Easy Modbus
  1. Home
  2. Modbus register maps
  3. Lochinvar
  4. SYNC condensing boilers / water heaters 1.0, 1.3, 1.5 (Modbus communication board)

Boiler · Modbus register map

Lochinvar SYNC condensing boilers / water heaters 1.0, 1.3, 1.5 (Modbus communication board) Modbus register map

Updated 17 November 2026

Short answer

Lochinvar's SYNC appliances have two heat modules and talk Modbus RTU through an RS-485 communication board. The BAS writes a configuration word, an enable word, a rate or setpoint command and optional remote temperatures; it reads switch and flame states, outlet/inlet/flue temperatures for both modules, cascade power and status, blocking and lockout codes.

This page lists 54 Modbus registers for the Lochinvar SYNC condensing boilers / water heaters 1.0, 1.3, 1.5 (Modbus communication board) — 8 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Lochinvar’s own free documentation (linked below) and checked against it.

Manufacturer
Lochinvar
Model
SYNC condensing boilers / water heaters 1.0, 1.3, 1.5 (Modbus communication board)
Equipment type
Boiler
Registers
54 (8 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Also known as
SYNC 1.0, SYNC 1.3, SYNC 1.5, SYNC, Lochinvar SYNC, SYNC-MODB
Source document
Modbus and BACnet Communication Instructions - SYNC models 1.0 - 1.3 - 1.5 · SYNC-MODB 100161723_2000017706 Rev L
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Lochinvar SYNC condensing boilers / water heaters 1.0, 1.3, 1.5 (Modbus communication board)

Integration in brief

Set the address, baud and parity on the board DIP switches, choose Demand Configuration 4, 5 or 6, then write 40001 (configuration) and the commands: enable only = 40001 0x0001 + 40002 0x0001; enable + rate = 40001 0x0005 + 40002 0x0001 + 40003 rate; rate only = 40001 0x0004 + 40003. Monitor 30009-30016 and 30018-30025.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 0ConfigurationBITMAP16Configuration bitsRead/write
HR 1CoilsUINT16Enable commandRead/write
HR 20-10 Volt Input / Rate Command / Setpoint CommandUINT16Rate (%) or setpoint commandRead/write
IR 8Outlet Temperature 1UINT16Outlet temperature, module 1Read
IR 13Unit 1 Status CodeUINT16Status code, module 1Read
IR 14Unit 1 Blocking CodeUINT16Blocking code, module 1Read
IR 15Unit 1 Lockout CodeUINT16Lockout code, module 1Read
IR 22Unit 2 Status CodeUINT16Status code, module 2Read

Enable Modbus control & writes

Set Demand Configuration to 4 (enable only), 5 (enable + rate/setpoint) or 6 (rate only) under Main > Setup > Service/Setup > Demand Config. Re-send 40001 before each command.

Communication loss & watchdog

Modbus/BACnet timeout under Main > Setup > BMS: if no write with fresh values arrives in time the unit reverts to its own controls (the manual quotes 5-120 s, default 10 s, in one place and 0-120 s in another). Commands without temperatures must be refreshed at least every 4 minutes.

Byte order & addressing

Network setup

Watch out for

Lochinvar SYNC condensing boilers / water heaters 1.0, 1.3, 1.5 (Modbus communication board) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

