Boiler controller · Modbus register map
Patterson-Kelley NURO boiler controller (Modbus BMS port) Modbus register map
Updated 17 November 2026
NURO is the boiler controller used on Patterson-Kelley (Harsco Industrial) commercial boilers, with an RS-485 Modbus RTU port for a building management system. All values are unsigned integers in holding registers. This map covers the boiler temperatures, analog I/O, digital I/O bit maps, active setpoints, demand source and status, boiler state, flame signal, firing rate and error code.
This page lists 22 Modbus registers for the Patterson-Kelley NURO boiler controller (Modbus BMS port) — 0 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Patterson-Kelley’s own free documentation (linked below) and checked against it.
- Manufacturer
- Patterson-Kelley
- Model
- NURO boiler controller (Modbus BMS port)
- Equipment type
- Boiler controller
- Registers
- 22 (0 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 8N2
- Documented addressing
- 0-based (the number printed is the address on the wire)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- Patterson-Kelley NURO, Harsco Industrial Patterson-Kelley NURO
Integration notes: Patterson-Kelley NURO boiler controller (Modbus BMS port)
Set MODBUS BMS BAUD RATE and MODBUS BMS SLAVE ADDRESS in the NURO menu, wire RS-485 at 8N2, and read holding registers 100-154 with FC 03. Temperatures are °C x10.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 100 | Outlet temperature | UINT16 | Outlet temperature | Read |
| HR 101 | Inlet temperature | UINT16 | Inlet temperature | Read |
| HR 132 | Boiler state | UINT16 | Boiler state | Read |
| HR 135 | Firing rate | UINT16 | Firing rate | Read |
| HR 136 | Error code | UINT32 ABCD | Error code | Read |
| HR 130 | Demand source | UINT16 | Demand source | Read |
Enable Modbus control & writes
Set MODBUS BMS BAUD RATE (9600, 19200 or 38400) and MODBUS BMS SLAVE ADDRESS under All Parameters > Boiler Parameters > General Boiler Settings.
Byte order & addressing
- 0-based addresses; 40001 + register in 4xxxx tools.
- Firing rate 0-200 = 0-100 %.
- Fixed format 8 data bits, no parity, 2 stop bits.
Network setup
- RS-485 two-wire.
- With several NUROs on one bus, wait 20 ms when switching between slave addresses.
Watch out for
- Temperature registers return 32768-34048 when a sensor is shorted, open or out of range.
Patterson-Kelley NURO boiler controller (Modbus BMS port) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 100 | Outlet temperature | 0.1 °C units; 32768 short, 33024 open, 33537 high range, 33792 low range, 34048 not reliable. | UINT16 | × 0.1 | °C | Read | ||
| HR | 101 | Inlet temperature | 0.1 °C units; 32768 short, 33024 open, 33537 high range, 33792 low range, 34048 not reliable. | UINT16 | × 0.1 | °C | Read | ||
| HR | 102 | Stack temperature | 0.1 °C units; 32768 short, 33024 open, 33537 high range, 33792 low range, 34048 not reliable. | UINT16 | × 0.1 | °C | Read | ||
| HR | 103 | DHW temperature | 0.1 °C units; 32768 short, 33024 open, 33537 high range, 33792 low range, 34048 not reliable. | UINT16 | × 0.1 | °C | Read | ||
| HR | 104 | Header temperature | 0.1 °C units; 32768 short, 33024 open, 33537 high range, 33792 low range, 34048 not reliable. | UINT16 | × 0.1 | °C | Read | ||
| HR | 105 | HX temperature | 0.1 °C units; 32768 short, 33024 open, 33537 high range, 33792 low range, 34048 not reliable. | UINT16 | × 0.1 | °C | Read | ||
| HR | 106 | ODA temperature filtered | 0.1 °C units; 32768 short, 33024 open, 33537 high range, 33792 low range, 34048 not reliable. | UINT16 | × 0.1 | °C | Read | ||
| HR | 107 | Extra field temperature | 0.1 °C units; 32768 short, 33024 open, 33537 high range, 33792 low range, 34048 not reliable. | UINT16 | × 0.1 | °C | Read | ||
| HR | 108 | Wireless temperature (ODA) | 0.1 °C units; 32768 short, 33024 open, 33537 high range, 33792 low range, 34048 not reliable. | UINT16 | × 0.1 | °C | Read | ||
