- Power-fin PBX / PFX boilers and water heaters 502-1302, 1501-2001 (Modbus communication board)
Boiler · Modbus register map
Lochinvar Power-fin PBX / PFX boilers and water heaters 502-1302, 1501-2001 (Modbus communication board) Modbus register map
Updated 17 November 2026
Older-generation Lochinvar Power-fin boilers and water heaters with the SMART SYSTEM control talk Modbus RTU through an RS-485 communication board. The BAS writes a configuration word, an enable word, a rate or setpoint command and optional remote temperatures; it reads switch and flame states, outlet/inlet/flue temperatures, firing rate, cascade power, status/blocking/lockout codes and cascade members' lockout codes.
This page lists 48 Modbus registers for the Lochinvar Power-fin PBX / PFX boilers and water heaters 502-1302, 1501-2001 (Modbus communication board) — 9 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Lochinvar’s own free documentation (linked below) and checked against it.
- Manufacturer
- Lochinvar
- Model
- Power-fin PBX / PFX boilers and water heaters 502-1302, 1501-2001 (Modbus communication board)
- Equipment type
- Boiler
- Registers
- 48 (9 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Also known as
- Power-fin, Power-Fin, PBX502, PBX1302, PBX1501, PBX2001, PFX502, PFX2001, PBX-PFX-MODB, SMART SYSTEM
Integration notes: Lochinvar Power-fin PBX / PFX boilers and water heaters 502-1302, 1501-2001 (Modbus communication board)
Set address, baud and parity on the board DIP switches, set parameter H5 ModBus to Active, then write 40001 and the commands: enable only = 40001 0x0001 + 40002 0x0001; enable + BMS = 40001 0x0005 + 40002 0x0001 + 40003 rate; BMS only = 40001 0x0004 + 40003. Monitor 30009-30016.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 0 | Configuration | BITMAP16 | Configuration bits | Read/write |
| HR 1 | Coils | UINT16 | Enable command | Read/write |
| HR 2 | 0-10 Volt Input / Rate Command / Setpoint Command | UINT16 | Rate (%) or setpoint command | Read/write |
| IR 8 | Outlet Temperature | UINT16 | Outlet temperature | Read |
| IR 11 | Firing Rate | UINT16 | Firing rate | Read |
| IR 13 | Status Code | UINT16 | Status code | Read |
| IR 14 | Blocking Code | UINT16 | Blocking code | Read |
| IR 15 | Lockout Code | UINT16 | Lockout code | Read |
Enable Modbus control & writes
Monitoring works with the default control setup. To send commands set parameter H5 ModBus to Active (see the Power-fin service manual), choose the enable/BMS demand configuration, and re-send 40001 before each command.
Communication loss & watchdog
Two timers: BAS-supplied system/tank temperatures must be refreshed within parameter H6 ModBus Time (the operation section gives 1-255 s; the configuration section says 5-120 s, default 10 s); all other commands time out after a fixed 4 minutes, after which the control reverts to its local inputs.
Byte order & addressing
- Modicon addressing: 30009 is input register 8 on the wire.
- Temperatures are degrees C x 10.
- A setpoint sent through 40003 is the 0-10 V equivalent percentage interpolated from the BMS low/high setpoint parameters, not degrees.
- Read the lockout code only when the status code is 40.
Network setup
- DIP switches 1-8: Modbus address (binary sum, 1-247).
- DIP switch 9: 0 = 9600 baud, 1 = 19200 baud.
- DIP switch 10: 0 = no parity with 2 stop bits, 1 = even parity with 1 stop bit.
- RTU only; check 120 ohm termination.
Watch out for
- Board LED D7: 1 s bright / 1 s dim = normal; 1.5 s on / 0.5 s off = no Modbus traffic; 0.5 s on / 1.5 s off = no burner-control communication.
