Sensor (extractive gas detector) · Modbus register map

Honeywell Midas gas detector (Modbus/TCP) Modbus register map

Updated 17 November 2026

Short answer

The Midas is a Honeywell pumped single-point gas detector for asphyxiant, toxic and flammable gases with relays, 4-20 mA and Ethernet. Its Modbus/TCP server gives a packed status word, gas reading with decimal point and units, temperature, cell life, flow, alarm and fault flags, serial numbers, plus two command registers for alarm reset, inhibit and relay control. Float registers are left out.

This page lists 16 Modbus registers for the Honeywell Midas gas detector (Modbus/TCP) — 2 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Honeywell’s own free documentation (linked below) and checked against it.

Manufacturer
Honeywell
Model
Midas gas detector (Modbus/TCP)
Equipment type
Sensor (extractive gas detector)
Registers
16 (2 writable)
Transport
Modbus TCP
Default unit ID
Not stated
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Firmware
Midas software V1.08 (earlier releases support a subset)
Also known as
Midas, MIDAS gas detector
Source document
Midas Gas Detector User Manual · 3010M5000 Revision 32 · rev. 2024-12-04
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Honeywell Midas gas detector (Modbus/TCP)

Integration in brief

Connect to the Midas IP with Modbus/TCP and read holding registers 0-17; gas = 40005 / 10^(40007 bits 0-2), alarms and faults from 40001/40017/40018.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 4Gas concentration integer (CONC)UINT16Gas concentrationRead
HR 6Decimal point and units (DPUN)UINT16Decimal point and unitsRead
HR 0Status (STTS)BITMAP16Status and alarmsRead
HR 17Fault status (FSI)BITMAP16Fault flagsRead
HR 20Command register 1 (CMD1)UINT16Command (reset/inhibit)Write
HR 10Sample flow (FLOW)UINT16Sample flowRead

Enable Modbus control & writes

Modbus/TCP is part of the Ethernet interface. For relay commands enable remote relay control in the SEt/FLt menu or web page.

Byte order & addressing

Network setup

Watch out for

Honeywell Midas gas detector (Modbus/TCP) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

16 of 16 shown
Honeywell Midas gas detector (Modbus/TCP) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 40001Status (STTS)Bits 0-3 monitoring state, bits 4-5 fault state; flags below.BITMAP16Readbit 6 = Alarm 1 active; bit 7 = Alarm 2 active; bit 8 = Relay 1 energized; bit 9 = Relay 2 energized; bit 10 = Relay 3 energized; bit 11 = Heartbeat (toggles every two seconds); bit 12 = Relays under remote Modbus/TCP control
HR1doc 40002Gas selection (GASS)Low byte gas ID, high byte sensor cartridge ID.UINT16Read
HR4doc 40005Gas concentration integer (CONC)Divide by 10^decimal (40007 bits 0-2); ppm for ppm/ppb gases.UINT16Read
HR5doc 40006Most important active fault number (NOFT)Fault code; see the troubleshooting table in the manual.UINT16Read
HR6doc 40007Decimal point and units (DPUN)Bits 0-2 decimals; high byte units: 1 ppm, 2 ppb, 4 %vol, 8 %LEL, 16 mA.UINT16Read
HR7doc 40008Temperature (TEMP)INT16°CRead
HR8doc 40009Cell life remaining (CLRH)UINT16hRead
HR9doc 40010Heartbeat counter (HRTB)Low 16 bits of time in seconds.UINT16sRead
HR10doc 40011Sample flow (FLOW)UINT16cc/minRead
HR16doc 40017Alarm status (ASI)BITMAP16Readbit 0 = Alarm 1 active; bit 1 = Alarm 2 active
HR17doc 40018Fault status (FSI)BITMAP16Readbit 0 = Maintenance fault; bit 1 = Instrument fault; bit 2 = Flow fault; bit 3 = Internal communication fault; bit 4 = Pyrolyzer fault; bit 5 = Sensor fault; bit 6 = Range over fault
HR20doc 40021Command register 1 (CMD1)Write the action code (hex 0x015E-0x0B5E) together with CMD2.UINT16Write350 = With CMD2 = 13862: reset alarms and faults; 606 = Inhibit alarms; 862 = Inhibit alarms and faults; 1118 = Inhibit all; 1374 = No inhibit; 1630 = Energize relay 1; 1886 = De-energize relay 1; 2142 = Energize relay 2; 2398 = De-energize relay 2; 2654 = Energize relay 3; 2910 = De-energize relay 3
HR21doc 40022Command register 2 (CMD2)Must be 0x3626 (13862) for a command to act.UINT16Write
HR70doc 40071-40075Detector serial numberASCII, 2 characters per register, first character in the high byte.STRING[10]Read
HR75doc 40076-40080Sensor serial numberASCII, 2 characters per register, first character in the high byte.STRING[10]Read
HR80doc 40081Mode status (MSI)BITMAP16Readbit 0 = Warm-up; bit 1 = Monitor mode; bit 2 = Test mode; bit 3 = Maintenance mode

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Honeywell Midas gas detector (Modbus/TCP)

What Modbus registers does the Honeywell Midas gas detector (Modbus/TCP) have?

This map lists 16 registers: 16 holding registers. 2 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Honeywell Midas gas detector (Modbus/TCP) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are listed by reference address 40001-40081 (Modicon style): 40001 status = wire address 0, 40005 gas reading = 4, 40021 CMD1 = 20.

What are the minimum Modbus registers to integrate the Honeywell Midas gas detector (Modbus/TCP)?

Start with HR 4 Gas concentration integer (CONC) (Gas concentration); HR 6 Decimal point and units (DPUN) (Decimal point and units); HR 0 Status (STTS) (Status and alarms); HR 17 Fault status (FSI) (Fault flags); HR 20 Command register 1 (CMD1) (Command (reset/inhibit)); HR 10 Sample flow (FLOW) (Sample flow).

How do I enable Modbus control of the Honeywell Midas gas detector (Modbus/TCP)?

Modbus/TCP is part of the Ethernet interface. For relay commands enable remote relay control in the SEt/FLt menu or web page.

Where is the official Honeywell Midas gas detector (Modbus/TCP) Modbus documentation?

The source is Midas Gas Detector User Manual (3010M5000 Revision 32), revision 2024-12-04, published free by Honeywell at https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/hgas/en-us/products/high-tech-and-semiconductor/midas/documents/hon-ia-pmc-3010m5000-midas-a-001-rev-32-um-en.pdf.

More Honeywell Modbus register maps

Other gas detectors register maps

All gas detectors Modbus register maps →

Source: Midas Gas Detector User Manual · 3010M5000 Revision 32 · rev. 2024-12-04. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.