Boiler controller · Modbus register map

Honeywell SOLA hydronic boiler control (Modbus interface) Modbus register map

Updated 17 November 2026

Short answer

SOLA is Honeywell's integrated burner and hydronic control used by many boiler OEMs. Its RS-485 Modbus RTU port exposes everything as 16-bit holding registers, with digital signals packed into bit-map registers. This map covers the status area: change flags, digital I/O, limits, demand source, temperatures, firing rate, flame signal, burner control status and lockout codes, sensor states, CH/DHW/lead-lag status and pump status.

This page lists 140 Modbus registers for the Honeywell SOLA hydronic boiler control (Modbus interface) — 1 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Honeywell’s own free documentation (linked below) and checked against it.

Manufacturer
Honeywell
Model
SOLA hydronic boiler control (Modbus interface)
Equipment type
Boiler controller
Registers
140 (1 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
38400 baud, 8N1
Documented addressing
0-based (the number printed is the address on the wire)
Also known as
R7910, R7911, Honeywell SOLA, SOLA ICP
Source document
Software Interface Specification - SOLA Modbus Interface · Rev. 4.1.1 · rev. 2013-10-14 · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Honeywell SOLA hydronic boiler control (Modbus interface)

Integration in brief

Connect to the SOLA's 3-pin RS-485 Modbus port (38400 8N1) and read holding registers with FC 03 from address 0. Temperatures are 0.1 °C integers; burner status is at 32, lockout code at 34.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 7Outlet (S3S4) or Outlet limit (S3) sensorUINT16Outlet temperatureRead
HR 8Firing rateUINT16Firing rateRead
HR 10Flame signalUINT16Flame signalRead
HR 32Burner control statusUINT16Burner control statusRead
HR 34Lockout codeUINT16Lockout codeRead
HR 6Demand sourceUINT16Demand sourceRead
HR 16Active CH setpointUINT16Active CH setpointRead

Enable Modbus control & writes

Use one of the SOLA's RS-485 Modbus ports (MB1 or MB2); the control answers to a single Modbus address. Register writes are limited by the access level shown in register 19 (none, installer, OEM or all).

Byte order & addressing

Network setup

Watch out for

Honeywell SOLA hydronic boiler control (Modbus interface) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