Lochinvar Power-fin PBX / PFX boilers and water heaters 502-1302, 1501-2001 (Modbus communication board) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 0doc 00001 | Enable | Enable command from the BAS. | BIT | Read/write | 0 = Off; 1 = On | |||
| CO | 4doc 00005 | Tank Thermostat | DHW tank thermostat demand from the BAS. | BIT | Read/write | 0 = Off; 1 = On | |||
| DI | 0doc 10001 | Manual Reset High Limit | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 1doc 10002 | Flow Switch | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 2doc 10003 | Gas Pressure Switch | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 3doc 10004 | Louver Proving Switch | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 4doc 10005 | Air Pressure Switch | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 5doc 10006 | Blocked Drain Switch | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 6doc 10007 | Auto Reset High Limit | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 7doc 10008 | Flame | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 8doc 10009 | Enable | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 9doc 10010 | Tank Thermostat | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 32doc 10033 | Run-time Contacts | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 33doc 10034 | Alarm Contacts | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 34doc 10035 | SH Pump | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 35doc 10036 | HWG Pump | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 37doc 10038 | Gas Valve | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 38doc 10039 | System Pump | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 48doc 10049 | Blower Power | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 50doc 10051 | Hot Surface Ignitor | BIT | Read | 0 = Off; 1 = On | ||||
| IR | 0doc 30001 | Discrete Inputs 1-16 | Packed copy of discrete inputs 1-16. | UINT16 | Read | ||||
| IR | 1doc 30002 | Discrete Inputs 17-32 | Packed copy of discrete inputs 17-32. | UINT16 | Read | ||||
| IR | 2doc 30003 | Discrete Inputs 33-48 | Packed copy of discrete inputs 33-48. | UINT16 | Read | ||||
| IR | 5doc 30006 | Cascade Total Power | Total cascade capacity (100-800 %). | UINT16 | % | Read | |||
| IR | 6doc 30007 | Cascade Current Power | Current cascade output (0-800 %). | UINT16 | % | Read | |||
| IR | 8doc 30009 | Outlet Temperature | Raw is degrees C x 10 (manual example: 683 = 68.3 C). | UINT16 | × 0.1 | °C | Read | ||
| IR | 9doc 30010 | Inlet Temperature | INT16 | × 0.1 | °C | Read | |||
| IR | 10doc 30011 | Flue Temperature | INT16 | × 0.1 | °C | Read | |||
| IR | 11doc 30012 | Firing Rate | 0-100 %. | UINT16 | % | Read | |||
| IR | 13doc 30014 | Status Code | What the unit is doing; 40 = lockout. | UINT16 | Read | 2 = Heat demand blocked: high outlet temperature; 3 = Heat demand blocked: high flue temperature; 4 = Heat demand blocked: high delta T; 5 = Heat demand blocked: initializing 3-way valve; 6 = Heat demand blocked: exercising 3-way valve; 7 = Heat demand blocked: different personality plug code; 8 = Heat demand blocked: low 24 VAC; 9 = Space heat demand blocked: outdoor shutdown; 10 = Blocked: boiler switched off at the display; 16 = Service mode active; 18 = Water heater DHW demand active; 19 = Boiler DHW demand active; 21 = Space heat demand from enable input; 22 = Space heat demand from BMS; 23 = Space heat demand from cascade; 30 = Freeze protection heat demand; 32 = DHW pump delay; 33 = Boiler pump delay; 34 = Standby; 40 = Lockout | |||
| IR | 14doc 30015 | Blocking Code | Why heat demand is blocked. | UINT16 | Read | 0 = No blocking; 1 = Flow switch open; 2 = Opening 3-way valve; 3 = Exercising 3-way valve; 5 = Low 24 VAC supply; 6 = Manual reset high limit; 7 = Outdoor shutdown; 8 = Boiler turned off; 10 = High delta T; 11 = High outlet temperature; 12 = Anti-cycling; 13 = Different personality plug setting; 14 = Mains frequency change; 15 = High flue temperature | |||
