Sensor (extractive gas detector) · Modbus register map
Honeywell Midas gas detector (Modbus/TCP) Modbus register map
Updated 17 November 2026
The Midas is a Honeywell pumped single-point gas detector for asphyxiant, toxic and flammable gases with relays, 4-20 mA and Ethernet. Its Modbus/TCP server gives a packed status word, gas reading with decimal point and units, temperature, cell life, flow, alarm and fault flags, serial numbers, plus two command registers for alarm reset, inhibit and relay control. Float registers are left out.
This page lists 16 Modbus registers for the Honeywell Midas gas detector (Modbus/TCP) — 2 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Honeywell’s own free documentation (linked below) and checked against it.
- Manufacturer
- Honeywell
- Model
- Midas gas detector (Modbus/TCP)
- Equipment type
- Sensor (extractive gas detector)
- Registers
- 16 (2 writable)
- Transport
- Modbus TCP
- Default unit ID
- Not stated
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Firmware
- Midas software V1.08 (earlier releases support a subset)
- Also known as
- Midas, MIDAS gas detector
Integration notes: Honeywell Midas gas detector (Modbus/TCP)
Connect to the Midas IP with Modbus/TCP and read holding registers 0-17; gas = 40005 / 10^(40007 bits 0-2), alarms and faults from 40001/40017/40018.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 4 | Gas concentration integer (CONC) | UINT16 | Gas concentration | Read |
| HR 6 | Decimal point and units (DPUN) | UINT16 | Decimal point and units | Read |
| HR 0 | Status (STTS) | BITMAP16 | Status and alarms | Read |
| HR 17 | Fault status (FSI) | BITMAP16 | Fault flags | Read |
| HR 20 | Command register 1 (CMD1) | UINT16 | Command (reset/inhibit) | Write |
| HR 10 | Sample flow (FLOW) | UINT16 | Sample flow | Read |
Enable Modbus control & writes
Modbus/TCP is part of the Ethernet interface. For relay commands enable remote relay control in the SEt/FLt menu or web page.
Byte order & addressing
- Commands need both CMD1 and CMD2 written; the device avoids write-coil commands on purpose.
- Gas reading is in ppm for ppm and ppb gases, otherwise in display units.
Network setup
- Ethernet with Power over Ethernet (802.3af).
- Protect it behind a firewall; Modbus/TCP has no authentication.
Watch out for
- Read 40007 together with 40005 to apply the decimal point.
Honeywell Midas gas detector (Modbus/TCP) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 40001 | Status (STTS) | Bits 0-3 monitoring state, bits 4-5 fault state; flags below. | BITMAP16 | Read | bit 6 = Alarm 1 active; bit 7 = Alarm 2 active; bit 8 = Relay 1 energized; bit 9 = Relay 2 energized; bit 10 = Relay 3 energized; bit 11 = Heartbeat (toggles every two seconds); bit 12 = Relays under remote Modbus/TCP control | |||
| HR | 1doc 40002 | Gas selection (GASS) | Low byte gas ID, high byte sensor cartridge ID. | UINT16 | Read | ||||
| HR | 4doc 40005 | Gas concentration integer (CONC) | Divide by 10^decimal (40007 bits 0-2); ppm for ppm/ppb gases. | UINT16 | Read | ||||
| HR | 5doc 40006 | Most important active fault number (NOFT) | Fault code; see the troubleshooting table in the manual. | UINT16 | Read | ||||
| HR | 6doc 40007 | Decimal point and units (DPUN) | Bits 0-2 decimals; high byte units: 1 ppm, 2 ppb, 4 %vol, 8 %LEL, 16 mA. | UINT16 | Read | ||||
| HR | 7doc 40008 | Temperature (TEMP) | INT16 | °C | Read | ||||
| HR | 8doc 40009 | Cell life remaining (CLRH) | UINT16 | h | Read | ||||