54 of 54 shown
Lochinvar SYNC condensing boilers / water heaters 1.0, 1.3, 1.5 (Modbus communication board) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
CO0doc 00001Unit EnableEnable command from the BAS.BITRead/write0 = Off; 1 = On
CO4doc 00005Tank ThermostatDHW tank thermostat demand from the BAS.BITRead/write0 = Off; 1 = On
DI0doc 10001Manual Reset High Limit 1BITRead0 = Off; 1 = On
DI1doc 10002Flow Switch 1BITRead0 = Off; 1 = On
DI2doc 10003Gas Pressure Switch 1BITRead0 = Off; 1 = On
DI3doc 10004Louver Proving Switch 1BITRead0 = Off; 1 = On
DI4doc 10005Flap Valve 1BITRead0 = Off; 1 = On
DI5doc 10006Blocked Drain Switch 1BITRead0 = Off; 1 = On
DI6doc 10007Auto Reset High Limit 1BITRead0 = Off; 1 = On
DI7doc 10008Flame 1BITRead0 = Off; 1 = On
DI8doc 10009EnableBITRead0 = Off; 1 = On
DI9doc 10010Tank ThermostatBITRead0 = Off; 1 = On
DI16doc 10017Manual Reset High Limit 2BITRead0 = Off; 1 = On
DI17doc 10018Flow Switch 2BITRead0 = Off; 1 = On
DI18doc 10019Gas Pressure Switch 2BITRead0 = Off; 1 = On
DI19doc 10020Louver Proving Switch 2BITRead0 = Off; 1 = On
DI20doc 10021Flap Valve 2BITRead0 = Off; 1 = On
DI21doc 10022Blocked Drain Switch 2BITRead0 = Off; 1 = On
DI22doc 10023Flame 2BITRead0 = Off; 1 = On
DI32doc 10033Run-time Contacts 1BITRead0 = Off; 1 = On
DI33doc 10034Alarm Contacts 1BITRead0 = Off; 1 = On
DI34doc 10035Boiler Pump 1BITRead0 = Off; 1 = On
DI35doc 10036DHW Pump 1BITRead0 = Off; 1 = On
DI37doc 10038Gas Valve 1BITRead0 = Off; 1 = On
DI38doc 10039System PumpBITRead0 = Off; 1 = On
DI40doc 10041Run-time Contacts 2BITRead0 = Off; 1 = On
DI41doc 10042Alarm Contacts 2BITRead0 = Off; 1 = On
DI42doc 10043Boiler Pump 2BITRead0 = Off; 1 = On
DI45doc 10046Gas Valve 2BITRead0 = Off; 1 = On
DI48doc 10049Fan Power 1BITRead0 = Off; 1 = On
DI49doc 10050Fan Power 2BITRead0 = Off; 1 = On
IR0doc 30001Discrete Inputs 1-16Packed copy of discrete inputs 1-16.UINT16Read
IR1doc 30002Discrete Inputs 17-32Packed copy of discrete inputs 17-32.UINT16Read
IR2doc 30003Discrete Inputs 33-48Packed copy of discrete inputs 33-48.UINT16Read
IR5doc 30006Cascade Total PowerTotal cascade capacity (100-800 %).UINT16%Read
IR6doc 30007Cascade Current PowerCurrent cascade output (0-800 %).UINT16%Read
IR8doc 30009Outlet Temperature 1Raw is degrees C x 10 (manual example: 683 = 68.3 C).UINT16× 0.1°CRead
IR9doc 30010Inlet Temperature 1INT16× 0.1°CRead
IR10doc 30011Flue Temperature 1INT16× 0.1°CRead
IR13doc 30014Unit 1 Status CodeWhat heat module 1 is doing; 40 = lockout.UINT16Read2 = Heat demand blocked: high absolute outlet temperature; 3 = Heat demand blocked: high absolute flue temperature; 4 = Heat demand blocked: high absolute delta T (outlet - inlet); 8 = Heat demand blocked: low 24 VAC; 9 = Outdoor shutdown; 10 = Blocked: unit switched off at the display; 12 = Blocked: no correct cascade communication; 16 = Service function; 19 = DHW function, storage tank; 21 = Space heating demand from room thermostat; 22 = Space heating demand from boiler management system; 23 = Space heating demand from cascade; 30 = Heat demand from freeze protection; 32 = DHW pump delay; 33 = Space heating pump delay; 34 = No heat function (after pump delay); 40 = Lockout; 32764 = Busy updating status; 32765 = DHW blocked: no tank sensor; 32766 = Burner control(s) manually shut down; 32767 = Code not present
IR14doc 30015Unit 1 Blocking CodeWhy heat demand is blocked on module 1.UINT16Read0 = No blocking (see sub-blockings); 1 = Space heating blocking; 2 = Low 24 VAC supply; 3 = General block; 4 = Manual reset high limit open; 5 = Unit switched off (display ENTER switch); 6 = Wrong cascade communication; 7 = High delta T; 8 = High flue temperature; 9 = High outlet temperature; 10 = Service blocking; 12 = DHW blocking, high outlet temperature (storage tank); 13 = Anti-cycling time; 14 = Storage tank demand blocked by fan problem; 15 = No system sensor connected with leader control present; 16 = Fan speed limited: high outlet temperature; 17 = Fan minimum lowered: low flame current; 18 = Max fan speed limited: high delta T; 19 = Max fan speed limited: high flue temperature; 32767 = Code not present
