Sensor (water leak detector) · Modbus register map
Teracom TSF400-4 water-leak detector with Modbus RTU Modbus register map
Updated 19 November 2026
The TSF400-4 is a Teracom floor-standing water-leak detector with five electrodes on its base and a Modbus RTU RS-485 interface. It reports the leak state as a normal and an inverted flag, in both holding and input registers.
This page lists 13 Modbus registers for the Teracom TSF400-4 water-leak detector with Modbus RTU — 4 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Teracom’s own free documentation (linked below) and checked against it.
- Manufacturer
- Teracom
- Model
- TSF400-4 water-leak detector with Modbus RTU
- Equipment type
- Sensor (water leak detector)
- Registers
- 13 (4 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 19200 baud, 8E1
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Also known as
- TSF400-4
- Source document
- TSF400-4 User manual · Revision R1.2 · rev. 2026-10
Integration notes: Teracom TSF400-4 water-leak detector with Modbus RTU
Poll PDU 102 with function 03 (1 = water present) or input register PDU 2 with function 04. Mind the polarity of the non-inverted flag.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 100 | Alarm | UINT16 | Leak flag (1 = dry) | Read |
| HR 102 | Alarm (inverse) | UINT16 | Leak flag inverted (1 = water) | Read |
| IR 1 | Alarm | UINT16 | Leak flag via FC04 | Read |
| IR 2 | Alarm (inverse) | UINT16 | Inverted leak flag via FC04 | Read |
Enable Modbus control & writes
Modbus RTU is the only interface and is always active; there is nothing to switch on. Factory settings are address 1, 19200 baud, 8E1.
Byte order & addressing
- Baud rate and framing changes only take effect after the device is powered off and on again.
- Word order for every 32-bit value is set by the Data order register (PDU 13); check it before blaming the scaling.
Network setup
- Set unit ID (PDU 10), baud (PDU 11) and framing (PDU 12), then power-cycle the device.
- Terminate both ends of the RS-485 bus with 120 ohm resistors; a daisy chain is recommended.
Watch out for
- The non-inverted Alarm flag is 1 when no water is present, so treat a comms timeout as a fault rather than as dry.
Teracom TSF400-4 water-leak detector with Modbus RTU Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 1doc 30002 | Alarm | Leak state; reads 1 while dry. | UINT16 | Read | 0 = Water present; 1 = Water absent | |||
| IR | 2doc 30003 | Alarm (inverse) | Inverted leak state; reads 1 when water is present. | UINT16 | Read | 0 = Water absent; 1 = Water present | |||
| HR | 10doc 40011 | Modbus address | Modbus slave address of the device. | UINT16 | Read/write | ||||
| HR | 11doc 40012 | Baud rate | Serial baud rate; takes effect after a power cycle. | UINT16 | Read/write | ||||
| HR | 12doc 40013 | Parity, data, stop bits | Parity/data/stop framing; takes effect after a power cycle. | UINT16 | Read/write | 1 = 8 data bits, even parity, 1 stop (E81); 2 = 8 data bits, odd parity, 1 stop (O81); 3 = 8 data bits, no parity, 1 stop (N81) | |||
| HR | 13doc 40014 | Data order | Word order used for all 32-bit values. | UINT16 | Read/write | 1 = MSWF - most significant word first; 2 = LSWF - least significant word first | |||
| HR | 14doc 40015 | Device code | Fixed product identification code. | UINT16 | Read | ||||
| HR | 15doc 40016 | FW version | Firmware version number. | UINT16 | Read | ||||
| HR | 18doc 40019 | Vendor URL | Maker URL as UTF-8 text (64 bytes). | STRING[64] | Read | ||||
| HR | 86doc 40087 | Signed integer test value | INT16 | Read | |||||
| HR | 91doc 40092 | Unsigned integer test value | UINT16 | Read | |||||
| HR | 100doc 40101 | Alarm | Leak state; reads 1 while dry. | UINT16 | Read | 0 = Water present; 1 = Water absent | |||
| HR | 102doc 40103 | Alarm (inverse) | Inverted leak state; reads 1 when water is present. | UINT16 | Read | 0 = Water absent; 1 = Water present |
Notes on this map
- Addresses are taken from the manual's PDU address column (0-based); the logical column adds 40001 for holding registers and 30001 for input registers, as the manual states.
