Sensor (Ethernet I/O module) · Modbus register map
Teracom TCW241 Ethernet I/O module Modbus register map
Updated 19 November 2026
The TCW241 is a Teracom Ethernet I/O module with 4 dry-contact inputs, 4 analog inputs (0-60 VDC), 4 relays and a 1-Wire bus for up to 8 Teracom sensors. Over Modbus TCP it exposes relays as coils, inputs as discrete inputs and all settings, readings and alarm flags as holding registers.
This page lists 204 Modbus registers for the Teracom TCW241 Ethernet I/O module — 132 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Teracom’s own free documentation (linked below) and checked against it.
- Manufacturer
- Teracom
- Model
- TCW241 Ethernet I/O module
- Equipment type
- Sensor (Ethernet I/O module)
- Registers
- 204 (132 writable)
- Transport
- Modbus TCP
- Default unit ID
- Not stated
- TCP port
- 502
- Documented addressing
- 0-based (the number printed is the address on the wire)
- 32-bit word order
- ABCD high word first (big-endian)
- Firmware
- v2.012 or later
- Also known as
- TCW241
- Source document
- TCW241 User manual · Revision R4.30 · rev. 2026-09
Integration notes: Teracom TCW241 Ethernet I/O module
Enable Modbus TCP in the web interface, then switch relays as coils 100-103, read inputs as discrete inputs 100-103 and read analog and 1-Wire values as floats from holding registers 17500+ and 19800+.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| CO 100 | Relay 1 | BIT | Relay 1 | Read/write |
| DI 100 | Digital input 1 | BIT | Digital input 1 | Read |
| HR 17500 | Analog input 1 value | FLOAT32 ABCD | Analog input 1 | Read |
| HR 19800 | Sensor 1, S11 value | FLOAT32 ABCD | Sensor 1 first value | Read |
| HR 20000 | Sensor 1, S11 alarm status | UINT16 | Sensor 1 alarm | Read |
| HR 50003 | HW error | UINT16 | Hardware error | Read |
Enable Modbus control & writes
Modbus TCP/IP is disabled by default. Enable it on the services page of the web interface (standard port 502).
Byte order & addressing
- Floats are high word first (ABCD).
- PDU 50000 reports whether settings are saved (0 = unsaved, 1 = saved).
Network setup
- The factory IP is 192.168.1.2; change it in the network settings, then enable Modbus TCP/IP.
Teracom TCW241 Ethernet I/O module Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 100 | Relay 1 | BIT | Read/write | |||||
| CO | 101 | Relay 2 | BIT | Read/write | |||||
| CO | 102 | Relay 3 | BIT | Read/write | |||||
| CO | 103 | Relay 4 | BIT | Read/write | |||||
| DI | 100 | Digital input 1 | BIT | Read | |||||
| DI | 101 | Digital input 2 | BIT | Read | |||||
| DI | 102 | Digital input 3 | BIT | Read | |||||
| DI | 103 | Digital input 4 | BIT | Read | |||||
| HR | 15000 | Relay 1 description | User label text, UTF-8, zero padded. | STRING[64] | Read/write | ||||
| HR | 15032 | Relay 2 description | User label text, UTF-8, zero padded. | STRING[64] | Read/write | ||||
| HR | 15064 | Relay 3 description | User label text, UTF-8, zero padded. | STRING[64] | Read/write | ||||
| HR | 15096 | Relay 4 description | User label text, UTF-8, zero padded. | STRING[64] | Read/write | ||||
| HR | 15200 | Relay 1 pulse width | FLOAT32 | ABCD | Read/write | ||||
| HR | 15202 | Relay 2 pulse width | FLOAT32 | ABCD | Read/write | ||||
| HR | 15204 | Relay 3 pulse width | FLOAT32 | ABCD | Read/write | ||||
| HR | 15206 | Relay 4 pulse width | FLOAT32 | ABCD | Read/write | ||||
| HR | 15300 | Relay 1 activated from | UINT16 | Read/write | 0 = manual; 1 = sensor11; 2 = sensor12; 3 = sensor21; 4 = sensor22; 5 = sensor31; 6 = sensor32; 7 = sensor41; 8 = sensor42; 9 = sensor51; 10 = sensor52; 11 = sensor61; 12 = sensor62; 13 = sensor71; 14 = sensor72; 15 = sensor81; 16 = sensor82; 17 = analog1; 18 = analog2; 19 = analog3; 20 = analog4; 21 = digital1; 22 = digital2; 23 = digital3; 24 = digital4; 25 = anyAlarm; 26 = anySensor; 27 = anyAnalog; 28 = anyDigital; 29 = func1; 30 = func2; 31 = func3; 32 = func4; 33 = shedule1; 34 = shedule2; 35 = shedule3; 36 = shedule4; 37 = virtual1; 38 = virtual2; 39 = virtual3; 40 = virtual4 | ||||
