Boiler · Modbus register map

Lochinvar Power-fin PBX / PFX boilers and water heaters 502-1302, 1501-2001 (Modbus communication board) Modbus register map

Updated 17 November 2026

Short answer

Older-generation Lochinvar Power-fin boilers and water heaters with the SMART SYSTEM control talk Modbus RTU through an RS-485 communication board. The BAS writes a configuration word, an enable word, a rate or setpoint command and optional remote temperatures; it reads switch and flame states, outlet/inlet/flue temperatures, firing rate, cascade power, status/blocking/lockout codes and cascade members' lockout codes.

This page lists 48 Modbus registers for the Lochinvar Power-fin PBX / PFX boilers and water heaters 502-1302, 1501-2001 (Modbus communication board) — 9 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Lochinvar’s own free documentation (linked below) and checked against it.

Manufacturer
Lochinvar
Model
Power-fin PBX / PFX boilers and water heaters 502-1302, 1501-2001 (Modbus communication board)
Equipment type
Boiler
Registers
48 (9 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Also known as
Power-fin, Power-Fin, PBX502, PBX1302, PBX1501, PBX2001, PFX502, PFX2001, PBX-PFX-MODB, SMART SYSTEM
Source document
ModBus and BACnet Communication Instructions - Power-fin Models 502-1302; 1501-2001 · PBX-PFX-MODB 100161633_2000016132 Rev D
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Lochinvar Power-fin PBX / PFX boilers and water heaters 502-1302, 1501-2001 (Modbus communication board)

Integration in brief

Set address, baud and parity on the board DIP switches, set parameter H5 ModBus to Active, then write 40001 and the commands: enable only = 40001 0x0001 + 40002 0x0001; enable + BMS = 40001 0x0005 + 40002 0x0001 + 40003 rate; BMS only = 40001 0x0004 + 40003. Monitor 30009-30016.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 0ConfigurationBITMAP16Configuration bitsRead/write
HR 1CoilsUINT16Enable commandRead/write
HR 20-10 Volt Input / Rate Command / Setpoint CommandUINT16Rate (%) or setpoint commandRead/write
IR 8Outlet TemperatureUINT16Outlet temperatureRead
IR 11Firing RateUINT16Firing rateRead
IR 13Status CodeUINT16Status codeRead
IR 14Blocking CodeUINT16Blocking codeRead
IR 15Lockout CodeUINT16Lockout codeRead

Enable Modbus control & writes

Monitoring works with the default control setup. To send commands set parameter H5 ModBus to Active (see the Power-fin service manual), choose the enable/BMS demand configuration, and re-send 40001 before each command.

Communication loss & watchdog

Two timers: BAS-supplied system/tank temperatures must be refreshed within parameter H6 ModBus Time (the operation section gives 1-255 s; the configuration section says 5-120 s, default 10 s); all other commands time out after a fixed 4 minutes, after which the control reverts to its local inputs.

Byte order & addressing

Network setup

Watch out for

Lochinvar Power-fin PBX / PFX boilers and water heaters 502-1302, 1501-2001 (Modbus communication board) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