| IR | 15doc 30016 | Lockout Code | Only valid while the status code is 40. | UINT16 | Read | 163 = Different personality plug; 164 = Flame current circuit test failed; 165 = HSI current too low during ignition; 166 = Auto reset high limit; 167 = Blocked drain switch open; 168 = Louver proving switch open; 169 = Gas pressure switch open; 170 = Flow switch open; 178 = Flue sensor open; 179 = Inlet sensor shorted; 180 = Inlet sensor open; 192 = Outlet sensor shorted; 193 = Outlet sensor open; 204 = EEPROM CRC fault; 205 = EEPROM programmed; 206 = EEPROM programming error; 207 = EEPROM error; 229 = Watchdog; 230 = Low fan speed; 231 = High fan speed; 232 = No flame while running; 233 = No flame at ignition; 234 = Air pressure switch stuck open; 235 = Air pressure switch stuck closed; 236 = Air pressure switch stuck open; 237 = Flame out of sequence; 240 = Manual reset high limit | |||
| IR | 25doc 30026 | Discrete Inputs 49-64 | Packed copy of discrete inputs 49-64. | UINT16 | Read | ||||
| IR | 26doc 30027 | Lockout Code Leader | Lockout code of the cascade leader. | UINT16 | Read | ||||
| IR | 27doc 30028 | Lockout Code Member 1 | Lockout code of cascade member 1. | UINT16 | Read | ||||
| IR | 28doc 30029 | Lockout Code Member 2 | Lockout code of cascade member 2. | UINT16 | Read | ||||
| IR | 29doc 30030 | Lockout Code Member 3 | Lockout code of cascade member 3. | UINT16 | Read | ||||
| IR | 30doc 30031 | Lockout Code Member 4 | Lockout code of cascade member 4. | UINT16 | Read | ||||
| IR | 31doc 30032 | Lockout Code Member 5 | Lockout code of cascade member 5. | UINT16 | Read | ||||
| IR | 32doc 30033 | Lockout Code Member 6 | Lockout code of cascade member 6. | UINT16 | Read | ||||
| IR | 33doc 30034 | Lockout Code Member 7 | Lockout code of cascade member 7. | UINT16 | Read | ||||
| HR | 0doc 40001 | Configuration | Selects which values the BAS supplies instead of the unit's own inputs. | BITMAP16 | Read/write | bit 0 = Enable from BAS; bit 1 = Tank Thermostat from BAS; bit 2 = Rate Command / 0-10V Input / Setpoint Command from BAS; bit 3 = Tank Setpoint from BAS; bit 4 = System Supply Temperature from BAS; bit 5 = Outdoor Temperature from BAS; bit 6 = Tank Temperature from BAS; bit 7 = System Return Temperature from BAS | |||
| HR | 1doc 40002 | Coils | Command word; manual examples: 0x0001 enables, 0x0008 = tank thermostat, 0x0000 disables. | UINT16 | Read/write | ||||
| HR | 2doc 40003 | 0-10 Volt Input / Rate Command / Setpoint Command | Modulation % or setpoint, per the BMS type setting (0-100). | UINT16 | % | Read/write | |||
| HR | 4doc 40005 | Tank Temperature | Tank temperature supplied by the BAS. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 5doc 40006 | Outdoor Temperature | Outdoor temperature supplied by the BAS (-40 to 60 C). | INT16 | × 0.1 | °C | Read/write | ||
| HR | 6doc 40007 | System Supply Temperature | System supply temperature supplied by the BAS. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 7doc 40008 | System Return Temperature | System return temperature supplied by the BAS. | INT16 | × 0.1 | °C | Read/write |
Notes on this map
- Temperatures: the conversion section says the Power-fin passes temperatures in degrees C and the value must be divided by 10 (examples: 26.7 C sent as 267; outlet 683 = 68.3 C). Scale 0.1 is applied to the temperature registers with 0.1 resolution in the map.
- Left out: System/Cascade Setpoint (30004), Outlet Setpoint (30008) and Tank Setpoint (40004). The map gives them a 0.5 C resolution while the conversion text says temperatures are C x 10, so their scaling is not settled.
- Signed types: inlet, flue and BAS-supplied temperatures have negative minimums in the map and are listed as INT16; the manual itself only says 16-bit word.
