Easy Modbus
  1. Home
  2. Modbus register maps
  3. Weil-McLain
  4. Unity 2 control (ECO Tec 80-199, SVF 500/600 boilers)

Boiler · Modbus register map

Weil-McLain Unity 2 control (ECO Tec 80-199, SVF 500/600 boilers) Modbus register map

Updated 17 November 2026

Short answer

Weil-McLain's Unity 2 boiler control has a built-in Modbus RTU slave on the BMS terminals of J12 (a plug-in harness on ECO Tec, pre-installed board on SVF). This map covers the supplement's 'frequently used points': model, boiler state, active priority, blower speed and modulation, flame signal, all temperature sensors in degrees F, DHW flow, gas valve and 120 V output status, and gas type.

This page lists 30 Modbus registers for the Weil-McLain Unity 2 control (ECO Tec 80-199, SVF 500/600 boilers) — 0 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Weil-McLain’s own free documentation (linked below) and checked against it.

Manufacturer
Weil-McLain
Model
Unity 2 control (ECO Tec 80-199, SVF 500/600 boilers)
Equipment type
Boiler
Registers
30 (0 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Documented addressing
hexadecimal, 0-based
Also known as
ECO Tec 80, ECO Tec 110, ECO Tec 150, ECO Tec 199, ECO Tec Combi, SVF 500, SVF 600, Unity2
Source document
Unity 2 Control Modbus Supplement - Software Interface Specification (Eco Tec 80/110/150/199 and SVF 500/600) · 550-100-266/1023 · rev. 2023-10
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Weil-McLain Unity 2 control (ECO Tec 80-199, SVF 500/600 boilers)

Integration in brief

Enable Modbus on the boiler's contractor menu, match address/baud/parity/stop bits, then read 0xA002-0xA01E with function 03 for state, firing and temperatures.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 40962Boiler stateUINT16Boiler stateRead
HR 40967Modulation percentageUINT16Modulation %Read
HR 40970Target temperatureUINT16Target temperatureRead
HR 40971Boiler out 1 temperatureUINT16Boiler outlet temperatureRead
HR 40973Boiler in temperatureUINT16Boiler inlet temperatureRead
HR 40978Outdoor temperatureINT16Outdoor temperatureRead

Enable Modbus control & writes

Contractor menu (press and hold the WM logo on the home screen) > Modbus settings: set Enable = YES, address, parity, baud and stop bits. BMS wiring is J12-1 (A+), J12-2 (B-), J12-5 (common).

Byte order & addressing

Network setup

Watch out for

Weil-McLain Unity 2 control (ECO Tec 80-199, SVF 500/600 boilers) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