- All 32-bit values follow the Data order register (PDU 13): 1 = most significant word first (factory default), 2 = least significant word first. The map shows the default, ABCD.
- Left out: the 32-bit float/integer test-value registers (PDU 82-95), which only exist to check word order; the 16-bit test values are kept.
- The same two alarm flags are readable as holding registers (PDU 100, 102) and as input registers (PDU 1, 2); the normal flag reads 1 when the floor is dry.
- The device has no 32-bit measurement registers; the Data order register only affects the test values.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Teracom TSF400-4 water-leak detector with Modbus RTU
What Modbus registers does the Teracom TSF400-4 water-leak detector with Modbus RTU have?
This map lists 13 registers: 2 input registers, 11 holding registers. 4 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Teracom TSF400-4 water-leak detector with Modbus RTU Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The register table prints both a PDU (wire) address and a logical address (PDU + 40001 for holding registers). 'documented' holds the logical number; the PDU number is what goes in the request, e.g. logical 40101 = PDU 100.
What are the minimum Modbus registers to integrate the Teracom TSF400-4 water-leak detector with Modbus RTU?
Start with HR 100 Alarm (Leak flag (1 = dry)); HR 102 Alarm (inverse) (Leak flag inverted (1 = water)); IR 1 Alarm (Leak flag via FC04); IR 2 Alarm (inverse) (Inverted leak flag via FC04).
How do I enable Modbus control of the Teracom TSF400-4 water-leak detector with Modbus RTU?
Modbus RTU is the only interface and is always active; there is nothing to switch on. Factory settings are address 1, 19200 baud, 8E1.
Where is the official Teracom TSF400-4 water-leak detector with Modbus RTU Modbus documentation?
The source is TSF400-4 User manual (Revision R1.2), revision 2026-10, published free by Teracom at https://www.teracomsystems.com/download/tsf400-4-water-leak-detector-with-modbus-rtu-interface-user-manual/.
More Teracom Modbus register maps
- Sensor (temperature / humidity data logger)
Teracom TCW210-TH temperature and humidity data logger
TCW210-TH per the Teracom TCW210-TH user manual Revision R1.26, firmware V2.012 or later.
Also known as: TCW210-TH, TCW210 - Sensor (Ethernet data logger / I/O module)
Teracom TCW220 Ethernet data logger
TCW220 per the Teracom TCW220 user manual Revision R4.24, firmware V2.012 or later.
Also known as: TCW220 - Sensor (Ethernet I/O module)
Teracom TCW241 Ethernet I/O module
TCW241 per the Teracom TCW241 user manual Revision R4.30, firmware v2.012 or later.
Also known as: TCW241 - Energy meter (Ethernet energy monitoring / data logger)
Teracom TCW260 Ethernet energy monitoring module
TCW260 per the Teracom TCW260 user manual Revision R1.19, firmware V3.009 or later.
Also known as: TCW260 - Sensor (Ethernet analog / digital output module)
Teracom TCW280 Ethernet analog output module
TCW280 per the Teracom TCW280 user manual TCW280_R1.8.
Also known as: TCW280 - Sensor (1-Wire to Modbus gateway)
Teracom TCW320x-WMG 1-Wire to Modbus gateway
TCW320E-WMG (Ethernet) and TCW320W-WMG (Wi-Fi) per the user manual Revision R1.0; both share one fixed register map.
Also known as: TCW320E-WMG, TCW320W-WMG - Energy meter (S0 pulse counter / digital input module)
Teracom TDI340 4-channel S0 pulse counter with Modbus RTU
TDI340 per the Teracom TDI340 user manual Revision R1.11, firmware V1.06 or later.
Also known as: TDI340 - Sensor (relay output module)
Teracom TDO340 4-channel Modbus RTU relay output module
TDO340 per the Teracom TDO340 user manual Revision R1.2, firmware V1.03 or later.
Also known as: TDO340 - Sensor (humidity / temperature)
Teracom TSH300v3 RS-485 humidity and temperature sensor
TSH300v3 per the Teracom TSH300v3 user manual Revision R1.17.
