Easy Modbus
  1. Home
  2. Modbus register maps
  3. Teracom
  4. TCW220 Ethernet data logger

Sensor (Ethernet data logger / I/O module) · Modbus register map

Teracom TCW220 Ethernet data logger Modbus register map

Updated 19 November 2026

Short answer

The TCW220 is a Teracom Ethernet data logger with 2 analog inputs, 2 dry-contact inputs, 2 relays and a 1-Wire bus for up to 8 Teracom sensors. Over Modbus TCP it serves relays as coils, inputs as discrete inputs, and readings, limits and alarm flags as holding registers.

This page lists 178 Modbus registers for the Teracom TCW220 Ethernet data logger — 113 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Teracom’s own free documentation (linked below) and checked against it.

Manufacturer
Teracom
Model
TCW220 Ethernet data logger
Equipment type
Sensor (Ethernet data logger / I/O module)
Registers
178 (113 writable)
Transport
Modbus TCP
Default unit ID
Not stated
TCP port
502
Documented addressing
0-based (the number printed is the address on the wire)
32-bit word order
ABCD high word first (big-endian)
Firmware
V2.012 or later
Also known as
TCW220
Source document
TCW220 User manual · Revision R4.24 · rev. 2026-09
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Teracom TCW220 Ethernet data logger

Integration in brief

Enable Modbus TCP, then switch relays as coils 100-101, read inputs as discrete inputs 100-101 and read analog and 1-Wire floats from holding registers 17500+ and 19800+.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
CO 100Relay 1BITRelay 1Read/write
DI 100Digital input 1BITDigital input 1Read
HR 17500Analog input 1 valueFLOAT32 ABCDAnalog input 1Read
HR 19800Sensor 1, S11 valueFLOAT32 ABCDSensor 1 first valueRead
HR 20000Sensor 1, S11 alarm statusUINT16Sensor 1 alarmRead
HR 50003HW errorUINT16Hardware errorRead/write

Enable Modbus control & writes

Modbus TCP/IP is disabled by default. Enable it on the services page of the web interface (standard port 502).

Byte order & addressing

Network setup

Teracom TCW220 Ethernet data logger Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

