alarm limit.FLOAT32ABCDRead/write
HR19318Sensor 4, S41 minLower alarm limit.FLOAT32ABCDRead/write
HR19320Sensor 4, S42 minLower alarm limit.FLOAT32ABCDRead/write
HR19322Sensor 4, S43 minLower alarm limit.FLOAT32ABCDRead/write
HR19324Sensor 5, S51 minLower alarm limit.FLOAT32ABCDRead/write
HR19326Sensor 5, S52 minLower alarm limit.FLOAT32ABCDRead/write
HR19328Sensor 5, S53 minLower alarm limit.FLOAT32ABCDRead/write
HR19330Sensor 6, S61 minLower alarm limit.FLOAT32ABCDRead/write
HR19332Sensor 6, S62 minLower alarm limit.FLOAT32ABCDRead/write
HR19334Sensor 6, S63 minLower alarm limit.FLOAT32ABCDRead/write
HR19336Sensor 7, S71 minLower alarm limit.FLOAT32ABCDRead/write
HR19338Sensor 7, S72 minLower alarm limit.FLOAT32ABCDRead/write
HR19340Sensor 7, S73 minLower alarm limit.FLOAT32ABCDRead/write
HR19342Sensor 8, S81 minLower alarm limit.FLOAT32ABCDRead/write
HR19344Sensor 8, S82 minLower alarm limit.FLOAT32ABCDRead/write
HR19346Sensor 8, S83 minLower alarm limit.FLOAT32ABCDRead/write
HR19400Sensor 1, S11 hysteresisAlarm hysteresis.FLOAT32ABCDRead/write
HR19402Sensor 1, S12 hysteresisAlarm hysteresis.FLOAT32ABCDRead/write
HR19404Sensor 1, S13 hysteresisAlarm hysteresis.FLOAT32ABCDRead/write
HR19406Sensor 2, S21 hysteresisAlarm hysteresis.FLOAT32ABCDRead/write
HR19408Sensor 2, S22 hysteresisAlarm hysteresis.FLOAT32ABCDRead/write
HR19410Sensor 2, S23 hysteresisAlarm hysteresis.FLOAT32ABCDRead/write
HR19412Sensor 3, S31 hysteresisAlarm hysteresis.FLOAT32ABCDRead/write
HR19414Sensor 3, S32 hysteresisAlarm hysteresis.FLOAT32ABCDRead/write
HR19416Sensor 3, S33 hysteresisAlarm hysteresis.FLOAT32ABCDRead/write
HR19418Sensor 4, S41 hysteresisAlarm hysteresis.FLOAT32ABCDRead/write
HR19420Sensor 4, S42 hysteresisAlarm hysteresis.FLOAT32ABCDRead/write
HR19422Sensor 4, S43 hysteresisAlarm hysteresis.FLOAT32ABCDRead/write
HR19424Sensor 5, S51 hysteresisAlarm hysteresis.FLOAT32ABCDRead/write
HR19426Sensor 5, S52 hysteresisAlarm hysteresis.FLOAT32ABCDRead/write
HR19428Sensor 5, S53 hysteresisAlarm hysteresis.FLOAT32ABCDRead/write
HR19430Sensor 6, S61 hysteresisAlarm hysteresis.FLOAT32ABCDRead/write
HR19432Sensor 6, S62 hysteresisAlarm hysteresis.FLOAT32ABCDRead/write
HR19434Sensor 6, S63 hysteresisAlarm hysteresis.FLOAT32ABCDRead/write
HR19436Sensor 7, S71 hysteresisAlarm hysteresis.FLOAT32ABCDRead/write
HR19438Sensor 7, S72 hysteresisAlarm hysteresis.FLOAT32ABCDRead/write
HR19440Sensor 7, S73 hysteresisAlarm hysteresis.FLOAT32ABCDRead/write
HR19442Sensor 8, S81 hysteresisAlarm hysteresis.FLOAT32ABCDRead/write
HR19444Sensor 8, S82 hysteresisAlarm hysteresis.FLOAT32ABCDRead/write
HR19446Sensor 8, S83 hysteresisAlarm hysteresis.FLOAT32ABCDRead/write
HR19500Sensor 1, S11 multiplierScaling multiplier applied to the reading.FLOAT32ABCDRead/write
HR19502Sensor 1, S12 multiplierScaling multiplier applied to the reading.FLOAT32ABCDRead/write
HR19504Sensor 1, S13 multiplierScaling multiplier applied to the reading.FLOAT32ABCDRead/write
HR19506Sensor 2, S21 multiplierScaling multiplier applied to the reading.FLOAT32ABCDRead/write
HR19508Sensor 2, S22 multiplierScaling multiplier applied to the reading.FLOAT32ABCDRead/write
HR19510Sensor 2, S23 multiplierScaling multiplier applied to the reading.FLOAT32ABCDRead/write
HR19512Sensor 3, S31 multiplierScaling multiplier applied to the reading.FLOAT32ABCDRead/write
HR19514Sensor 3, S32 multiplierScaling multiplier applied to the reading.FLOAT32ABCDRead/write
HR19516Sensor 3, S33 multiplierScaling multiplier applied to the reading.FLOAT32ABCDRead/write
