- SYNC condensing boilers / water heaters 1.0, 1.3, 1.5 (Modbus communication board)
Boiler · Modbus register map
Lochinvar SYNC condensing boilers / water heaters 1.0, 1.3, 1.5 (Modbus communication board) Modbus register map
Updated 17 November 2026
Lochinvar's SYNC appliances have two heat modules and talk Modbus RTU through an RS-485 communication board. The BAS writes a configuration word, an enable word, a rate or setpoint command and optional remote temperatures; it reads switch and flame states, outlet/inlet/flue temperatures for both modules, cascade power and status, blocking and lockout codes.
This page lists 54 Modbus registers for the Lochinvar SYNC condensing boilers / water heaters 1.0, 1.3, 1.5 (Modbus communication board) — 8 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Lochinvar’s own free documentation (linked below) and checked against it.
- Manufacturer
- Lochinvar
- Model
- SYNC condensing boilers / water heaters 1.0, 1.3, 1.5 (Modbus communication board)
- Equipment type
- Boiler
- Registers
- 54 (8 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Also known as
- SYNC 1.0, SYNC 1.3, SYNC 1.5, SYNC, Lochinvar SYNC, SYNC-MODB
Integration notes: Lochinvar SYNC condensing boilers / water heaters 1.0, 1.3, 1.5 (Modbus communication board)
Set the address, baud and parity on the board DIP switches, choose Demand Configuration 4, 5 or 6, then write 40001 (configuration) and the commands: enable only = 40001 0x0001 + 40002 0x0001; enable + rate = 40001 0x0005 + 40002 0x0001 + 40003 rate; rate only = 40001 0x0004 + 40003. Monitor 30009-30016 and 30018-30025.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 0 | Configuration | BITMAP16 | Configuration bits | Read/write |
| HR 1 | Coils | UINT16 | Enable command | Read/write |
| HR 2 | 0-10 Volt Input / Rate Command / Setpoint Command | UINT16 | Rate (%) or setpoint command | Read/write |
| IR 8 | Outlet Temperature 1 | UINT16 | Outlet temperature, module 1 | Read |
| IR 13 | Unit 1 Status Code | UINT16 | Status code, module 1 | Read |
| IR 14 | Unit 1 Blocking Code | UINT16 | Blocking code, module 1 | Read |
| IR 15 | Unit 1 Lockout Code | UINT16 | Lockout code, module 1 | Read |
| IR 22 | Unit 2 Status Code | UINT16 | Status code, module 2 | Read |
Enable Modbus control & writes
Set Demand Configuration to 4 (enable only), 5 (enable + rate/setpoint) or 6 (rate only) under Main > Setup > Service/Setup > Demand Config. Re-send 40001 before each command.
Communication loss & watchdog
Modbus/BACnet timeout under Main > Setup > BMS: if no write with fresh values arrives in time the unit reverts to its own controls (the manual quotes 5-120 s, default 10 s, in one place and 0-120 s in another). Commands without temperatures must be refreshed at least every 4 minutes.
Byte order & addressing
- Modicon addressing: 30009 is input register 8 on the wire.
- Temperatures are degrees C x 10.
- A setpoint sent through 40003 is the 0-10 V equivalent percentage interpolated from the BMS low/high setpoint parameters, not degrees.
- Read the lockout code only when the matching status code is 40.
Network setup
- DIP switches 1-8: Modbus address (binary sum, 1-247).
- DIP switch 9: 0 = 9600 baud, 1 = 19200 baud.
- DIP switch 10: 0 = no parity with 2 stop bits, 1 = even parity with 1 stop bit.
- RTU only; check 120 ohm termination.
Watch out for
- Board LED D7: 1 s on / 1 s off = normal; 1.5 s on / 0.5 s off = no Modbus traffic; 0.5 s on / 1.5 s off = no burner-control communication.
- Module 2 points (x017-x050, 30017-30025) only apply to the second heat module.