48 of 48 shown
Lochinvar Power-fin PBX / PFX boilers and water heaters 502-1302, 1501-2001 (Modbus communication board) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
CO0doc 00001EnableEnable command from the BAS.BITRead/write0 = Off; 1 = On
CO4doc 00005Tank ThermostatDHW tank thermostat demand from the BAS.BITRead/write0 = Off; 1 = On
DI0doc 10001Manual Reset High LimitBITRead0 = Off; 1 = On
DI1doc 10002Flow SwitchBITRead0 = Off; 1 = On
DI2doc 10003Gas Pressure SwitchBITRead0 = Off; 1 = On
DI3doc 10004Louver Proving SwitchBITRead0 = Off; 1 = On
DI4doc 10005Air Pressure SwitchBITRead0 = Off; 1 = On
DI5doc 10006Blocked Drain SwitchBITRead0 = Off; 1 = On
DI6doc 10007Auto Reset High LimitBITRead0 = Off; 1 = On
DI7doc 10008FlameBITRead0 = Off; 1 = On
DI8doc 10009EnableBITRead0 = Off; 1 = On
DI9doc 10010Tank ThermostatBITRead0 = Off; 1 = On
DI32doc 10033Run-time ContactsBITRead0 = Off; 1 = On
DI33doc 10034Alarm ContactsBITRead0 = Off; 1 = On
DI34doc 10035SH PumpBITRead0 = Off; 1 = On
DI35doc 10036HWG PumpBITRead0 = Off; 1 = On
DI37doc 10038Gas ValveBITRead0 = Off; 1 = On
DI38doc 10039System PumpBITRead0 = Off; 1 = On
DI48doc 10049Blower PowerBITRead0 = Off; 1 = On
DI50doc 10051Hot Surface IgnitorBITRead0 = Off; 1 = On
IR0doc 30001Discrete Inputs 1-16Packed copy of discrete inputs 1-16.UINT16Read
IR1doc 30002Discrete Inputs 17-32Packed copy of discrete inputs 17-32.UINT16Read
IR2doc 30003Discrete Inputs 33-48Packed copy of discrete inputs 33-48.UINT16Read
IR5doc 30006Cascade Total PowerTotal cascade capacity (100-800 %).UINT16%Read
IR6doc 30007Cascade Current PowerCurrent cascade output (0-800 %).UINT16%Read
IR8doc 30009Outlet TemperatureRaw is degrees C x 10 (manual example: 683 = 68.3 C).UINT16× 0.1°CRead
IR9doc 30010Inlet TemperatureINT16× 0.1°CRead
IR10doc 30011Flue TemperatureINT16× 0.1°CRead
IR11doc 30012Firing Rate0-100 %.UINT16%Read
IR13doc 30014Status CodeWhat the unit is doing; 40 = lockout.UINT16Read2 = Heat demand blocked: high outlet temperature; 3 = Heat demand blocked: high flue temperature; 4 = Heat demand blocked: high delta T; 5 = Heat demand blocked: initializing 3-way valve; 6 = Heat demand blocked: exercising 3-way valve; 7 = Heat demand blocked: different personality plug code; 8 = Heat demand blocked: low 24 VAC; 9 = Space heat demand blocked: outdoor shutdown; 10 = Blocked: boiler switched off at the display; 16 = Service mode active; 18 = Water heater DHW demand active; 19 = Boiler DHW demand active; 21 = Space heat demand from enable input; 22 = Space heat demand from BMS; 23 = Space heat demand from cascade; 30 = Freeze protection heat demand; 32 = DHW pump delay; 33 = Boiler pump delay; 34 = Standby; 40 = Lockout
IR14doc 30015Blocking CodeWhy heat demand is blocked.UINT16Read0 = No blocking; 1 = Flow switch open; 2 = Opening 3-way valve; 3 = Exercising 3-way valve; 5 = Low 24 VAC supply; 6 = Manual reset high limit; 7 = Outdoor shutdown; 8 = Boiler turned off; 10 = High delta T; 11 = High outlet temperature; 12 = Anti-cycling; 13 = Different personality plug setting; 14 = Mains frequency change; 15 = High flue temperature
IR15doc 30016Lockout CodeOnly valid while the status code is 40.UINT16Read163 = Different personality plug; 164 = Flame current circuit test failed; 165 = HSI current too low during ignition; 166 = Auto reset high limit; 167 = Blocked drain switch open; 168 = Louver proving switch open; 169 = Gas pressure switch open; 170 = Flow switch open; 178 = Flue sensor open; 179 = Inlet sensor shorted; 180 = Inlet sensor open; 192 = Outlet sensor shorted; 193 = Outlet sensor open; 204 = EEPROM CRC fault; 205 = EEPROM programmed; 206 = EEPROM programming error; 207 = EEPROM error; 229 = Watchdog; 230 = Low fan speed; 231 = High fan speed; 232 = No flame while running; 233 = No flame at ignition; 234 = Air pressure switch stuck open; 235 = Air pressure switch stuck closed; 236 = Air pressure switch stuck open; 237 = Flame out of sequence; 240 = Manual reset high limit
IR25doc 30026Discrete Inputs 49-64Packed copy of discrete inputs 49-64.UINT16Read
IR26doc 30027Lockout Code LeaderLockout code of the cascade leader.UINT16Read
IR27doc 30028Lockout Code Member 1Lockout code of cascade member 1.UINT16Read
IR28doc 30029Lockout Code Member 2Lockout code of cascade member 2.UINT16Read
IR29doc 30030Lockout Code Member 3Lockout code of cascade member 3.UINT16Read
IR30doc 30031Lockout Code Member 4Lockout code of cascade member 4.UINT16Read
IR31doc 30032Lockout Code Member 5Lockout code of cascade member 5.UINT16Read
IR32doc 30033Lockout Code Member 6Lockout code of cascade member 6.UINT16Read
IR33doc 30034Lockout Code Member 7Lockout code of cascade member 7.UINT16Read
HR0doc 40001ConfigurationSelects which values the BAS supplies instead of the unit's own inputs.BITMAP16Read/writebit 0 = Enable from BAS; bit 1 = Tank Thermostat from BAS; bit 2 = Rate Command / 0-10V Input / Setpoint Command from BAS; bit 3 = Tank Setpoint from BAS; bit 4 = System Supply Temperature from BAS; bit 5 = Outdoor Temperature from BAS; bit 6 = Tank Temperature from BAS; bit 7 = System Return Temperature from BAS
HR1doc 40002CoilsCommand word; manual examples: 0x0001 enables, 0x0008 = tank thermostat, 0x0000 disables.UINT16Read/write
HR2doc 400030-10 Volt Input / Rate Command / Setpoint CommandModulation % or setpoint, per the BMS type setting (0-100).UINT16%Read/write
HR4doc 40005Tank TemperatureTank temperature supplied by the BAS.INT16× 0.1°CRead/write
HR5doc 40006Outdoor TemperatureOutdoor temperature supplied by the BAS (-40 to 60 C).INT16× 0.1°CRead/write
HR6doc 40007System Supply TemperatureSystem supply temperature supplied by the BAS.INT16× 0.1°CRead/write
HR7doc 40008System Return TemperatureSystem return temperature supplied by the BAS.INT16× 0.1°CRead/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Lochinvar Power-fin PBX / PFX boilers and water heaters 502-1302, 1501-2001 (Modbus communication board)