| HR | 15301 | Relay 2 activated from | UINT16 | Read/write | 0 = manual; 1 = sensor11; 2 = sensor12; 3 = sensor21; 4 = sensor22; 5 = sensor31; 6 = sensor32; 7 = sensor41; 8 = sensor42; 9 = sensor51; 10 = sensor52; 11 = sensor61; 12 = sensor62; 13 = sensor71; 14 = sensor72; 15 = sensor81; 16 = sensor82; 17 = analog1; 18 = analog2; 19 = analog3; 20 = analog4; 21 = digital1; 22 = digital2; 23 = digital3; 24 = digital4; 25 = anyAlarm; 26 = anySensor; 27 = anyAnalog; 28 = anyDigital; 29 = func1; 30 = func2; 31 = func3; 32 = func4; 33 = shedule1; 34 = shedule2; 35 = shedule3; 36 = shedule4; 37 = virtual1; 38 = virtual2; 39 = virtual3; 40 = virtual4 | ||||
| HR | 15302 | Relay 3 activated from | UINT16 | Read/write | 0 = manual; 1 = sensor11; 2 = sensor12; 3 = sensor21; 4 = sensor22; 5 = sensor31; 6 = sensor32; 7 = sensor41; 8 = sensor42; 9 = sensor51; 10 = sensor52; 11 = sensor61; 12 = sensor62; 13 = sensor71; 14 = sensor72; 15 = sensor81; 16 = sensor82; 17 = analog1; 18 = analog2; 19 = analog3; 20 = analog4; 21 = digital1; 22 = digital2; 23 = digital3; 24 = digital4; 25 = anyAlarm; 26 = anySensor; 27 = anyAnalog; 28 = anyDigital; 29 = func1; 30 = func2; 31 = func3; 32 = func4; 33 = shedule1; 34 = shedule2; 35 = shedule3; 36 = shedule4; 37 = virtual1; 38 = virtual2; 39 = virtual3; 40 = virtual4 | ||||
| HR | 15303 | Relay 4 activated from | UINT16 | Read/write | 0 = manual; 1 = sensor11; 2 = sensor12; 3 = sensor21; 4 = sensor22; 5 = sensor31; 6 = sensor32; 7 = sensor41; 8 = sensor42; 9 = sensor51; 10 = sensor52; 11 = sensor61; 12 = sensor62; 13 = sensor71; 14 = sensor72; 15 = sensor81; 16 = sensor82; 17 = analog1; 18 = analog2; 19 = analog3; 20 = analog4; 21 = digital1; 22 = digital2; 23 = digital3; 24 = digital4; 25 = anyAlarm; 26 = anySensor; 27 = anyAnalog; 28 = anyDigital; 29 = func1; 30 = func2; 31 = func3; 32 = func4; 33 = shedule1; 34 = shedule2; 35 = shedule3; 36 = shedule4; 37 = virtual1; 38 = virtual2; 39 = virtual3; 40 = virtual4 | ||||
| HR | 15400 | Relay 1 action on alarm | UINT16 | Read/write | 0 = on; 2 = pulse | ||||
| HR | 15401 | Relay 2 action on alarm | UINT16 | Read/write | 0 = on; 2 = pulse | ||||
| HR | 15402 | Relay 3 action on alarm | UINT16 | Read/write | 0 = on; 2 = pulse | ||||
| HR | 15403 | Relay 4 action on alarm | UINT16 | Read/write | 0 = on; 2 = pulse | ||||
| HR | 15500 | Relays state after restart | UINT16 | Read/write | 0 = off; 1 = on; 2 = last state | ||||
| HR | 16000 | Digital input 1 description | User label text, UTF-8, zero padded. | STRING[64] | Read/write | ||||
| HR | 16032 | Digital input 2 description | User label text, UTF-8, zero padded. | STRING[64] | Read/write | ||||
| HR | 16064 | Digital input 3 description | User label text, UTF-8, zero padded. | STRING[64] | Read/write | ||||
| HR | 16096 | Digital input 4 description | User label text, UTF-8, zero padded. | STRING[64] | Read/write | ||||
| HR | 16200 | Digital input 1 alarm state | Alarm flag for this value. | UINT16 | Read | ||||
| HR | 16201 | Digital input 2 alarm state | Alarm flag for this value. | UINT16 | Read | ||||
| HR | 16202 | Digital input 3 alarm state | Alarm flag for this value. | UINT16 | Read | ||||
| HR | 16203 | Digital input 4 alarm state | Alarm flag for this value. | UINT16 | Read | ||||
| HR | 17000 | Analog input 1 description | User label text, UTF-8, zero padded. | STRING[64] | Read/write | ||||
| HR | 17032 | Analog input 2 description | User label text, UTF-8, zero padded. | STRING[64] | Read/write | ||||
| HR | 17064 | Analog input 3 description | User label text, UTF-8, zero padded. | STRING[64] | Read/write | ||||
