Boiler controller · Modbus register map

Patterson-Kelley NURO boiler controller (Modbus BMS port) Modbus register map

Updated 17 November 2026

Short answer

NURO is the boiler controller used on Patterson-Kelley (Harsco Industrial) commercial boilers, with an RS-485 Modbus RTU port for a building management system. All values are unsigned integers in holding registers. This map covers the boiler temperatures, analog I/O, digital I/O bit maps, active setpoints, demand source and status, boiler state, flame signal, firing rate and error code.

This page lists 22 Modbus registers for the Patterson-Kelley NURO boiler controller (Modbus BMS port) — 0 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Patterson-Kelley’s own free documentation (linked below) and checked against it.

Manufacturer
Patterson-Kelley
Model
NURO boiler controller (Modbus BMS port)
Equipment type
Boiler controller
Registers
22 (0 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
8N2
Documented addressing
0-based (the number printed is the address on the wire)
32-bit word order
ABCD high word first (big-endian)
Also known as
Patterson-Kelley NURO, Harsco Industrial Patterson-Kelley NURO
Source document
NURO Advanced Users Guide - Appendix A: Modbus Configuration · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Patterson-Kelley NURO boiler controller (Modbus BMS port)

Integration in brief

Set MODBUS BMS BAUD RATE and MODBUS BMS SLAVE ADDRESS in the NURO menu, wire RS-485 at 8N2, and read holding registers 100-154 with FC 03. Temperatures are °C x10.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 100Outlet temperatureUINT16Outlet temperatureRead
HR 101Inlet temperatureUINT16Inlet temperatureRead
HR 132Boiler stateUINT16Boiler stateRead
HR 135Firing rateUINT16Firing rateRead
HR 136Error codeUINT32 ABCDError codeRead
HR 130Demand sourceUINT16Demand sourceRead

Enable Modbus control & writes

Set MODBUS BMS BAUD RATE (9600, 19200 or 38400) and MODBUS BMS SLAVE ADDRESS under All Parameters > Boiler Parameters > General Boiler Settings.

Byte order & addressing

Network setup

Watch out for

Patterson-Kelley NURO boiler controller (Modbus BMS port) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

