- Armor 1250-4000 commercial water heaters, Series 100 & 101 (Modbus communication board)
Boiler (commercial water heater) · Modbus register map
Lochinvar Armor 1250-4000 commercial water heaters, Series 100 & 101 (Modbus communication board) Modbus register map
Updated 17 November 2026
The large Armor water heaters (1250-4000 MBH) use the SMART SYSTEM control and a Modbus RTU communication board on RS-485. The BAS can write a configuration word, an enable word, a rate or setpoint command and a remote tank temperature; it reads switch and flame states, outlet/inlet/flue temperatures, firing rate, cascade power and the status, blocking and lockout codes of the unit and its cascade members.
This page lists 42 Modbus registers for the Lochinvar Armor 1250-4000 commercial water heaters, Series 100 & 101 (Modbus communication board) — 6 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Lochinvar’s own free documentation (linked below) and checked against it.
- Manufacturer
- Lochinvar
- Model
- Armor 1250-4000 commercial water heaters, Series 100 & 101 (Modbus communication board)
- Equipment type
- Boiler (commercial water heater)
- Registers
- 42 (6 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Also known as
- Armor 1250, Armor 1500, Armor 2000, Armor 2500, Armor 3000, Armor 3500, Armor 4000, AWH, AWH1250, AWH4000, SMART SYSTEM
Integration notes: Lochinvar Armor 1250-4000 commercial water heaters, Series 100 & 101 (Modbus communication board)
Set address, baud and parity on the board DIP switches, set parameter H5 ModBus to Active, then write 40001 and the commands: enable only = 40001 0x0001 + 40002 0x0001; enable + BMS = 40001 0x0005 + 40002 0x0001 + 40003 rate; BMS only = 40001 0x0004 + 40003. Monitor 30009-30016.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 0 | Configuration | BITMAP16 | Configuration bits | Read/write |
| HR 1 | Coils | UINT16 | Enable command | Read/write |
| HR 2 | 0-10 Volt Input / Rate Command / Setpoint Command | UINT16 | Rate (%) or setpoint command | Read/write |
| IR 8 | Outlet Temperature | UINT16 | Outlet temperature | Read |
| IR 11 | Firing Rate | UINT16 | Firing rate | Read |
| IR 13 | Status Code | UINT16 | Status code | Read |
| IR 14 | Blocking Code | UINT16 | Blocking code | Read |
| IR 15 | Lockout Code | UINT16 | Lockout code | Read |
Enable Modbus control & writes
Monitoring works with the default control setup. To send commands set parameter H5 ModBus to Active (see the Armor service manual), choose the enable/BMS demand configuration, and re-send 40001 before each command.
Communication loss & watchdog
Two timers: a BAS-supplied tank temperature must be refreshed within parameter H6 ModBus Time (the operation section gives 1-255 s; the configuration section says 5-120 s, default 10 s); all other commands time out after a fixed 4 minutes, after which the control reverts to its local inputs.
Byte order & addressing
- Modicon addressing: 30009 is input register 8 on the wire.
- Temperatures are degrees C x 10.
- A setpoint sent through 40003 is the 0-10 V equivalent percentage interpolated from the BMS low/high setpoint parameters, not degrees.
- Read the lockout code only when the status code is 40.
Network setup
- DIP switches 1-8: Modbus address (binary sum, 1-247).
- DIP switch 9: 0 = 9600 baud, 1 = 19200 baud.
- DIP switch 10: 0 = no parity with 2 stop bits, 1 = even parity with 1 stop bit.
- RTU only; check 120 ohm termination.
Watch out for
- Board LED D7: 1 s bright / 1 s dim = normal; 1.5 s on / 0.5 s off = no Modbus traffic; 0.5 s on / 1.5 s off = no burner-control communication.
