Boiler controller · Modbus register map
Honeywell SOLA hydronic boiler control (Modbus interface) Modbus register map
Updated 17 November 2026
SOLA is Honeywell's integrated burner and hydronic control used by many boiler OEMs. Its RS-485 Modbus RTU port exposes everything as 16-bit holding registers, with digital signals packed into bit-map registers. This map covers the status area: change flags, digital I/O, limits, demand source, temperatures, firing rate, flame signal, burner control status and lockout codes, sensor states, CH/DHW/lead-lag status and pump status.
This page lists 140 Modbus registers for the Honeywell SOLA hydronic boiler control (Modbus interface) — 1 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Honeywell’s own free documentation (linked below) and checked against it.
- Manufacturer
- Honeywell
- Model
- SOLA hydronic boiler control (Modbus interface)
- Equipment type
- Boiler controller
- Registers
- 140 (1 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 38400 baud, 8N1
- Documented addressing
- 0-based (the number printed is the address on the wire)
- Also known as
- R7910, R7911, Honeywell SOLA, SOLA ICP
Integration notes: Honeywell SOLA hydronic boiler control (Modbus interface)
Connect to the SOLA's 3-pin RS-485 Modbus port (38400 8N1) and read holding registers with FC 03 from address 0. Temperatures are 0.1 °C integers; burner status is at 32, lockout code at 34.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 7 | Outlet (S3S4) or Outlet limit (S3) sensor | UINT16 | Outlet temperature | Read |
| HR 8 | Firing rate | UINT16 | Firing rate | Read |
| HR 10 | Flame signal | UINT16 | Flame signal | Read |
| HR 32 | Burner control status | UINT16 | Burner control status | Read |
| HR 34 | Lockout code | UINT16 | Lockout code | Read |
| HR 6 | Demand source | UINT16 | Demand source | Read |
| HR 16 | Active CH setpoint | UINT16 | Active CH setpoint | Read |
Enable Modbus control & writes
Use one of the SOLA's RS-485 Modbus ports (MB1 or MB2); the control answers to a single Modbus address. Register writes are limited by the access level shown in register 19 (none, installer, OEM or all).
Byte order & addressing
- Addresses are 0-based; add 40001 for 4xxxx tools.
- Status-change registers 0, 1 and 23 clear when read.
- Digital signals are bits inside holding registers, not coils.
Network setup
- RS-485 terminals: 1 = Data+ (a), 2 = Data- (b), 3 = common.
- Fixed format: 38400 bps, 8 data bits, no parity, 1 stop bit.
Watch out for
- OEM boilers may disable or relabel some SOLA functions; confirm with the boiler maker's documentation.
- 0x8FFF in a temperature register means that function is not enabled; 0x7FFF and 0x8000-0x8500 are sensor fault codes.
Honeywell SOLA hydronic boiler control (Modbus interface) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 0000 | Status Change | Cleared after read; flags which register groups changed. | BITMAP16 | Read | bit 0 = Active Lockout; bit 1 = Burner control status; bit 2 = Sensor status; bit 3 = Demand&Modulation status; bit 4 = CH status; bit 5 = DHW status; bit 6 = Pump status; bit 7 = Statistics; bit 8 = Lead Lag status; bit 9 = Lockout history; bit 10 = Alert log | |||
| HR | 1doc 0001 | Configuration Change | Cleared after read; flags which register groups changed. | BITMAP16 | Read | bit 0 = System configuration; bit 1 = Modulation configuration; bit 2 = CH configuration; bit 3 = Burner control configuration; bit 4 = Fan configuration; bit 5 = Pump configuration; bit 6 = Annunciation configuration; bit 7 = DHW configuration; bit 8 = Limits configuration; bit 9 = Anti-condensation configuration; bit 10 = Outdoor reset configuration; bit 11 = Frost protection configuration; bit 12 = Lead Lag configuration; bit 14 = PM configuration; bit 15 = PCB configuration | |||