140 of 140 shown
Honeywell SOLA hydronic boiler control (Modbus interface) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 0000Status ChangeCleared after read; flags which register groups changed.BITMAP16Readbit 0 = Active Lockout; bit 1 = Burner control status; bit 2 = Sensor status; bit 3 = Demand&Modulation status; bit 4 = CH status; bit 5 = DHW status; bit 6 = Pump status; bit 7 = Statistics; bit 8 = Lead Lag status; bit 9 = Lockout history; bit 10 = Alert log
HR1doc 0001Configuration ChangeCleared after read; flags which register groups changed.BITMAP16Readbit 0 = System configuration; bit 1 = Modulation configuration; bit 2 = CH configuration; bit 3 = Burner control configuration; bit 4 = Fan configuration; bit 5 = Pump configuration; bit 6 = Annunciation configuration; bit 7 = DHW configuration; bit 8 = Limits configuration; bit 9 = Anti-condensation configuration; bit 10 = Outdoor reset configuration; bit 11 = Frost protection configuration; bit 12 = Lead Lag configuration; bit 14 = PM configuration; bit 15 = PCB configuration
HR2doc 0002Digital I/OBITMAP16Readbit 0 = Pump A; bit 1 = Pump B; bit 2 = Pump C; bit 3 = Blower motor/HSI; bit 4 = External ignition; bit 5 = Pilot valve; bit 6 = Main valve; bit 7 = Alarm; bit 8 = Interlock (ILK); bit 9 = Pre-ignition interlock (PII); bit 10 = Load Control Input(LCI); bit 11 = Low Fire Switch (LFS); bit 12 = High Fire Switch (HFS); bit 13 = STAT (Demand); bit 14 = Time of Day; bit 15 = Safety relay
HR3doc 0003Annunciation I/OBITMAP16Readbit 0 = Annunciator 1/IAS; bit 1 = Annunciator 2; bit 2 = Annunciator 3; bit 3 = Annunciator 4; bit 4 = Annunciator 5; bit 5 = Annunciator 6; bit 6 = Annunciator 7/HFS; bit 7 = Annunciator 8/LFS
HR4doc 0004LimitsBITMAP16Readbit 0 = Outlet high limit; bit 1 = DHW high limit; bit 2 = Stack limit; bit 3 = Delta T inlet/outlet limit; bit 4 = Delta T exchanger/outlet limit; bit 5 = Delta T inlet/exchanger limit; bit 6 = Inversion inlet/outlet limit; bit 7 = Inversion exchanger/outlet limit; bit 8 = Inversion inlet/exchanger limit; bit 9 = Outlet T-rise limit; bit 10 = Exchanger T-rise limit; bit 11 = Heat exchanger high limit
HR5doc 0005Program Module (PM) statusBITMAP16Readbit 0 = PM installed; bit 1 = Lead/Lag enabled; bit 2 = Valid copyright; bit 8 = OEM parameter PCB stored in PM; bit 9 = OEM range PCB stored in PM; bit 10 = OEM alert PCB stored in PM
HR6doc 0006Demand sourceUINT16Read0 = Unknown; 1 = No source demand; 2 = CH; 3 = DHW; 4 = Lead Lag slave; 5 = Lead Lag master; 6 = CH frost protection; 7 = DHW frost protection; 8 = No demand due to burner switch (register 199) turned off; 9 = DHW storage; 11 = Warm weather shutdown; 12 = Hot standby
HR7doc 0007Outlet (S3S4) or Outlet limit (S3) sensor0.1 °C units; register listed as U16 although the range starts at -40 °C.UINT16× 0.1°CRead
HR8doc 0008Firing rateFiring rate: RPM, or 0.1 % steps if bit 15 is set (per modulation output setting).UINT16Read
HR9doc 0009Fan speedUINT16RPMRead
HR10doc 0010Flame signal0.01 V or 0.01 uA, depending on flame sensor (0.00-50.00).UINT16× 0.01Read
HR11doc 0011Inlet (S1) sensor0.1 °C units; register listed as U16 although the range starts at -40 °C.UINT16× 0.1°CRead
HR12doc 0012DHW (S6S7) or DHW limit (S6) sensor0.1 °C units; register listed as U16 although the range starts at -40 °C.UINT16× 0.1°CRead
HR13doc 0013S5 sensor0.1 °C units; register listed as U16 although the range starts at -40 °C.UINT16× 0.1°CRead
HR14doc 0014Stack (S8S9) or Stack limit (S8) sensor0.1 °C units; register listed as U16 although the range starts at -40 °C.UINT16× 0.1°CRead
HR15doc 00154-20 mA remote control input (S2) terminal0.1 mA units when S2 is a 4-20 mA input; other uses per register 609.UINT16× 0.1mARead
HR16doc 0016Active CH setpoint0.1 °C units; register listed as U16 although the range starts at -40 °C.UINT16× 0.1°CRead
HR17doc 0017Active DHW setpoint0.1 °C units; register listed as U16 although the range starts at -40 °C.UINT16× 0.1°CRead
HR18doc 0018Active LL setpoint0.1 °C units; register listed as U16 although the range starts at -40 °C.UINT16× 0.1°CRead
HR19doc 0019Register Access StatusUINT16Read0 = No register writes allowed; 1 = Installer register writes allowed; 2 = OEM register writes allowed; 3 = All register writes allowed
HR20doc 0020Steam pressureUINT16× 0.1psiRead