Lochinvar Armor 1250-4000 commercial water heaters, Series 100 & 101 (Modbus communication board) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 0doc 00001 | Enable | Enable command from the BAS. | BIT | Read/write | 0 = Off; 1 = On | |||
| CO | 4doc 00005 | Tank Thermostat | DHW tank thermostat demand from the BAS. | BIT | Read/write | 0 = Off; 1 = On | |||
| DI | 0doc 10001 | Manual Reset High Limit | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 1doc 10002 | Flow Switch | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 2doc 10003 | Gas Pressure Switch | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 3doc 10004 | Louver Proving Switch | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 5doc 10006 | Blocked Drain Switch | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 6doc 10007 | Auto Reset High Limit | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 7doc 10008 | Flame | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 8doc 10009 | Enable | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 9doc 10010 | Tank Thermostat | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 32doc 10033 | Run-time Contacts | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 33doc 10034 | Alarm Contacts | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 35doc 10036 | DHW Pump | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 37doc 10038 | Gas Valve | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 38doc 10039 | Recirculation Pump | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 48doc 10049 | Blower Power | BIT | Read | 0 = Off; 1 = On | ||||
| IR | 0doc 30001 | Discrete Inputs 1-16 | Packed copy of discrete inputs 1-16. | UINT16 | Read | ||||
| IR | 1doc 30002 | Discrete Inputs 17-32 | Packed copy of discrete inputs 17-32. | UINT16 | Read | ||||
| IR | 2doc 30003 | Discrete Inputs 33-48 | Packed copy of discrete inputs 33-48. | UINT16 | Read | ||||
| IR | 5doc 30006 | Cascade Total Power | Total cascade capacity (100-800 %). | UINT16 | % | Read | |||
| IR | 6doc 30007 | Cascade Current Power | Current cascade output (0-800 %). | UINT16 | % | Read | |||
| IR | 8doc 30009 | Outlet Temperature | Raw is degrees C x 10. | UINT16 | × 0.1 | °C | Read | ||
| IR | 9doc 30010 | Inlet Temperature | INT16 | × 0.1 | °C | Read | |||
| IR | 10doc 30011 | Flue Temperature | INT16 | × 0.1 | °C | Read | |||
| IR | 11doc 30012 | Firing Rate | 0-100 %. | UINT16 | % | Read | |||
| IR | 13doc 30014 | Status Code | What the unit is doing; 40 = lockout. | UINT16 | Read | 2 = Heat demand blocked: high outlet temperature; 3 = Heat demand blocked: high flue temperature; 4 = Heat demand blocked: high delta T; 7 = Heat demand blocked: different personality plug code; 8 = Heat demand blocked: low 24 VAC; 10 = Blocked: switched off at the display; 16 = Service mode active; 18 = Water heater DHW demand active; 23 = Heat demand from cascade; 30 = Freeze protection heat demand; 32 = DHW pump delay; 34 = Standby; 40 = Lockout | |||
| IR | 14doc 30015 | Blocking Code | Why heat demand is blocked. | UINT16 | Read | 0 = No blocking; 1 = Flow switch open; 5 = Low 24 VAC supply; 6 = Manual reset high limit; 8 = Appliance turned off; 10 = High delta T; 11 = High outlet temperature; 12 = Anti-cycling; 13 = Different personality plug setting; 15 = High flue temperature | |||
| IR | 15doc 30016 | Lockout Code | Only valid while the status code is 40. | UINT16 | Read | 163 = Different personality plug; 164 = Flame current circuit test failed; 166 = Auto reset high limit; 167 = Blocked drain switch open; 168 = Louver proving switch open; 169 = Gas pressure switch open; 170 = Flow switch open; 178 = Flue sensor open; 179 = Inlet sensor shorted; 180 = Inlet sensor open; 192 = Outlet sensor shorted; 193 = Outlet sensor open; 204 = EEPROM CRC fault; 205 = EEPROM programmed; 206 = EEPROM programming error; 207 = EEPROM error; 229 = Watchdog; 230 = Low fan speed; 231 = High fan speed; 232 = No flame while running; 233 = No flame at ignition; 237 = Flame out of sequence; 240 = Manual reset high limit | |||
| IR | 25doc 30026 | Discrete Inputs 49-64 | Packed copy of discrete inputs 49-64. | UINT16 | Read | ||||
| IR | 26doc 30027 | Lockout Code Leader | Lockout code of the cascade leader. | UINT16 | Read | ||||
| IR | 27doc 30028 | Lockout Code Member 1 | Lockout code of cascade member 1. | UINT16 | Read | ||||
| IR | 28doc 30029 | Lockout Code Member 2 | Lockout code of cascade member 2. | UINT16 | Read | ||||
| IR | 29doc 30030 | Lockout Code Member 3 | Lockout code of cascade member 3. | UINT16 | Read | ||||
| IR | 30doc 30031 | Lockout Code Member 4 | Lockout code of cascade member 4. | UINT16 | Read | ||||
| IR | 31doc 30032 | Lockout Code Member 5 | Lockout code of cascade member 5. | UINT16 | Read | ||||
| IR | 32doc 30033 | Lockout Code Member 6 | Lockout code of cascade member 6. | UINT16 | Read | ||||
| IR | 33doc 30034 | Lockout Code Member 7 | Lockout code of cascade member 7. | UINT16 | Read | ||||
| HR | 0doc 40001 | Configuration | Selects which values the BAS supplies instead of the unit's own inputs. | BITMAP16 | Read/write | bit 0 = Enable from BAS; bit 1 = Tank Thermostat from BAS; bit 2 = Rate Command / 0-10V Input / Setpoint Command from BAS; bit 3 = Tank Setpoint from BAS; bit 6 = Tank Temperature from BAS | |||
| HR | 1doc 40002 | Coils | Command word; the manual writes 0x0001 to enable and 0x0000 to disable. | UINT16 | Read/write | ||||
| HR | 2doc 40003 | 0-10 Volt Input / Rate Command / Setpoint Command | Modulation % or setpoint, per the BMS type setting (0-100). | UINT16 | % | Read/write | |||
| HR | 4doc 40005 | Tank Temperature | Tank temperature supplied by the BAS. | INT16 | × 0.1 | °C | Read/write |
Notes on this map
- Temperatures: the conversion section says the Armor passes temperatures in degrees C and the value must be divided by 10. Scale 0.1 is applied to the temperature registers with 0.1 resolution in the map.