178 of 178 shown
Teracom TCW220 Ethernet data logger Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
CO100Relay 1Relay state; write with FC05/15.BITRead/write
CO101Relay 2Relay state; write with FC05/15.BITRead/write
DI100Digital input 1Dry-contact input state.BITRead
DI101Digital input 2Dry-contact input state.BITRead
HR15000Relay 1 descriptionUser label text, UTF-8, zero padded.STRING[64]Read/write
HR15032Relay 2 descriptionUser label text, UTF-8, zero padded.STRING[64]Read/write
HR15200Relay 1 pulse widthPulse duration; the Modbus table gives no unit.FLOAT32ABCDRead/write
HR15202Relay 2 pulse widthPulse duration; the Modbus table gives no unit.FLOAT32ABCDRead/write
HR15300Relay 1 activated fromSource that drives this relay (manual, sensor, input, virtual...).UINT16Read/write0 = manual; 1 = sensor11; 2 = sensor12; 3 = sensor21; 4 = sensor22; 5 = sensor31; 6 = sensor32; 7 = sensor41; 8 = sensor42; 9 = sensor51; 10 = sensor52; 11 = sensor61; 12 = sensor62; 13 = sensor71; 14 = sensor72; 15 = sensor81; 16 = sensor82; 17 = analog1; 18 = analog2; 19 = digital1; 20 = digital2; 21 = anyAlarm; 22 = virtual1; 23 = virtual2; 24 = virtual3; 25 = virtual4
HR15301Relay 2 activated fromSource that drives this relay (manual, sensor, input, virtual...).UINT16Read/write0 = manual; 1 = sensor11; 2 = sensor12; 3 = sensor21; 4 = sensor22; 5 = sensor31; 6 = sensor32; 7 = sensor41; 8 = sensor42; 9 = sensor51; 10 = sensor52; 11 = sensor61; 12 = sensor62; 13 = sensor71; 14 = sensor72; 15 = sensor81; 16 = sensor82; 17 = analog1; 18 = analog2; 19 = digital1; 20 = digital2; 21 = anyAlarm; 22 = virtual1; 23 = virtual2; 24 = virtual3; 25 = virtual4
HR15400Relay 1 action on alarmRelay action when its source alarms.UINT16Read/write0 = on; 2 = pulse
HR15401Relay 2 action on alarmRelay action when its source alarms.UINT16Read/write0 = on; 2 = pulse
HR15500Relays state after restartUINT16Read/write0 = off; 1 = on; 2 = last state
HR16000Digital input 1 descriptionUser label text, UTF-8, zero padded.STRING[64]Read/write
HR16032Digital input 2 descriptionUser label text, UTF-8, zero padded.STRING[64]Read/write
HR16200Digital input 1 alarm stateAlarm flag for this value.UINT16Read
HR16201Digital input 2 alarm stateAlarm flag for this value.UINT16Read
HR17000Analog input 1 descriptionUser label text, UTF-8, zero padded.STRING[64]Read/write
HR17032Analog input 2 descriptionUser label text, UTF-8, zero padded.STRING[64]Read/write
HR17200Analog input 1 maxUpper alarm limit.FLOAT32ABCDRead/write
HR17202Analog input 2 maxUpper alarm limit.FLOAT32ABCDRead/write
HR17300Analog input 1 minLower alarm limit.FLOAT32ABCDRead/write
HR17302Analog input 2 minLower alarm limit.FLOAT32ABCDRead/write
HR17400Analog input 1 hysteresisAlarm hysteresis.FLOAT32ABCDRead/write
HR17402Analog input 2 hysteresisAlarm hysteresis.FLOAT32ABCDRead/write
HR17500Analog input 1 valueAnalog input reading after multiplier and offset.FLOAT32ABCDRead
HR17502Analog input 2 valueAnalog input reading after multiplier and offset.FLOAT32ABCDRead
HR18100Sensor 1 descriptionUser label text, UTF-8, zero padded.STRING[64]Read/write
HR18132Sensor 2 descriptionUser label text, UTF-8, zero padded.STRING[64]Read/write
HR18164Sensor 3 descriptionUser label text, UTF-8, zero padded.STRING[64]Read/write
HR18196Sensor 4 descriptionUser label text, UTF-8, zero padded.STRING[64]Read/write
HR18228Sensor 5 descriptionUser label text, UTF-8, zero padded.STRING[64]Read/write
HR18260Sensor 6 descriptionUser label text, UTF-8, zero padded.STRING[64]Read/write
HR18292Sensor 7 descriptionUser label text, UTF-8, zero padded.STRING[64]Read/write
HR18324Sensor 8 descriptionUser label text, UTF-8, zero padded.STRING[64]Read/write