| HR | 2doc 0002 | Digital I/O | BITMAP16 | Read | bit 0 = Pump A; bit 1 = Pump B; bit 2 = Pump C; bit 3 = Blower motor/HSI; bit 4 = External ignition; bit 5 = Pilot valve; bit 6 = Main valve; bit 7 = Alarm; bit 8 = Interlock (ILK); bit 9 = Pre-ignition interlock (PII); bit 10 = Load Control Input(LCI); bit 11 = Low Fire Switch (LFS); bit 12 = High Fire Switch (HFS); bit 13 = STAT (Demand); bit 14 = Time of Day; bit 15 = Safety relay | ||||
| HR | 3doc 0003 | Annunciation I/O | BITMAP16 | Read | bit 0 = Annunciator 1/IAS; bit 1 = Annunciator 2; bit 2 = Annunciator 3; bit 3 = Annunciator 4; bit 4 = Annunciator 5; bit 5 = Annunciator 6; bit 6 = Annunciator 7/HFS; bit 7 = Annunciator 8/LFS | ||||
| HR | 4doc 0004 | Limits | BITMAP16 | Read | bit 0 = Outlet high limit; bit 1 = DHW high limit; bit 2 = Stack limit; bit 3 = Delta T inlet/outlet limit; bit 4 = Delta T exchanger/outlet limit; bit 5 = Delta T inlet/exchanger limit; bit 6 = Inversion inlet/outlet limit; bit 7 = Inversion exchanger/outlet limit; bit 8 = Inversion inlet/exchanger limit; bit 9 = Outlet T-rise limit; bit 10 = Exchanger T-rise limit; bit 11 = Heat exchanger high limit | ||||
| HR | 5doc 0005 | Program Module (PM) status | BITMAP16 | Read | bit 0 = PM installed; bit 1 = Lead/Lag enabled; bit 2 = Valid copyright; bit 8 = OEM parameter PCB stored in PM; bit 9 = OEM range PCB stored in PM; bit 10 = OEM alert PCB stored in PM | ||||
| HR | 6doc 0006 | Demand source | UINT16 | Read | 0 = Unknown; 1 = No source demand; 2 = CH; 3 = DHW; 4 = Lead Lag slave; 5 = Lead Lag master; 6 = CH frost protection; 7 = DHW frost protection; 8 = No demand due to burner switch (register 199) turned off; 9 = DHW storage; 11 = Warm weather shutdown; 12 = Hot standby | ||||
| HR | 7doc 0007 | Outlet (S3S4) or Outlet limit (S3) sensor | 0.1 °C units; register listed as U16 although the range starts at -40 °C. | UINT16 | × 0.1 | °C | Read | ||
| HR | 8doc 0008 | Firing rate | Firing rate: RPM, or 0.1 % steps if bit 15 is set (per modulation output setting). | UINT16 | Read | ||||
| HR | 9doc 0009 | Fan speed | UINT16 | RPM | Read | ||||
| HR | 10doc 0010 | Flame signal | 0.01 V or 0.01 uA, depending on flame sensor (0.00-50.00). | UINT16 | × 0.01 | Read | |||
| HR | 11doc 0011 | Inlet (S1) sensor | 0.1 °C units; register listed as U16 although the range starts at -40 °C. | UINT16 | × 0.1 | °C | Read | ||
| HR | 12doc 0012 | DHW (S6S7) or DHW limit (S6) sensor | 0.1 °C units; register listed as U16 although the range starts at -40 °C. | UINT16 | × 0.1 | °C | Read | ||
| HR | 13doc 0013 | S5 sensor | 0.1 °C units; register listed as U16 although the range starts at -40 °C. | UINT16 | × 0.1 | °C | Read | ||
| HR | 14doc 0014 | Stack (S8S9) or Stack limit (S8) sensor | 0.1 °C units; register listed as U16 although the range starts at -40 °C. | UINT16 | × 0.1 | °C | Read | ||
| HR | 15doc 0015 | 4-20 mA remote control input (S2) terminal | 0.1 mA units when S2 is a 4-20 mA input; other uses per register 609. | UINT16 | × 0.1 | mA | Read | ||
| HR | 16doc 0016 | Active CH setpoint | 0.1 °C units; register listed as U16 although the range starts at -40 °C. | UINT16 | × 0.1 | °C | Read | ||
| HR | 17doc 0017 | Active DHW setpoint | 0.1 °C units; register listed as U16 although the range starts at -40 °C. | UINT16 | × 0.1 | °C | Read | ||
| HR | 18doc 0018 | Active LL setpoint | 0.1 °C units; register listed as U16 although the range starts at -40 °C. | UINT16 | × 0.1 | °C | Read | ||