HR21doc 0021Analog modulation input0 = no signal, else 4-20 mA (0.1 mA); mirrors register 15 for 4-20 mA S2.UINT16× 0.1mARead
HR22doc 0022Active CH pressure setpointUINT16× 0.1psiRead
HR23doc 0023Extended Status ChangeCleared after read; flags which register groups changed.BITMAP16Readbit 3 = DHW plate heat exchanger status; bit 4 = DHW plate heat exchanger configuration
HR25doc 0025Active CH operating point0.1 °C units; register listed as U16 although the range starts at -40 °C.UINT16× 0.1°CRead
HR26doc 0026Active DHW operating point0.1 °C units; register listed as U16 although the range starts at -40 °C.UINT16× 0.1°CRead
HR27doc 0027Active Lead Lag operating point0.1 °C units; register listed as U16 although the range starts at -40 °C.UINT16× 0.1°CRead
HR28doc 0028Active system operating point0.1 °C units; register listed as U16 although the range starts at -40 °C.UINT16× 0.1°CRead
HR29doc 0029Active system setpoint0.1 °C units; register listed as U16 although the range starts at -40 °C.UINT16× 0.1°CRead
HR30doc 0030Active system on hysteresis0.1 °C units.UINT16× 0.1°CRead
HR31doc 0031Active system off hysteresis0.1 °C units.UINT16× 0.1°CRead
HR32doc 0032Burner control statusUINT16Read0 = Disabled; 1 = Locked out; 4 = Anti-short cycle; 5 = Unconfigured safety data; 34 = Standby Hold; 35 = Standby Delay; 48 = Normal Standby; 49 = Preparing; 50 = Ignition; 51 = Firing; 52 = Postpurge
HR33doc 0033Burner control stateSequence state code, see table 12 in the source.UINT16Read
HR34doc 0034Lockout code1-4096 = lockout number (table 9 in the source).UINT16Read0 = No lockout
HR35doc 0035Alarm reasonUINT16Read0 = None; 1 = Lockout (see Lockout code, register 34); 2 = Alert (see Table 11); 3 = Other
HR36doc 0036Annunciator first outUINT16Read0 = None or undetermined; 1 = ILK; 2 = PII; 11 = Annunciator 1; 12 = Annunciator 2; 13 = Annunciator 3; 14 = Annunciator 4; 15 = Annunciator 5; 16 = Annunciator 6; 17 = Annunciator 7; 18 = Annunciator 8
HR37doc 0037Annunciator holdUINT16Read0 = None or undetermined; 1 = ILK; 2 = PII; 3 = LCI; 11 = Annunciator 1; 12 = Annunciator 2; 13 = Annunciator 3; 14 = Annunciator 4; 15 = Annunciator 5; 16 = Annunciator 6; 17 = Annunciator 7; 18 = Annunciator 8
HR38doc 0038Sequence timeUINT16sRead
HR39doc 0039Delay timeUINT16sRead
HR40doc 0040Hold codeHold reason; same codes as lockout (table 8 in the source).UINT16Read
HR41doc 0041Burner control flagsBITMAP16Readbit 0 = Flame detected; bit 1 = DHW remote STAT demand indicated; bit 2 = Blocked condensate detected
HR42doc 0042CH remote StatUINT16Read/write0 = No remote STAT demand; 1 = Remote STAT demand indicated
HR43doc 0043Outlet operation (S4=J8-10) terminal0.1 °C units (listed as U16, range from -40 °C); other sensor types per register 610.UINT16× 0.1°CRead
HR44doc 0044DHW operation (S7=J9-3) terminal0.1 °C units (listed as U16, range from -40 °C); other sensor types per register 612.UINT16× 0.1°CRead
HR45doc 0045Stack or Heat exchanger operation (S9=J9-6) terminal0.1 °C units (listed as U16, range from -40 °C); other sensor types per register 613.UINT16× 0.1°CRead
HR46doc 0046Outlet operation sensor (S4=J8-10) stateUINT16Read0 = None; 1 = Normal; 2 = Open; 3 = Shorted; 4 = Outside high range; 5 = Outside low range; 6 = Not reliable
HR47doc 0047DHW operation sensor (S7=J9-3) stateUINT16Read0 = None; 1 = Normal; 2 = Open; 3 = Shorted; 4 = Outside high range; 5 = Outside low range; 6 = Not reliable
HR48doc 0048Outlet limit sensor (S3=J8-8) stateUINT16Read0 = None; 1 = Normal; 2 = Open; 3 = Shorted; 4 = Outside high range; 5 = Outside low range; 6 = Not reliable
HR49doc 0049Inlet sensor (S1=J8-4) stateUINT16Read0 = None; 1 = Normal; 2 = Open; 3 = Shorted; 4 = Outside high range; 5 = Outside low range; 6 = Not reliable
HR50doc 0050DHW limit sensor (S7=J9-1) stateUINT16Read0 = None; 1 = Normal; 2 = Open; 3 = Shorted; 4 = Outside high range; 5 = Outside low range; 6 = Not reliable
HR51doc 0051Stack limit sensor (S8=J9-4) stateUINT16Read0 = None; 1 = Normal; 2 = Open; 3 = Shorted; 4 = Outside high range; 5 = Outside low range; 6 = Not reliable
HR52doc 0052S5 (J8-11) sensor stateUINT16Read0 = None; 1 = Normal; 2 = Open; 3 = Shorted; 4 = Outside high range; 5 = Outside low range; 6 = Not reliable
HR53doc 00534-20mA remote control input (S2=J8-6) stateUINT16Read0 = None; 1 = Normal; 2 = Open; 3 = Shorted; 4 = Outside high range; 5 = Outside low range; 6 = Not reliable