| HR | 9doc 40010 | Heartbeat counter (HRTB) | Low 16 bits of time in seconds. | UINT16 | s | Read | |||
| HR | 10doc 40011 | Sample flow (FLOW) | UINT16 | cc/min | Read | ||||
| HR | 16doc 40017 | Alarm status (ASI) | BITMAP16 | Read | bit 0 = Alarm 1 active; bit 1 = Alarm 2 active | ||||
| HR | 17doc 40018 | Fault status (FSI) | BITMAP16 | Read | bit 0 = Maintenance fault; bit 1 = Instrument fault; bit 2 = Flow fault; bit 3 = Internal communication fault; bit 4 = Pyrolyzer fault; bit 5 = Sensor fault; bit 6 = Range over fault | ||||
| HR | 20doc 40021 | Command register 1 (CMD1) | Write the action code (hex 0x015E-0x0B5E) together with CMD2. | UINT16 | Write | 350 = With CMD2 = 13862: reset alarms and faults; 606 = Inhibit alarms; 862 = Inhibit alarms and faults; 1118 = Inhibit all; 1374 = No inhibit; 1630 = Energize relay 1; 1886 = De-energize relay 1; 2142 = Energize relay 2; 2398 = De-energize relay 2; 2654 = Energize relay 3; 2910 = De-energize relay 3 | |||
| HR | 21doc 40022 | Command register 2 (CMD2) | Must be 0x3626 (13862) for a command to act. | UINT16 | Write | ||||
| HR | 70doc 40071-40075 | Detector serial number | ASCII, 2 characters per register, first character in the high byte. | STRING[10] | Read | ||||
| HR | 75doc 40076-40080 | Sensor serial number | ASCII, 2 characters per register, first character in the high byte. | STRING[10] | Read | ||||
| HR | 80doc 40081 | Mode status (MSI) | BITMAP16 | Read | bit 0 = Warm-up; bit 1 = Monitor mode; bit 2 = Test mode; bit 3 = Maintenance mode |
Notes on this map
- Left out: float registers FCN 40003-40004, alarm thresholds A1T/A2T 40013-40016 (also writable) and high scale 40019-40020. The manual only says floats are "little-endian or Intel format", which does not settle the register word order.
- Status register 40001 packs numbers: bits 0-3 monitoring state (0 warm-up, 1 monitor, 2 alarms inhibited, 3 alarms and faults inhibited, 4 fully inhibited, 5 alarm/fault simulation, 6 bump test, 7 4-20 mA calibration, 8 other calibration); bits 4-5 fault state (0 none, 1 maintenance, 2 instrument).
- Commands: write CMD1 and CMD2 together with function 06 or 16; the manual example resets alarms by writing 350 to 40021 and 13862 to 40022. Relay commands only work if remote relay control is enabled (SEt/FLt menu or Fault Configuration web page); it is off by default.
- Serial-number string example from the manual: ABCD12345 reads 0x4142 0x4344 0x3132 0x3334 0x3500 (high byte first).
- Reads use function 03. The TCP port is not stated in this appendix.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Honeywell Midas gas detector (Modbus/TCP)
What Modbus registers does the Honeywell Midas gas detector (Modbus/TCP) have?
This map lists 16 registers: 16 holding registers. 2 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Honeywell Midas gas detector (Modbus/TCP) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are listed by reference address 40001-40081 (Modicon style): 40001 status = wire address 0, 40005 gas reading = 4, 40021 CMD1 = 20.
What are the minimum Modbus registers to integrate the Honeywell Midas gas detector (Modbus/TCP)?
Start with HR 4 Gas concentration integer (CONC) (Gas concentration); HR 6 Decimal point and units (DPUN) (Decimal point and units); HR 0 Status (STTS) (Status and alarms); HR 17 Fault status (FSI) (Fault flags); HR 20 Command register 1 (CMD1) (Command (reset/inhibit)); HR 10 Sample flow (FLOW) (Sample flow).