| HR | 19doc 0019 | Register Access Status | UINT16 | Read | 0 = No register writes allowed; 1 = Installer register writes allowed; 2 = OEM register writes allowed; 3 = All register writes allowed | ||||
| HR | 20doc 0020 | Steam pressure | UINT16 | × 0.1 | psi | Read | |||
| HR | 21doc 0021 | Analog modulation input | 0 = no signal, else 4-20 mA (0.1 mA); mirrors register 15 for 4-20 mA S2. | UINT16 | × 0.1 | mA | Read | ||
| HR | 22doc 0022 | Active CH pressure setpoint | UINT16 | × 0.1 | psi | Read | |||
| HR | 23doc 0023 | Extended Status Change | Cleared after read; flags which register groups changed. | BITMAP16 | Read | bit 3 = DHW plate heat exchanger status; bit 4 = DHW plate heat exchanger configuration | |||
| HR | 25doc 0025 | Active CH operating point | 0.1 °C units; register listed as U16 although the range starts at -40 °C. | UINT16 | × 0.1 | °C | Read | ||
| HR | 26doc 0026 | Active DHW operating point | 0.1 °C units; register listed as U16 although the range starts at -40 °C. | UINT16 | × 0.1 | °C | Read | ||
| HR | 27doc 0027 | Active Lead Lag operating point | 0.1 °C units; register listed as U16 although the range starts at -40 °C. | UINT16 | × 0.1 | °C | Read | ||
| HR | 28doc 0028 | Active system operating point | 0.1 °C units; register listed as U16 although the range starts at -40 °C. | UINT16 | × 0.1 | °C | Read | ||
| HR | 29doc 0029 | Active system setpoint | 0.1 °C units; register listed as U16 although the range starts at -40 °C. | UINT16 | × 0.1 | °C | Read | ||
| HR | 30doc 0030 | Active system on hysteresis | 0.1 °C units. | UINT16 | × 0.1 | °C | Read | ||
| HR | 31doc 0031 | Active system off hysteresis | 0.1 °C units. | UINT16 | × 0.1 | °C | Read | ||
| HR | 32doc 0032 | Burner control status | UINT16 | Read | 0 = Disabled; 1 = Locked out; 4 = Anti-short cycle; 5 = Unconfigured safety data; 34 = Standby Hold; 35 = Standby Delay; 48 = Normal Standby; 49 = Preparing; 50 = Ignition; 51 = Firing; 52 = Postpurge | ||||
| HR | 33doc 0033 | Burner control state | Sequence state code, see table 12 in the source. | UINT16 | Read | ||||
| HR | 34doc 0034 | Lockout code | 1-4096 = lockout number (table 9 in the source). | UINT16 | Read | 0 = No lockout | |||
| HR | 35doc 0035 | Alarm reason | UINT16 | Read | 0 = None; 1 = Lockout (see Lockout code, register 34); 2 = Alert (see Table 11); 3 = Other | ||||
| HR | 36doc 0036 | Annunciator first out | UINT16 | Read | 0 = None or undetermined; 1 = ILK; 2 = PII; 11 = Annunciator 1; 12 = Annunciator 2; 13 = Annunciator 3; 14 = Annunciator 4; 15 = Annunciator 5; 16 = Annunciator 6; 17 = Annunciator 7; 18 = Annunciator 8 | ||||
| HR | 37doc 0037 | Annunciator hold | UINT16 | Read | 0 = None or undetermined; 1 = ILK; 2 = PII; 3 = LCI; 11 = Annunciator 1; 12 = Annunciator 2; 13 = Annunciator 3; 14 = Annunciator 4; 15 = Annunciator 5; 16 = Annunciator 6; 17 = Annunciator 7; 18 = Annunciator 8 | ||||
| HR | 38doc 0038 | Sequence time | UINT16 | s | Read | ||||
| HR | 39doc 0039 | Delay time | UINT16 | s | Read | ||||
| HR | 40doc 0040 | Hold code | Hold reason; same codes as lockout (table 8 in the source). | UINT16 | Read | ||||
| HR | 41doc 0041 | Burner control flags | BITMAP16 | Read | bit 0 = Flame detected; bit 1 = DHW remote STAT demand indicated; bit 2 = Blocked condensate detected | ||||
| HR | 42doc 0042 | CH remote Stat | UINT16 | Read/write | 0 = No remote STAT demand; 1 = Remote STAT demand indicated | ||||
| HR | 43doc 0043 | Outlet operation (S4=J8-10) terminal | 0.1 °C units (listed as U16, range from -40 °C); other sensor types per register 610. | UINT16 | × 0.1 | °C | Read | ||