HR19518Sensor 4, S41 multiplierScaling multiplier applied to the reading.FLOAT32ABCDRead/write
HR19520Sensor 4, S42 multiplierScaling multiplier applied to the reading.FLOAT32ABCDRead/write
HR19522Sensor 4, S43 multiplierScaling multiplier applied to the reading.FLOAT32ABCDRead/write
HR19524Sensor 5, S51 multiplierScaling multiplier applied to the reading.FLOAT32ABCDRead/write
HR19526Sensor 5, S52 multiplierScaling multiplier applied to the reading.FLOAT32ABCDRead/write
HR19528Sensor 5, S53 multiplierScaling multiplier applied to the reading.FLOAT32ABCDRead/write
HR19530Sensor 6, S61 multiplierScaling multiplier applied to the reading.FLOAT32ABCDRead/write
HR19532Sensor 6, S62 multiplierScaling multiplier applied to the reading.FLOAT32ABCDRead/write
HR19534Sensor 6, S63 multiplierScaling multiplier applied to the reading.FLOAT32ABCDRead/write
HR19536Sensor 7, S71 multiplierScaling multiplier applied to the reading.FLOAT32ABCDRead/write
HR19538Sensor 7, S72 multiplierScaling multiplier applied to the reading.FLOAT32ABCDRead/write
HR19540Sensor 7, S73 multiplierScaling multiplier applied to the reading.FLOAT32ABCDRead/write
HR19542Sensor 8, S81 multiplierScaling multiplier applied to the reading.FLOAT32ABCDRead/write
HR19544Sensor 8, S82 multiplierScaling multiplier applied to the reading.FLOAT32ABCDRead/write
HR19546Sensor 8, S83 multiplierScaling multiplier applied to the reading.FLOAT32ABCDRead/write
HR19600Sensor 1, S11 offsetOffset added after the multiplier.FLOAT32ABCDRead/write
HR19602Sensor 1, S12 offsetOffset added after the multiplier.FLOAT32ABCDRead/write
HR19604Sensor 1, S13 offsetOffset added after the multiplier.FLOAT32ABCDRead/write
HR19606Sensor 2, S21 offsetOffset added after the multiplier.FLOAT32ABCDRead/write
HR19608Sensor 2, S22 offsetOffset added after the multiplier.FLOAT32ABCDRead/write
HR19610Sensor 2, S23 offsetOffset added after the multiplier.FLOAT32ABCDRead/write
HR19612Sensor 3, S31 offsetOffset added after the multiplier.FLOAT32ABCDRead/write
HR19614Sensor 3, S32 offsetOffset added after the multiplier.FLOAT32ABCDRead/write
HR19616Sensor 3, S33 offsetOffset added after the multiplier.FLOAT32ABCDRead/write
HR19618Sensor 4, S41 offsetOffset added after the multiplier.FLOAT32ABCDRead/write
HR19620Sensor 4, S42 offsetOffset added after the multiplier.FLOAT32ABCDRead/write
HR19622Sensor 4, S43 offsetOffset added after the multiplier.FLOAT32ABCDRead/write
HR19624Sensor 5, S51 offsetOffset added after the multiplier.FLOAT32ABCDRead/write
HR19626Sensor 5, S52 offsetOffset added after the multiplier.FLOAT32ABCDRead/write
HR19628Sensor 5, S53 offsetOffset added after the multiplier.FLOAT32ABCDRead/write
HR19630Sensor 6, S61 offsetOffset added after the multiplier.FLOAT32ABCDRead/write
HR19632Sensor 6, S62 offsetOffset added after the multiplier.FLOAT32ABCDRead/write
HR19634Sensor 6, S63 offsetOffset added after the multiplier.FLOAT32ABCDRead/write
HR19636Sensor 7, S71 offsetOffset added after the multiplier.FLOAT32ABCDRead/write
HR19638Sensor 7, S72 offsetOffset added after the multiplier.FLOAT32ABCDRead/write
HR19640Sensor 7, S73 offsetOffset added after the multiplier.FLOAT32ABCDRead/write
HR19642Sensor 8, S81 offsetOffset added after the multiplier.FLOAT32ABCDRead/write
HR19644Sensor 8, S82 offsetOffset added after the multiplier.FLOAT32ABCDRead/write
HR19646Sensor 8, S83 offsetOffset added after the multiplier.FLOAT32ABCDRead/write
HR19700Sensor 1 IDSensor ROM ID as text.STRING[16]Read