| HR | 17096 | Analog input 4 description | User label text, UTF-8, zero padded. | STRING[64] | Read/write | ||||
| HR | 17200 | Analog input 1 max | Upper alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 17202 | Analog input 2 max | Upper alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 17204 | Analog input 3 max | Upper alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 17206 | Analog input 4 max | Upper alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 17300 | Analog input 1 min | Lower alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 17302 | Analog input 2 min | Lower alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 17304 | Analog input 3 min | Lower alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 17306 | Analog input 4 min | Lower alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 17400 | Analog input 1 hysteresis | Alarm hysteresis. | FLOAT32 | ABCD | Read/write | |||
| HR | 17402 | Analog input 2 hysteresis | Alarm hysteresis. | FLOAT32 | ABCD | Read/write | |||
| HR | 17404 | Analog input 3 hysteresis | Alarm hysteresis. | FLOAT32 | ABCD | Read/write | |||
| HR | 17406 | Analog input 4 hysteresis | Alarm hysteresis. | FLOAT32 | ABCD | Read/write | |||
| HR | 17500 | Analog input 1 value | FLOAT32 | ABCD | Read | ||||
| HR | 17502 | Analog input 2 value | FLOAT32 | ABCD | Read | ||||
| HR | 17504 | Analog input 3 value | FLOAT32 | ABCD | Read | ||||
| HR | 17506 | Analog input 4 value | FLOAT32 | ABCD | Read | ||||
| HR | 18100 | Sensor 1 description | User label text, UTF-8, zero padded. | STRING[64] | Read/write | ||||
| HR | 18132 | Sensor 2 description | User label text, UTF-8, zero padded. | STRING[64] | Read/write | ||||
| HR | 18164 | Sensor 3 description | User label text, UTF-8, zero padded. | STRING[64] | Read/write | ||||
| HR | 18196 | Sensor 4 description | User label text, UTF-8, zero padded. | STRING[64] | Read/write | ||||
| HR | 18228 | Sensor 5 description | User label text, UTF-8, zero padded. | STRING[64] | Read/write | ||||
| HR | 18260 | Sensor 6 description | User label text, UTF-8, zero padded. | STRING[64] | Read/write | ||||
| HR | 18292 | Sensor 7 description | User label text, UTF-8, zero padded. | STRING[64] | Read/write | ||||
| HR | 18324 | Sensor 8 description | User label text, UTF-8, zero padded. | STRING[64] | Read/write | ||||
| HR | 18400 | Sensor 1, S11 dimension | Unit text for this value, UTF-8. | STRING[64] | Read | ||||
| HR | 18432 | Sensor 1, S12 dimension | Unit text for this value, UTF-8. | STRING[64] | Read | ||||
| HR | 18464 | Sensor 2, S21 dimension | Unit text for this value, UTF-8. | STRING[64] | Read | ||||
| HR | 18496 | Sensor 2, S22 dimension | Unit text for this value, UTF-8. | STRING[64] | Read | ||||
| HR | 18528 | Sensor 3, S31 dimension | Unit text for this value, UTF-8. | STRING[64] | Read | ||||
| HR | 18560 | Sensor 3, S32 dimension | Unit text for this value, UTF-8. | STRING[64] | Read | ||||
| HR | 18592 | Sensor 4, S41 dimension | Unit text for this value, UTF-8. | STRING[64] | Read | ||||
| HR | 18624 | Sensor 4, S42 dimension | Unit text for this value, UTF-8. | STRING[64] | Read | ||||
| HR | 18656 | Sensor 5, S51 dimension | Unit text for this value, UTF-8. | STRING[64] | Read | ||||
| HR | 18688 | Sensor 5, S52 dimension | Unit text for this value, UTF-8. | STRING[64] | Read | ||||
| HR | 18720 | Sensor 6, S61 dimension | Unit text for this value, UTF-8. | STRING[64] | Read | ||||
| HR | 18752 | Sensor 6, S62 dimension | Unit text for this value, UTF-8. | STRING[64] | Read | ||||
| HR | 18784 | Sensor 7, S71 dimension | Unit text for this value, UTF-8. | STRING[64] | Read | ||||
| HR | 18816 | Sensor 7, S72 dimension | Unit text for this value, UTF-8. | STRING[64] | Read | ||||