| HR | 44doc 0044 | DHW operation (S7=J9-3) terminal | 0.1 °C units (listed as U16, range from -40 °C); other sensor types per register 612. | UINT16 | × 0.1 | °C | Read | ||
| HR | 45doc 0045 | Stack or Heat exchanger operation (S9=J9-6) terminal | 0.1 °C units (listed as U16, range from -40 °C); other sensor types per register 613. | UINT16 | × 0.1 | °C | Read | ||
| HR | 46doc 0046 | Outlet operation sensor (S4=J8-10) state | UINT16 | Read | 0 = None; 1 = Normal; 2 = Open; 3 = Shorted; 4 = Outside high range; 5 = Outside low range; 6 = Not reliable | ||||
| HR | 47doc 0047 | DHW operation sensor (S7=J9-3) state | UINT16 | Read | 0 = None; 1 = Normal; 2 = Open; 3 = Shorted; 4 = Outside high range; 5 = Outside low range; 6 = Not reliable | ||||
| HR | 48doc 0048 | Outlet limit sensor (S3=J8-8) state | UINT16 | Read | 0 = None; 1 = Normal; 2 = Open; 3 = Shorted; 4 = Outside high range; 5 = Outside low range; 6 = Not reliable | ||||
| HR | 49doc 0049 | Inlet sensor (S1=J8-4) state | UINT16 | Read | 0 = None; 1 = Normal; 2 = Open; 3 = Shorted; 4 = Outside high range; 5 = Outside low range; 6 = Not reliable | ||||
| HR | 50doc 0050 | DHW limit sensor (S7=J9-1) state | UINT16 | Read | 0 = None; 1 = Normal; 2 = Open; 3 = Shorted; 4 = Outside high range; 5 = Outside low range; 6 = Not reliable | ||||
| HR | 51doc 0051 | Stack limit sensor (S8=J9-4) state | UINT16 | Read | 0 = None; 1 = Normal; 2 = Open; 3 = Shorted; 4 = Outside high range; 5 = Outside low range; 6 = Not reliable | ||||
| HR | 52doc 0052 | S5 (J8-11) sensor state | UINT16 | Read | 0 = None; 1 = Normal; 2 = Open; 3 = Shorted; 4 = Outside high range; 5 = Outside low range; 6 = Not reliable | ||||
| HR | 53doc 0053 | 4-20mA remote control input (S2=J8-6) state | UINT16 | Read | 0 = None; 1 = Normal; 2 = Open; 3 = Shorted; 4 = Outside high range; 5 = Outside low range; 6 = Not reliable | ||||
| HR | 54doc 0054 | Pressure sensor (S1=J8-4) state | UINT16 | Read | 0 = None; 1 = Normal; 2 = Open; 3 = Shorted; 4 = Outside high range; 5 = Outside low range; 6 = Not reliable | ||||
| HR | 55doc 0055 | Stack operation or Heat exchanger sensor (S9=J9-6) state | UINT16 | Read | 0 = None; 1 = Normal; 2 = Open; 3 = Shorted; 4 = Outside high range; 5 = Outside low range; 6 = Not reliable | ||||
| HR | 56doc 0056 | Active rate limiter | UINT16 | Read | 0 = None; 1 = Outlet high limit; 2 = Delta T limit; 3 = Stack limit; 4 = Slow start limit; 5 = Anti-condensation; 6 = Minimum modulation; 7 = Forced rate; 8 = IAS is open | ||||
| HR | 57doc 0057 | Limited rate | Firing rate: RPM, or 0.1 % steps if bit 15 is set (per modulation output setting). | UINT16 | Read | ||||
| HR | 58doc 0058 | Active rate override | UINT16 | Read | 0 = None; 1 = Burner control default; 2 = Burner control; 3 = Manual firing rate; 4 = Manual firing rate off; 5 = Fan on during off cycle; 6 = Assured low fire cutoff | ||||
| HR | 59doc 0059 | Override rate | Firing rate: RPM, or 0.1 % steps if bit 15 is set (per modulation output setting). | UINT16 | Read | ||||
| HR | 60doc 0060 | Demand rate | Firing rate: RPM, or 0.1 % steps if bit 15 is set (per modulation output setting). | UINT16 | Read | ||||
| HR | 61doc 0061 | Active system sensor | UINT16 | Read | 0 = No active sensor; 1 = DHW (S6S7) sensor; 2 = Outlet (S3S4) sensor; 3 = Inlet (S1) sensor; 4 = 4-20mA input (S2); 5 = S5 sensor; 6 = S10 sensor; 7 = Steam (S1) sensor; 8 = DHW (S6S7) and Inlet (S1) sensor; 9 = DHW (S6S7) and S5 sensor; 10 = Outlet (S3S4) and Inlet (S1) sensor; 11 = Outlet (S3S4) and S5 sensor | ||||
| HR | 62doc 0062 | Active Lead Lag sensor | UINT16 | Read | 0 = No active sensor; 2 = Outlet (S3S4) sensor; 5 = S5 sensor; 6 = S10 sensor | ||||