| HR | 109 | Analog input | 4-20 mA sent as 40-200. | UINT16 | × 0.1 | mA | Read | ||
| HR | 110 | Analog output | 4-20 mA sent as 40-200. | UINT16 | × 0.1 | mA | Read | ||
| HR | 111 | Burner control digital I/O | BITMAP16 | Read | bit 0 = Relay A on; bit 1 = Relay B on; bit 2 = Relay C on; bit 3 = Relay D on; bit 4 = External ignition on; bit 5 = Gas valve open; bit 7 = Alarm relay on; bit 8 = Interlock control circuit; bit 9 = Damper end switch input; bit 10 = Limit control circuit; bit 13 = Enable; bit 14 = Night setback input; bit 15 = Safety relay | ||||
| HR | 112 | Burner control digital I/O 2 | BITMAP16 | Read | bit 0 = Air switch; bit 1 = Start interlock 1; bit 2 = Start interlock 2; bit 3 = Auxiliary input 1; bit 4 = Low water cut-off; bit 5 = High temperature limit; bit 6 = High gas pressure; bit 7 = Auxiliary input 2 | ||||
| HR | 113 | CH mode active setpoint | 0.1 °C units; 33536 = mode not active. | UINT16 | × 0.1 | °C | Read | ||
| HR | 114 | DHW mode active setpoint | 0.1 °C units; 33536 = mode not active. | UINT16 | × 0.1 | °C | Read | ||
| HR | 130 | Demand source | 5/6 = simultaneous demand; the first named drives the firing rate. | UINT16 | Read | 0 = None; 1 = CH; 2 = DHW; 3 = Freeze protection; 4 = Manual; 5 = CH & DHW; 6 = DHW & CH | |||
| HR | 131 | Active demand status | UINT16 | Read | 0 = Normal; 1 = System pump pre pump; 2 = System pump post pump; 3 = CH pump pre pump; 4 = CH pump post pump; 5 = Tank pump pre pump; 6 = Tank pump post pump; 7 = DHW pump pre pump; 8 = DHW pump post pump; 9 = Waiting anti cycle; 10 = Mod back max temp; 11 = Low fire hold; 12 = Limit time to high fire; 13 = Limit accelerate; 14 = Limit decelerate; 15 = Waiting for mode demand; 16 = Waiting for boiler to start; 17 = CH pump running; 18 = System pump running; 19 = DHW pump running; 20 = Tank pump running | ||||
| HR | 132 | Boiler state | UINT16 | Read | 0 = Waiting for communication; 1 = Standby; 2 = Lockout; 3 = Hold; 4 = Waiting for air switch close; 5 = Waiting for air switch open; 6 = Opening damper; 7 = Waiting for damper to open; 8 = Pre purge; 9 = Post purge; 10 = Run; 11 = Mod back delta temp; 12 = Mod back max temp; 13 = Mod back stack temp; 14 = Pre-ignition; 15 = Ignition; 16 = Mod back delta temp exceeded; 17 = Mod back max temp exceeded; 18 = Mod back stack temp exceeded; 19 = Rate modified by air switch; 20 = Rate modified by outlet temperature; 21 = Rate modified by delta limit; 22 = Rate modified by stack limit; 23 = Starting; 24 = Fan only; 25 = Stopping | ||||
| HR | 133 | Flame signal | 0.01-50.00 V. | UINT16 | × 0.01 | V | Read | ||
| HR | 135 | Firing rate | 0-200 = 0-100 % firing rate. | UINT16 | × 0.5 | % | Read | ||
| HR | 136 | Error code | See the error table in the source. | UINT32 | ABCD | Read | |||
| HR | 138 | Error type | UINT16 | Read | 0 = No error; 1 = Lockout; 2 = Boiler hold; 3 = Mode hold; 4 = Alert caused alarm |
Notes on this map
- Source host: an unaltered extract of the Patterson-Kelley guide hosted by Contemporary Controls; we did not find a public manufacturer copy.
- Word order: the guide says 32-bit values are sent in two registers and the total is first register x 65536 + second register, so high word first (ABCD).
- All data is sent as unsigned integers; temperatures are always °C x10 regardless of display units. Sensor fault codes replace the temperature value (see descriptions).
- Fan speed (134) is left out because the guide gives only 'fan speed type' without unit or scaling. The BMS control registers 171-193 (CH/DHW boiler control and BMS setpoints) are left out because the extracted table does not show their access or precision clearly.
- Reading a reserved address returns an illegal-address exception.
- Supported functions: FC 03 read holding registers and FC 06 write single register.