HR18400Sensor 1, S11 dimensionUnit text for this value, UTF-8.STRING[64]Read
HR18432Sensor 1, S12 dimensionUnit text for this value, UTF-8.STRING[64]Read
HR18464Sensor 2, S21 dimensionUnit text for this value, UTF-8.STRING[64]Read
HR18496Sensor 2, S22 dimensionUnit text for this value, UTF-8.STRING[64]Read
HR18528Sensor 3, S31 dimensionUnit text for this value, UTF-8.STRING[64]Read
HR18560Sensor 3, S32 dimensionUnit text for this value, UTF-8.STRING[64]Read
HR18592Sensor 4, S41 dimensionUnit text for this value, UTF-8.STRING[64]Read
HR18624Sensor 4, S42 dimensionUnit text for this value, UTF-8.STRING[64]Read
HR18656Sensor 5, S51 dimensionUnit text for this value, UTF-8.STRING[64]Read
HR18688Sensor 5, S52 dimensionUnit text for this value, UTF-8.STRING[64]Read
HR18720Sensor 6, S61 dimensionUnit text for this value, UTF-8.STRING[64]Read
HR18752Sensor 6, S62 dimensionUnit text for this value, UTF-8.STRING[64]Read
HR18784Sensor 7, S71 dimensionUnit text for this value, UTF-8.STRING[64]Read
HR18816Sensor 7, S72 dimensionUnit text for this value, UTF-8.STRING[64]Read
HR18848Sensor 8, S81 dimensionUnit text for this value, UTF-8.STRING[64]Read
HR18880Sensor 8, S82 dimensionUnit text for this value, UTF-8.STRING[64]Read
HR19200Sensor 1, S11 maxUpper alarm limit.FLOAT32ABCDRead/write
HR19202Sensor 1, S12 maxUpper alarm limit.FLOAT32ABCDRead/write
HR19204Sensor 2, S21 maxUpper alarm limit.FLOAT32ABCDRead/write
HR19206Sensor 2, S22 maxUpper alarm limit.FLOAT32ABCDRead/write
HR19208Sensor 3, S31 maxUpper alarm limit.FLOAT32ABCDRead/write
HR19210Sensor 3, S32 maxUpper alarm limit.FLOAT32ABCDRead/write
HR19212Sensor 4, S41 maxUpper alarm limit.FLOAT32ABCDRead/write
HR19214Sensor 4, S42 maxUpper alarm limit.FLOAT32ABCDRead/write
HR19216Sensor 5, S51 maxUpper alarm limit.FLOAT32ABCDRead/write
HR19218Sensor 5, S52 maxUpper alarm limit.FLOAT32ABCDRead/write
HR19220Sensor 6, S61 maxUpper alarm limit.FLOAT32ABCDRead/write
HR19222Sensor 6, S62 maxUpper alarm limit.FLOAT32ABCDRead/write
HR19224Sensor 7, S71 maxUpper alarm limit.FLOAT32ABCDRead/write
HR19226Sensor 7, S72 maxUpper alarm limit.FLOAT32ABCDRead/write
HR19228Sensor 8, S81 maxUpper alarm limit.FLOAT32ABCDRead/write
HR19230Sensor 8, S82 maxUpper alarm limit.FLOAT32ABCDRead/write
HR19300Sensor 1, S11 minLower alarm limit.FLOAT32ABCDRead/write
HR19302Sensor 1, S12 minLower alarm limit.FLOAT32ABCDRead/write
HR19304Sensor 2, S21 minLower alarm limit.FLOAT32ABCDRead/write
HR19306Sensor 2, S22 minLower alarm limit.FLOAT32ABCDRead/write
HR19308Sensor 3, S31 minLower alarm limit.FLOAT32ABCDRead/write
HR19310Sensor 3, S32 minLower alarm limit.FLOAT32ABCDRead/write
HR19312Sensor 4, S41 minLower alarm limit.FLOAT32ABCDRead/write
HR19314Sensor 4, S42 minLower alarm limit.FLOAT32ABCDRead/write
HR19316Sensor 5, S51 minLower alarm limit.FLOAT32ABCDRead/write
HR19318Sensor 5, S52 minLower alarm limit.FLOAT32ABCDRead/write
HR19320Sensor 6, S61 minLower alarm limit.FLOAT32ABCDRead/write
HR19322Sensor 6, S62 minLower alarm limit.FLOAT32ABCDRead/write
HR19324Sensor 7, S71 minLower alarm limit.FLOAT32ABCDRead/write
HR19326Sensor 7, S72 minLower alarm limit.FLOAT32ABCDRead/write
HR19328Sensor 8, S81 minLower alarm limit.FLOAT32ABCDRead/write
HR19330Sensor 8, S82 minLower alarm limit.FLOAT32ABCDRead/write
HR19400Sensor 1, S11 hysteresisAlarm hysteresis.FLOAT32ABCDRead/write
HR19402Sensor 1, S12 hysteresisAlarm hysteresis.FLOAT32ABCDRead/write
HR19404Sensor 2, S21 hysteresisAlarm hysteresis.FLOAT32ABCDRead/write
HR19406Sensor 2, S22 hysteresisAlarm hysteresis.FLOAT32ABCDRead/write
HR19408Sensor 3, S31 hysteresisAlarm hysteresis.FLOAT32ABCDRead/write
HR19410Sensor 3, S32 hysteresisAlarm hysteresis.FLOAT32ABCDRead/write
HR19412Sensor 4, S41 hysteresisAlarm hysteresis.FLOAT32ABCDRead/write