| HR | 18848 | Sensor 8, S81 dimension | Unit text for this value, UTF-8. | STRING[64] | Read | ||||
| HR | 18880 | Sensor 8, S82 dimension | Unit text for this value, UTF-8. | STRING[64] | Read | ||||
| HR | 19200 | Sensor 1, S11 max | Upper alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19202 | Sensor 1, S12 max | Upper alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19204 | Sensor 2, S21 max | Upper alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19206 | Sensor 2, S22 max | Upper alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19208 | Sensor 3, S31 max | Upper alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19210 | Sensor 3, S32 max | Upper alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19212 | Sensor 4, S41 max | Upper alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19214 | Sensor 4, S42 max | Upper alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19216 | Sensor 5, S51 max | Upper alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19218 | Sensor 5, S52 max | Upper alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19220 | Sensor 6, S61max | FLOAT32 | ABCD | Read/write | ||||
| HR | 19222 | Sensor 6, S62 max | Upper alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19224 | Sensor 7, S71 max | Upper alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19226 | Sensor 7, S72 max | Upper alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19228 | Sensor 8, S81 max | Upper alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19230 | Sensor 8, S82 max | Upper alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19300 | Sensor 1, S11 min | Lower alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19302 | Sensor 1, S12 min | Lower alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19304 | Sensor 2, S21 min | Lower alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19306 | Sensor 2, S22 min | Lower alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19308 | Sensor 3, S31 min | Lower alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19310 | Sensor 3, S32 min | Lower alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19312 | Sensor 4, S41 min | Lower alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19314 | Sensor 4, S42 min | Lower alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19316 | Sensor 5, S51 min | Lower alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19318 | Sensor 5, S52 min | Lower alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19320 | Sensor 6, S61 min | Lower alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19322 | Sensor 6, S62 min | Lower alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19324 | Sensor 7, S71 min | Lower alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19326 | Sensor 7, S72 min | Lower alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19328 | Sensor 8, S81 min | Lower alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19330 | Sensor 8, S82 min | Lower alarm limit. | FLOAT32 | ABCD | Read/write | |||
| HR | 19400 | Sensor 1, S11 hysteresis | Alarm hysteresis. | FLOAT32 | ABCD | Read/write | |||
| HR | 19402 | Sensor 1, S12 hysteresis | Alarm hysteresis. | FLOAT32 | ABCD | Read/write | |||
| HR | 19404 | Sensor 2, S21 hysteresis | Alarm hysteresis. | FLOAT32 | ABCD | Read/write | |||
| HR | 19406 | Sensor 2, S22 hysteresis | Alarm hysteresis. | FLOAT32 | ABCD | Read/write | |||
| HR | 19408 | Sensor 3, S31 hysteresis | Alarm hysteresis. | FLOAT32 | ABCD | Read/write | |||
| HR | 19410 | Sensor 3, S32 hysteresis | Alarm hysteresis. | FLOAT32 | ABCD | Read/write | |||
| HR | 19412 | Sensor 4, S41 hysteresis | Alarm hysteresis. | FLOAT32 | ABCD | Read/write | |||
| HR | 19414 | Sensor 4, S42 hysteresis | Alarm hysteresis. | FLOAT32 | ABCD | Read/write | |||