| HR | 64doc 0064 | CH status | UINT16 | Read | 0 = Unknown; 1 = Disabled; 2 = Normal; 3 = Suspended | ||||
| HR | 65doc 0065 | CH setpoint source | UINT16 | Read | 0 = Unknown; 1 = Normal setpoint; 2 = TOD setpoint; 3 = Outdoor reset; 4 = Remote control; 7 = Outdoor reset time of day; 9 = Outdoor boost | ||||
| HR | 66doc 0066 | CH heat demand | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 67doc 0067 | CH burner demand | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 68doc 0068 | CH requested rate | Firing rate: RPM, or 0.1 % steps if bit 15 is set (per modulation output setting). | UINT16 | Read | ||||
| HR | 69doc 0069 | CH frost heat demand | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 70doc 0070 | CH frost burner demand | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 71doc 0071 | Active CH on hysteresis | 0.1 °C units. | UINT16 | × 0.1 | °C | Read | ||
| HR | 72doc 0072 | Active CH off hysteresis | 0.1 °C units. | UINT16 | × 0.1 | °C | Read | ||
| HR | 73doc 0073 | Active CH pressure on hysteresis | UINT16 | × 0.1 | psi | Read | |||
| HR | 74doc 0074 | Active CH pressure off hysteresis | UINT16 | × 0.1 | psi | Read | |||
| HR | 75doc 0075 | Active CH pressure operating point | UINT16 | × 0.1 | psi | Read | |||
| HR | 76doc 0076 | Active CH sensor | UINT16 | Read | 0 = No active sensor; 2 = Outlet (S3S4) sensor; 3 = Inlet (S1) sensor; 4 = 4-20mA input (S2); 5 = S5 sensor; 6 = S10 sensor; 7 = Steam (S1) sensor | ||||
| HR | 77doc 0077 | Heat Demand | UINT16 | Read | |||||
| HR | 78doc 0078 | BURNER DEMAND | UINT16 | Read | |||||
| HR | 79doc 0079 | Active DHW sensor | UINT16 | Read | 0 = No active sensor; 1 = DHW (S6S7) sensor; 2 = Outlet (S3S4) sensor; 3 = Inlet (S1) sensor | ||||
| HR | 80doc 0080 | DHW status | UINT16 | Read | 0 = Unknown; 1 = Disabled; 2 = Normal; 3 = Suspended | ||||
| HR | 81doc 0081 | DHW setpoint source | UINT16 | Read | 0 = Unknown; 1 = Normal setpoint; 2 = TOD setpoint; 5 = DHW tap setpoint; 6 = DHW preheat setpoint | ||||
| HR | 82doc 0082 | DHW priority count | UINT16 | s | Read | ||||
| HR | 83doc 0083 | DHW heat demand | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 84doc 0084 | DHW burner demand | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 85doc 0085 | DHW requested rate | Firing rate: RPM, or 0.1 % steps if bit 15 is set (per modulation output setting). | UINT16 | Read | ||||
| HR | 86doc 0086 | DHW frost heat demand | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 87doc 0087 | DHW frost burner demand | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 88doc 0088 | Active DHW on hysteresis | 0.1 °C units. | UINT16 | × 0.1 | °C | Read | ||
| HR | 89doc 0089 | Active DHW off hysteresis | 0.1 °C units. | UINT16 | × 0.1 | °C | Read | ||
| HR | 90doc 0090 | DHW storage time | UINT16 | s | Read | ||||
| HR | 91doc 0091 | DHW storage heat demand | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 92doc 0092 | DHW storage burner demand | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 93doc 0093 | Pump A status | BITMAP16 | Read | bit 0 = On due to normal demand; bit 1 = Forced on; bit 2 = Forced off; bit 3 = On due to overrun; bit 4 = On due to exercise; bit 5 = Pump exercise requested; bit 6 = Pump assigned to logical pump; bit 8 = CH pump demand; bit 9 = DHW pump demand; bit 10 = Boiler pump demand; bit 11 = System pump demand; bit 12 = Auxiliary 1 pump demand; bit 13 = Auxiliary 2 pump demand | ||||
| HR | 94doc 0094 | Pump B status | BITMAP16 | Read | bit 0 = On due to normal demand; bit 1 = Forced on; bit 2 = Forced off; bit 3 = On due to overrun; bit 4 = On due to exercise; bit 5 = Pump exercise requested; bit 6 = Pump assigned to logical pump; bit 8 = CH pump demand; bit 9 = DHW pump demand; bit 10 = Boiler pump demand; bit 11 = System pump demand; bit 12 = Auxiliary 1 pump demand; bit 13 = Auxiliary 2 pump demand | ||||