HR19414Sensor 4, S42 hysteresisAlarm hysteresis.FLOAT32ABCDRead/write
HR19416Sensor 5, S51 hysteresisAlarm hysteresis.FLOAT32ABCDRead/write
HR19418Sensor 5, S52 hysteresisAlarm hysteresis.FLOAT32ABCDRead/write
HR19420Sensor 6, S61 hysteresisAlarm hysteresis.FLOAT32ABCDRead/write
HR19422Sensor 6, S62 hysteresisAlarm hysteresis.FLOAT32ABCDRead/write
HR19424Sensor 7, S71 hysteresisAlarm hysteresis.FLOAT32ABCDRead/write
HR19426Sensor 7, S72 hysteresisAlarm hysteresis.FLOAT32ABCDRead/write
HR19428Sensor 8, S81 hysteresisAlarm hysteresis.FLOAT32ABCDRead/write
HR19430Sensor 8, S82 hysteresisAlarm hysteresis.FLOAT32ABCDRead/write
HR19500Sensor 1, S11 multiplierScaling multiplier applied to the reading.FLOAT32ABCDRead/write
HR19502Sensor 1, S12 multiplierScaling multiplier applied to the reading.FLOAT32ABCDRead/write
HR19504Sensor 2, S21 multiplierScaling multiplier applied to the reading.FLOAT32ABCDRead/write
HR19506Sensor 2, S22 multiplierScaling multiplier applied to the reading.FLOAT32ABCDRead/write
HR19508Sensor 3, S31 multiplierScaling multiplier applied to the reading.FLOAT32ABCDRead/write
HR19510Sensor 3, S32 multiplierScaling multiplier applied to the reading.FLOAT32ABCDRead/write
HR19512Sensor 4, S41 multiplierScaling multiplier applied to the reading.FLOAT32ABCDRead/write
HR19514Sensor 4, S42 multiplierScaling multiplier applied to the reading.FLOAT32ABCDRead/write
HR19516Sensor 5, S51 multiplierScaling multiplier applied to the reading.FLOAT32ABCDRead/write
HR19518Sensor 5, S52 multiplierScaling multiplier applied to the reading.FLOAT32ABCDRead/write
HR19520Sensor 6, S61 multiplierScaling multiplier applied to the reading.FLOAT32ABCDRead/write
HR19522Sensor 6, S62 multiplierScaling multiplier applied to the reading.FLOAT32ABCDRead/write
HR19524Sensor 7, S71 multiplierScaling multiplier applied to the reading.FLOAT32ABCDRead/write
HR19526Sensor 7, S72 multiplierScaling multiplier applied to the reading.FLOAT32ABCDRead/write
HR19528Sensor 8, S81 multiplierScaling multiplier applied to the reading.FLOAT32ABCDRead/write
HR19530Sensor 8, S82 multiplierScaling multiplier applied to the reading.FLOAT32ABCDRead/write
HR19600Sensor 1, S11 offsetOffset added after the multiplier.FLOAT32ABCDRead/write
HR19602Sensor 1, S12 offsetOffset added after the multiplier.FLOAT32ABCDRead/write
HR19604Sensor 2, S21 offsetOffset added after the multiplier.FLOAT32ABCDRead/write
HR19606Sensor 2, S22 offsetOffset added after the multiplier.FLOAT32ABCDRead/write
HR19608Sensor 3, S31 offsetOffset added after the multiplier.FLOAT32ABCDRead/write
HR19610Sensor 3, S32 offsetOffset added after the multiplier.FLOAT32ABCDRead/write
HR19612Sensor 4, S41 offsetOffset added after the multiplier.FLOAT32ABCDRead/write
HR19614Sensor 4, S42 offsetOffset added after the multiplier.FLOAT32ABCDRead/write
HR19616Sensor 5, S51 offsetOffset added after the multiplier.FLOAT32ABCDRead/write
HR19618Sensor 5, S52 offsetOffset added after the multiplier.FLOAT32ABCDRead/write
HR19620Sensor 6, S61 offsetOffset added after the multiplier.FLOAT32ABCDRead/write
HR19622Sensor 6, S62 offsetOffset added after the multiplier.FLOAT32ABCDRead/write
HR19624Sensor 7, S71 offsetOffset added after the multiplier.FLOAT32ABCDRead/write
HR19626Sensor 7, S72 offsetOffset added after the multiplier.FLOAT32ABCDRead/write
HR19628Sensor 8, S81 offsetOffset added after the multiplier.FLOAT32ABCDRead/write
HR19630Sensor 8, S82 offsetOffset added after the multiplier.FLOAT32ABCDRead/write
HR19700Sensor 1 IDSensor ROM ID as text.STRING[16]Read
HR19708Sensor 2 IDSensor ROM ID as text.STRING[16]Read
HR19716Sensor 3 IDSensor ROM ID as text.STRING[16]Read
HR19724Sensor 4 IDSensor ROM ID as text.STRING[16]Read