IR15doc 30016Unit 1 Lockout CodeOnly valid while the status code is 40.UINT16Read161 = EEPROM: parameters not re-programmed by Lochinvar; 164 = EEPROM: no reset allowed (> 15 min); 166 = EEPROM: auto reset high limit / HEX over-temp switch / burner door temperature; 167 = EEPROM: blocked drain; 168 = EEPROM: louver proving; 169 = EEPROM: gas pressure switch; 170 = EEPROM: flow switch; 177 = Sensor 3 (flue) short; 178 = Sensor 3 (flue) open; 179 = Sensor 2 (inlet) short; 180 = Sensor 2 (inlet) open; 192 = Sensor 1 (outlet) short; 193 = Sensor 1 (outlet) open; 204 = CRC EEPROM failed; 205 = EEPROM programmed (display shows PP); 206 = EEPROM programming error; 207 = EEPROM write error; 229 = EEPROM: watchdog; 230 = EEPROM: fan low (should be high); 231 = EEPROM: fan high (should be low); 232 = EEPROM: no flame while running; 233 = EEPROM: no flame after ignition; 234 = EEPROM: APS and fan output at the same time; 235 = EEPROM: APS active, not closed; 236 = EEPROM: APS active, not open; 237 = EEPROM: flame out of sequence; 239 = EEPROM: gas valve relay test failed; 240 = EEPROM: manual reset high limit; 32767 = Code not present
IR17doc 30018Outlet Temperature 2UINT16× 0.1°CRead
IR18doc 30019Inlet Temperature 2INT16× 0.1°CRead
IR19doc 30020Flue Temperature 2INT16× 0.1°CRead
IR22doc 30023Unit 2 Status CodeWhat heat module 2 is doing; 40 = lockout.UINT16Read2 = Heat demand blocked: high absolute outlet temperature; 3 = Heat demand blocked: high absolute flue temperature; 4 = Heat demand blocked: high absolute delta T (outlet - inlet); 8 = Heat demand blocked: low 24 VAC; 9 = Outdoor shutdown; 10 = Blocked: unit switched off at the display; 12 = Blocked: no correct cascade communication; 16 = Service function; 19 = DHW function, storage tank; 21 = Space heating demand from room thermostat; 22 = Space heating demand from boiler management system; 23 = Space heating demand from cascade; 30 = Heat demand from freeze protection; 32 = DHW pump delay; 33 = Space heating pump delay; 34 = No heat function (after pump delay); 40 = Lockout; 32764 = Busy updating status; 32765 = DHW blocked: no tank sensor; 32766 = Burner control(s) manually shut down; 32767 = Code not present
IR23doc 30024Unit 2 Blocking CodeWhy heat demand is blocked on module 2.UINT16Read0 = No blocking (see sub-blockings); 1 = Space heating blocking; 2 = Low 24 VAC supply; 3 = General block; 4 = Manual reset high limit open; 5 = Unit switched off (display ENTER switch); 6 = Wrong cascade communication; 7 = High delta T; 8 = High flue temperature; 9 = High outlet temperature; 10 = Service blocking; 12 = DHW blocking, high outlet temperature (storage tank); 13 = Anti-cycling time; 14 = Storage tank demand blocked by fan problem; 15 = No system sensor connected with leader control present; 16 = Fan speed limited: high outlet temperature; 17 = Fan minimum lowered: low flame current; 18 = Max fan speed limited: high delta T; 19 = Max fan speed limited: high flue temperature; 32767 = Code not present
IR24doc 30025Unit 2 Lockout CodeOnly valid while the status code is 40.UINT16Read161 = EEPROM: parameters not re-programmed by Lochinvar; 164 = EEPROM: no reset allowed (> 15 min); 166 = EEPROM: auto reset high limit / HEX over-temp switch / burner door temperature; 167 = EEPROM: blocked drain; 168 = EEPROM: louver proving; 169 = EEPROM: gas pressure switch; 170 = EEPROM: flow switch; 177 = Sensor 3 (flue) short; 178 = Sensor 3 (flue) open; 179 = Sensor 2 (inlet) short; 180 = Sensor 2 (inlet) open; 192 = Sensor 1 (outlet) short; 193 = Sensor 1 (outlet) open; 204 = CRC EEPROM failed; 205 = EEPROM programmed (display shows PP); 206 = EEPROM programming error; 207 = EEPROM write error; 229 = EEPROM: watchdog; 230 = EEPROM: fan low (should be high); 231 = EEPROM: fan high (should be low); 232 = EEPROM: no flame while running; 233 = EEPROM: no flame after ignition; 234 = EEPROM: APS and fan output at the same time; 235 = EEPROM: APS active, not closed; 236 = EEPROM: APS active, not open; 237 = EEPROM: flame out of sequence; 239 = EEPROM: gas valve relay test failed; 240 = EEPROM: manual reset high limit; 32767 = Code not present
HR0doc 40001ConfigurationSelects which values the BAS supplies instead of the unit's own inputs.BITMAP16Read/writebit 0 = Unit Enable from BAS; bit 1 = Tank Thermostat from BAS; bit 2 = Rate Command / 0-10V Input / Setpoint Command from BAS; bit 3 = Tank Setpoint from BAS; bit 4 = System Supply Temperature from BAS; bit 5 = Outdoor Temperature from BAS; bit 6 = Tank Temperature from BAS; bit 7 = System Return Temperature from BAS
HR1doc 40002CoilsCommand word; the manual writes 0x0001 to enable and 0x0000 to disable.UINT16Read/write
HR2doc 400030-10 Volt Input / Rate Command / Setpoint CommandModulation % or setpoint, per the BMS Type setting (0-100).UINT16%Read/write
HR4doc 40005Tank TemperatureTank temperature supplied by the BAS.INT16× 0.1°CRead/write
HR5doc 40006Outdoor TemperatureOutdoor temperature supplied by the BAS (-40 to 60 C).INT16× 0.1°CRead/write
HR6doc 40007System Supply TemperatureSystem supply temperature supplied by the BAS.INT16× 0.1°CRead/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Lochinvar SYNC condensing boilers / water heaters 1.0, 1.3, 1.5 (Modbus communication board)

