- OLCT 700 / OLCT 710 IR infrared combustible / CO2 gas detector (RS-485 Modbus)
Sensor (fixed gas detector) · Modbus register map
Teledyne Oldham Simtronics OLCT 700 / OLCT 710 IR infrared combustible / CO2 gas detector (RS-485 Modbus) Modbus register map
Updated 17 November 2026
The OLCT 700 and OLCT 710 IR are Oldham-branded versions of the Teledyne 700-series smart infrared combustible / CO2 gas detectors. Next to the 4-20 mA loop they answer Modbus RTU on RS-485 with 22 holding registers: range, gas reading, span level, sensor life, fault bits, loop current, supply voltage, model-specific diagnostics, calibration command and gas/units text. This map covers all of them except temperature.
This page lists 16 Modbus registers for the Teledyne Oldham Simtronics OLCT 700 / OLCT 710 IR infrared combustible / CO2 gas detector (RS-485 Modbus) — 5 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Teledyne Oldham Simtronics’s own free documentation (linked below) and checked against it.
- Manufacturer
- Teledyne Oldham Simtronics
- Model
- OLCT 700 / OLCT 710 IR infrared combustible / CO2 gas detector (RS-485 Modbus)
- Equipment type
- Sensor (fixed gas detector)
- Registers
- 16 (5 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 9600 baud, 8N1
- Documented addressing
- 0-based (the number printed is the address on the wire)
- Also known as
- OLCT 700 IR, OLCT 710 IR, Oldham OLCT 700 IR, 700 IR series
Integration notes: Teledyne Oldham Simtronics OLCT 700 / OLCT 710 IR infrared combustible / CO2 gas detector (RS-485 Modbus)
Give each sensor its own serial ID from the magnetic-switch menu, wire RS-485 at 9600 8N1 and poll holding registers 0-9 with function 03; read 40005 for faults.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 2 | Gas concentration | UINT16 | Gas concentration | Read |
| HR 1 | Detectable range | UINT16 | Detectable range (full scale) | Read/write |
| HR 5 | Fault status bits | BITMAP16 | Fault status bits | Read |
| HR 4 | Sensor life | UINT16 | Sensor life | Read |
| HR 8 | 4-20 mA output | UINT16 | Loop current | Read |
| HR 16 | Gas/units notation string | STRING[12] | Gas and units text | Read |
Enable Modbus control & writes
The manual describes no separate enable step; set a unique serial ID in Program Mode (Set Serial ID).
Byte order & addressing
- Register numbers start at 40000 = wire address 0.
- The text names function 03 as the only supported code, but the register table lists function 06 for writing the R/W registers.
- Text characters are low byte first.
Network setup
- 9600 baud, 8 data bits, no parity, 1 stop bit.
- Serial ID is entered in hexadecimal (01, 02 ... 0A ...).
Watch out for
- Bit 14 of the fault register is set while the sensor is in calibration.
Teledyne Oldham Simtronics OLCT 700 / OLCT 710 IR infrared combustible / CO2 gas detector (RS-485 Modbus) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 40000 | Device type | Reads 8. | UINT16 | Read | 8 = OLCT 700/710 detector | |||
| HR | 1doc 40001 | Detectable range | Full scale in the units of the notation string. | UINT16 | Read/write | ||||
| HR | 2doc 40002 | Gas concentration | Raw reading; see Range Divisor (40014). | UINT16 | Read | ||||
| HR | 3doc 40003 | AutoSpan level | Span gas concentration used for calibration. | UINT16 | Read/write | ||||
| HR | 4doc 40004 | Sensor life | Remaining sensor life. | UINT16 | % | Read | |||
| HR | 5doc 40005 | Fault status bits | Faults clear themselves when the condition clears. | BITMAP16 | Read | bit 0 = Global fault; bit 1 = AutoSpan fault; bit 2 = Temperature fault; bit 3 = 4-20 mA fault; bit 4 = Input voltage fault; bit 5 = Memory fault; bit 6 = Processor fault; bit 7 = Clearing fault; bit 8 = Stability fault; bit 9 = Range fault; bit 10 = Sensor fault; bit 11 = Zero fault; bit 12 = Sensor fault 2; bit 14 = In calibration; bit 15 = Communication error | |||
| HR | 6doc 40006 | Model number | UINT16 | Read | 1 = DM; 2 = FP; 3 = IR; 4 = TP; 5 = PID | ||||
| HR | 7doc 40007 | Days since calibration | UINT16 | days | Read | ||||
| HR | 8doc 40008 | 4-20 mA output | Current loop output value. | UINT16 | × 0.01 | mA | Read | ||
| HR | 9doc 40009 | Input voltage | UINT16 | × 0.01 | V | Read | |||
| HR | 11doc 40011 | Gas factor | Range 20-565. | UINT16 | Read/write | ||||
| HR | 12doc 40012 | Active counts | UINT16 | Read | |||||
| HR | 13doc 40013 | Reference counts | UINT16 | Read | |||||
| HR | 14doc 40014 | Range divisor | 1, 10, 100 or 1000. | UINT16 | Read/write | ||||
| HR | 15doc 40015 | Calibration status / enable | Read gives status; write starts an action. | UINT16 | Read/write | 0 = Read: idle; 1 = Read: zero calibration started / Write: set zero; 2 = Read: span calibration started / Write: set span; 3 = Read: span set; 4 = Read: span calibration unsuccessful; 8 = Write: signal simulation mode; 9 = Write: set FP bridge voltage; 10 = Write: set TP heater power; 11 = Write: set IR gain | |||
| HR | 16doc 40016-40021 | Gas/units notation string | Units, a space, then gas name, null-terminated; first character in the low byte of each register. | STRING[12] | Read |
Notes on this map
- All registers are single 16-bit holding registers; the manual shares one table across FP, IR and TP detectors and model register 40006 tells them apart. Registers 40011-40014 change meaning with the model; only the IR detector meanings are given here.