HR19708Sensor 2 IDSensor ROM ID as text.STRING[16]Read
HR19716Sensor 3 IDSensor ROM ID as text.STRING[16]Read
HR19724Sensor 4 IDSensor ROM ID as text.STRING[16]Read
HR19732Sensor 5 IDSensor ROM ID as text.STRING[16]Read
HR19740Sensor 6 IDSensor ROM ID as text.STRING[16]Read
HR19748Sensor 7 IDSensor ROM ID as text.STRING[16]Read
HR19756Sensor 8 IDSensor ROM ID as text.STRING[16]Read
HR19800Sensor 1, S11 valueSensor reading after multiplier and offset; unit per its dimension string.FLOAT32ABCDRead
HR19802Sensor 1, S12 valueSensor reading after multiplier and offset; unit per its dimension string.FLOAT32ABCDRead
HR19804Sensor 1, S13 valueSensor reading after multiplier and offset; unit per its dimension string.FLOAT32ABCDRead
HR19806Sensor 2, S21 valueSensor reading after multiplier and offset; unit per its dimension string.FLOAT32ABCDRead
HR19808Sensor 2, S22 valueSensor reading after multiplier and offset; unit per its dimension string.FLOAT32ABCDRead
HR19810Sensor 2, S23 valueSensor reading after multiplier and offset; unit per its dimension string.FLOAT32ABCDRead
HR19812Sensor 3, S31 valueSensor reading after multiplier and offset; unit per its dimension string.FLOAT32ABCDRead
HR19814Sensor 3, S32 valueSensor reading after multiplier and offset; unit per its dimension string.FLOAT32ABCDRead
HR19816Sensor 3, S33 valueSensor reading after multiplier and offset; unit per its dimension string.FLOAT32ABCDRead
HR19818Sensor 4, S41 valueSensor reading after multiplier and offset; unit per its dimension string.FLOAT32ABCDRead
HR19820Sensor 4, S42 valueSensor reading after multiplier and offset; unit per its dimension string.FLOAT32ABCDRead
HR19822Sensor 4, S43 valueSensor reading after multiplier and offset; unit per its dimension string.FLOAT32ABCDRead
HR19824Sensor 5, S51 valueSensor reading after multiplier and offset; unit per its dimension string.FLOAT32ABCDRead
HR19826Sensor 5, S52 valueSensor reading after multiplier and offset; unit per its dimension string.FLOAT32ABCDRead
HR19828Sensor 5, S53 valueSensor reading after multiplier and offset; unit per its dimension string.FLOAT32ABCDRead
HR19830Sensor 6, S61 valueSensor reading after multiplier and offset; unit per its dimension string.FLOAT32ABCDRead
HR19832Sensor 6, S62 valueSensor reading after multiplier and offset; unit per its dimension string.FLOAT32ABCDRead
HR19834Sensor 6, S63 valueSensor reading after multiplier and offset; unit per its dimension string.FLOAT32ABCDRead
HR19836Sensor 7, S71 valueSensor reading after multiplier and offset; unit per its dimension string.FLOAT32ABCDRead
HR19838Sensor 7, S72 valueSensor reading after multiplier and offset; unit per its dimension string.FLOAT32ABCDRead
HR19840Sensor 7, S73 valueSensor reading after multiplier and offset; unit per its dimension string.FLOAT32ABCDRead
HR19842Sensor 8, S81 valueSensor reading after multiplier and offset; unit per its dimension string.FLOAT32ABCDRead
HR19844Sensor 8, S82 valueSensor reading after multiplier and offset; unit per its dimension string.FLOAT32ABCDRead
HR19846Sensor 8, S83 valueSensor reading after multiplier and offset; unit per its dimension string.FLOAT32ABCDRead
HR19900Sensor 1, S11 row valueFLOAT32ABCDRead
HR19902Sensor 1, S12 row valueFLOAT32ABCDRead
HR19904Sensor 1, S13 row valueFLOAT32ABCDRead
HR19906Sensor 2, S21 row valueFLOAT32ABCDRead
HR19908Sensor 2, S22 row valueFLOAT32ABCDRead
HR19910Sensor 2, S23 row valueFLOAT32ABCDRead
HR19912Sensor 3, S31 row valueFLOAT32ABCDRead
HR19914Sensor 3, S32 row valueFLOAT32ABCDRead