| HR | 19416 | Sensor 5, S51 hysteresis | Alarm hysteresis. | FLOAT32 | ABCD | Read/write | |||
| HR | 19418 | Sensor 5, S52 hysteresis | Alarm hysteresis. | FLOAT32 | ABCD | Read/write | |||
| HR | 19420 | Sensor 6, S61 hysteresis | Alarm hysteresis. | FLOAT32 | ABCD | Read/write | |||
| HR | 19422 | Sensor 6, S62 hysteresis | Alarm hysteresis. | FLOAT32 | ABCD | Read/write | |||
| HR | 19424 | Sensor 7, S71 hysteresis | Alarm hysteresis. | FLOAT32 | ABCD | Read/write | |||
| HR | 19426 | Sensor 7, S72 hysteresis | Alarm hysteresis. | FLOAT32 | ABCD | Read/write | |||
| HR | 19428 | Sensor 8, S81 hysteresis | Alarm hysteresis. | FLOAT32 | ABCD | Read/write | |||
| HR | 19430 | Sensor 8, S82 hysteresis | Alarm hysteresis. | FLOAT32 | ABCD | Read/write | |||
| HR | 19500 | Sensor 1, S11 multiplier | Scaling multiplier applied to the reading. | FLOAT32 | ABCD | Read/write | |||
| HR | 19502 | Sensor 1, S12 multiplier | Scaling multiplier applied to the reading. | FLOAT32 | ABCD | Read/write | |||
| HR | 19504 | Sensor 2, S21 multiplier | Scaling multiplier applied to the reading. | FLOAT32 | ABCD | Read/write | |||
| HR | 19506 | Sensor 2, S22 multiplier | Scaling multiplier applied to the reading. | FLOAT32 | ABCD | Read/write | |||
| HR | 19508 | Sensor 3, S31 multiplier | Scaling multiplier applied to the reading. | FLOAT32 | ABCD | Read/write | |||
| HR | 19510 | Sensor 3, S32 multiplier | Scaling multiplier applied to the reading. | FLOAT32 | ABCD | Read/write | |||
| HR | 19512 | Sensor 4, S41 multiplier | Scaling multiplier applied to the reading. | FLOAT32 | ABCD | Read/write | |||
| HR | 19514 | Sensor 4, S42 multiplier | Scaling multiplier applied to the reading. | FLOAT32 | ABCD | Read/write | |||
| HR | 19516 | Sensor 5, S51 multiplier | Scaling multiplier applied to the reading. | FLOAT32 | ABCD | Read/write | |||
| HR | 19518 | Sensor 5, S52 multiplier | Scaling multiplier applied to the reading. | FLOAT32 | ABCD | Read/write | |||
| HR | 19520 | Sensor 6, S61 multiplier | Scaling multiplier applied to the reading. | FLOAT32 | ABCD | Read/write | |||
| HR | 19522 | Sensor 6, S62 multiplier | Scaling multiplier applied to the reading. | FLOAT32 | ABCD | Read/write | |||
| HR | 19524 | Sensor 7, S71 multiplier | Scaling multiplier applied to the reading. | FLOAT32 | ABCD | Read/write | |||
| HR | 19526 | Sensor 7, S72 multiplier | Scaling multiplier applied to the reading. | FLOAT32 | ABCD | Read/write | |||
| HR | 19528 | Sensor 8, S81 multiplier | Scaling multiplier applied to the reading. | FLOAT32 | ABCD | Read/write | |||
| HR | 19530 | Sensor 8, S82 multiplier | Scaling multiplier applied to the reading. | FLOAT32 | ABCD | Read/write | |||
| HR | 19600 | Sensor 1, S11 offset | Offset added after the multiplier. | FLOAT32 | ABCD | Read/write | |||
| HR | 19602 | Sensor 1, S12 offset | Offset added after the multiplier. | FLOAT32 | ABCD | Read/write | |||
| HR | 19604 | Sensor 2, S21 offset | Offset added after the multiplier. | FLOAT32 | ABCD | Read/write | |||
| HR | 19606 | Sensor 2, S22 offset | Offset added after the multiplier. | FLOAT32 | ABCD | Read/write | |||
| HR | 19608 | Sensor 3, S31 offset | Offset added after the multiplier. | FLOAT32 | ABCD | Read/write | |||
| HR | 19610 | Sensor 3, S32 offset | Offset added after the multiplier. | FLOAT32 | ABCD | Read/write | |||
| HR | 19612 | Sensor 4, S41 offset | Offset added after the multiplier. | FLOAT32 | ABCD | Read/write | |||
| HR | 19614 | Sensor 4, S42 offset | Offset added after the multiplier. | FLOAT32 | ABCD | Read/write | |||
| HR | 19616 | Sensor 5, S51 offset | Offset added after the multiplier. | FLOAT32 | ABCD | Read/write | |||
| HR | 19618 | Sensor 5, S52 offset | Offset added after the multiplier. | FLOAT32 | ABCD | Read/write | |||