- Left out: System/Cascade Setpoint (30004) and Tank Setpoint (40004). The map gives them a 0.5 C resolution while the conversion text says temperatures are C x 10, so their scaling is not settled.
- Signed types: inlet, flue and tank temperatures have negative minimums in the map and are listed as INT16; the manual itself only says 16-bit word.
- Input registers 30001-30003 and 30026 are packed copies of the discrete inputs; the bit order is not stated, so they are UINT16. Use the discrete inputs instead.
- The smaller Armor 151-1000 uses a different manual; see the Knight/Armor map.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Lochinvar Armor 1250-4000 commercial water heaters, Series 100 & 101 (Modbus communication board)
What Modbus registers does the Lochinvar Armor 1250-4000 commercial water heaters, Series 100 & 101 (Modbus communication board) have?
This map lists 42 registers: 2 coils, 15 discrete inputs, 21 input registers, 4 holding registers. 6 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Lochinvar Armor 1250-4000 commercial water heaters, Series 100 & 101 (Modbus communication board) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Addresses are printed Modicon-style (00001, 10001, 30001, 40001). Subtract the table base and 1 for the wire address; the manual's exception-code text confirms PDU addresses start at 0.
What are the minimum Modbus registers to integrate the Lochinvar Armor 1250-4000 commercial water heaters, Series 100 & 101 (Modbus communication board)?
Start with HR 0 Configuration (Configuration bits); HR 1 Coils (Enable command); HR 2 0-10 Volt Input / Rate Command / Setpoint Command (Rate (%) or setpoint command); IR 8 Outlet Temperature (Outlet temperature); IR 11 Firing Rate (Firing rate); IR 13 Status Code (Status code); IR 14 Blocking Code (Blocking code); IR 15 Lockout Code (Lockout code).
How do I enable Modbus control of the Lochinvar Armor 1250-4000 commercial water heaters, Series 100 & 101 (Modbus communication board)?
Monitoring works with the default control setup. To send commands set parameter H5 ModBus to Active (see the Armor service manual), choose the enable/BMS demand configuration, and re-send 40001 before each command.
What happens when the Lochinvar Armor 1250-4000 commercial water heaters, Series 100 & 101 (Modbus communication board) loses Modbus communication?
Two timers: a BAS-supplied tank temperature must be refreshed within parameter H6 ModBus Time (the operation section gives 1-255 s; the configuration section says 5-120 s, default 10 s); all other commands time out after a fixed 4 minutes, after which the control reverts to its local inputs.
Where is the official Lochinvar Armor 1250-4000 commercial water heaters, Series 100 & 101 (Modbus communication board) Modbus documentation?
The source is ModBus and BACnet Communication Instructions - Armor Models 1250-4000, Series 100 & 101 (100305786_2000558371 Rev C), published free by Lochinvar at https://assets.lochinvar.com/damroot/Original/10014/100305786_2000558371_Rev%20C_AWH%20Modbus%20Bacnet%20Manual%20(52880).pdf.
More Lochinvar Modbus register maps
- Boiler
Lochinvar Copper-fin II / IIE boiler, water heater and pool heater (ModBus communication board)
Lochinvar Copper-fin II/IIE boilers and water heaters 402-2072 and pool heaters 502-2072 with the MTR-01 ModBus board, per manual 100160882 Rev G.
Also known as: Copper-fin II, Copper-fin IIE, CBX, CFX, CHX, CPX, C(F,H,P)X, Copperfin - Boiler
Lochinvar Crest / Crest with Hellcat boilers (ModBus communication board)
Lochinvar Crest FB/OF 751-6001 and FCB1000-6000 (including Crest with Hellcat) with the ModBus communication board.
