- Home
- Modbus register maps
- Teledyne Oldham Simtronics
- OLCT 700 / OLCT 710 FP catalytic bead combustible gas detector (RS-485 Modbus)
Sensor (fixed gas detector) · Modbus register map
Teledyne Oldham Simtronics OLCT 700 / OLCT 710 FP catalytic bead combustible gas detector (RS-485 Modbus) Modbus register map
Updated 17 November 2026
The OLCT 700 and OLCT 710 FP are Oldham-branded versions of the Teledyne 700-series smart catalytic bead combustible gas detectors. Next to the 4-20 mA loop they answer Modbus RTU on RS-485 with 22 holding registers: range, gas reading, span level, sensor life, fault bits, loop current, supply voltage, model-specific diagnostics, calibration command and gas/units text. This map covers all of them except temperature.
This page lists 16 Modbus registers for the Teledyne Oldham Simtronics OLCT 700 / OLCT 710 FP catalytic bead combustible gas detector (RS-485 Modbus) — 4 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Teledyne Oldham Simtronics’s own free documentation (linked below) and checked against it.
- Manufacturer
- Teledyne Oldham Simtronics
- Model
- OLCT 700 / OLCT 710 FP catalytic bead combustible gas detector (RS-485 Modbus)
- Equipment type
- Sensor (fixed gas detector)
- Registers
- 16 (4 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 9600 baud, 8N1
- Documented addressing
- 0-based (the number printed is the address on the wire)
- Also known as
- OLCT 700 FP, OLCT 710 FP, Oldham OLCT 700 FP, 700 FP series
Integration notes: Teledyne Oldham Simtronics OLCT 700 / OLCT 710 FP catalytic bead combustible gas detector (RS-485 Modbus)
Give each sensor its own serial ID from the magnetic-switch menu, wire RS-485 at 9600 8N1 and poll holding registers 0-9 with function 03; read 40005 for faults.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 2 | Gas concentration | UINT16 | Gas concentration | Read |
| HR 1 | Detectable range | UINT16 | Detectable range (full scale) | Read |
| HR 5 | Fault status bits | BITMAP16 | Fault status bits | Read |
| HR 4 | Sensor life | UINT16 | Sensor life | Read |
| HR 8 | 4-20 mA output | UINT16 | Loop current | Read |
| HR 16 | Gas/units notation string | STRING[12] | Gas and units text | Read |
Enable Modbus control & writes
The manual describes no separate enable step; set a unique serial ID in Program Mode (Set Serial ID).
Byte order & addressing
- Register numbers start at 40000 = wire address 0.
- The text names function 03 as the only supported code, but the register table lists function 06 for writing the R/W registers.
- Text characters are low byte first.
Network setup
- 9600 baud, 8 data bits, no parity, 1 stop bit.
- Serial ID is entered in hexadecimal (01, 02 ... 0A ...).
Watch out for
- Bit 14 of the fault register is set while the sensor is in calibration.
Teledyne Oldham Simtronics OLCT 700 / OLCT 710 FP catalytic bead combustible gas detector (RS-485 Modbus) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 40000 | Device type | Reads 8. | UINT16 | Read | 8 = OLCT 700/710 detector | |||
| HR | 1doc 40001 | Detectable range | Full scale in the units of the notation string. Read only on FP detectors. | UINT16 | Read | ||||
| HR | 2doc 40002 | Gas concentration | Gas reading in the units of the notation string (normally %LEL). | UINT16 | Read | ||||
| HR | 3doc 40003 | AutoSpan level | Span gas concentration used for calibration. | UINT16 | Read/write | ||||
| HR | 4doc 40004 | Sensor life | Remaining sensor life. | UINT16 | % | Read | |||
| HR | 5doc 40005 | Fault status bits | Faults clear themselves when the condition clears. | BITMAP16 | Read | bit 0 = Global fault; bit 1 = AutoSpan fault; bit 2 = Temperature fault; bit 3 = 4-20 mA fault; bit 4 = Input voltage fault; bit 5 = Memory fault; bit 6 = Processor fault; bit 7 = Clearing fault; bit 8 = Stability fault; bit 9 = Range fault; bit 10 = Sensor fault; bit 11 = Zero fault; bit 12 = Sensor fault 2; bit 14 = In calibration; bit 15 = Communication error | |||
| HR | 6doc 40006 | Model number | UINT16 | Read | 1 = DM; 2 = FP; 3 = IR; 4 = TP; 5 = PID | ||||
| HR | 7doc 40007 | Days since calibration | UINT16 | days | Read | ||||
| HR | 8doc 40008 | 4-20 mA output | Current loop output value. | UINT16 | × 0.01 | mA | Read | ||
| HR | 9doc 40009 | Input voltage | UINT16 | × 0.01 | V | Read | |||
| HR | 11doc 40011 | Gas factor | Range 79-565. | UINT16 | Read/write | ||||
| HR | 12doc 40012 | Cal factor | Range 79-565. | UINT16 | Read/write | ||||
| HR | 13doc 40013 | Bridge current | UINT16 | mA | Read | ||||
| HR | 14doc 40014 | Bridge voltage | Read only. | UINT16 | mV | Read | |||
| HR | 15doc 40015 | Calibration status / enable | Read gives status; write starts an action. | UINT16 | Read/write | 0 = Read: idle; 1 = Read: zero calibration started / Write: set zero; 2 = Read: span calibration started / Write: set span; 3 = Read: span set; 4 = Read: span calibration unsuccessful; 8 = Write: signal simulation mode; 9 = Write: set FP bridge voltage; 10 = Write: set TP heater power; 11 = Write: set IR gain | |||
| HR | 16doc 40016-40021 | Gas/units notation string | Units, a space, then gas name, null-terminated; first character in the low byte of each register. | STRING[12] | Read |
Notes on this map
- All registers are single 16-bit holding registers; the manual shares one table across FP, IR and TP detectors and model register 40006 tells them apart. Registers 40011-40014 change meaning with the model; only the FP detector meanings are given here.
