Boiler · Modbus register map

Mestek KNSLM boiler control (KN2 / KN4 / rAy series) Modbus register map

Updated 17 November 2026

Short answer

The KNSLM is the boiler control named in this Mestek register list for the KN2, KN4 and rAy series; one connected (master) boiler can report on up to 15 member boilers. Over Modbus a BMS sets heat demand, system and outdoor-reset setpoints and the clock through holding registers, and reads header, supply, return and outdoor temperatures plus per-boiler status flags, runtimes, cycle counts and modulation through input registers.

This page lists 192 Modbus registers for the Mestek KNSLM boiler control (KN2 / KN4 / rAy series) — 17 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Mestek’s own free documentation (linked below) and checked against it.

Manufacturer
Mestek
Model
KNSLM boiler control (KN2 / KN4 / rAy series)
Equipment type
Boiler
Registers
192 (17 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
ABCD high word first (big-endian)
Firmware
V1.10 list; some registers 2.70+
Also known as
KNSLM, KN2, KN4, rAy
Source document
KNSLM (KN2/KN4/rAy) Series Boiler - Modbus Registers · V1.10 · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Mestek KNSLM boiler control (KN2 / KN4 / rAy series)

Integration in brief

Write the system setpoint (40003) and heat demand (40001), and keep reloading the setpoint timer (40002) so the boiler does not fall back to its local setpoint. Poll input registers 30001-30006 for system temperatures and the boiler status blocks for alarms.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 0Heat demandUINT16Heat demandRead/write
HR 1Setpoint timerUINT16Setpoint failsafe timerRead/write
HR 2System setpointUINT16System setpointRead/write
IR 2Header / system temperatureINT16Header temperatureRead
IR 3Supply temperatureINT16Supply temperatureRead
IR 4Return temperatureINT16Return temperatureRead
IR 16Boiler 01 status 2BITMAP16Master boiler status 2 (alarm / failed / running)Read
IR 239Operating setpointINT16Active operating setpointRead

Enable Modbus control & writes

Not described in this register list; set up Modbus in the boiler control as per the boiler manual.

Communication loss & watchdog

Setpoint timer 40002: if it counts down to zero the control assumes the BMS has failed and reloads its saved local setpoint. Writing any read/write register reloads it to 60 s if it is below 60 (firmware 2.70+; older firmware only on a setpoint write).

Byte order & addressing

Watch out for

Mestek KNSLM boiler control (KN2 / KN4 / rAy series) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