Also known as: Crest, Crest FB751-6001, Crest OF751-6001, Crest FCB1000-6000, Hellcat, MTR-01 - Boiler / water heater
Lochinvar Knight / Armor / Wall Mount boilers (ModBus communication board)
Knight 81-286, Knight XL 400-1000, Armor 151-1000, Outdoor Knight/Knight XL/Armor, AQUAS 400-801, FTXL 400-1000, Wall Mount 51-211, Wall Hung 55-399, Wall Mount Armor 125-200 and Shield 125-500 with the Lochinvar ModBus communication board.
Also known as: Knight, Knight XL, Outdoor Knight, Outdoor Knight XL, Armor, Outdoor Armor, Wall Mount Armor, Knight Wall Mount, Knight Wall Hung, AQUAS, FTXL, Shield - Boiler (electric)
Lochinvar Lectrus KEB electric boilers / water heaters 0015-0150 (Modbus communication board)
Lochinvar Lectrus KEB 0015-0150 electric boilers/water heaters with the Modbus/BACnet communication board, per MODB-I-O-KEB Rev A.
Also known as: Lectrus, KEB0015, KEB0150, KEB 0015-0150, MODB-I-O-KEB, Lochinvar Lectrus - Boiler
Lochinvar Power-fin PBX / PFX boilers and water heaters 502-1302, 1501-2001 (Modbus communication board)
Lochinvar Power-fin PB/PF 'X' models 502-1302 and 1501-2001 with the SMART SYSTEM control and Modbus/BACnet communication board, per PBX-PFX-MODB Rev D.
Also known as: Power-fin, Power-Fin, PBX502, PBX1302, PBX1501, PBX2001, PFX502, PFX2001, PBX-PFX-MODB, SMART SYSTEM - Boiler
Lochinvar SYNC condensing boilers / water heaters 1.0, 1.3, 1.5 (Modbus communication board)
Lochinvar SYNC 1.0 / 1.3 / 1.5 dual-module boilers and water heaters with the Modbus/BACnet communication board, per SYNC-MODB Rev L.
Also known as: SYNC 1.0, SYNC 1.3, SYNC 1.5, SYNC, Lochinvar SYNC, SYNC-MODB
Other boilers & water heaters register maps
- Boiler
Mestek KNSLM boiler control (KN2 / KN4 / rAy series)
KNSLM boiler control (KN2/KN4/rAy series), register list V1.10; registers marked 2.70+ need firmware 2.70 or later.
Also known as: KNSLM, KN2, KN4, rAy - Boiler
Buderus SSB condensing boilers (built-in Modbus RTU)
Buderus SSB series condensing boilers (Bosch Thermotechnology, North America) using the Modbus terminals on the boiler's internal terminal strip, per installation instructions 6720818450 (2015/10).
Also known as: SSB, Buderus SSB boiler, Bosch SSB, 6720818450 - Boiler (water heater controller)
PVI Industries XR10CX water heater digital operating controller (Modbus RTU)
PVI XR10CX digital operating controls on RS-485 Modbus RTU, per PVI manual PV500-67 (06/2014).
Also known as: XR10CX, PV500-67 - Boiler controller
Honeywell SOLA hydronic boiler control (Modbus interface)
Honeywell SOLA (R7910/R7911) integrated boiler controls, status registers 0-173 of the SOLA Modbus Interface specification Rev 4.1.1 (2013-10-14). Used inside many OEM condensing boilers.
Also known as: R7910, R7911, Honeywell SOLA, SOLA ICP - Boiler / heating system controller
Buderus Logamatic 5000 boiler and system controller (Modbus TCP, datapoint list 4.0)
Buderus Logamatic 5313 and 5311 (and the Bosch Control 8313/8311 equivalents) acting as master, firmware 1.3 or later with the 4.0 datapoint list; addresses for slave controllers differ.
Also known as: Logamatic 5313, Logamatic 5311, Bosch Control 8313, Bosch Control 8311, Control 8000, BCT 531, Logamatic 5000 Modbus - Boiler (water heater controller)
PVI Industries TempTrac water heater electronic controller (Modbus RTU)
PVI TempTrac thermostatic controllers (firmware 0.3 and 0.5) on RS-485 Modbus RTU, per PVI manual PV500-42 (06/2014).
Also known as: TempTrac, PV500-42
All boilers & water heaters Modbus register maps →
Source: ModBus and BACnet Communication Instructions - Armor Models 1250-4000, Series 100 & 101 · 100305786_2000558371 Rev C. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.