HR54doc 0054Pressure sensor (S1=J8-4) stateUINT16Read0 = None; 1 = Normal; 2 = Open; 3 = Shorted; 4 = Outside high range; 5 = Outside low range; 6 = Not reliable
HR55doc 0055Stack operation or Heat exchanger sensor (S9=J9-6) stateUINT16Read0 = None; 1 = Normal; 2 = Open; 3 = Shorted; 4 = Outside high range; 5 = Outside low range; 6 = Not reliable
HR56doc 0056Active rate limiterUINT16Read0 = None; 1 = Outlet high limit; 2 = Delta T limit; 3 = Stack limit; 4 = Slow start limit; 5 = Anti-condensation; 6 = Minimum modulation; 7 = Forced rate; 8 = IAS is open
HR57doc 0057Limited rateFiring rate: RPM, or 0.1 % steps if bit 15 is set (per modulation output setting).UINT16Read
HR58doc 0058Active rate overrideUINT16Read0 = None; 1 = Burner control default; 2 = Burner control; 3 = Manual firing rate; 4 = Manual firing rate off; 5 = Fan on during off cycle; 6 = Assured low fire cutoff
HR59doc 0059Override rateFiring rate: RPM, or 0.1 % steps if bit 15 is set (per modulation output setting).UINT16Read
HR60doc 0060Demand rateFiring rate: RPM, or 0.1 % steps if bit 15 is set (per modulation output setting).UINT16Read
HR61doc 0061Active system sensorUINT16Read0 = No active sensor; 1 = DHW (S6S7) sensor; 2 = Outlet (S3S4) sensor; 3 = Inlet (S1) sensor; 4 = 4-20mA input (S2); 5 = S5 sensor; 6 = S10 sensor; 7 = Steam (S1) sensor; 8 = DHW (S6S7) and Inlet (S1) sensor; 9 = DHW (S6S7) and S5 sensor; 10 = Outlet (S3S4) and Inlet (S1) sensor; 11 = Outlet (S3S4) and S5 sensor
HR62doc 0062Active Lead Lag sensorUINT16Read0 = No active sensor; 2 = Outlet (S3S4) sensor; 5 = S5 sensor; 6 = S10 sensor
HR64doc 0064CH statusUINT16Read0 = Unknown; 1 = Disabled; 2 = Normal; 3 = Suspended
HR65doc 0065CH setpoint sourceUINT16Read0 = Unknown; 1 = Normal setpoint; 2 = TOD setpoint; 3 = Outdoor reset; 4 = Remote control; 7 = Outdoor reset time of day; 9 = Outdoor boost
HR66doc 0066CH heat demandUINT16Read0 = Off; 1 = On
HR67doc 0067CH burner demandUINT16Read0 = Off; 1 = On
HR68doc 0068CH requested rateFiring rate: RPM, or 0.1 % steps if bit 15 is set (per modulation output setting).UINT16Read
HR69doc 0069CH frost heat demandUINT16Read0 = Off; 1 = On
HR70doc 0070CH frost burner demandUINT16Read0 = Off; 1 = On
HR71doc 0071Active CH on hysteresis0.1 °C units.UINT16× 0.1°CRead
HR72doc 0072Active CH off hysteresis0.1 °C units.UINT16× 0.1°CRead
HR73doc 0073Active CH pressure on hysteresisUINT16× 0.1psiRead
HR74doc 0074Active CH pressure off hysteresisUINT16× 0.1psiRead
HR75doc 0075Active CH pressure operating pointUINT16× 0.1psiRead
HR76doc 0076Active CH sensorUINT16Read0 = No active sensor; 2 = Outlet (S3S4) sensor; 3 = Inlet (S1) sensor; 4 = 4-20mA input (S2); 5 = S5 sensor; 6 = S10 sensor; 7 = Steam (S1) sensor
HR77doc 0077Heat DemandUINT16Read
HR78doc 0078BURNER DEMANDUINT16Read
HR79doc 0079Active DHW sensorUINT16Read0 = No active sensor; 1 = DHW (S6S7) sensor; 2 = Outlet (S3S4) sensor; 3 = Inlet (S1) sensor
HR80doc 0080DHW statusUINT16Read0 = Unknown; 1 = Disabled; 2 = Normal; 3 = Suspended
HR81doc 0081DHW setpoint sourceUINT16Read0 = Unknown; 1 = Normal setpoint; 2 = TOD setpoint; 5 = DHW tap setpoint; 6 = DHW preheat setpoint
HR82doc 0082DHW priority countUINT16sRead
HR83doc 0083DHW heat demandUINT16Read0 = Off; 1 = On
HR84doc 0084DHW burner demandUINT16Read0 = Off; 1 = On
HR85doc 0085DHW requested rateFiring rate: RPM, or 0.1 % steps if bit 15 is set (per modulation output setting).UINT16Read
HR86doc 0086DHW frost heat demandUINT16Read0 = Off; 1 = On
HR87doc 0087DHW frost burner demandUINT16Read0 = Off; 1 = On
HR88doc 0088Active DHW on hysteresis0.1 °C units.UINT16× 0.1°CRead
HR89doc 0089Active DHW off hysteresis0.1 °C units.UINT16× 0.1°CRead
HR90doc 0090DHW storage timeUINT16sRead
HR91doc 0091DHW storage heat demandUINT16Read0 = Off; 1 = On
HR92doc 0092DHW storage burner demandUINT16Read0 = Off; 1 = On
HR93doc 0093Pump A statusBITMAP16Readbit 0 = On due to normal demand; bit 1 = Forced on; bit 2 = Forced off; bit 3 = On due to overrun; bit 4 = On due to exercise; bit 5 = Pump exercise requested; bit 6 = Pump assigned to logical pump; bit 8 = CH pump demand; bit 9 = DHW pump demand; bit 10 = Boiler pump demand; bit 11 = System pump demand; bit 12 = Auxiliary 1 pump demand; bit 13 = Auxiliary 2 pump demand
