- Unity 2 control (ECO Tec 80-199, SVF 500/600 boilers)
Boiler · Modbus register map
Weil-McLain Unity 2 control (ECO Tec 80-199, SVF 500/600 boilers) Modbus register map
Updated 17 November 2026
Weil-McLain's Unity 2 boiler control has a built-in Modbus RTU slave on the BMS terminals of J12 (a plug-in harness on ECO Tec, pre-installed board on SVF). This map covers the supplement's 'frequently used points': model, boiler state, active priority, blower speed and modulation, flame signal, all temperature sensors in degrees F, DHW flow, gas valve and 120 V output status, and gas type.
This page lists 30 Modbus registers for the Weil-McLain Unity 2 control (ECO Tec 80-199, SVF 500/600 boilers) — 0 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Weil-McLain’s own free documentation (linked below) and checked against it.
- Manufacturer
- Weil-McLain
- Model
- Unity 2 control (ECO Tec 80-199, SVF 500/600 boilers)
- Equipment type
- Boiler
- Registers
- 30 (0 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- hexadecimal, 0-based
- Also known as
- ECO Tec 80, ECO Tec 110, ECO Tec 150, ECO Tec 199, ECO Tec Combi, SVF 500, SVF 600, Unity2
Integration notes: Weil-McLain Unity 2 control (ECO Tec 80-199, SVF 500/600 boilers)
Enable Modbus on the boiler's contractor menu, match address/baud/parity/stop bits, then read 0xA002-0xA01E with function 03 for state, firing and temperatures.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 40962 | Boiler state | UINT16 | Boiler state | Read |
| HR 40967 | Modulation percentage | UINT16 | Modulation % | Read |
| HR 40970 | Target temperature | UINT16 | Target temperature | Read |
| HR 40971 | Boiler out 1 temperature | UINT16 | Boiler outlet temperature | Read |
| HR 40973 | Boiler in temperature | UINT16 | Boiler inlet temperature | Read |
| HR 40978 | Outdoor temperature | INT16 | Outdoor temperature | Read |
Enable Modbus control & writes
Contractor menu (press and hold the WM logo on the home screen) > Modbus settings: set Enable = YES, address, parity, baud and stop bits. BMS wiring is J12-1 (A+), J12-2 (B-), J12-5 (common).
Byte order & addressing
- Register numbers like 40962 are real addresses (0xA002), not Modicon references.
- Temperatures in F with fault codes 1233-1237.
Network setup
- Baud 4800, 9600 or 38400; parity even/odd/none; 1 or 2 stop bits.
Watch out for
- On multi-boiler systems the Unity 2 must be the master control.
Weil-McLain Unity 2 control (ECO Tec 80-199, SVF 500/600 boilers) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 40961doc 40961 / 0xA001 | Boiler model | Printed type UINT8. | UINT16 | Read | 16 = Eco Tec 80; 17 = Eco Tec 110; 18 = Eco Tec 110 Combi; 19 = Eco Tec 150; 20 = Eco Tec 150 Combi; 21 = Eco Tec 199; 22 = Eco Tec 199 Combi; 64 = SVF 500; 65 = SVF 600; 255 = Not configured | |||
| HR | 40962doc 40962 / 0xA002 | Boiler state | UINT16 | Read | 0 = Standby; 1 = Prepump; 2 = Prepurge; 3 = Ignition speed; 4 = Pre-ignition; 5 = GV open test; 6 = GV closed test; 7 = Ignition; 8 = Heating; 9 = Postpurge; 10 = Lockout; 11 = Postpump; 12 = Inter-purge; 13 = Init; 14 = Config check | ||||
| HR | 40963doc 40963 / 0xA003 | Active inputs | No value coding given in the list. | UINT16 | Read | ||||
| HR | 40964doc 40964 / 0xA004 | Active priority | Printed type UINT8. | UINT16 | Read | 0 = Local priority 1; 1 = Network 1; 2 = Network 2; 3 = Local priority 2; 4 = Local priority 3; 6 = Freeze protection; 7 = System pump; 8 = Priority off; 9 = No active priority | |||
| HR | 40965doc 40965 / 0xA005 | Desired blower speed | UINT16 | rpm | Read | ||||
| HR | 40966doc 40966 / 0xA006 | Actual blower speed | UINT16 | rpm | Read | ||||
| HR | 40967doc 40967 / 0xA007 | Modulation percentage | UINT16 | × 0.1 | % | Read | |||
| HR | 40968doc 40968 / 0xA008 | Desired blower PWM | UINT16 | Read | |||||
| HR | 40969doc 40969 / 0xA009 | Flame signal | 23 = 2.3 µA. | UINT16 | × 0.1 | µA | Read | ||
| HR | 40970doc 40970 / 0xA00A | Target temperature | Degrees F; 1233-1237 are sensor fault codes. | UINT16 | °F | Read | 1233 = No sensor; 1234 = Sensor shorted; 1235 = Sensor open; 1236 = Redundant sensor failed; 1237 = Lost communications to sensor | ||