- The manual footnote on reading scale refers to Low Range, which the FP detector does not have; the reading is taken as whole units.
- Range, reading and span level are in the units of the notation string (PPM, PPB or %).
- Register 40010 (temperature, °C) is left out: the manual gives no data type, so it is unclear how readings below 0 °C are coded.
- The notation string stores the first character in the low byte of each register (low byte, high byte, ...), the reverse of the usual Modbus string order.
- Bit 13 of the fault register is reserved.
- Default serial ID is 01; it is set in the sensor menu (Set Serial ID) in hexadecimal.
- The manual prints device type 8 as "OLCT 700/710 Detector"; the register layout is the same as the Teledyne Detcon 700 series.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Teledyne Oldham Simtronics OLCT 700 / OLCT 710 FP catalytic bead combustible gas detector (RS-485 Modbus)
What Modbus registers does the Teledyne Oldham Simtronics OLCT 700 / OLCT 710 FP catalytic bead combustible gas detector (RS-485 Modbus) have?
This map lists 16 registers: 16 holding registers. 4 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Teledyne Oldham Simtronics OLCT 700 / OLCT 710 FP catalytic bead combustible gas detector (RS-485 Modbus) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual prints registers as 40000-40021, starting at 40000, so the digits after the leading 4 are the 0-based wire address: 40000 (device type) is address 0 and 40002 (gas reading) is address 2. Only function 03 reads them; writable ones use function 06.
What are the minimum Modbus registers to integrate the Teledyne Oldham Simtronics OLCT 700 / OLCT 710 FP catalytic bead combustible gas detector (RS-485 Modbus)?
Start with HR 2 Gas concentration (Gas concentration); HR 1 Detectable range (Detectable range (full scale)); HR 5 Fault status bits (Fault status bits); HR 4 Sensor life (Sensor life); HR 8 4-20 mA output (Loop current); HR 16 Gas/units notation string (Gas and units text).
How do I enable Modbus control of the Teledyne Oldham Simtronics OLCT 700 / OLCT 710 FP catalytic bead combustible gas detector (RS-485 Modbus)?
The manual describes no separate enable step; set a unique serial ID in Program Mode (Set Serial ID).
Where is the official Teledyne Oldham Simtronics OLCT 700 / OLCT 710 FP catalytic bead combustible gas detector (RS-485 Modbus) Modbus documentation?
The source is 700 FP Series Combustible Gas Detector OLCT 700 / OLCT 710 Instruction Manual (NP700FPIMEN Revision E.0), revision 2021-11, published free by Teledyne Oldham Simtronics at https://www.teledynegasandflamedetection.com/en-us/Products/docs/fixedgas-700series-olct700-710-fp-usermanual-english.pdf.
More Teledyne Oldham Simtronics Modbus register maps
Other gas detectors register maps
- Gas detection controller (sensor)
Gas Detection Australia GDA 4022
Gas Detection Australia 4022 two-sensor gas detection controller, Modbus document 4022 V4.2 Rev 2.0 (16/11/2022).
Also known as: 4022 V4.2, GDA-4022 - Sensor (infrared gas analyzer)
Teledyne Analytical Instruments 7500 / 7600 infrared gas analyzer (Modbus RTU)
Teledyne 7500 and 7600 infrared gas analyzers with the Modbus communication function; channel registers CH1-CH8 apply to both models, CH9-CH12 to the 7600 only.
Also known as: Teledyne 7500, Teledyne 7600, Model 7500, Model 7600 - Sensor (fixed gas detector)
Teledyne Detcon Model TP-700 MOS (metal oxide) H2S sensor (RS-485 Modbus)
Teledyne Detcon TP-700 smart sensors with the 4-20 mA and RS-485 Modbus outputs, instruction manual Document #3150, Rev. 4.6.
Also known as: TP-700, Detcon TP-700, Teledyne Detcon TP-700 - Sensor (CO2 / gas)
CO2Meter CM500 CO2 sensor / controller (RS-485 Modbus RTU)
CO2Meter.com CM500 with the RS-485 Modbus RTU interface, per the vendor's 'RS485 Communications Modbus Protocol' sheet (no document number).
Also known as: CM500, CO2Meter CM500 - Sensor (environmental / leak monitor)
RLE Technologies Falcon F200 environment and leak monitoring appliance (Modbus TCP)
RLE Falcon F200 with firmware 4100.1 or later; register guide v06.21.
Also known as: F200, Falcon F200 - Sensor (fixed gas detector)
Teledyne Detcon Model IR-700 infrared combustible / CO2 gas sensor (RS-485 Modbus)
Teledyne Detcon IR-700 smart sensors with the 4-20 mA and RS-485 Modbus outputs, instruction manual Document #3169, Rev. 4.9.
Also known as: IR-700, Detcon IR-700, Teledyne Detcon IR-700
All gas detectors Modbus register maps →
Source: 700 FP Series Combustible Gas Detector OLCT 700 / OLCT 710 Instruction Manual · NP700FPIMEN Revision E.0 · rev. 2021-11. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.