| HR | 19620 | Sensor 6, S61 offset | Offset added after the multiplier. | FLOAT32 | ABCD | Read/write | |||
| HR | 19622 | Sensor 6, S62 offset | Offset added after the multiplier. | FLOAT32 | ABCD | Read/write | |||
| HR | 19624 | Sensor 7, S71 offset | Offset added after the multiplier. | FLOAT32 | ABCD | Read/write | |||
| HR | 19626 | Sensor 7, S72 offset | Offset added after the multiplier. | FLOAT32 | ABCD | Read/write | |||
| HR | 19628 | Sensor 8, S81 offset | Offset added after the multiplier. | FLOAT32 | ABCD | Read/write | |||
| HR | 19630 | Sensor 8, S82 offset | Offset added after the multiplier. | FLOAT32 | ABCD | Read/write | |||
| HR | 19700 | Sensor 1 ID | Sensor ROM ID as text. | STRING[16] | Read | ||||
| HR | 19708 | Sensor 2 ID | Sensor ROM ID as text. | STRING[16] | Read | ||||
| HR | 19716 | Sensor 3 ID | Sensor ROM ID as text. | STRING[16] | Read | ||||
| HR | 19724 | Sensor 4 ID | Sensor ROM ID as text. | STRING[16] | Read | ||||
| HR | 19732 | Sensor 5 ID | Sensor ROM ID as text. | STRING[16] | Read | ||||
| HR | 19740 | Sensor 6 ID | Sensor ROM ID as text. | STRING[16] | Read | ||||
| HR | 19748 | Sensor 7 ID | Sensor ROM ID as text. | STRING[16] | Read | ||||
| HR | 19756 | Sensor 8 ID | Sensor ROM ID as text. | STRING[16] | Read | ||||
| HR | 19800 | Sensor 1, S11 value | FLOAT32 | ABCD | Read | ||||
| HR | 19802 | Sensor 1, S12 value | FLOAT32 | ABCD | Read | ||||
| HR | 19804 | Sensor 2, S21 value | FLOAT32 | ABCD | Read | ||||
| HR | 19806 | Sensor 2, S22 value | FLOAT32 | ABCD | Read | ||||
| HR | 19808 | Sensor 3, S31 value | FLOAT32 | ABCD | Read | ||||
| HR | 19810 | Sensor 3, S32 value | FLOAT32 | ABCD | Read | ||||
| HR | 19812 | Sensor 4, S41 value | FLOAT32 | ABCD | Read | ||||
| HR | 19814 | Sensor 4, S42 value | FLOAT32 | ABCD | Read | ||||
| HR | 19816 | Sensor 5, S51 value | FLOAT32 | ABCD | Read | ||||
| HR | 19818 | Sensor 5, S52 value | FLOAT32 | ABCD | Read | ||||
| HR | 19820 | Sensor 6, S61 value | FLOAT32 | ABCD | Read | ||||
| HR | 19822 | Sensor 6, S62 value | FLOAT32 | ABCD | Read | ||||
| HR | 19824 | Sensor 7, S71 value | FLOAT32 | ABCD | Read | ||||
| HR | 19826 | Sensor 7, S72 value | FLOAT32 | ABCD | Read | ||||
| HR | 19828 | Sensor 8, S81 value | FLOAT32 | ABCD | Read | ||||
| HR | 19830 | Sensor 8, S82 value | FLOAT32 | ABCD | Read | ||||
| HR | 20000 | Sensor 1, S11 alarm status | Alarm flag for this value. | UINT16 | Read | 0 = normal; 1 = alarm | |||
| HR | 20001 | Sensor 1, S12 alarm status | Alarm flag for this value. | UINT16 | Read | 0 = normal; 1 = alarm | |||
| HR | 20002 | Sensor 2, S21 alarm status | Alarm flag for this value. | UINT16 | Read | 0 = normal; 1 = alarm | |||
| HR | 20003 | Sensor 2, S22 alarm status | Alarm flag for this value. | UINT16 | Read | 0 = normal; 1 = alarm | |||
| HR | 20004 | Sensor 3, S31 alarm status | Alarm flag for this value. | UINT16 | Read | 0 = normal; 1 = alarm | |||
| HR | 20005 | Sensor 3, S32 alarm status | Alarm flag for this value. | UINT16 | Read | 0 = normal; 1 = alarm | |||
| HR | 20006 | Sensor 4, S41 alarm status | Alarm flag for this value. | UINT16 | Read | 0 = normal; 1 = alarm | |||
| HR | 20007 | Sensor 4, S42 alarm status | Alarm flag for this value. | UINT16 | Read | 0 = normal; 1 = alarm | |||
| HR | 20008 | Sensor 5, S51 alarm status | Alarm flag for this value. | UINT16 | Read | 0 = normal; 1 = alarm | |||
| HR | 20009 | Sensor 5, S52 alarm status | Alarm flag for this value. | UINT16 | Read | 0 = normal; 1 = alarm | |||
| HR | 20010 | Sensor 6, S61 alarm status | Alarm flag for this value. | UINT16 | Read | 0 = normal; 1 = alarm | |||
| HR | 20011 | Sensor 6, S62 alarm status | Alarm flag for this value. | UINT16 | Read | 0 = normal; 1 = alarm | |||