- Input registers 30001-30003 and 30026 are packed copies of the discrete inputs; the bit order is not stated, so they are UINT16. Use the discrete inputs instead.
- Lockout code 234 and 236 are both printed as 'Air Pressure Switch stuck open'; both are kept as printed.
- This is the older PBX/PFX (SMART SYSTEM) board. Newer Power-fin boards have a separate manual and are not covered here.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Lochinvar Power-fin PBX / PFX boilers and water heaters 502-1302, 1501-2001 (Modbus communication board)
What Modbus registers does the Lochinvar Power-fin PBX / PFX boilers and water heaters 502-1302, 1501-2001 (Modbus communication board) have?
This map lists 48 registers: 2 coils, 18 discrete inputs, 21 input registers, 7 holding registers. 9 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Lochinvar Power-fin PBX / PFX boilers and water heaters 502-1302, 1501-2001 (Modbus communication board) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Addresses are printed Modicon-style (00001, 10001, 30001, 40001). Subtract the table base and 1 for the wire address; the manual's exception-code text confirms PDU addresses start at 0.
What are the minimum Modbus registers to integrate the Lochinvar Power-fin PBX / PFX boilers and water heaters 502-1302, 1501-2001 (Modbus communication board)?
Start with HR 0 Configuration (Configuration bits); HR 1 Coils (Enable command); HR 2 0-10 Volt Input / Rate Command / Setpoint Command (Rate (%) or setpoint command); IR 8 Outlet Temperature (Outlet temperature); IR 11 Firing Rate (Firing rate); IR 13 Status Code (Status code); IR 14 Blocking Code (Blocking code); IR 15 Lockout Code (Lockout code).
How do I enable Modbus control of the Lochinvar Power-fin PBX / PFX boilers and water heaters 502-1302, 1501-2001 (Modbus communication board)?
Monitoring works with the default control setup. To send commands set parameter H5 ModBus to Active (see the Power-fin service manual), choose the enable/BMS demand configuration, and re-send 40001 before each command.
What happens when the Lochinvar Power-fin PBX / PFX boilers and water heaters 502-1302, 1501-2001 (Modbus communication board) loses Modbus communication?
Two timers: BAS-supplied system/tank temperatures must be refreshed within parameter H6 ModBus Time (the operation section gives 1-255 s; the configuration section says 5-120 s, default 10 s); all other commands time out after a fixed 4 minutes, after which the control reverts to its local inputs.
Where is the official Lochinvar Power-fin PBX / PFX boilers and water heaters 502-1302, 1501-2001 (Modbus communication board) Modbus documentation?
The source is ModBus and BACnet Communication Instructions - Power-fin Models 502-1302; 1501-2001 (PBX-PFX-MODB 100161633_2000016132 Rev D), published free by Lochinvar at https://assets.lochinvar.com/damroot/Original/10014/PBX-PFX-MODB_100161633_2000016132_REV%20D_BACNET(56304).pdf.
More Lochinvar Modbus register maps
- Boiler (commercial water heater)
Lochinvar Armor 1250-4000 commercial water heaters, Series 100 & 101 (Modbus communication board)
Lochinvar Armor water heaters, models 1250-4000, Series 100 and 101, with the SMART SYSTEM control and Modbus/BACnet communication board, per 100305786_2000558371 Rev C.
Also known as: Armor 1250, Armor 1500, Armor 2000, Armor 2500, Armor 3000, Armor 3500, Armor 4000, AWH, AWH1250, AWH4000, SMART SYSTEM - Boiler
Lochinvar Copper-fin II / IIE boiler, water heater and pool heater (ModBus communication board)
Lochinvar Copper-fin II/IIE boilers and water heaters 402-2072 and pool heaters 502-2072 with the MTR-01 ModBus board, per manual 100160882 Rev G.
Also known as: Copper-fin II, Copper-fin IIE, CBX, CFX, CHX, CPX, C(F,H,P)X, Copperfin - Boiler
Lochinvar Crest / Crest with Hellcat boilers (ModBus communication board)
Lochinvar Crest FB/OF 751-6001 and FCB1000-6000 (including Crest with Hellcat) with the ModBus communication board.