| HR | 40971doc 40971 / 0xA00B | Boiler out 1 temperature | Degrees F; 1233-1237 are sensor fault codes. | UINT16 | °F | Read | 1233 = No sensor; 1234 = Sensor shorted; 1235 = Sensor open; 1236 = Redundant sensor failed; 1237 = Lost communications to sensor | ||
| HR | 40972doc 40972 / 0xA00C | Boiler out 2 temperature | Degrees F; 1233-1237 are sensor fault codes. | UINT16 | °F | Read | 1233 = No sensor; 1234 = Sensor shorted; 1235 = Sensor open; 1236 = Redundant sensor failed; 1237 = Lost communications to sensor | ||
| HR | 40973doc 40973 / 0xA00D | Boiler in temperature | Degrees F; 1233-1237 are sensor fault codes. | UINT16 | °F | Read | 1233 = No sensor; 1234 = Sensor shorted; 1235 = Sensor open; 1236 = Redundant sensor failed; 1237 = Lost communications to sensor | ||
| HR | 40974doc 40974 / 0xA00E | Flue 1 temperature | Degrees F; 1233-1237 are sensor fault codes. | INT16 | °F | Read | 1233 = No sensor; 1234 = Sensor shorted; 1235 = Sensor open; 1236 = Redundant sensor failed; 1237 = Lost communications to sensor | ||
| HR | 40975doc 40975 / 0xA00F | Flue 2 temperature | Degrees F; 1233-1237 are sensor fault codes. | INT16 | °F | Read | 1233 = No sensor; 1234 = Sensor shorted; 1235 = Sensor open; 1236 = Redundant sensor failed; 1237 = Lost communications to sensor | ||
| HR | 40976doc 40976 / 0xA010 | System supply temperature | Degrees F; 1233-1237 are sensor fault codes. | UINT16 | °F | Read | 1233 = No sensor; 1234 = Sensor shorted; 1235 = Sensor open; 1236 = Redundant sensor failed; 1237 = Lost communications to sensor | ||
| HR | 40977doc 40977 / 0xA011 | System return temperature | Degrees F; 1233-1237 are sensor fault codes. | UINT16 | °F | Read | 1233 = No sensor; 1234 = Sensor shorted; 1235 = Sensor open; 1236 = Redundant sensor failed; 1237 = Lost communications to sensor | ||
| HR | 40978doc 40978 / 0xA012 | Outdoor temperature | Degrees F; 1233-1237 are sensor fault codes. | INT16 | °F | Read | 1233 = No sensor; 1234 = Sensor shorted; 1235 = Sensor open; 1236 = Redundant sensor failed; 1237 = Lost communications to sensor | ||
| HR | 40979doc 40979 / 0xA013 | DHW 1 temperature | Degrees F; 1233-1237 are sensor fault codes. | UINT16 | °F | Read | 1233 = No sensor; 1234 = Sensor shorted; 1235 = Sensor open; 1236 = Redundant sensor failed; 1237 = Lost communications to sensor | ||
| HR | 40980doc 40980 / 0xA014 | DHW 2 temperature | Degrees F; 1233-1237 are sensor fault codes. | UINT16 | °F | Read | 1233 = No sensor; 1234 = Sensor shorted; 1235 = Sensor open; 1236 = Redundant sensor failed; 1237 = Lost communications to sensor | ||
| HR | 40982doc 40982 / 0xA016 | DHW flow rate | 35 = 3.5 GPM. | UINT16 | × 0.1 | gpm | Read | ||
| HR | 40983doc 40983 / 0xA017 | Gas valve relay 1 | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 40984doc 40984 / 0xA018 | Gas valve relay 2 | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 40985doc 40985 / 0xA019 | External ignition/pilot relay | Printed type UINT8. | UINT16 | Read | 0 = Off; 1 = On | |||
| HR | 40986doc 40986 / 0xA01A | 120 V output 1 | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 40987doc 40987 / 0xA01B | 120 V output 2 | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 40988doc 40988 / 0xA01C | 120 V output 3 | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 40989doc 40989 / 0xA01D | 120 V output 4 | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 40990doc 40990 / 0xA01E | 120 V output 5 | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 41091doc 41091 / 0xA083 | Gas type | Printed type UINT8. | UINT16 | Read | 0 = Natural gas; 1 = Liquid propane |
Notes on this map
- Several registers are typed UINT8 in the list; Modbus returns them as a 16-bit register and they are typed UINT16 here.
- Temperatures are whole degrees F; the values 1233-1237 are sensor fault codes, not temperatures.
- Only the frequently used points list and gas type are mapped. The 118-page supplement also covers priorities, network/shadow boilers, faults and history; those registers are left out to keep the map short.
- Modbus settings (enable, address 0-255, parity even/odd/none, baud 4800/9600/38400, 1 or 2 stop bits) are made on the boiler display's Modbus settings screen; no defaults are given.