HR94doc 0094Pump B statusBITMAP16Readbit 0 = On due to normal demand; bit 1 = Forced on; bit 2 = Forced off; bit 3 = On due to overrun; bit 4 = On due to exercise; bit 5 = Pump exercise requested; bit 6 = Pump assigned to logical pump; bit 8 = CH pump demand; bit 9 = DHW pump demand; bit 10 = Boiler pump demand; bit 11 = System pump demand; bit 12 = Auxiliary 1 pump demand; bit 13 = Auxiliary 2 pump demand
HR95doc 0095CH pump start delay timeUINT16Read
HR96doc 0096CH pump statusCoding depends on application build (tables 13/14 in the source).UINT16Read
HR97doc 0097CH pump overrun timeUINT16sRead
HR98doc 0098CH FP overrun timeUINT16sRead
HR99doc 0099CH pump idle days countUINT16daysRead
HR100doc 0100DHW pump statusCoding depends on application build (tables 13/14 in the source).UINT16Read
HR101doc 0101DHW pump start delay timeUINT16sRead
HR102doc 0102DHW pump overrun timeUINT16sRead
HR103doc 0103DHW FP overrun timeUINT16sRead
HR104doc 0104DHW pump idle days countUINT16daysRead
HR105doc 0105System pump statusCoding depends on application build (tables 13/14 in the source).UINT16Read
HR106doc 0106System pump overrun timeUINT16sRead
HR107doc 0107System pump idle days countUINT16daysRead
HR108doc 0108Boiler pump statusCoding depends on application build (tables 13/14 in the source).UINT16Read
HR109doc 0109Boiler pump overrun timeUINT16sRead
HR110doc 0110Boiler pump idle days countUINT16daysRead
HR111doc 0111Auxiliary 1 pump statusCoding depends on application build (tables 13/14 in the source).UINT16Read
HR112doc 0112Auxiliary 1 pump idle days countUINT16daysRead
HR113doc 0113Auxiliary 2 pump statusSee table 14 in the source.UINT16Read
HR114doc 0114Auxiliary 2 pump overrun timeUINT16sRead
HR115doc 0115Auxiliary 2 pump idle days countUINT16daysRead
HR119doc 0119Auxiliary 1 pump overrun timeUINT16sRead
HR148doc 0148Auxiliary 2 pump start delay timeUINT16Read
HR149doc 0149Boiler pump start delay timeUINT16Read
HR150doc 0150System pump start delay timeUINT16Read
HR151doc 0151Auxiliary 1 pump start delay timeUINT16Read
HR152doc 0152DHW tap heat demandUINT16Read0 = Off; 1 = On
HR153doc 0153DHW preheat demandUINT16Read0 = Off; 1 = On
HR154doc 0154DHW change rateRate of change, 0.1 °C units.UINT16× 0.1°C/sRead
HR155doc 0155DHW tap on recognition timeUINT16sRead
HR156doc 0156DHW tap on timeUINT16sRead
HR157doc 0157DHW preheat delay after tap timeUINT16sRead
HR158doc 0158DHW preheat on recognition timeUINT16sRead
HR159doc 0159DHW preheat on timeUINT16sRead
HR160doc 0160Lead Lag master statusUINT16Read0 = Unknown; 1 = Disabled; 2 = Normal; 3 = Suspended
HR161doc 0161Lead Lag slave statusBITMAP16Readbit 9 = Local frost protection request; bit 10 = Frost protection burner request; bit 11 = DHW frost protection request; bit 12 = CH frost protection request; bit 13 = Slave is modulating; bit 14 = Slave mode has priority over CH & DHW; bit 15 = Slave command received
HR162doc 0162Lead Lag master setpoint sourceUINT16Read0 = Unknown; 1 = CH setpoint; 2 = CH TOD setpoint; 3 = Outdoor reset; 4 = Remote control (4-20mA or Modbus); 7 = Outdoor reset time of day; 9 = Outdoor boost
HR163doc 0163Lead Lag master heat demandUINT16Read0 = Off; 1 = On
HR164doc 0164Lead Lag slave burner demandUINT16Read0 = Off; 1 = On
HR165doc 0165Lead Lag slave requested rateFiring rate: RPM, or 0.1 % steps if bit 15 is set (per modulation output setting).UINT16Read
HR166doc 0166Active Lead Lag on hysteresis0.1 °C units.UINT16× 0.1°CRead
HR167doc 0167Active Lead Lag off hysteresis0.1 °C units.UINT16× 0.1°CRead
HR168doc 0168Pump C statusBITMAP16Readbit 0 = On due to normal demand; bit 1 = Forced on; bit 2 = Forced off; bit 3 = On due to overrun; bit 4 = On due to exercise; bit 5 = Pump exercise requested; bit 6 = Pump assigned to logical pump; bit 8 = CH pump demand; bit 9 = DHW pump demand; bit 10 = Boiler pump demand; bit 11 = System pump demand; bit 12 = Auxiliary 1 pump demand; bit 13 = Auxiliary 2 pump demand
HR170doc 0170Outdoor temperature0.1 °C units; register listed as U16 although the range starts at -40 °C.UINT16× 0.1°CRead
HR171doc 0171Outdoor sensor stateUINT16Read0 = None; 1 = Normal; 2 = Open; 3 = Shorted; 4 = Outside high range; 5 = Outside low range; 6 = Not reliable
HR172doc 0172Outlet T-rise rateRate of change, 0.1 °C units.UINT16× 0.1°C/sRead
HR173doc 0173Exchanger T-rise rateRate of change, 0.1 °C units.UINT16× 0.1°C/sRead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Honeywell SOLA hydronic boiler control (Modbus interface)

