Sensor (water leak detector) · Modbus register map

Teracom TSF400-4 water-leak detector with Modbus RTU Modbus register map

Updated 19 November 2026

Short answer

The TSF400-4 is a Teracom floor-standing water-leak detector with five electrodes on its base and a Modbus RTU RS-485 interface. It reports the leak state as a normal and an inverted flag, in both holding and input registers.

This page lists 13 Modbus registers for the Teracom TSF400-4 water-leak detector with Modbus RTU — 4 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Teracom’s own free documentation (linked below) and checked against it.

Manufacturer
Teracom
Model
TSF400-4 water-leak detector with Modbus RTU
Equipment type
Sensor (water leak detector)
Registers
13 (4 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
19200 baud, 8E1
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Also known as
TSF400-4
Source document
TSF400-4 User manual · Revision R1.2 · rev. 2026-10
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Teracom TSF400-4 water-leak detector with Modbus RTU

Integration in brief

Poll PDU 102 with function 03 (1 = water present) or input register PDU 2 with function 04. Mind the polarity of the non-inverted flag.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 100AlarmUINT16Leak flag (1 = dry)Read
HR 102Alarm (inverse)UINT16Leak flag inverted (1 = water)Read
IR 1AlarmUINT16Leak flag via FC04Read
IR 2Alarm (inverse)UINT16Inverted leak flag via FC04Read

Enable Modbus control & writes

Modbus RTU is the only interface and is always active; there is nothing to switch on. Factory settings are address 1, 19200 baud, 8E1.

Byte order & addressing

Network setup

Watch out for

Teracom TSF400-4 water-leak detector with Modbus RTU Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

13 of 13 shown
Teracom TSF400-4 water-leak detector with Modbus RTU Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR1doc 30002AlarmLeak state; reads 1 while dry.UINT16Read0 = Water present; 1 = Water absent
IR2doc 30003Alarm (inverse)Inverted leak state; reads 1 when water is present.UINT16Read0 = Water absent; 1 = Water present
HR10doc 40011Modbus addressModbus slave address of the device.UINT16Read/write
HR11doc 40012Baud rateSerial baud rate; takes effect after a power cycle.UINT16Read/write
HR12doc 40013Parity, data, stop bitsParity/data/stop framing; takes effect after a power cycle.UINT16Read/write1 = 8 data bits, even parity, 1 stop (E81); 2 = 8 data bits, odd parity, 1 stop (O81); 3 = 8 data bits, no parity, 1 stop (N81)
HR13doc 40014Data orderWord order used for all 32-bit values.UINT16Read/write1 = MSWF - most significant word first; 2 = LSWF - least significant word first
HR14doc 40015Device codeFixed product identification code.UINT16Read
HR15doc 40016FW versionFirmware version number.UINT16Read
HR18doc 40019Vendor URLMaker URL as UTF-8 text (64 bytes).STRING[64]Read
HR86doc 40087Signed integer test valueINT16Read
HR91doc 40092Unsigned integer test valueUINT16Read
HR100doc 40101AlarmLeak state; reads 1 while dry.UINT16Read0 = Water present; 1 = Water absent
HR102doc 40103Alarm (inverse)Inverted leak state; reads 1 when water is present.UINT16Read0 = Water absent; 1 = Water present

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Teracom TSF400-4 water-leak detector with Modbus RTU

What Modbus registers does the Teracom TSF400-4 water-leak detector with Modbus RTU have?

This map lists 13 registers: 2 input registers, 11 holding registers. 4 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Teracom TSF400-4 water-leak detector with Modbus RTU Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The register table prints both a PDU (wire) address and a logical address (PDU + 40001 for holding registers). 'documented' holds the logical number; the PDU number is what goes in the request, e.g. logical 40101 = PDU 100.

What are the minimum Modbus registers to integrate the Teracom TSF400-4 water-leak detector with Modbus RTU?

Start with HR 100 Alarm (Leak flag (1 = dry)); HR 102 Alarm (inverse) (Leak flag inverted (1 = water)); IR 1 Alarm (Leak flag via FC04); IR 2 Alarm (inverse) (Inverted leak flag via FC04).

How do I enable Modbus control of the Teracom TSF400-4 water-leak detector with Modbus RTU?

Modbus RTU is the only interface and is always active; there is nothing to switch on. Factory settings are address 1, 19200 baud, 8E1.

Where is the official Teracom TSF400-4 water-leak detector with Modbus RTU Modbus documentation?

The source is TSF400-4 User manual (Revision R1.2), revision 2026-10, published free by Teracom at https://www.teracomsystems.com/download/tsf400-4-water-leak-detector-with-modbus-rtu-interface-user-manual/.

More Teracom Modbus register maps

Other gas detectors register maps

All gas detectors Modbus register maps →

Source: TSF400-4 User manual · Revision R1.2 · rev. 2026-10. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.