What Modbus registers does the Lochinvar SYNC condensing boilers / water heaters 1.0, 1.3, 1.5 (Modbus communication board) have?

This map lists 54 registers: 2 coils, 29 discrete inputs, 17 input registers, 6 holding registers. 8 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Lochinvar SYNC condensing boilers / water heaters 1.0, 1.3, 1.5 (Modbus communication board) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Addresses are printed Modicon-style (00001, 10001, 30001, 40001). Subtract the table base and 1 for the wire address; the manual's exception-code text confirms PDU addresses start at 0.

What are the minimum Modbus registers to integrate the Lochinvar SYNC condensing boilers / water heaters 1.0, 1.3, 1.5 (Modbus communication board)?

Start with HR 0 Configuration (Configuration bits); HR 1 Coils (Enable command); HR 2 0-10 Volt Input / Rate Command / Setpoint Command (Rate (%) or setpoint command); IR 8 Outlet Temperature 1 (Outlet temperature, module 1); IR 13 Unit 1 Status Code (Status code, module 1); IR 14 Unit 1 Blocking Code (Blocking code, module 1); IR 15 Unit 1 Lockout Code (Lockout code, module 1); IR 22 Unit 2 Status Code (Status code, module 2).

How do I enable Modbus control of the Lochinvar SYNC condensing boilers / water heaters 1.0, 1.3, 1.5 (Modbus communication board)?

Set Demand Configuration to 4 (enable only), 5 (enable + rate/setpoint) or 6 (rate only) under Main > Setup > Service/Setup > Demand Config. Re-send 40001 before each command.

What happens when the Lochinvar SYNC condensing boilers / water heaters 1.0, 1.3, 1.5 (Modbus communication board) loses Modbus communication?

Modbus/BACnet timeout under Main > Setup > BMS: if no write with fresh values arrives in time the unit reverts to its own controls (the manual quotes 5-120 s, default 10 s, in one place and 0-120 s in another). Commands without temperatures must be refreshed at least every 4 minutes.

Where is the official Lochinvar SYNC condensing boilers / water heaters 1.0, 1.3, 1.5 (Modbus communication board) Modbus documentation?

The source is Modbus and BACnet Communication Instructions - SYNC models 1.0 - 1.3 - 1.5 (SYNC-MODB 100161723_2000017706 Rev L), published free by Lochinvar at https://assets.lochinvar.com/damroot/Original/10014/594260SYNC-MODB_100161723_2000017706__REV%20L_BACNET.pdf.

More Lochinvar Modbus register maps

Other boilers & water heaters register maps

All boilers & water heaters Modbus register maps →

Source: Modbus and BACnet Communication Instructions - SYNC models 1.0 - 1.3 - 1.5 · SYNC-MODB 100161723_2000017706 Rev L. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.