Lochinvar SYNC condensing boilers / water heaters 1.0, 1.3, 1.5 (Modbus communication board) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 0doc 00001 | Unit Enable | Enable command from the BAS. | BIT | Read/write | 0 = Off; 1 = On | |||
| CO | 4doc 00005 | Tank Thermostat | DHW tank thermostat demand from the BAS. | BIT | Read/write | 0 = Off; 1 = On | |||
| DI | 0doc 10001 | Manual Reset High Limit 1 | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 1doc 10002 | Flow Switch 1 | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 2doc 10003 | Gas Pressure Switch 1 | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 3doc 10004 | Louver Proving Switch 1 | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 4doc 10005 | Flap Valve 1 | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 5doc 10006 | Blocked Drain Switch 1 | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 6doc 10007 | Auto Reset High Limit 1 | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 7doc 10008 | Flame 1 | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 8doc 10009 | Enable | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 9doc 10010 | Tank Thermostat | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 16doc 10017 | Manual Reset High Limit 2 | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 17doc 10018 | Flow Switch 2 | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 18doc 10019 | Gas Pressure Switch 2 | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 19doc 10020 | Louver Proving Switch 2 | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 20doc 10021 | Flap Valve 2 | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 21doc 10022 | Blocked Drain Switch 2 | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 22doc 10023 | Flame 2 | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 32doc 10033 | Run-time Contacts 1 | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 33doc 10034 | Alarm Contacts 1 | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 34doc 10035 | Boiler Pump 1 | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 35doc 10036 | DHW Pump 1 | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 37doc 10038 | Gas Valve 1 | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 38doc 10039 | System Pump | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 40doc 10041 | Run-time Contacts 2 | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 41doc 10042 | Alarm Contacts 2 | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 42doc 10043 | Boiler Pump 2 | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 45doc 10046 | Gas Valve 2 | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 48doc 10049 | Fan Power 1 | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 49doc 10050 | Fan Power 2 | BIT | Read | 0 = Off; 1 = On | ||||
| IR | 0doc 30001 | Discrete Inputs 1-16 | Packed copy of discrete inputs 1-16. | UINT16 | Read | ||||
| IR | 1doc 30002 | Discrete Inputs 17-32 | Packed copy of discrete inputs 17-32. | UINT16 | Read | ||||
| IR | 2doc 30003 | Discrete Inputs 33-48 | Packed copy of discrete inputs 33-48. | UINT16 | Read | ||||
| IR | 5doc 30006 | Cascade Total Power | Total cascade capacity (100-800 %). | UINT16 | % | Read | |||
| IR | 6doc 30007 | Cascade Current Power | Current cascade output (0-800 %). | UINT16 | % | Read | |||
| IR | 8doc 30009 | Outlet Temperature 1 | Raw is degrees C x 10 (manual example: 683 = 68.3 C). | UINT16 | × 0.1 | °C | Read | ||
| IR | 9doc 30010 | Inlet Temperature 1 | INT16 | × 0.1 | °C | Read | |||
| IR | 10doc 30011 | Flue Temperature 1 | INT16 | × 0.1 | °C | Read | |||
