Easy Modbus
  1. Home
  2. Modbus register maps
  3. Teledyne Oldham Simtronics
  4. OLCT 700 / OLCT 710 FP catalytic bead combustible gas detector (RS-485 Modbus)

Sensor (fixed gas detector) · Modbus register map

Teledyne Oldham Simtronics OLCT 700 / OLCT 710 FP catalytic bead combustible gas detector (RS-485 Modbus) Modbus register map

Updated 17 November 2026

Short answer

The OLCT 700 and OLCT 710 FP are Oldham-branded versions of the Teledyne 700-series smart catalytic bead combustible gas detectors. Next to the 4-20 mA loop they answer Modbus RTU on RS-485 with 22 holding registers: range, gas reading, span level, sensor life, fault bits, loop current, supply voltage, model-specific diagnostics, calibration command and gas/units text. This map covers all of them except temperature.

This page lists 16 Modbus registers for the Teledyne Oldham Simtronics OLCT 700 / OLCT 710 FP catalytic bead combustible gas detector (RS-485 Modbus) — 4 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Teledyne Oldham Simtronics’s own free documentation (linked below) and checked against it.

Manufacturer
Teledyne Oldham Simtronics
Model
OLCT 700 / OLCT 710 FP catalytic bead combustible gas detector (RS-485 Modbus)
Equipment type
Sensor (fixed gas detector)
Registers
16 (4 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
9600 baud, 8N1
Documented addressing
0-based (the number printed is the address on the wire)
Also known as
OLCT 700 FP, OLCT 710 FP, Oldham OLCT 700 FP, 700 FP series
Source document
700 FP Series Combustible Gas Detector OLCT 700 / OLCT 710 Instruction Manual · NP700FPIMEN Revision E.0 · rev. 2021-11
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Teledyne Oldham Simtronics OLCT 700 / OLCT 710 FP catalytic bead combustible gas detector (RS-485 Modbus)

Integration in brief

Give each sensor its own serial ID from the magnetic-switch menu, wire RS-485 at 9600 8N1 and poll holding registers 0-9 with function 03; read 40005 for faults.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 2Gas concentrationUINT16Gas concentrationRead
HR 1Detectable rangeUINT16Detectable range (full scale)Read
HR 5Fault status bitsBITMAP16Fault status bitsRead
HR 4Sensor lifeUINT16Sensor lifeRead
HR 84-20 mA outputUINT16Loop currentRead
HR 16Gas/units notation stringSTRING[12]Gas and units textRead

Enable Modbus control & writes

The manual describes no separate enable step; set a unique serial ID in Program Mode (Set Serial ID).

Byte order & addressing

Network setup

Watch out for

Teledyne Oldham Simtronics OLCT 700 / OLCT 710 FP catalytic bead combustible gas detector (RS-485 Modbus) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

16 of 16 shown
Teledyne Oldham Simtronics OLCT 700 / OLCT 710 FP catalytic bead combustible gas detector (RS-485 Modbus) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 40000Device typeReads 8.UINT16Read8 = OLCT 700/710 detector
HR1doc 40001Detectable rangeFull scale in the units of the notation string. Read only on FP detectors.UINT16Read
HR2doc 40002Gas concentrationGas reading in the units of the notation string (normally %LEL).UINT16Read
HR3doc 40003AutoSpan levelSpan gas concentration used for calibration.UINT16Read/write
HR4doc 40004Sensor lifeRemaining sensor life.UINT16%Read
HR5doc 40005Fault status bitsFaults clear themselves when the condition clears.BITMAP16Readbit 0 = Global fault; bit 1 = AutoSpan fault; bit 2 = Temperature fault; bit 3 = 4-20 mA fault; bit 4 = Input voltage fault; bit 5 = Memory fault; bit 6 = Processor fault; bit 7 = Clearing fault; bit 8 = Stability fault; bit 9 = Range fault; bit 10 = Sensor fault; bit 11 = Zero fault; bit 12 = Sensor fault 2; bit 14 = In calibration; bit 15 = Communication error
HR6doc 40006Model numberUINT16Read1 = DM; 2 = FP; 3 = IR; 4 = TP; 5 = PID
HR7doc 40007Days since calibrationUINT16daysRead
HR8doc 400084-20 mA outputCurrent loop output value.UINT16× 0.01mARead
HR9doc 40009Input voltageUINT16× 0.01VRead
HR11doc 40011Gas factorRange 79-565.UINT16Read/write
HR12doc 40012Cal factorRange 79-565.UINT16Read/write
HR13doc 40013Bridge currentUINT16mARead
HR14doc 40014Bridge voltageRead only.UINT16mVRead
HR15doc 40015Calibration status / enableRead gives status; write starts an action.UINT16Read/write0 = Read: idle; 1 = Read: zero calibration started / Write: set zero; 2 = Read: span calibration started / Write: set span; 3 = Read: span set; 4 = Read: span calibration unsuccessful; 8 = Write: signal simulation mode; 9 = Write: set FP bridge voltage; 10 = Write: set TP heater power; 11 = Write: set IR gain
HR16doc 40016-40021Gas/units notation stringUnits, a space, then gas name, null-terminated; first character in the low byte of each register.STRING[12]Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Teledyne Oldham Simtronics OLCT 700 / OLCT 710 FP catalytic bead combustible gas detector (RS-485 Modbus)

What Modbus registers does the Teledyne Oldham Simtronics OLCT 700 / OLCT 710 FP catalytic bead combustible gas detector (RS-485 Modbus) have?

This map lists 16 registers: 16 holding registers. 4 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Teledyne Oldham Simtronics OLCT 700 / OLCT 710 FP catalytic bead combustible gas detector (RS-485 Modbus) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual prints registers as 40000-40021, starting at 40000, so the digits after the leading 4 are the 0-based wire address: 40000 (device type) is address 0 and 40002 (gas reading) is address 2. Only function 03 reads them; writable ones use function 06.

What are the minimum Modbus registers to integrate the Teledyne Oldham Simtronics OLCT 700 / OLCT 710 FP catalytic bead combustible gas detector (RS-485 Modbus)?

Start with HR 2 Gas concentration (Gas concentration); HR 1 Detectable range (Detectable range (full scale)); HR 5 Fault status bits (Fault status bits); HR 4 Sensor life (Sensor life); HR 8 4-20 mA output (Loop current); HR 16 Gas/units notation string (Gas and units text).

How do I enable Modbus control of the Teledyne Oldham Simtronics OLCT 700 / OLCT 710 FP catalytic bead combustible gas detector (RS-485 Modbus)?

The manual describes no separate enable step; set a unique serial ID in Program Mode (Set Serial ID).

Where is the official Teledyne Oldham Simtronics OLCT 700 / OLCT 710 FP catalytic bead combustible gas detector (RS-485 Modbus) Modbus documentation?

The source is 700 FP Series Combustible Gas Detector OLCT 700 / OLCT 710 Instruction Manual (NP700FPIMEN Revision E.0), revision 2021-11, published free by Teledyne Oldham Simtronics at https://www.teledynegasandflamedetection.com/en-us/Products/docs/fixedgas-700series-olct700-710-fp-usermanual-english.pdf.

More Teledyne Oldham Simtronics Modbus register maps

Other gas detectors register maps

All gas detectors Modbus register maps →

Source: 700 FP Series Combustible Gas Detector OLCT 700 / OLCT 710 Instruction Manual · NP700FPIMEN Revision E.0 · rev. 2021-11. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.