| HR | 95doc 0095 | CH pump start delay time | UINT16 | Read | |||||
| HR | 96doc 0096 | CH pump status | Coding depends on application build (tables 13/14 in the source). | UINT16 | Read | ||||
| HR | 97doc 0097 | CH pump overrun time | UINT16 | s | Read | ||||
| HR | 98doc 0098 | CH FP overrun time | UINT16 | s | Read | ||||
| HR | 99doc 0099 | CH pump idle days count | UINT16 | days | Read | ||||
| HR | 100doc 0100 | DHW pump status | Coding depends on application build (tables 13/14 in the source). | UINT16 | Read | ||||
| HR | 101doc 0101 | DHW pump start delay time | UINT16 | s | Read | ||||
| HR | 102doc 0102 | DHW pump overrun time | UINT16 | s | Read | ||||
| HR | 103doc 0103 | DHW FP overrun time | UINT16 | s | Read | ||||
| HR | 104doc 0104 | DHW pump idle days count | UINT16 | days | Read | ||||
| HR | 105doc 0105 | System pump status | Coding depends on application build (tables 13/14 in the source). | UINT16 | Read | ||||
| HR | 106doc 0106 | System pump overrun time | UINT16 | s | Read | ||||
| HR | 107doc 0107 | System pump idle days count | UINT16 | days | Read | ||||
| HR | 108doc 0108 | Boiler pump status | Coding depends on application build (tables 13/14 in the source). | UINT16 | Read | ||||
| HR | 109doc 0109 | Boiler pump overrun time | UINT16 | s | Read | ||||
| HR | 110doc 0110 | Boiler pump idle days count | UINT16 | days | Read | ||||
| HR | 111doc 0111 | Auxiliary 1 pump status | Coding depends on application build (tables 13/14 in the source). | UINT16 | Read | ||||
| HR | 112doc 0112 | Auxiliary 1 pump idle days count | UINT16 | days | Read | ||||
| HR | 113doc 0113 | Auxiliary 2 pump status | See table 14 in the source. | UINT16 | Read | ||||
| HR | 114doc 0114 | Auxiliary 2 pump overrun time | UINT16 | s | Read | ||||
| HR | 115doc 0115 | Auxiliary 2 pump idle days count | UINT16 | days | Read | ||||
| HR | 119doc 0119 | Auxiliary 1 pump overrun time | UINT16 | s | Read | ||||
| HR | 148doc 0148 | Auxiliary 2 pump start delay time | UINT16 | Read | |||||
| HR | 149doc 0149 | Boiler pump start delay time | UINT16 | Read | |||||
| HR | 150doc 0150 | System pump start delay time | UINT16 | Read | |||||
| HR | 151doc 0151 | Auxiliary 1 pump start delay time | UINT16 | Read | |||||
| HR | 152doc 0152 | DHW tap heat demand | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 153doc 0153 | DHW preheat demand | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 154doc 0154 | DHW change rate | Rate of change, 0.1 °C units. | UINT16 | × 0.1 | °C/s | Read | ||
| HR | 155doc 0155 | DHW tap on recognition time | UINT16 | s | Read | ||||
| HR | 156doc 0156 | DHW tap on time | UINT16 | s | Read | ||||
| HR | 157doc 0157 | DHW preheat delay after tap time | UINT16 | s | Read | ||||
| HR | 158doc 0158 | DHW preheat on recognition time | UINT16 | s | Read | ||||
| HR | 159doc 0159 | DHW preheat on time | UINT16 | s | Read | ||||
| HR | 160doc 0160 | Lead Lag master status | UINT16 | Read | 0 = Unknown; 1 = Disabled; 2 = Normal; 3 = Suspended | ||||
| HR | 161doc 0161 | Lead Lag slave status | BITMAP16 | Read | bit 9 = Local frost protection request; bit 10 = Frost protection burner request; bit 11 = DHW frost protection request; bit 12 = CH frost protection request; bit 13 = Slave is modulating; bit 14 = Slave mode has priority over CH & DHW; bit 15 = Slave command received | ||||