Also known as: Crest, Crest FB751-6001, Crest OF751-6001, Crest FCB1000-6000, Hellcat, MTR-01 - Boiler / water heater
Lochinvar Knight / Armor / Wall Mount boilers (ModBus communication board)
Knight 81-286, Knight XL 400-1000, Armor 151-1000, Outdoor Knight/Knight XL/Armor, AQUAS 400-801, FTXL 400-1000, Wall Mount 51-211, Wall Hung 55-399, Wall Mount Armor 125-200 and Shield 125-500 with the Lochinvar ModBus communication board.
Also known as: Knight, Knight XL, Outdoor Knight, Outdoor Knight XL, Armor, Outdoor Armor, Wall Mount Armor, Knight Wall Mount, Knight Wall Hung, AQUAS, FTXL, Shield - Boiler (electric)
Lochinvar Lectrus KEB electric boilers / water heaters 0015-0150 (Modbus communication board)
Lochinvar Lectrus KEB 0015-0150 electric boilers/water heaters with the Modbus/BACnet communication board, per MODB-I-O-KEB Rev A.
Also known as: Lectrus, KEB0015, KEB0150, KEB 0015-0150, MODB-I-O-KEB, Lochinvar Lectrus - Boiler
Lochinvar SYNC condensing boilers / water heaters 1.0, 1.3, 1.5 (Modbus communication board)
Lochinvar SYNC 1.0 / 1.3 / 1.5 dual-module boilers and water heaters with the Modbus/BACnet communication board, per SYNC-MODB Rev L.
Also known as: SYNC 1.0, SYNC 1.3, SYNC 1.5, SYNC, Lochinvar SYNC, SYNC-MODB
Other boilers & water heaters register maps
- Boiler / water heater controller
AERCO C-More Boiler Controller (Benchmark / KC series)
AERCO C-More boiler controllers (software 2.00 or later) used on Benchmark and KC Series boilers and water heaters, as a Modbus RTU slave.
Also known as: C-More, Benchmark, KC1000, KC Series, Benchmark boiler, Benchmark water heater - Boiler controller
Patterson-Kelley NURO boiler controller (Modbus BMS port)
Patterson-Kelley NURO boiler control, Modbus register map from Appendix A of the NURO Advanced Users Guide.
Also known as: Patterson-Kelley NURO, Harsco Industrial Patterson-Kelley NURO - Boiler (burner / boiler controller)
Cleaver-Brooks CB Falcon hydronic / steam boiler control
Cleaver-Brooks CB Falcon boiler controls on the MB1 or MB2 Modbus port, per manual 750-308.
Also known as: CB Falcon, Falcon boiler control - Boiler
Weil-McLain Unity 2 control (ECO Tec 80-199, SVF 500/600 boilers)
Weil-McLain boilers with the Unity 2 control (ECO Tec 80/110/150/199 wall-mount and combi, SVF 500/600), per Modbus supplement 550-100-266/1023.
Also known as: ECO Tec 80, ECO Tec 110, ECO Tec 150, ECO Tec 199, ECO Tec Combi, SVF 500, SVF 600, Unity2 - Boiler
Mestek KNSLM boiler control (KN2 / KN4 / rAy series)
KNSLM boiler control (KN2/KN4/rAy series), register list V1.10; registers marked 2.70+ need firmware 2.70 or later.
Also known as: KNSLM, KN2, KN4, rAy - Boiler
Buderus SSB condensing boilers (built-in Modbus RTU)
Buderus SSB series condensing boilers (Bosch Thermotechnology, North America) using the Modbus terminals on the boiler's internal terminal strip, per installation instructions 6720818450 (2015/10).
Also known as: SSB, Buderus SSB boiler, Bosch SSB, 6720818450
All boilers & water heaters Modbus register maps →
Source: ModBus and BACnet Communication Instructions - Power-fin Models 502-1302; 1501-2001 · PBX-PFX-MODB 100161633_2000016132 Rev D. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.