| HR | 20012 | Sensor 7, S71 alarm status | Alarm flag for this value. | UINT16 | Read | 0 = normal; 1 = alarm | |||
| HR | 20013 | Sensor 7, S72 alarm status | Alarm flag for this value. | UINT16 | Read | 0 = normal; 1 = alarm | |||
| HR | 20014 | Sensor 8, S81 alarm status | Alarm flag for this value. | UINT16 | Read | 0 = normal; 1 = alarm | |||
| HR | 20015 | Sensor 8, S82 alarm status | Alarm flag for this value. | UINT16 | Read | 0 = normal; 1 = alarm | |||
| HR | 50000 | Save configuration | UINT16 | Read/write | 0 = unsaved; 1 = saved | ||||
| HR | 50001 | Restart device | UINT16 | Read/write | 0 = cancel; 1 = restart | ||||
| HR | 50002 | Temperature unit | UINT16 | Read/write | 0 = Celsius; 1 = Fahrenheit | ||||
| HR | 50003 | HW error | UINT16 | Read | 0 = noErr; 1 = hwErr | ||||
| HR | 50100 | Device ID | Sensor ROM ID as text. | STRING[18] | Read | ||||
| HR | 50200 | Hostname | STRING[16] | Read | |||||
| HR | 50300 | Device IP | STRING[16] | Read |
Notes on this map
- Word order: the manual says float registers are sent big-endian and its example response 41BD 0655 decodes to 23.628, i.e. high word first (ABCD).
- Strings are fixed-length UTF-8, zero padded; 64-byte fields span 32 registers.
- 1-Wire sensor values (S11..S82) are floats whose unit comes from the matching dimension string; each sensor has two value slots (Sx1, Sx2).
- The manual gives no Modbus unit ID requirement.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Teracom TCW241 Ethernet I/O module
What Modbus registers does the Teracom TCW241 Ethernet I/O module have?
This map lists 204 registers: 4 coils, 4 discrete inputs, 196 holding registers. 132 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Teracom TCW241 Ethernet I/O module Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The address table prints PDU (wire) addresses in decimal. The manual's example frame reads register 19800 as 0x4D58 on the wire, so no offset is applied.
What byte order does the Teracom TCW241 Ethernet I/O module use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Teracom TCW241 Ethernet I/O module?
Start with CO 100 Relay 1 (Relay 1); DI 100 Digital input 1 (Digital input 1); HR 17500 Analog input 1 value (Analog input 1); HR 19800 Sensor 1, S11 value (Sensor 1 first value); HR 20000 Sensor 1, S11 alarm status (Sensor 1 alarm); HR 50003 HW error (Hardware error).
How do I enable Modbus control of the Teracom TCW241 Ethernet I/O module?
Modbus TCP/IP is disabled by default. Enable it on the services page of the web interface (standard port 502).
Where is the official Teracom TCW241 Ethernet I/O module Modbus documentation?
The source is TCW241 User manual (Revision R4.30), revision 2026-09, published free by Teracom at https://www.teracomsystems.com/download/ethernet-io-module-tcw241-user-manual/.
More Teracom Modbus register maps
- Sensor (temperature / humidity data logger)
Teracom TCW210-TH temperature and humidity data logger
TCW210-TH per the Teracom TCW210-TH user manual Revision R1.26, firmware V2.012 or later.
Also known as: TCW210-TH, TCW210 - Sensor (Ethernet data logger / I/O module)
Teracom TCW220 Ethernet data logger
TCW220 per the Teracom TCW220 user manual Revision R4.24, firmware V2.012 or later.
Also known as: TCW220 - Energy meter (Ethernet energy monitoring / data logger)
Teracom TCW260 Ethernet energy monitoring module
TCW260 per the Teracom TCW260 user manual Revision R1.19, firmware V3.009 or later.
Also known as: TCW260 - Sensor (Ethernet analog / digital output module)
Teracom TCW280 Ethernet analog output module
TCW280 per the Teracom TCW280 user manual TCW280_R1.8.
Also known as: TCW280 - Sensor (1-Wire to Modbus gateway)
Teracom TCW320x-WMG 1-Wire to Modbus gateway
TCW320E-WMG (Ethernet) and TCW320W-WMG (Wi-Fi) per the user manual Revision R1.0; both share one fixed register map.