How do I enable Modbus control of the Honeywell Midas gas detector (Modbus/TCP)?
Modbus/TCP is part of the Ethernet interface. For relay commands enable remote relay control in the SEt/FLt menu or web page.
Where is the official Honeywell Midas gas detector (Modbus/TCP) Modbus documentation?
The source is Midas Gas Detector User Manual (3010M5000 Revision 32), revision 2024-12-04, published free by Honeywell at https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/hgas/en-us/products/high-tech-and-semiconductor/midas/documents/hon-ia-pmc-3010m5000-midas-a-001-rev-32-um-en.pdf.
More Honeywell Modbus register maps
- Sensor (extractive gas detector)
Honeywell Midas S2 extractive gas transmitter (Modbus/TCP)
Honeywell Midas S2 single-point extractive gas transmitters with Ethernet/PoE, user manual 3023M5001 Rev A, Modbus/TCP register map (Table 6-1).
Also known as: Midas S2, MIDAS-S2, Midas S2 gas detector - Boiler controller
Honeywell SOLA hydronic boiler control (Modbus interface)
Honeywell SOLA (R7910/R7911) integrated boiler controls, status registers 0-173 of the SOLA Modbus Interface specification Rev 4.1.1 (2013-10-14). Used inside many OEM condensing boilers.
Also known as: R7910, R7911, Honeywell SOLA, SOLA ICP
Other gas detectors register maps
- Sensor (fixed gas detector)
Teledyne Detcon Model CX-IR infrared combustible gas sensor (Modbus RTU)
Teledyne Detcon CX-IR wired infrared gas sensors (RS-485 Modbus RTU and 4-20 mA), instruction manual Document #4428 Rev. 1.9.
Also known as: CX-IR, Detcon CX-IR - Sensor controller (gas detection)
Teledyne Detcon Model X40 integrated alarm and control system (Modbus slave port)
Teledyne Detcon X40 gas detection controllers (8 and 32 channel, N4X and N1P enclosures), instruction manual Document #3672 Rev. 3.8, slave port register map.
Also known as: X40-08-N4X, X40-32-N4X, X40-32-N1P, X40 controller - Sensor (refrigerant / toxic gas detector)
Danfoss Gas Detection Units GD Basic / Premium / Heavy Duty (Modbus RTU)
Danfoss GD Basic, Premium and Heavy Duty gas detection units on their own RS-485 Modbus port (Part 2 of the guide). The gas detection controller's X-bus map in Part 1 is not included.
Also known as: GDA, GDC, GDHC, GDHF, GDH, GD Basic, GD Premium, GD Heavy Duty - Sensor (gas detector)
Senva TG series toxic/combustible gas monitor (RS-485 Modbus)
Senva TG series RS-485 gas monitors (one or two gas sensors, optional temperature), Modbus Protocol Guide 154-0036-0A (2020-02-07).
Also known as: Senva TG, TG series - Sensor (fixed gas detector)
Teledyne Detcon Model PI-700 photoionization (PID) VOC sensor (RS-485 Modbus)
Teledyne Detcon PI-700 smart sensors with the 4-20 mA and RS-485 Modbus outputs, instruction manual Document #3228, Rev. 4.0.
Also known as: PI-700, Detcon PI-700, Teledyne Detcon PI-700 - Sensor (gas transmitter / gas detector)
Analytical Technology (ATI) D12 / F12 gas transmitter (H10, catalytic bead, wet H2S sensors) Modbus interface
ATI D12 and F12 transmitters with the Modbus option fitted to H10 toxic, catalytic bead or wet H2S sensors (Appendix table 4.1). IR-sensor D12s use a different table.
Also known as: D12, F12, D12 gas transmitter, F12 gas transmitter
All gas detectors Modbus register maps →
Source: Midas Gas Detector User Manual · 3010M5000 Revision 32 · rev. 2024-12-04. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.