| IR | 13doc 30014 | Unit 1 Status Code | What heat module 1 is doing; 40 = lockout. | UINT16 | Read | 2 = Heat demand blocked: high absolute outlet temperature; 3 = Heat demand blocked: high absolute flue temperature; 4 = Heat demand blocked: high absolute delta T (outlet - inlet); 8 = Heat demand blocked: low 24 VAC; 9 = Outdoor shutdown; 10 = Blocked: unit switched off at the display; 12 = Blocked: no correct cascade communication; 16 = Service function; 19 = DHW function, storage tank; 21 = Space heating demand from room thermostat; 22 = Space heating demand from boiler management system; 23 = Space heating demand from cascade; 30 = Heat demand from freeze protection; 32 = DHW pump delay; 33 = Space heating pump delay; 34 = No heat function (after pump delay); 40 = Lockout; 32764 = Busy updating status; 32765 = DHW blocked: no tank sensor; 32766 = Burner control(s) manually shut down; 32767 = Code not present | |||
| IR | 14doc 30015 | Unit 1 Blocking Code | Why heat demand is blocked on module 1. | UINT16 | Read | 0 = No blocking (see sub-blockings); 1 = Space heating blocking; 2 = Low 24 VAC supply; 3 = General block; 4 = Manual reset high limit open; 5 = Unit switched off (display ENTER switch); 6 = Wrong cascade communication; 7 = High delta T; 8 = High flue temperature; 9 = High outlet temperature; 10 = Service blocking; 12 = DHW blocking, high outlet temperature (storage tank); 13 = Anti-cycling time; 14 = Storage tank demand blocked by fan problem; 15 = No system sensor connected with leader control present; 16 = Fan speed limited: high outlet temperature; 17 = Fan minimum lowered: low flame current; 18 = Max fan speed limited: high delta T; 19 = Max fan speed limited: high flue temperature; 32767 = Code not present | |||
| IR | 15doc 30016 | Unit 1 Lockout Code | Only valid while the status code is 40. | UINT16 | Read | 161 = EEPROM: parameters not re-programmed by Lochinvar; 164 = EEPROM: no reset allowed (> 15 min); 166 = EEPROM: auto reset high limit / HEX over-temp switch / burner door temperature; 167 = EEPROM: blocked drain; 168 = EEPROM: louver proving; 169 = EEPROM: gas pressure switch; 170 = EEPROM: flow switch; 177 = Sensor 3 (flue) short; 178 = Sensor 3 (flue) open; 179 = Sensor 2 (inlet) short; 180 = Sensor 2 (inlet) open; 192 = Sensor 1 (outlet) short; 193 = Sensor 1 (outlet) open; 204 = CRC EEPROM failed; 205 = EEPROM programmed (display shows PP); 206 = EEPROM programming error; 207 = EEPROM write error; 229 = EEPROM: watchdog; 230 = EEPROM: fan low (should be high); 231 = EEPROM: fan high (should be low); 232 = EEPROM: no flame while running; 233 = EEPROM: no flame after ignition; 234 = EEPROM: APS and fan output at the same time; 235 = EEPROM: APS active, not closed; 236 = EEPROM: APS active, not open; 237 = EEPROM: flame out of sequence; 239 = EEPROM: gas valve relay test failed; 240 = EEPROM: manual reset high limit; 32767 = Code not present | |||
| IR | 17doc 30018 | Outlet Temperature 2 | UINT16 | × 0.1 | °C | Read | |||
| IR | 18doc 30019 | Inlet Temperature 2 | INT16 | × 0.1 | °C | Read | |||
| IR | 19doc 30020 | Flue Temperature 2 | INT16 | × 0.1 | °C | Read | |||
| IR | 22doc 30023 | Unit 2 Status Code | What heat module 2 is doing; 40 = lockout. | UINT16 | Read | 2 = Heat demand blocked: high absolute outlet temperature; 3 = Heat demand blocked: high absolute flue temperature; 4 = Heat demand blocked: high absolute delta T (outlet - inlet); 8 = Heat demand blocked: low 24 VAC; 9 = Outdoor shutdown; 10 = Blocked: unit switched off at the display; 12 = Blocked: no correct cascade communication; 16 = Service function; 19 = DHW function, storage tank; 21 = Space heating demand from room thermostat; 22 = Space heating demand from boiler management system; 23 = Space heating demand from cascade; 30 = Heat demand from freeze protection; 32 = DHW pump delay; 33 = Space heating pump delay; 34 = No heat function (after pump delay); 40 = Lockout; 32764 = Busy updating status; 32765 = DHW blocked: no tank sensor; 32766 = Burner control(s) manually shut down; 32767 = Code not present | |||