| HR | 162doc 0162 | Lead Lag master setpoint source | UINT16 | Read | 0 = Unknown; 1 = CH setpoint; 2 = CH TOD setpoint; 3 = Outdoor reset; 4 = Remote control (4-20mA or Modbus); 7 = Outdoor reset time of day; 9 = Outdoor boost | ||||
| HR | 163doc 0163 | Lead Lag master heat demand | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 164doc 0164 | Lead Lag slave burner demand | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 165doc 0165 | Lead Lag slave requested rate | Firing rate: RPM, or 0.1 % steps if bit 15 is set (per modulation output setting). | UINT16 | Read | ||||
| HR | 166doc 0166 | Active Lead Lag on hysteresis | 0.1 °C units. | UINT16 | × 0.1 | °C | Read | ||
| HR | 167doc 0167 | Active Lead Lag off hysteresis | 0.1 °C units. | UINT16 | × 0.1 | °C | Read | ||
| HR | 168doc 0168 | Pump C status | BITMAP16 | Read | bit 0 = On due to normal demand; bit 1 = Forced on; bit 2 = Forced off; bit 3 = On due to overrun; bit 4 = On due to exercise; bit 5 = Pump exercise requested; bit 6 = Pump assigned to logical pump; bit 8 = CH pump demand; bit 9 = DHW pump demand; bit 10 = Boiler pump demand; bit 11 = System pump demand; bit 12 = Auxiliary 1 pump demand; bit 13 = Auxiliary 2 pump demand | ||||
| HR | 170doc 0170 | Outdoor temperature | 0.1 °C units; register listed as U16 although the range starts at -40 °C. | UINT16 | × 0.1 | °C | Read | ||
| HR | 171doc 0171 | Outdoor sensor state | UINT16 | Read | 0 = None; 1 = Normal; 2 = Open; 3 = Shorted; 4 = Outside high range; 5 = Outside low range; 6 = Not reliable | ||||
| HR | 172doc 0172 | Outlet T-rise rate | Rate of change, 0.1 °C units. | UINT16 | × 0.1 | °C/s | Read | ||
| HR | 173doc 0173 | Exchanger T-rise rate | Rate of change, 0.1 °C units. | UINT16 | × 0.1 | °C/s | Read |
Notes on this map
- Source host: Honeywell's specification as hosted by Contemporary Controls (a Honeywell integration partner); Honeywell does not host it publicly that we could find.
- All temperatures are in 0.1 °C regardless of the display unit setting. The specification lists these registers as U16 even though the range is -40 to 130 °C; check how sub-zero values arrive on site. A temperature that does not apply (function not enabled) reads 0x8FFF; sensor faults replace the reading with the codes in table 4 of the source (0x7FFF, 0x8000-0x8500).
- Firing-rate type registers carry either RPM or a 0.1 % value; the most significant bit tells which (0 = RPM, 1 = %), as set by the modulation output parameter (register 192).
- Left out: the 32-bit statistics counters (128-147); the specification says 32-bit items use two consecutive registers but does not state the word order. Also left out: configuration registers above 173, alert/lockout history, lead-lag slave tables and the variable-length data items.
- Pump status coding depends on application build (before/after 1600); see tables 13-14 in the source.
- Up to 125 registers per read and 20 per write; variable-length items must be read on their own.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Honeywell SOLA hydronic boiler control (Modbus interface)
What Modbus registers does the Honeywell SOLA hydronic boiler control (Modbus interface) have?
This map lists 140 registers: 140 holding registers. 1 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Honeywell SOLA hydronic boiler control (Modbus interface) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The specification says register addresses start at 0 per the Modbus specification; add 40001 to the decimal address for traditional 4xxxx numbering. Register 7 (outlet temperature) is requested as address 7 (40008).
What are the minimum Modbus registers to integrate the Honeywell SOLA hydronic boiler control (Modbus interface)?