What Modbus registers does the Lochinvar Power-fin PBX / PFX boilers and water heaters 502-1302, 1501-2001 (Modbus communication board) have?

This map lists 48 registers: 2 coils, 18 discrete inputs, 21 input registers, 7 holding registers. 9 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Lochinvar Power-fin PBX / PFX boilers and water heaters 502-1302, 1501-2001 (Modbus communication board) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Addresses are printed Modicon-style (00001, 10001, 30001, 40001). Subtract the table base and 1 for the wire address; the manual's exception-code text confirms PDU addresses start at 0.

What are the minimum Modbus registers to integrate the Lochinvar Power-fin PBX / PFX boilers and water heaters 502-1302, 1501-2001 (Modbus communication board)?

Start with HR 0 Configuration (Configuration bits); HR 1 Coils (Enable command); HR 2 0-10 Volt Input / Rate Command / Setpoint Command (Rate (%) or setpoint command); IR 8 Outlet Temperature (Outlet temperature); IR 11 Firing Rate (Firing rate); IR 13 Status Code (Status code); IR 14 Blocking Code (Blocking code); IR 15 Lockout Code (Lockout code).

How do I enable Modbus control of the Lochinvar Power-fin PBX / PFX boilers and water heaters 502-1302, 1501-2001 (Modbus communication board)?

Monitoring works with the default control setup. To send commands set parameter H5 ModBus to Active (see the Power-fin service manual), choose the enable/BMS demand configuration, and re-send 40001 before each command.

What happens when the Lochinvar Power-fin PBX / PFX boilers and water heaters 502-1302, 1501-2001 (Modbus communication board) loses Modbus communication?

Two timers: BAS-supplied system/tank temperatures must be refreshed within parameter H6 ModBus Time (the operation section gives 1-255 s; the configuration section says 5-120 s, default 10 s); all other commands time out after a fixed 4 minutes, after which the control reverts to its local inputs.

Where is the official Lochinvar Power-fin PBX / PFX boilers and water heaters 502-1302, 1501-2001 (Modbus communication board) Modbus documentation?

The source is ModBus and BACnet Communication Instructions - Power-fin Models 502-1302; 1501-2001 (PBX-PFX-MODB 100161633_2000016132 Rev D), published free by Lochinvar at https://assets.lochinvar.com/damroot/Original/10014/PBX-PFX-MODB_100161633_2000016132_REV%20D_BACNET(56304).pdf.

More Lochinvar Modbus register maps

Other boilers & water heaters register maps

All boilers & water heaters Modbus register maps →

Source: ModBus and BACnet Communication Instructions - Power-fin Models 502-1302; 1501-2001 · PBX-PFX-MODB 100161633_2000016132 Rev D. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.