Also known as: TCW320E-WMG, TCW320W-WMG - Energy meter (S0 pulse counter / digital input module)
Teracom TDI340 4-channel S0 pulse counter with Modbus RTU
TDI340 per the Teracom TDI340 user manual Revision R1.11, firmware V1.06 or later.
Also known as: TDI340 - Sensor (relay output module)
Teracom TDO340 4-channel Modbus RTU relay output module
TDO340 per the Teracom TDO340 user manual Revision R1.2, firmware V1.03 or later.
Also known as: TDO340 - Sensor (water leak detector)
Teracom TSF400-4 water-leak detector with Modbus RTU
TSF400-4 per the Teracom TSF400-4 user manual Revision R1.2.
Also known as: TSF400-4 - Sensor (humidity / temperature)
Teracom TSH300v3 RS-485 humidity and temperature sensor
TSH300v3 per the Teracom TSH300v3 user manual Revision R1.17.
Also known as: TSH300, TSH300v3 - Sensor (humidity / temperature)
Teracom TSH331 IP54 Modbus RTU humidity and temperature sensor
TSH331 per the Teracom TSH331 user manual Rev. 1.5, firmware v1.08 or later.
Also known as: TSH331 - Sensor (CO2 / pressure)
Teracom TSM400-4-CP Modbus CO2 and barometric pressure sensor
TSM400-4-CP per the Teracom TSM400-4-CP user manual TSM400-4-CP-R1.9.
Also known as: TSM400-4-CP - Sensor (CO2 / humidity / temperature / pressure)
Teracom TSM400-4-CPTH Modbus CO2, humidity, temperature and pressure multi-sensor
TSM400-4-CPTH per the Teracom TSM400-4-CPTH user manual TSM400-4-CPTH-R1.9.
Also known as: TSM400-4-CPTH - Sensor (humidity / temperature)
Teracom TSM400-4-TH Modbus humidity and temperature sensor
TSM400-4-TH per the Teracom TSM400-4-TH user manual TSM400-4-TH-R1.10.
Also known as: TSM400-4-TH - Sensor (temperature)
Teracom TST300v3 / TST300v4 RS-485 precision temperature sensor
TST300v3/v4 per the Teracom TST300v3/v4 user manual Revision R1.19.
Also known as: TST300, TST300v3, TST300v4 - Sensor (thermocouple input module)
Teracom TST320 2-channel thermocouple module with Modbus RTU
TST320 per the Teracom TST320 user manual Revision R1.6.
Also known as: TST320 - Sensor (AC/DC voltage transducer)
Teracom TSV300 AC/DC voltage transducer with Modbus RTU
TSV300 per the Teracom TSV300 user manual Revision R1.4, firmware V1.06 or later.
Also known as: TSV300
Other remote i/o modules register maps
- Sensor (Ethernet digital I/O module)
Acromag BusWorks XT1121-000 16-channel sourcing digital I/O (Modbus TCP)
BusWorks XT1121-000 per user's manual 8500950P (revision P, 18 Nov 2022).
Also known as: XT1121-000, XT1121, BusWorks XT1121 - Sensor (PWM output and counter input module)
ICP DAS M-7088 8-channel PWM output / counter input module (Modbus RTU)
ICP DAS M-7088 eight-channel PWM output module with eight digital inputs and counters, Modbus RTU firmware.
Also known as: M-7088, M7088 - Sensor (remote I/O module, digital inputs/outputs)
Seneca R-16DI-8DO Ethernet I/O (16 digital inputs, 8 digital outputs)
R-16DI-8DO in the Series R I/O manual MI-00604-29-EN.
Also known as: R16DI8DO, R-16DI-8DO, Seneca R series 16DI 8DO - Sensor (I/O module, 4 thermocouple inputs)
Seneca Z-4TC 4-channel thermocouple input module
Seneca Z-4TC DIN-rail module with four thermocouple/mV inputs and RS-485 Modbus RTU, per user manual MI00258-3-EN.
Also known as: Z-4TC - Sensor (remote I/O module)
Unipi Technology Unipi Extension xS51 I/O module
Unipi Extension xS51 RS-485 module per the Unipi Extension xS51 Modbus map v2.0.
Also known as: Unipi Extension xS51, xS51 - Sensor / remote I/O module
Brainboxes ED-538 Ethernet digital I/O (Modbus TCP)
Brainboxes ED-538 Ethernet I/O module with the protocol set to Modbus TCP.
Also known as: ED-538, ED538
All remote i/o modules Modbus register maps →
Source: TCW241 User manual · Revision R4.30 · rev. 2026-09. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.