- The IR special register 40014 is a range divisor (1, 10, 100 or 1000); the manual does not spell out how it applies to the gas reading, so scale is left at 1.
- Range, reading and span level are in the units of the notation string (PPM, PPB or %).
- Register 40010 (temperature, °C) is left out: the manual gives no data type, so it is unclear how readings below 0 °C are coded.
- The notation string stores the first character in the low byte of each register (low byte, high byte, ...), the reverse of the usual Modbus string order.
- Bit 13 of the fault register is reserved.
- Default serial ID is 01; it is set in the sensor menu (Set Serial ID) in hexadecimal.
- The manual prints device type 8 as "OLCT 700/710 Detector"; the register layout is the same as the Teledyne Detcon 700 series.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Teledyne Oldham Simtronics OLCT 700 / OLCT 710 IR infrared combustible / CO2 gas detector (RS-485 Modbus)
What Modbus registers does the Teledyne Oldham Simtronics OLCT 700 / OLCT 710 IR infrared combustible / CO2 gas detector (RS-485 Modbus) have?
This map lists 16 registers: 16 holding registers. 5 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Teledyne Oldham Simtronics OLCT 700 / OLCT 710 IR infrared combustible / CO2 gas detector (RS-485 Modbus) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual prints registers as 40000-40021, starting at 40000, so the digits after the leading 4 are the 0-based wire address: 40000 (device type) is address 0 and 40002 (gas reading) is address 2. Only function 03 reads them; writable ones use function 06.
What are the minimum Modbus registers to integrate the Teledyne Oldham Simtronics OLCT 700 / OLCT 710 IR infrared combustible / CO2 gas detector (RS-485 Modbus)?
Start with HR 2 Gas concentration (Gas concentration); HR 1 Detectable range (Detectable range (full scale)); HR 5 Fault status bits (Fault status bits); HR 4 Sensor life (Sensor life); HR 8 4-20 mA output (Loop current); HR 16 Gas/units notation string (Gas and units text).
How do I enable Modbus control of the Teledyne Oldham Simtronics OLCT 700 / OLCT 710 IR infrared combustible / CO2 gas detector (RS-485 Modbus)?
The manual describes no separate enable step; set a unique serial ID in Program Mode (Set Serial ID).
Where is the official Teledyne Oldham Simtronics OLCT 700 / OLCT 710 IR infrared combustible / CO2 gas detector (RS-485 Modbus) Modbus documentation?
The source is 700 IR Series Infrared Gas Detector for Combustible and CO2 Gases OLCT 700 / OLCT 710 User Manual (NP700IRIMEN Revision E.0), revision 2023-11, published free by Teledyne Oldham Simtronics at https://www.teledynegasandflamedetection.com/sites/teledynegasandflamedetection.com/files/product-specs/olct700_%26_710_ir_user_manual_en_olct_700_%26_710_ir_revc.0_english.pdf.
More Teledyne Oldham Simtronics Modbus register maps
Other gas detectors register maps
- Sensor (extractive gas detector)
Honeywell Midas gas detector (Modbus/TCP)
Honeywell Midas extractive gas detectors (original Midas platform, software V1.08), user manual 3010M5000 revision 32, Appendix A Modbus/TCP interface.
Also known as: Midas, MIDAS gas detector - Sensor (fixed gas detector)
Teledyne Detcon Model CX-IR infrared combustible gas sensor (Modbus RTU)
Teledyne Detcon CX-IR wired infrared gas sensors (RS-485 Modbus RTU and 4-20 mA), instruction manual Document #4428 Rev. 1.9.
Also known as: CX-IR, Detcon CX-IR - Sensor controller (gas detection)
Teledyne Detcon Model X40 integrated alarm and control system (Modbus slave port)
Teledyne Detcon X40 gas detection controllers (8 and 32 channel, N4X and N1P enclosures), instruction manual Document #3672 Rev. 3.8, slave port register map.
Also known as: X40-08-N4X, X40-32-N4X, X40-32-N1P, X40 controller - Sensor (refrigerant / toxic gas detector)
Danfoss Gas Detection Units GD Basic / Premium / Heavy Duty (Modbus RTU)
Danfoss GD Basic, Premium and Heavy Duty gas detection units on their own RS-485 Modbus port (Part 2 of the guide). The gas detection controller's X-bus map in Part 1 is not included.
Also known as: GDA, GDC, GDHC, GDHF, GDH, GD Basic, GD Premium, GD Heavy Duty - Sensor (gas detector)
Senva TG series toxic/combustible gas monitor (RS-485 Modbus)
Senva TG series RS-485 gas monitors (one or two gas sensors, optional temperature), Modbus Protocol Guide 154-0036-0A (2020-02-07).
Also known as: Senva TG, TG series - Sensor (fixed gas detector)
Teledyne Detcon Model PI-700 photoionization (PID) VOC sensor (RS-485 Modbus)
Teledyne Detcon PI-700 smart sensors with the 4-20 mA and RS-485 Modbus outputs, instruction manual Document #3228, Rev. 4.0.
Also known as: PI-700, Detcon PI-700, Teledyne Detcon PI-700
All gas detectors Modbus register maps →
Source: 700 IR Series Infrared Gas Detector for Combustible and CO2 Gases OLCT 700 / OLCT 710 User Manual · NP700IRIMEN Revision E.0 · rev. 2023-11. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.