- The supplement does not name Modbus function codes. Its single register list mixes read-only and user-writable registers, which fits the holding-register table, so the points are listed as holding registers (function 03).
- Revision date taken from the part number suffix /1023 (October 2023).
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Weil-McLain Unity 2 control (ECO Tec 80-199, SVF 500/600 boilers)
What Modbus registers does the Weil-McLain Unity 2 control (ECO Tec 80-199, SVF 500/600 boilers) have?
This map lists 30 registers: 30 holding registers. 0 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Weil-McLain Unity 2 control (ECO Tec 80-199, SVF 500/600 boilers) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The supplement lists each register in decimal and hex and says the control speaks hex: use the hex value as the register address. 0xA002 (decimal 40962) is sent as 0xA002; it is not a Modicon 4xxxx number, so do not subtract 40001.
What are the minimum Modbus registers to integrate the Weil-McLain Unity 2 control (ECO Tec 80-199, SVF 500/600 boilers)?
Start with HR 40962 Boiler state (Boiler state); HR 40967 Modulation percentage (Modulation %); HR 40970 Target temperature (Target temperature); HR 40971 Boiler out 1 temperature (Boiler outlet temperature); HR 40973 Boiler in temperature (Boiler inlet temperature); HR 40978 Outdoor temperature (Outdoor temperature).
How do I enable Modbus control of the Weil-McLain Unity 2 control (ECO Tec 80-199, SVF 500/600 boilers)?
Contractor menu (press and hold the WM logo on the home screen) > Modbus settings: set Enable = YES, address, parity, baud and stop bits. BMS wiring is J12-1 (A+), J12-2 (B-), J12-5 (common).
Where is the official Weil-McLain Unity 2 control (ECO Tec 80-199, SVF 500/600 boilers) Modbus documentation?
The source is Unity 2 Control Modbus Supplement - Software Interface Specification (Eco Tec 80/110/150/199 and SVF 500/600) (550-100-266/1023), revision 2023-10, published free by Weil-McLain at https://www.weil-mclain.com/wp-content/uploads/ECT-SVF-Unity2-Control-Modbus-Supplement.pdf.
Other boilers & water heaters register maps
- Boiler (commercial water heater)
Lochinvar Armor 1250-4000 commercial water heaters, Series 100 & 101 (Modbus communication board)
Lochinvar Armor water heaters, models 1250-4000, Series 100 and 101, with the SMART SYSTEM control and Modbus/BACnet communication board, per 100305786_2000558371 Rev C.
Also known as: Armor 1250, Armor 1500, Armor 2000, Armor 2500, Armor 3000, Armor 3500, Armor 4000, AWH, AWH1250, AWH4000, SMART SYSTEM - Boiler
Mestek KNSLM boiler control (KN2 / KN4 / rAy series)
KNSLM boiler control (KN2/KN4/rAy series), register list V1.10; registers marked 2.70+ need firmware 2.70 or later.
Also known as: KNSLM, KN2, KN4, rAy - Boiler
Buderus SSB condensing boilers (built-in Modbus RTU)
Buderus SSB series condensing boilers (Bosch Thermotechnology, North America) using the Modbus terminals on the boiler's internal terminal strip, per installation instructions 6720818450 (2015/10).
Also known as: SSB, Buderus SSB boiler, Bosch SSB, 6720818450 - Boiler / water heater
Lochinvar Knight / Armor / Wall Mount boilers (ModBus communication board)
Knight 81-286, Knight XL 400-1000, Armor 151-1000, Outdoor Knight/Knight XL/Armor, AQUAS 400-801, FTXL 400-1000, Wall Mount 51-211, Wall Hung 55-399, Wall Mount Armor 125-200 and Shield 125-500 with the Lochinvar ModBus communication board.
Also known as: Knight, Knight XL, Outdoor Knight, Outdoor Knight XL, Armor, Outdoor Armor, Wall Mount Armor, Knight Wall Mount, Knight Wall Hung, AQUAS, FTXL, Shield - Boiler (water heater controller)
PVI Industries XR10CX water heater digital operating controller (Modbus RTU)
PVI XR10CX digital operating controls on RS-485 Modbus RTU, per PVI manual PV500-67 (06/2014).
Also known as: XR10CX, PV500-67 - Boiler controller
Honeywell SOLA hydronic boiler control (Modbus interface)
Honeywell SOLA (R7910/R7911) integrated boiler controls, status registers 0-173 of the SOLA Modbus Interface specification Rev 4.1.1 (2013-10-14). Used inside many OEM condensing boilers.
Also known as: R7910, R7911, Honeywell SOLA, SOLA ICP
All boilers & water heaters Modbus register maps →
Source: Unity 2 Control Modbus Supplement - Software Interface Specification (Eco Tec 80/110/150/199 and SVF 500/600) · 550-100-266/1023 · rev. 2023-10. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.