HR19916Sensor 3, S33 row valueFLOAT32ABCDRead
HR19918Sensor 4, S41 row valueFLOAT32ABCDRead
HR19920Sensor 4, S42 row valueFLOAT32ABCDRead
HR19922Sensor 4, S43 row valueFLOAT32ABCDRead
HR19924Sensor 5, S51 row valueFLOAT32ABCDRead
HR19926Sensor 5, S52 row valueFLOAT32ABCDRead
HR19928Sensor 5, S53 row valueFLOAT32ABCDRead
HR19930Sensor 6, S61 row valueFLOAT32ABCDRead
HR19932Sensor 6, S62 row valueFLOAT32ABCDRead
HR19934Sensor 6, S63 row valueFLOAT32ABCDRead
HR19936Sensor 7, S71 row valueFLOAT32ABCDRead
HR19938Sensor 7, S72 row valueFLOAT32ABCDRead
HR19940Sensor 7, S73 row valueFLOAT32ABCDRead
HR19942Sensor 8, S81 row valueFLOAT32ABCDRead
HR19944Sensor 8, S82 row valueFLOAT32ABCDRead
HR19946Sensor 8, S83 row valueFLOAT32ABCDRead
HR20000Sensor 1, S11 alarm statusAlarm flag for this value.UINT16Read0 = normal; 1 = alarm
HR20001Sensor 1, S12 alarm statusAlarm flag for this value.UINT16Read0 = normal; 1 = alarm
HR20002Sensor 1, S13 alarm statusAlarm flag for this value.UINT16Read0 = normal; 1 = alarm
HR20003Sensor 2, S21 alarm statusAlarm flag for this value.UINT16Read0 = normal; 1 = alarm
HR20004Sensor 2, S22 alarm statusAlarm flag for this value.UINT16Read0 = normal; 1 = alarm
HR20005Sensor 2, S23 alarm statusAlarm flag for this value.UINT16Read0 = normal; 1 = alarm
HR20006Sensor 3, S31 alarm statusAlarm flag for this value.UINT16Read0 = normal; 1 = alarm
HR20007Sensor 3, S32 alarm statusAlarm flag for this value.UINT16Read0 = normal; 1 = alarm
HR20008Sensor 3, S33 alarm statusAlarm flag for this value.UINT16Read0 = normal; 1 = alarm
HR20009Sensor 4, S41 alarm statusAlarm flag for this value.UINT16Read0 = normal; 1 = alarm
HR20010Sensor 4, S42 alarm statusAlarm flag for this value.UINT16Read0 = normal; 1 = alarm
HR20011Sensor 4, S43 alarm statusAlarm flag for this value.UINT16Read0 = normal; 1 = alarm
HR20012Sensor 5, S51 alarm statusAlarm flag for this value.UINT16Read0 = normal; 1 = alarm
HR20013Sensor 5, S52 alarm statusAlarm flag for this value.UINT16Read0 = normal; 1 = alarm
HR20014Sensor 5, S53 alarm statusAlarm flag for this value.UINT16Read0 = normal; 1 = alarm
HR20015Sensor 6, S61 alarm statusAlarm flag for this value.UINT16Read0 = normal; 1 = alarm
HR20016Sensor 6, S62 alarm statusAlarm flag for this value.UINT16Read0 = normal; 1 = alarm
HR20017Sensor 6, S63 alarm statusAlarm flag for this value.UINT16Read0 = normal; 1 = alarm
HR20018Sensor 7, S71 alarm statusAlarm flag for this value.UINT16Read0 = normal; 1 = alarm
HR20019Sensor 7, S72 alarm statusAlarm flag for this value.UINT16Read0 = normal; 1 = alarm
HR20020Sensor 7, S73 alarm statusAlarm flag for this value.UINT16Read0 = normal; 1 = alarm
HR20021Sensor 8, S81 alarm statusAlarm flag for this value.UINT16Read0 = normal; 1 = alarm
HR20022Sensor 8, S82 alarm statusAlarm flag for this value.UINT16Read0 = normal; 1 = alarm
HR20023Sensor 8, S83 alarm statusAlarm flag for this value.UINT16Read0 = normal; 1 = alarm
HR50000Save configurationShows or triggers saving of the configuration.UINT16Read/write0 = unsaved; 1 = saved
HR50001Restart deviceWrite 1 to restart the module.UINT16Read/write0 = cancel; 1 = restart
HR50002Temperature unitUnit used for temperature values.UINT16Read/write0 = Celsius; 1 = Fahrenheit
HR50003HW errorUINT16Read/write0 = noErr; 1 = hwErr
HR50100Device IDSensor ROM ID as text.STRING[18]Read
HR50200HostnameSTRING[16]Read
HR50300Device IPSTRING[16]Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Teracom TCW210-TH temperature and humidity data logger