HR19732Sensor 5 IDSensor ROM ID as text.STRING[16]Read
HR19740Sensor 6 IDSensor ROM ID as text.STRING[16]Read
HR19748Sensor 7 IDSensor ROM ID as text.STRING[16]Read
HR19756Sensor 8 IDSensor ROM ID as text.STRING[16]Read
HR19800Sensor 1, S11 value1-Wire sensor reading; unit per its dimension string.FLOAT32ABCDRead
HR19802Sensor 1, S12 value1-Wire sensor reading; unit per its dimension string.FLOAT32ABCDRead
HR19804Sensor 2, S21 value1-Wire sensor reading; unit per its dimension string.FLOAT32ABCDRead
HR19806Sensor 2, S22 value1-Wire sensor reading; unit per its dimension string.FLOAT32ABCDRead
HR19808Sensor 3, S31 value1-Wire sensor reading; unit per its dimension string.FLOAT32ABCDRead
HR19810Sensor 3, S32 value1-Wire sensor reading; unit per its dimension string.FLOAT32ABCDRead
HR19812Sensor 4, S41 value1-Wire sensor reading; unit per its dimension string.FLOAT32ABCDRead
HR19814Sensor 4, S42 value1-Wire sensor reading; unit per its dimension string.FLOAT32ABCDRead
HR19816Sensor 5, S51 value1-Wire sensor reading; unit per its dimension string.FLOAT32ABCDRead
HR19818Sensor 5, S52 value1-Wire sensor reading; unit per its dimension string.FLOAT32ABCDRead
HR19820Sensor 6, S61 value1-Wire sensor reading; unit per its dimension string.FLOAT32ABCDRead
HR19822Sensor 6, S62 value1-Wire sensor reading; unit per its dimension string.FLOAT32ABCDRead
HR19824Sensor 7, S71 value1-Wire sensor reading; unit per its dimension string.FLOAT32ABCDRead
HR19826Sensor 7, S72 value1-Wire sensor reading; unit per its dimension string.FLOAT32ABCDRead
HR19828Sensor 8, S81 value1-Wire sensor reading; unit per its dimension string.FLOAT32ABCDRead
HR19830Sensor 8, S82 value1-Wire sensor reading; unit per its dimension string.FLOAT32ABCDRead
HR20000Sensor 1, S11 alarm statusAlarm flag for this value.UINT16Read0 = normal; 1 = alarm
HR20001Sensor 1, S12 alarm statusAlarm flag for this value.UINT16Read0 = normal; 1 = alarm
HR20002Sensor 2, S21 alarm statusAlarm flag for this value.UINT16Read0 = normal; 1 = alarm
HR20003Sensor 2, S22 alarm statusAlarm flag for this value.UINT16Read0 = normal; 1 = alarm
HR20004Sensor 3, S31 alarm statusAlarm flag for this value.UINT16Read0 = normal; 1 = alarm
HR20005Sensor 3, S32 alarm statusAlarm flag for this value.UINT16Read0 = normal; 1 = alarm
HR20006Sensor 4, S41 alarm statusAlarm flag for this value.UINT16Read0 = normal; 1 = alarm
HR20007Sensor 4, S42 alarm statusAlarm flag for this value.UINT16Read0 = normal; 1 = alarm
HR20008Sensor 5, S51 alarm statusAlarm flag for this value.UINT16Read0 = normal; 1 = alarm
HR20009Sensor 5, S52 alarm statusAlarm flag for this value.UINT16Read0 = normal; 1 = alarm
HR20010Sensor 6, S61 alarm statusAlarm flag for this value.UINT16Read0 = normal; 1 = alarm
HR20011Sensor 6, S62 alarm statusAlarm flag for this value.UINT16Read0 = normal; 1 = alarm
HR20012Sensor 7, S71 alarm statusAlarm flag for this value.UINT16Read0 = normal; 1 = alarm
HR20013Sensor 7, S72 alarm statusAlarm flag for this value.UINT16Read0 = normal; 1 = alarm
HR20014Sensor 8, S81 alarm statusAlarm flag for this value.UINT16Read0 = normal; 1 = alarm
HR20015Sensor 8, S82 alarm statusAlarm flag for this value.UINT16Read0 = normal; 1 = alarm
HR50000Save configurationShows or triggers saving of the configuration.UINT16Read/write0 = unsaved; 1 = saved
HR50001Restart deviceWrite 1 to restart the module.UINT16Read/write0 = cancel; 1 = restart
HR50002Temperature unitUnit used for temperature values.UINT16Read/write0 = Celsius; 1 = Fahrenheit
HR50003HW errorUINT16Read/write0 = noErr; 1 = hwErr
HR50100Device IDSensor ROM ID as text.STRING[18]Read
HR50200HostnameSTRING[16]Read
HR50300Device IPSTRING[16]Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Teracom TCW220 Ethernet data logger