22 of 22 shown
Patterson-Kelley NURO boiler controller (Modbus BMS port) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR100Outlet temperature0.1 °C units; 32768 short, 33024 open, 33537 high range, 33792 low range, 34048 not reliable.UINT16× 0.1°CRead
HR101Inlet temperature0.1 °C units; 32768 short, 33024 open, 33537 high range, 33792 low range, 34048 not reliable.UINT16× 0.1°CRead
HR102Stack temperature0.1 °C units; 32768 short, 33024 open, 33537 high range, 33792 low range, 34048 not reliable.UINT16× 0.1°CRead
HR103DHW temperature0.1 °C units; 32768 short, 33024 open, 33537 high range, 33792 low range, 34048 not reliable.UINT16× 0.1°CRead
HR104Header temperature0.1 °C units; 32768 short, 33024 open, 33537 high range, 33792 low range, 34048 not reliable.UINT16× 0.1°CRead
HR105HX temperature0.1 °C units; 32768 short, 33024 open, 33537 high range, 33792 low range, 34048 not reliable.UINT16× 0.1°CRead
HR106ODA temperature filtered0.1 °C units; 32768 short, 33024 open, 33537 high range, 33792 low range, 34048 not reliable.UINT16× 0.1°CRead
HR107Extra field temperature0.1 °C units; 32768 short, 33024 open, 33537 high range, 33792 low range, 34048 not reliable.UINT16× 0.1°CRead
HR108Wireless temperature (ODA)0.1 °C units; 32768 short, 33024 open, 33537 high range, 33792 low range, 34048 not reliable.UINT16× 0.1°CRead
HR109Analog input4-20 mA sent as 40-200.UINT16× 0.1mARead
HR110Analog output4-20 mA sent as 40-200.UINT16× 0.1mARead
HR111Burner control digital I/OBITMAP16Readbit 0 = Relay A on; bit 1 = Relay B on; bit 2 = Relay C on; bit 3 = Relay D on; bit 4 = External ignition on; bit 5 = Gas valve open; bit 7 = Alarm relay on; bit 8 = Interlock control circuit; bit 9 = Damper end switch input; bit 10 = Limit control circuit; bit 13 = Enable; bit 14 = Night setback input; bit 15 = Safety relay
HR112Burner control digital I/O 2BITMAP16Readbit 0 = Air switch; bit 1 = Start interlock 1; bit 2 = Start interlock 2; bit 3 = Auxiliary input 1; bit 4 = Low water cut-off; bit 5 = High temperature limit; bit 6 = High gas pressure; bit 7 = Auxiliary input 2
HR113CH mode active setpoint0.1 °C units; 33536 = mode not active.UINT16× 0.1°CRead
HR114DHW mode active setpoint0.1 °C units; 33536 = mode not active.UINT16× 0.1°CRead
HR130Demand source5/6 = simultaneous demand; the first named drives the firing rate.UINT16Read0 = None; 1 = CH; 2 = DHW; 3 = Freeze protection; 4 = Manual; 5 = CH & DHW; 6 = DHW & CH
HR131Active demand statusUINT16Read0 = Normal; 1 = System pump pre pump; 2 = System pump post pump; 3 = CH pump pre pump; 4 = CH pump post pump; 5 = Tank pump pre pump; 6 = Tank pump post pump; 7 = DHW pump pre pump; 8 = DHW pump post pump; 9 = Waiting anti cycle; 10 = Mod back max temp; 11 = Low fire hold; 12 = Limit time to high fire; 13 = Limit accelerate; 14 = Limit decelerate; 15 = Waiting for mode demand; 16 = Waiting for boiler to start; 17 = CH pump running; 18 = System pump running; 19 = DHW pump running; 20 = Tank pump running
HR132Boiler stateUINT16Read0 = Waiting for communication; 1 = Standby; 2 = Lockout; 3 = Hold; 4 = Waiting for air switch close; 5 = Waiting for air switch open; 6 = Opening damper; 7 = Waiting for damper to open; 8 = Pre purge; 9 = Post purge; 10 = Run; 11 = Mod back delta temp; 12 = Mod back max temp; 13 = Mod back stack temp; 14 = Pre-ignition; 15 = Ignition; 16 = Mod back delta temp exceeded; 17 = Mod back max temp exceeded; 18 = Mod back stack temp exceeded; 19 = Rate modified by air switch; 20 = Rate modified by outlet temperature; 21 = Rate modified by delta limit; 22 = Rate modified by stack limit; 23 = Starting; 24 = Fan only; 25 = Stopping
HR133Flame signal0.01-50.00 V.UINT16× 0.01VRead
HR135Firing rate0-200 = 0-100 % firing rate.UINT16× 0.5%Read
HR136Error codeSee the error table in the source.UINT32ABCDRead
HR138Error typeUINT16Read0 = No error; 1 = Lockout; 2 = Boiler hold; 3 = Mode hold; 4 = Alert caused alarm

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Patterson-Kelley NURO boiler controller (Modbus BMS port)

What Modbus registers does the Patterson-Kelley NURO boiler controller (Modbus BMS port) have?

This map lists 22 registers: 22 holding registers. 0 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Patterson-Kelley NURO boiler controller (Modbus BMS port) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide says register addresses start at 0 per the Modbus specification and that 40001 is added for traditional numbering, so register 100 (outlet temperature) is wire address 100 (40101).

What byte order does the Patterson-Kelley NURO boiler controller (Modbus BMS port) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Patterson-Kelley NURO boiler controller (Modbus BMS port)?

Start with HR 100 Outlet temperature (Outlet temperature); HR 101 Inlet temperature (Inlet temperature); HR 132 Boiler state (Boiler state); HR 135 Firing rate (Firing rate); HR 136 Error code (Error code); HR 130 Demand source (Demand source).

How do I enable Modbus control of the Patterson-Kelley NURO boiler controller (Modbus BMS port)?

Set MODBUS BMS BAUD RATE (9600, 19200 or 38400) and MODBUS BMS SLAVE ADDRESS under All Parameters > Boiler Parameters > General Boiler Settings.

Where is the official Patterson-Kelley NURO boiler controller (Modbus BMS port) Modbus documentation?

The source is NURO Advanced Users Guide - Appendix A: Modbus Configuration. Patterson-Kelley doesn't publish it on its own website, so this map was re-typed from a free copy at https://www.ccontrols.com/support/dp/NURO%20Advanced%20Users%20Guide.pdf. It may be an older revision, so check it against the live unit.

Other boilers & water heaters register maps

All boilers & water heaters Modbus register maps →

Source: NURO Advanced Users Guide - Appendix A: Modbus Configuration · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.