Start with HR 7 Outlet (S3S4) or Outlet limit (S3) sensor (Outlet temperature); HR 8 Firing rate (Firing rate); HR 10 Flame signal (Flame signal); HR 32 Burner control status (Burner control status); HR 34 Lockout code (Lockout code); HR 6 Demand source (Demand source); HR 16 Active CH setpoint (Active CH setpoint).
How do I enable Modbus control of the Honeywell SOLA hydronic boiler control (Modbus interface)?
Use one of the SOLA's RS-485 Modbus ports (MB1 or MB2); the control answers to a single Modbus address. Register writes are limited by the access level shown in register 19 (none, installer, OEM or all).
Where is the official Honeywell SOLA hydronic boiler control (Modbus interface) Modbus documentation?
The source is Software Interface Specification - SOLA Modbus Interface (Rev. 4.1.1), revision 2013-10-14. Honeywell doesn't publish it on its own website, so this map was re-typed from a free copy at https://www.ccontrols.com/support/dp/OEMModbusSIS4_1_1_1_1.pdf. It may be an older revision, so check it against the live unit.
More Honeywell Modbus register maps
- Sensor (extractive gas detector)
Honeywell Midas gas detector (Modbus/TCP)
Honeywell Midas extractive gas detectors (original Midas platform, software V1.08), user manual 3010M5000 revision 32, Appendix A Modbus/TCP interface.
Also known as: Midas, MIDAS gas detector - Sensor (extractive gas detector)
Honeywell Midas S2 extractive gas transmitter (Modbus/TCP)
Honeywell Midas S2 single-point extractive gas transmitters with Ethernet/PoE, user manual 3023M5001 Rev A, Modbus/TCP register map (Table 6-1).
Also known as: Midas S2, MIDAS-S2, Midas S2 gas detector
Other boilers & water heaters register maps
- Boiler
Lochinvar SYNC condensing boilers / water heaters 1.0, 1.3, 1.5 (Modbus communication board)
Lochinvar SYNC 1.0 / 1.3 / 1.5 dual-module boilers and water heaters with the Modbus/BACnet communication board, per SYNC-MODB Rev L.
Also known as: SYNC 1.0, SYNC 1.3, SYNC 1.5, SYNC, Lochinvar SYNC, SYNC-MODB - Boiler / heating system controller
Buderus Logamatic 5000 boiler and system controller (Modbus TCP, datapoint list 4.0)
Buderus Logamatic 5313 and 5311 (and the Bosch Control 8313/8311 equivalents) acting as master, firmware 1.3 or later with the 4.0 datapoint list; addresses for slave controllers differ.
Also known as: Logamatic 5313, Logamatic 5311, Bosch Control 8313, Bosch Control 8311, Control 8000, BCT 531, Logamatic 5000 Modbus - Boiler
Lochinvar Crest / Crest with Hellcat boilers (ModBus communication board)
Lochinvar Crest FB/OF 751-6001 and FCB1000-6000 (including Crest with Hellcat) with the ModBus communication board.
Also known as: Crest, Crest FB751-6001, Crest OF751-6001, Crest FCB1000-6000, Hellcat, MTR-01 - Boiler (water heater controller)
PVI Industries TempTrac water heater electronic controller (Modbus RTU)
PVI TempTrac thermostatic controllers (firmware 0.3 and 0.5) on RS-485 Modbus RTU, per PVI manual PV500-42 (06/2014).
Also known as: TempTrac, PV500-42 - Boiler (burner management / fuel-air ratio control)
Fireye PPC4000 parallel positioning burner control (Modbus RTU)
Fireye PPC4000 parallel positioning controls showing engineering code EC08 or later, per bulletin MOD-4001 (September 13, 2012). The later NXF4000 is not covered.
Also known as: PPC-4000, PPC4000, MOD-4001 - Boiler
Lochinvar Power-fin PBX / PFX boilers and water heaters 502-1302, 1501-2001 (Modbus communication board)
Lochinvar Power-fin PB/PF 'X' models 502-1302 and 1501-2001 with the SMART SYSTEM control and Modbus/BACnet communication board, per PBX-PFX-MODB Rev D.
Also known as: Power-fin, Power-Fin, PBX502, PBX1302, PBX1501, PBX2001, PFX502, PFX2001, PBX-PFX-MODB, SMART SYSTEM
All boilers & water heaters Modbus register maps →
Source: Software Interface Specification - SOLA Modbus Interface · Rev. 4.1.1 · rev. 2013-10-14 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.