30 of 30 shown
Weil-McLain Unity 2 control (ECO Tec 80-199, SVF 500/600 boilers) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR40961doc 40961 / 0xA001Boiler modelPrinted type UINT8.UINT16Read16 = Eco Tec 80; 17 = Eco Tec 110; 18 = Eco Tec 110 Combi; 19 = Eco Tec 150; 20 = Eco Tec 150 Combi; 21 = Eco Tec 199; 22 = Eco Tec 199 Combi; 64 = SVF 500; 65 = SVF 600; 255 = Not configured
HR40962doc 40962 / 0xA002Boiler stateUINT16Read0 = Standby; 1 = Prepump; 2 = Prepurge; 3 = Ignition speed; 4 = Pre-ignition; 5 = GV open test; 6 = GV closed test; 7 = Ignition; 8 = Heating; 9 = Postpurge; 10 = Lockout; 11 = Postpump; 12 = Inter-purge; 13 = Init; 14 = Config check
HR40963doc 40963 / 0xA003Active inputsNo value coding given in the list.UINT16Read
HR40964doc 40964 / 0xA004Active priorityPrinted type UINT8.UINT16Read0 = Local priority 1; 1 = Network 1; 2 = Network 2; 3 = Local priority 2; 4 = Local priority 3; 6 = Freeze protection; 7 = System pump; 8 = Priority off; 9 = No active priority
HR40965doc 40965 / 0xA005Desired blower speedUINT16rpmRead
HR40966doc 40966 / 0xA006Actual blower speedUINT16rpmRead
HR40967doc 40967 / 0xA007Modulation percentageUINT16× 0.1%Read
HR40968doc 40968 / 0xA008Desired blower PWMUINT16Read
HR40969doc 40969 / 0xA009Flame signal23 = 2.3 µA.UINT16× 0.1µARead
HR40970doc 40970 / 0xA00ATarget temperatureDegrees F; 1233-1237 are sensor fault codes.UINT16°FRead1233 = No sensor; 1234 = Sensor shorted; 1235 = Sensor open; 1236 = Redundant sensor failed; 1237 = Lost communications to sensor
HR40971doc 40971 / 0xA00BBoiler out 1 temperatureDegrees F; 1233-1237 are sensor fault codes.UINT16°FRead1233 = No sensor; 1234 = Sensor shorted; 1235 = Sensor open; 1236 = Redundant sensor failed; 1237 = Lost communications to sensor
HR40972doc 40972 / 0xA00CBoiler out 2 temperatureDegrees F; 1233-1237 are sensor fault codes.UINT16°FRead1233 = No sensor; 1234 = Sensor shorted; 1235 = Sensor open; 1236 = Redundant sensor failed; 1237 = Lost communications to sensor
HR40973doc 40973 / 0xA00DBoiler in temperatureDegrees F; 1233-1237 are sensor fault codes.UINT16°FRead1233 = No sensor; 1234 = Sensor shorted; 1235 = Sensor open; 1236 = Redundant sensor failed; 1237 = Lost communications to sensor
HR40974doc 40974 / 0xA00EFlue 1 temperatureDegrees F; 1233-1237 are sensor fault codes.INT16°FRead1233 = No sensor; 1234 = Sensor shorted; 1235 = Sensor open; 1236 = Redundant sensor failed; 1237 = Lost communications to sensor
HR40975doc 40975 / 0xA00FFlue 2 temperatureDegrees F; 1233-1237 are sensor fault codes.INT16°FRead1233 = No sensor; 1234 = Sensor shorted; 1235 = Sensor open; 1236 = Redundant sensor failed; 1237 = Lost communications to sensor
HR40976doc 40976 / 0xA010System supply temperatureDegrees F; 1233-1237 are sensor fault codes.UINT16°FRead1233 = No sensor; 1234 = Sensor shorted; 1235 = Sensor open; 1236 = Redundant sensor failed; 1237 = Lost communications to sensor
HR40977doc 40977 / 0xA011System return temperatureDegrees F; 1233-1237 are sensor fault codes.UINT16°FRead1233 = No sensor; 1234 = Sensor shorted; 1235 = Sensor open; 1236 = Redundant sensor failed; 1237 = Lost communications to sensor
HR40978doc 40978 / 0xA012Outdoor temperatureDegrees F; 1233-1237 are sensor fault codes.INT16°FRead1233 = No sensor; 1234 = Sensor shorted; 1235 = Sensor open; 1236 = Redundant sensor failed; 1237 = Lost communications to sensor
HR40979doc 40979 / 0xA013DHW 1 temperatureDegrees F; 1233-1237 are sensor fault codes.UINT16°FRead1233 = No sensor; 1234 = Sensor shorted; 1235 = Sensor open; 1236 = Redundant sensor failed; 1237 = Lost communications to sensor
HR40980doc 40980 / 0xA014DHW 2 temperatureDegrees F; 1233-1237 are sensor fault codes.UINT16°FRead1233 = No sensor; 1234 = Sensor shorted; 1235 = Sensor open; 1236 = Redundant sensor failed; 1237 = Lost communications to sensor
HR40982doc 40982 / 0xA016DHW flow rate35 = 3.5 GPM.UINT16× 0.1gpmRead
HR40983doc 40983 / 0xA017Gas valve relay 1UINT16Read0 = Off; 1 = On
HR40984doc 40984 / 0xA018Gas valve relay 2UINT16Read0 = Off; 1 = On
HR40985doc 40985 / 0xA019External ignition/pilot relayPrinted type UINT8.UINT16Read0 = Off; 1 = On
HR40986doc 40986 / 0xA01A120 V output 1UINT16Read0 = Off; 1 = On
HR40987doc 40987 / 0xA01B120 V output 2UINT16Read0 = Off; 1 = On
HR40988doc 40988 / 0xA01C120 V output 3UINT16Read0 = Off; 1 = On
HR40989doc 40989 / 0xA01D120 V output 4UINT16Read0 = Off; 1 = On
HR40990doc 40990 / 0xA01E120 V output 5UINT16Read0 = Off; 1 = On
HR41091doc 41091 / 0xA083Gas typePrinted type UINT8.UINT16Read0 = Natural gas; 1 = Liquid propane

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Weil-McLain Unity 2 control (ECO Tec 80-199, SVF 500/600 boilers)

What Modbus registers does the Weil-McLain Unity 2 control (ECO Tec 80-199, SVF 500/600 boilers) have?

This map lists 30 registers: 30 holding registers. 0 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Weil-McLain Unity 2 control (ECO Tec 80-199, SVF 500/600 boilers) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The supplement lists each register in decimal and hex and says the control speaks hex: use the hex value as the register address. 0xA002 (decimal 40962) is sent as 0xA002; it is not a Modicon 4xxxx number, so do not subtract 40001.

What are the minimum Modbus registers to integrate the Weil-McLain Unity 2 control (ECO Tec 80-199, SVF 500/600 boilers)?

Start with HR 40962 Boiler state (Boiler state); HR 40967 Modulation percentage (Modulation %); HR 40970 Target temperature (Target temperature); HR 40971 Boiler out 1 temperature (Boiler outlet temperature); HR 40973 Boiler in temperature (Boiler inlet temperature); HR 40978 Outdoor temperature (Outdoor temperature).

How do I enable Modbus control of the Weil-McLain Unity 2 control (ECO Tec 80-199, SVF 500/600 boilers)?

Contractor menu (press and hold the WM logo on the home screen) > Modbus settings: set Enable = YES, address, parity, baud and stop bits. BMS wiring is J12-1 (A+), J12-2 (B-), J12-5 (common).

Where is the official Weil-McLain Unity 2 control (ECO Tec 80-199, SVF 500/600 boilers) Modbus documentation?

The source is Unity 2 Control Modbus Supplement - Software Interface Specification (Eco Tec 80/110/150/199 and SVF 500/600) (550-100-266/1023), revision 2023-10, published free by Weil-McLain at https://www.weil-mclain.com/wp-content/uploads/ECT-SVF-Unity2-Control-Modbus-Supplement.pdf.

Other boilers & water heaters register maps

All boilers & water heaters Modbus register maps →

Source: Unity 2 Control Modbus Supplement - Software Interface Specification (Eco Tec 80/110/150/199 and SVF 500/600) · 550-100-266/1023 · rev. 2023-10. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.