| IR | 23doc 30024 | Unit 2 Blocking Code | Why heat demand is blocked on module 2. | UINT16 | Read | 0 = No blocking (see sub-blockings); 1 = Space heating blocking; 2 = Low 24 VAC supply; 3 = General block; 4 = Manual reset high limit open; 5 = Unit switched off (display ENTER switch); 6 = Wrong cascade communication; 7 = High delta T; 8 = High flue temperature; 9 = High outlet temperature; 10 = Service blocking; 12 = DHW blocking, high outlet temperature (storage tank); 13 = Anti-cycling time; 14 = Storage tank demand blocked by fan problem; 15 = No system sensor connected with leader control present; 16 = Fan speed limited: high outlet temperature; 17 = Fan minimum lowered: low flame current; 18 = Max fan speed limited: high delta T; 19 = Max fan speed limited: high flue temperature; 32767 = Code not present | |||
| IR | 24doc 30025 | Unit 2 Lockout Code | Only valid while the status code is 40. | UINT16 | Read | 161 = EEPROM: parameters not re-programmed by Lochinvar; 164 = EEPROM: no reset allowed (> 15 min); 166 = EEPROM: auto reset high limit / HEX over-temp switch / burner door temperature; 167 = EEPROM: blocked drain; 168 = EEPROM: louver proving; 169 = EEPROM: gas pressure switch; 170 = EEPROM: flow switch; 177 = Sensor 3 (flue) short; 178 = Sensor 3 (flue) open; 179 = Sensor 2 (inlet) short; 180 = Sensor 2 (inlet) open; 192 = Sensor 1 (outlet) short; 193 = Sensor 1 (outlet) open; 204 = CRC EEPROM failed; 205 = EEPROM programmed (display shows PP); 206 = EEPROM programming error; 207 = EEPROM write error; 229 = EEPROM: watchdog; 230 = EEPROM: fan low (should be high); 231 = EEPROM: fan high (should be low); 232 = EEPROM: no flame while running; 233 = EEPROM: no flame after ignition; 234 = EEPROM: APS and fan output at the same time; 235 = EEPROM: APS active, not closed; 236 = EEPROM: APS active, not open; 237 = EEPROM: flame out of sequence; 239 = EEPROM: gas valve relay test failed; 240 = EEPROM: manual reset high limit; 32767 = Code not present | |||
| HR | 0doc 40001 | Configuration | Selects which values the BAS supplies instead of the unit's own inputs. | BITMAP16 | Read/write | bit 0 = Unit Enable from BAS; bit 1 = Tank Thermostat from BAS; bit 2 = Rate Command / 0-10V Input / Setpoint Command from BAS; bit 3 = Tank Setpoint from BAS; bit 4 = System Supply Temperature from BAS; bit 5 = Outdoor Temperature from BAS; bit 6 = Tank Temperature from BAS; bit 7 = System Return Temperature from BAS | |||
| HR | 1doc 40002 | Coils | Command word; the manual writes 0x0001 to enable and 0x0000 to disable. | UINT16 | Read/write | ||||
| HR | 2doc 40003 | 0-10 Volt Input / Rate Command / Setpoint Command | Modulation % or setpoint, per the BMS Type setting (0-100). | UINT16 | % | Read/write | |||
| HR | 4doc 40005 | Tank Temperature | Tank temperature supplied by the BAS. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 5doc 40006 | Outdoor Temperature | Outdoor temperature supplied by the BAS (-40 to 60 C). | INT16 | × 0.1 | °C | Read/write | ||
| HR | 6doc 40007 | System Supply Temperature | System supply temperature supplied by the BAS. | INT16 | × 0.1 | °C | Read/write |
Notes on this map
- Temperatures: the conversion section says the unit passes temperatures in degrees C and the value must be divided by 10 (examples: 26.7 C sent as 267; outlet 683 = 68.3 C). Scale 0.1 is applied to the temperature registers with 0.1 resolution in the map.
- Left out: System/Cascade Setpoint (30004), Outlet Setpoint 1 and 2 (30008, 30017) and Tank Setpoint (40004). The map gives them a 0.5 C resolution while the conversion text says temperatures are C x 10, so their scaling is not settled.
- Left out: Firing Rate 1 and 2 (30012, 30021). The map prints a 0.1 resolution for a 0-100 % value but no example confirms whether the raw value is % or % x 10.
- Signed types: inlet, flue and BAS-supplied temperatures have negative minimums in the map and are listed as INT16; the manual itself only says 16-bit word.
- Configuration bit 7 names a System Return Temperature, but the SYNC map lists no register for it (it stops at 40007).