What Modbus registers does the Teracom TCW220 Ethernet data logger have?

This map lists 178 registers: 2 coils, 2 discrete inputs, 174 holding registers. 113 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Teracom TCW220 Ethernet data logger Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The address table prints PDU (wire) addresses in decimal. The manual's example frame reads register 19800 as 0x4D58 on the wire, so no offset is applied.

What byte order does the Teracom TCW220 Ethernet data logger use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Teracom TCW220 Ethernet data logger?

Start with CO 100 Relay 1 (Relay 1); DI 100 Digital input 1 (Digital input 1); HR 17500 Analog input 1 value (Analog input 1); HR 19800 Sensor 1, S11 value (Sensor 1 first value); HR 20000 Sensor 1, S11 alarm status (Sensor 1 alarm); HR 50003 HW error (Hardware error).

How do I enable Modbus control of the Teracom TCW220 Ethernet data logger?

Modbus TCP/IP is disabled by default. Enable it on the services page of the web interface (standard port 502).

Where is the official Teracom TCW220 Ethernet data logger Modbus documentation?

The source is TCW220 User manual (Revision R4.24), revision 2026-09, published free by Teracom at https://www.teracomsystems.com/download/ethernet-data-logger-tcw220-user-manual/.

More Teracom Modbus register maps

Other remote i/o modules register maps

All remote i/o modules Modbus register maps →

Source: TCW220 User manual · Revision R4.24 · rev. 2026-09. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.