- Left out: burner cycle count (151-152) and run hours (153-154). The table prints a precision of 0.1 for both, which conflicts with the 0-999,999 count range and the plain-integer example in Note 6, so the scaling is unclear.
- Firing rate (135) is printed with precision 0.1, but Note 5 defines it as 0-200 = 0-100 % (50 % sent as 100), so scale 0.5 is used.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Patterson-Kelley NURO boiler controller (Modbus BMS port)
What Modbus registers does the Patterson-Kelley NURO boiler controller (Modbus BMS port) have?
This map lists 22 registers: 22 holding registers. 0 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Patterson-Kelley NURO boiler controller (Modbus BMS port) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide says register addresses start at 0 per the Modbus specification and that 40001 is added for traditional numbering, so register 100 (outlet temperature) is wire address 100 (40101).
What byte order does the Patterson-Kelley NURO boiler controller (Modbus BMS port) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Patterson-Kelley NURO boiler controller (Modbus BMS port)?
Start with HR 100 Outlet temperature (Outlet temperature); HR 101 Inlet temperature (Inlet temperature); HR 132 Boiler state (Boiler state); HR 135 Firing rate (Firing rate); HR 136 Error code (Error code); HR 130 Demand source (Demand source).
How do I enable Modbus control of the Patterson-Kelley NURO boiler controller (Modbus BMS port)?
Set MODBUS BMS BAUD RATE (9600, 19200 or 38400) and MODBUS BMS SLAVE ADDRESS under All Parameters > Boiler Parameters > General Boiler Settings.
Where is the official Patterson-Kelley NURO boiler controller (Modbus BMS port) Modbus documentation?
The source is NURO Advanced Users Guide - Appendix A: Modbus Configuration. Patterson-Kelley doesn't publish it on its own website, so this map was re-typed from a free copy at https://www.ccontrols.com/support/dp/NURO%20Advanced%20Users%20Guide.pdf. It may be an older revision, so check it against the live unit.
Other boilers & water heaters register maps
- Boiler (burner / boiler controller)
Cleaver-Brooks CB Falcon hydronic / steam boiler control
Cleaver-Brooks CB Falcon boiler controls on the MB1 or MB2 Modbus port, per manual 750-308.
Also known as: CB Falcon, Falcon boiler control - Boiler (electric)
Lochinvar Lectrus KEB electric boilers / water heaters 0015-0150 (Modbus communication board)
Lochinvar Lectrus KEB 0015-0150 electric boilers/water heaters with the Modbus/BACnet communication board, per MODB-I-O-KEB Rev A.
Also known as: Lectrus, KEB0015, KEB0150, KEB 0015-0150, MODB-I-O-KEB, Lochinvar Lectrus - Boiler
Weil-McLain Unity 2 control (ECO Tec 80-199, SVF 500/600 boilers)
Weil-McLain boilers with the Unity 2 control (ECO Tec 80/110/150/199 wall-mount and combi, SVF 500/600), per Modbus supplement 550-100-266/1023.
Also known as: ECO Tec 80, ECO Tec 110, ECO Tec 150, ECO Tec 199, ECO Tec Combi, SVF 500, SVF 600, Unity2 - Boiler (commercial water heater)
Lochinvar Armor 1250-4000 commercial water heaters, Series 100 & 101 (Modbus communication board)
Lochinvar Armor water heaters, models 1250-4000, Series 100 and 101, with the SMART SYSTEM control and Modbus/BACnet communication board, per 100305786_2000558371 Rev C.
Also known as: Armor 1250, Armor 1500, Armor 2000, Armor 2500, Armor 3000, Armor 3500, Armor 4000, AWH, AWH1250, AWH4000, SMART SYSTEM - Boiler
Mestek KNSLM boiler control (KN2 / KN4 / rAy series)
KNSLM boiler control (KN2/KN4/rAy series), register list V1.10; registers marked 2.70+ need firmware 2.70 or later.
Also known as: KNSLM, KN2, KN4, rAy - Boiler
Buderus SSB condensing boilers (built-in Modbus RTU)
Buderus SSB series condensing boilers (Bosch Thermotechnology, North America) using the Modbus terminals on the boiler's internal terminal strip, per installation instructions 6720818450 (2015/10).
Also known as: SSB, Buderus SSB boiler, Bosch SSB, 6720818450
All boilers & water heaters Modbus register maps →
Source: NURO Advanced Users Guide - Appendix A: Modbus Configuration · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.