- The DHW remote-control example table labels 40004 as 'Rate Command'; the memory map has the rate command at 40003 and the tank setpoint at 40004.
- Input registers 30001-30003 are packed copies of the discrete inputs; the bit order is not stated, so they are UINT16. Use the discrete inputs instead.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Lochinvar SYNC condensing boilers / water heaters 1.0, 1.3, 1.5 (Modbus communication board)
What Modbus registers does the Lochinvar SYNC condensing boilers / water heaters 1.0, 1.3, 1.5 (Modbus communication board) have?
This map lists 54 registers: 2 coils, 29 discrete inputs, 17 input registers, 6 holding registers. 8 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Lochinvar SYNC condensing boilers / water heaters 1.0, 1.3, 1.5 (Modbus communication board) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Addresses are printed Modicon-style (00001, 10001, 30001, 40001). Subtract the table base and 1 for the wire address; the manual's exception-code text confirms PDU addresses start at 0.
What are the minimum Modbus registers to integrate the Lochinvar SYNC condensing boilers / water heaters 1.0, 1.3, 1.5 (Modbus communication board)?
Start with HR 0 Configuration (Configuration bits); HR 1 Coils (Enable command); HR 2 0-10 Volt Input / Rate Command / Setpoint Command (Rate (%) or setpoint command); IR 8 Outlet Temperature 1 (Outlet temperature, module 1); IR 13 Unit 1 Status Code (Status code, module 1); IR 14 Unit 1 Blocking Code (Blocking code, module 1); IR 15 Unit 1 Lockout Code (Lockout code, module 1); IR 22 Unit 2 Status Code (Status code, module 2).
How do I enable Modbus control of the Lochinvar SYNC condensing boilers / water heaters 1.0, 1.3, 1.5 (Modbus communication board)?
Set Demand Configuration to 4 (enable only), 5 (enable + rate/setpoint) or 6 (rate only) under Main > Setup > Service/Setup > Demand Config. Re-send 40001 before each command.
What happens when the Lochinvar SYNC condensing boilers / water heaters 1.0, 1.3, 1.5 (Modbus communication board) loses Modbus communication?
Modbus/BACnet timeout under Main > Setup > BMS: if no write with fresh values arrives in time the unit reverts to its own controls (the manual quotes 5-120 s, default 10 s, in one place and 0-120 s in another). Commands without temperatures must be refreshed at least every 4 minutes.
Where is the official Lochinvar SYNC condensing boilers / water heaters 1.0, 1.3, 1.5 (Modbus communication board) Modbus documentation?
The source is Modbus and BACnet Communication Instructions - SYNC models 1.0 - 1.3 - 1.5 (SYNC-MODB 100161723_2000017706 Rev L), published free by Lochinvar at https://assets.lochinvar.com/damroot/Original/10014/594260SYNC-MODB_100161723_2000017706__REV%20L_BACNET.pdf.
More Lochinvar Modbus register maps
- Boiler (commercial water heater)
Lochinvar Armor 1250-4000 commercial water heaters, Series 100 & 101 (Modbus communication board)
Lochinvar Armor water heaters, models 1250-4000, Series 100 and 101, with the SMART SYSTEM control and Modbus/BACnet communication board, per 100305786_2000558371 Rev C.
Also known as: Armor 1250, Armor 1500, Armor 2000, Armor 2500, Armor 3000, Armor 3500, Armor 4000, AWH, AWH1250, AWH4000, SMART SYSTEM - Boiler
Lochinvar Copper-fin II / IIE boiler, water heater and pool heater (ModBus communication board)
Lochinvar Copper-fin II/IIE boilers and water heaters 402-2072 and pool heaters 502-2072 with the MTR-01 ModBus board, per manual 100160882 Rev G.
Also known as: Copper-fin II, Copper-fin IIE, CBX, CFX, CHX, CPX, C(F,H,P)X, Copperfin - Boiler
Lochinvar Crest / Crest with Hellcat boilers (ModBus communication board)
Lochinvar Crest FB/OF 751-6001 and FCB1000-6000 (including Crest with Hellcat) with the ModBus communication board.