What Modbus registers does the Teracom TCW210-TH temperature and humidity data logger have?

This map lists 239 registers: 239 holding registers. 132 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Teracom TCW210-TH temperature and humidity data logger Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The address table prints PDU (wire) addresses in decimal. The manual's example frame reads register 19800 as 0x4D58 on the wire, so no offset is applied.

What byte order does the Teracom TCW210-TH temperature and humidity data logger use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Teracom TCW210-TH temperature and humidity data logger?

Start with HR 19800 Sensor 1, S11 value (Sensor 1 first value); HR 19802 Sensor 1, S12 value (Sensor 1 second value); HR 20000 Sensor 1, S11 alarm status (Sensor 1 first value alarm); HR 50002 Temperature unit (Temperature unit); HR 50003 HW error (Hardware error).

How do I enable Modbus control of the Teracom TCW210-TH temperature and humidity data logger?

Modbus TCP/IP is disabled by default. Enable it on the services page of the web interface (standard port 502).

Where is the official Teracom TCW210-TH temperature and humidity data logger Modbus documentation?

The source is TCW210-TH User manual (Revision R1.26), revision 2026-10, published free by Teracom at https://www.teracomsystems.com/download/temperature-humidity-data-logger-tcw210-th-user-manual/.

More Teracom Modbus register maps

Other valves, actuators & sensors register maps

All valves, actuators & sensors Modbus register maps →

Source: TCW210-TH User manual · Revision R1.26 · rev. 2026-10. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.