What Modbus registers does the Honeywell SOLA hydronic boiler control (Modbus interface) have?

This map lists 140 registers: 140 holding registers. 1 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Honeywell SOLA hydronic boiler control (Modbus interface) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The specification says register addresses start at 0 per the Modbus specification; add 40001 to the decimal address for traditional 4xxxx numbering. Register 7 (outlet temperature) is requested as address 7 (40008).

What are the minimum Modbus registers to integrate the Honeywell SOLA hydronic boiler control (Modbus interface)?

Start with HR 7 Outlet (S3S4) or Outlet limit (S3) sensor (Outlet temperature); HR 8 Firing rate (Firing rate); HR 10 Flame signal (Flame signal); HR 32 Burner control status (Burner control status); HR 34 Lockout code (Lockout code); HR 6 Demand source (Demand source); HR 16 Active CH setpoint (Active CH setpoint).

How do I enable Modbus control of the Honeywell SOLA hydronic boiler control (Modbus interface)?

Use one of the SOLA's RS-485 Modbus ports (MB1 or MB2); the control answers to a single Modbus address. Register writes are limited by the access level shown in register 19 (none, installer, OEM or all).

Where is the official Honeywell SOLA hydronic boiler control (Modbus interface) Modbus documentation?

The source is Software Interface Specification - SOLA Modbus Interface (Rev. 4.1.1), revision 2013-10-14. Honeywell doesn't publish it on its own website, so this map was re-typed from a free copy at https://www.ccontrols.com/support/dp/OEMModbusSIS4_1_1_1_1.pdf. It may be an older revision, so check it against the live unit.

More Honeywell Modbus register maps

Other boilers & water heaters register maps

All boilers & water heaters Modbus register maps →