Also known as: Crest, Crest FB751-6001, Crest OF751-6001, Crest FCB1000-6000, Hellcat, MTR-01 - Boiler / water heater
Lochinvar Knight / Armor / Wall Mount boilers (ModBus communication board)
Knight 81-286, Knight XL 400-1000, Armor 151-1000, Outdoor Knight/Knight XL/Armor, AQUAS 400-801, FTXL 400-1000, Wall Mount 51-211, Wall Hung 55-399, Wall Mount Armor 125-200 and Shield 125-500 with the Lochinvar ModBus communication board.
Also known as: Knight, Knight XL, Outdoor Knight, Outdoor Knight XL, Armor, Outdoor Armor, Wall Mount Armor, Knight Wall Mount, Knight Wall Hung, AQUAS, FTXL, Shield - Boiler (electric)
Lochinvar Lectrus KEB electric boilers / water heaters 0015-0150 (Modbus communication board)
Lochinvar Lectrus KEB 0015-0150 electric boilers/water heaters with the Modbus/BACnet communication board, per MODB-I-O-KEB Rev A.
Also known as: Lectrus, KEB0015, KEB0150, KEB 0015-0150, MODB-I-O-KEB, Lochinvar Lectrus - Boiler
Lochinvar Power-fin PBX / PFX boilers and water heaters 502-1302, 1501-2001 (Modbus communication board)
Lochinvar Power-fin PB/PF 'X' models 502-1302 and 1501-2001 with the SMART SYSTEM control and Modbus/BACnet communication board, per PBX-PFX-MODB Rev D.
Also known as: Power-fin, Power-Fin, PBX502, PBX1302, PBX1501, PBX2001, PFX502, PFX2001, PBX-PFX-MODB, SMART SYSTEM
Other boilers & water heaters register maps
- Boiler / heating system controller
Buderus Logamatic 5000 boiler and system controller (Modbus TCP, datapoint list 4.0)
Buderus Logamatic 5313 and 5311 (and the Bosch Control 8313/8311 equivalents) acting as master, firmware 1.3 or later with the 4.0 datapoint list; addresses for slave controllers differ.
Also known as: Logamatic 5313, Logamatic 5311, Bosch Control 8313, Bosch Control 8311, Control 8000, BCT 531, Logamatic 5000 Modbus - Boiler (water heater controller)
PVI Industries TempTrac water heater electronic controller (Modbus RTU)
PVI TempTrac thermostatic controllers (firmware 0.3 and 0.5) on RS-485 Modbus RTU, per PVI manual PV500-42 (06/2014).
Also known as: TempTrac, PV500-42 - Boiler (burner management / fuel-air ratio control)
Fireye PPC4000 parallel positioning burner control (Modbus RTU)
Fireye PPC4000 parallel positioning controls showing engineering code EC08 or later, per bulletin MOD-4001 (September 13, 2012). The later NXF4000 is not covered.
Also known as: PPC-4000, PPC4000, MOD-4001 - Boiler / water heater controller
AERCO C-More Boiler Controller (Benchmark / KC series)
AERCO C-More boiler controllers (software 2.00 or later) used on Benchmark and KC Series boilers and water heaters, as a Modbus RTU slave.
Also known as: C-More, Benchmark, KC1000, KC Series, Benchmark boiler, Benchmark water heater - Boiler controller
Patterson-Kelley NURO boiler controller (Modbus BMS port)
Patterson-Kelley NURO boiler control, Modbus register map from Appendix A of the NURO Advanced Users Guide.
Also known as: Patterson-Kelley NURO, Harsco Industrial Patterson-Kelley NURO - Boiler (burner / boiler controller)
Cleaver-Brooks CB Falcon hydronic / steam boiler control
Cleaver-Brooks CB Falcon boiler controls on the MB1 or MB2 Modbus port, per manual 750-308.
Also known as: CB Falcon, Falcon boiler control
All boilers & water heaters Modbus register maps →
Source: Modbus and BACnet Communication Instructions - SYNC models 1.0 - 1.3 - 1.5 · SYNC-MODB 100161723_2000017706 Rev L. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.