Also known as: TSH300, TSH300v3 - Sensor (humidity / temperature)
Teracom TSH331 IP54 Modbus RTU humidity and temperature sensor
TSH331 per the Teracom TSH331 user manual Rev. 1.5, firmware v1.08 or later.
Also known as: TSH331 - Sensor (CO2 / pressure)
Teracom TSM400-4-CP Modbus CO2 and barometric pressure sensor
TSM400-4-CP per the Teracom TSM400-4-CP user manual TSM400-4-CP-R1.9.
Also known as: TSM400-4-CP - Sensor (CO2 / humidity / temperature / pressure)
Teracom TSM400-4-CPTH Modbus CO2, humidity, temperature and pressure multi-sensor
TSM400-4-CPTH per the Teracom TSM400-4-CPTH user manual TSM400-4-CPTH-R1.9.
Also known as: TSM400-4-CPTH - Sensor (humidity / temperature)
Teracom TSM400-4-TH Modbus humidity and temperature sensor
TSM400-4-TH per the Teracom TSM400-4-TH user manual TSM400-4-TH-R1.10.
Also known as: TSM400-4-TH - Sensor (temperature)
Teracom TST300v3 / TST300v4 RS-485 precision temperature sensor
TST300v3/v4 per the Teracom TST300v3/v4 user manual Revision R1.19.
Also known as: TST300, TST300v3, TST300v4 - Sensor (thermocouple input module)
Teracom TST320 2-channel thermocouple module with Modbus RTU
TST320 per the Teracom TST320 user manual Revision R1.6.
Also known as: TST320 - Sensor (AC/DC voltage transducer)
Teracom TSV300 AC/DC voltage transducer with Modbus RTU
TSV300 per the Teracom TSV300 user manual Revision R1.4, firmware V1.06 or later.
Also known as: TSV300
Other gas detectors register maps
- Sensor (extractive gas detector)
Honeywell Midas S2 extractive gas transmitter (Modbus/TCP)
Honeywell Midas S2 single-point extractive gas transmitters with Ethernet/PoE, user manual 3023M5001 Rev A, Modbus/TCP register map (Table 6-1).
Also known as: Midas S2, MIDAS-S2, Midas S2 gas detector - Sensor (fixed gas detector)
Teledyne Detcon Model DM-700 electrochemical toxic gas / oxygen sensor (RS-485 Modbus)
Teledyne Detcon DM-700 smart sensors with the 4-20 mA and RS-485 Modbus outputs, instruction manual Document #3207, Rev. 5.9.
Also known as: DM-700, Detcon DM-700, Teledyne Detcon DM-700 - Sensor (fixed gas detector)
Teledyne Oldham Simtronics OLCT 700 / OLCT 710 FP catalytic bead combustible gas detector (RS-485 Modbus)
Teledyne Oldham Simtronics OLCT 700 and OLCT 710 FP detectors with 4-20 mA and RS-485 Modbus RTU, manual NP700FPIMEN Revision E.0.
Also known as: OLCT 700 FP, OLCT 710 FP, Oldham OLCT 700 FP, 700 FP series - Gas detection controller (sensor)
Gas Detection Australia GDA 4022
Gas Detection Australia 4022 two-sensor gas detection controller, Modbus document 4022 V4.2 Rev 2.0 (16/11/2022).
Also known as: 4022 V4.2, GDA-4022 - Sensor (infrared gas analyzer)
Teledyne Analytical Instruments 7500 / 7600 infrared gas analyzer (Modbus RTU)
Teledyne 7500 and 7600 infrared gas analyzers with the Modbus communication function; channel registers CH1-CH8 apply to both models, CH9-CH12 to the 7600 only.
Also known as: Teledyne 7500, Teledyne 7600, Model 7500, Model 7600 - Sensor (fixed gas detector)
Teledyne Detcon Model TP-700 MOS (metal oxide) H2S sensor (RS-485 Modbus)
Teledyne Detcon TP-700 smart sensors with the 4-20 mA and RS-485 Modbus outputs, instruction manual Document #3150, Rev. 4.6.
Also known as: TP-700, Detcon TP-700, Teledyne Detcon TP-700
All gas detectors Modbus register maps →
Source: TSF400-4 User manual · Revision R1.2 · rev. 2026-10. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.