192 of 192 shown
Mestek KNSLM boiler control (KN2 / KN4 / rAy series) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR0doc 30001Boilers onNumber of boilers running, 0-16.UINT16Read
IR2doc 30003Header / system temperatureINT16× 0.01°FRead
IR3doc 30004Supply temperatureINT16× 0.01°FRead
IR4doc 30005Return temperatureINT16× 0.01°FRead
IR5doc 30006Outside air temperatureINT16× 0.01°FRead
IR6doc 30007Spare 1 raw A/DINT16Read
IR7doc 30008Spare 2 raw A/DINT16Read
IR8doc 30009Clock month0 = January ... 11 = December.UINT16Read
IR9doc 30010Clock dayUINT16Read
IR10doc 30011Clock year0-99.UINT16Read
IR11doc 30012Clock hourUINT16Read
IR12doc 30013Clock minuteUINT16Read
IR13doc 30014Clock secondUINT16Read
IR14doc 30015Clock weekday1 = Monday ... 7 = Sunday.UINT16Read
IR15doc 30016Boiler 01 status 1Boiler 1 = master.BITMAP16Readbit 1 = Blower running; bit 2 = Ignition alarm; bit 4 = High limit tripped; bit 7 = Software operator on; bit 8 = Header sensor not detected; bit 9 = Supply sensor not detected; bit 10 = Return sensor not detected; bit 11 = Outside sensor not detected; bit 13 = Combustion air damper open; bit 14 = Master boiler; bit 15 = Boiler detected
IR16doc 30017Boiler 01 status 2BITMAP16Readbit 0 = Disabled; bit 1 = Heat demand; bit 2 = Alarm; bit 3 = Failed; bit 4 = Member error; bit 5 = Boiler running; bit 6 = Pump running; bit 11 = Spare 4 (user) interlock closed; bit 13 = Water prove (flow) interlock closed; bit 15 = Main valve open
IR17doc 30018Boiler 02 status 1Boiler 2 = member 01.BITMAP16Readbit 1 = Blower running; bit 2 = Ignition alarm; bit 4 = High limit tripped; bit 7 = Software operator on; bit 8 = Header sensor not detected; bit 9 = Supply sensor not detected; bit 10 = Return sensor not detected; bit 11 = Outside sensor not detected; bit 13 = Combustion air damper open; bit 14 = Master boiler; bit 15 = Boiler detected
IR18doc 30019Boiler 02 status 2BITMAP16Readbit 0 = Disabled; bit 1 = Heat demand; bit 2 = Alarm; bit 3 = Failed; bit 4 = Member error; bit 5 = Boiler running; bit 6 = Pump running; bit 11 = Spare 4 (user) interlock closed; bit 13 = Water prove (flow) interlock closed; bit 15 = Main valve open
IR19doc 30020Boiler 03 status 1Boiler 3 = member 02.BITMAP16Readbit 1 = Blower running; bit 2 = Ignition alarm; bit 4 = High limit tripped; bit 7 = Software operator on; bit 8 = Header sensor not detected; bit 9 = Supply sensor not detected; bit 10 = Return sensor not detected; bit 11 = Outside sensor not detected; bit 13 = Combustion air damper open; bit 14 = Master boiler; bit 15 = Boiler detected
IR20doc 30021Boiler 03 status 2BITMAP16Readbit 0 = Disabled; bit 1 = Heat demand; bit 2 = Alarm; bit 3 = Failed; bit 4 = Member error; bit 5 = Boiler running; bit 6 = Pump running; bit 11 = Spare 4 (user) interlock closed; bit 13 = Water prove (flow) interlock closed; bit 15 = Main valve open
IR21doc 30022Boiler 04 status 1Boiler 4 = member 03.BITMAP16Readbit 1 = Blower running; bit 2 = Ignition alarm; bit 4 = High limit tripped; bit 7 = Software operator on; bit 8 = Header sensor not detected; bit 9 = Supply sensor not detected; bit 10 = Return sensor not detected; bit 11 = Outside sensor not detected; bit 13 = Combustion air damper open; bit 14 = Master boiler; bit 15 = Boiler detected
IR22doc 30023Boiler 04 status 2BITMAP16Readbit 0 = Disabled; bit 1 = Heat demand; bit 2 = Alarm; bit 3 = Failed; bit 4 = Member error; bit 5 = Boiler running; bit 6 = Pump running; bit 11 = Spare 4 (user) interlock closed; bit 13 = Water prove (flow) interlock closed; bit 15 = Main valve open
IR23doc 30024Boiler 05 status 1Boiler 5 = member 04.BITMAP16Readbit 1 = Blower running; bit 2 = Ignition alarm; bit 4 = High limit tripped; bit 7 = Software operator on; bit 8 = Header sensor not detected; bit 9 = Supply sensor not detected; bit 10 = Return sensor not detected; bit 11 = Outside sensor not detected; bit 13 = Combustion air damper open; bit 14 = Master boiler; bit 15 = Boiler detected
IR24doc 30025Boiler 05 status 2BITMAP16Readbit 0 = Disabled; bit 1 = Heat demand; bit 2 = Alarm; bit 3 = Failed; bit 4 = Member error; bit 5 = Boiler running; bit 6 = Pump running; bit 11 = Spare 4 (user) interlock closed; bit 13 = Water prove (flow) interlock closed; bit 15 = Main valve open
IR25doc 30026Boiler 06 status 1Boiler 6 = member 05.BITMAP16Readbit 1 = Blower running; bit 2 = Ignition alarm; bit 4 = High limit tripped; bit 7 = Software operator on; bit 8 = Header sensor not detected; bit 9 = Supply sensor not detected; bit 10 = Return sensor not detected; bit 11 = Outside sensor not detected; bit 13 = Combustion air damper open; bit 14 = Master boiler; bit 15 = Boiler detected
IR26doc 30027Boiler 06 status 2BITMAP16Readbit 0 = Disabled; bit 1 = Heat demand; bit 2 = Alarm; bit 3 = Failed; bit 4 = Member error; bit 5 = Boiler running; bit 6 = Pump running; bit 11 = Spare 4 (user) interlock closed; bit 13 = Water prove (flow) interlock closed; bit 15 = Main valve open
IR27doc 30028Boiler 07 status 1Boiler 7 = member 06.BITMAP16Readbit 1 = Blower running; bit 2 = Ignition alarm; bit 4 = High limit tripped; bit 7 = Software operator on; bit 8 = Header sensor not detected; bit 9 = Supply sensor not detected; bit 10 = Return sensor not detected; bit 11 = Outside sensor not detected; bit 13 = Combustion air damper open; bit 14 = Master boiler; bit 15 = Boiler detected
IR28doc 30029Boiler 07 status 2BITMAP16Readbit 0 = Disabled; bit 1 = Heat demand; bit 2 = Alarm; bit 3 = Failed; bit 4 = Member error; bit 5 = Boiler running; bit 6 = Pump running; bit 11 = Spare 4 (user) interlock closed; bit 13 = Water prove (flow) interlock closed; bit 15 = Main valve open
IR29doc 30030Boiler 08 status 1Boiler 8 = member 07.BITMAP16Readbit 1 = Blower running; bit 2 = Ignition alarm; bit 4 = High limit tripped; bit 7 = Software operator on; bit 8 = Header sensor not detected; bit 9 = Supply sensor not detected; bit 10 = Return sensor not detected; bit 11 = Outside sensor not detected; bit 13 = Combustion air damper open; bit 14 = Master boiler; bit 15 = Boiler detected
IR30doc 30031Boiler 08 status 2BITMAP16Readbit 0 = Disabled; bit 1 = Heat demand; bit 2 = Alarm; bit 3 = Failed; bit 4 = Member error; bit 5 = Boiler running; bit 6 = Pump running; bit 11 = Spare 4 (user) interlock closed; bit 13 = Water prove (flow) interlock closed; bit 15 = Main valve open
IR31doc 30032Boiler 09 status 1Boiler 9 = member 08.BITMAP16Readbit 1 = Blower running; bit 2 = Ignition alarm; bit 4 = High limit tripped; bit 7 = Software operator on; bit 8 = Header sensor not detected; bit 9 = Supply sensor not detected; bit 10 = Return sensor not detected; bit 11 = Outside sensor not detected; bit 13 = Combustion air damper open; bit 14 = Master boiler; bit 15 = Boiler detected
IR32doc 30033Boiler 09 status 2BITMAP16Readbit 0 = Disabled; bit 1 = Heat demand; bit 2 = Alarm; bit 3 = Failed; bit 4 = Member error; bit 5 = Boiler running; bit 6 = Pump running; bit 11 = Spare 4 (user) interlock closed; bit 13 = Water prove (flow) interlock closed; bit 15 = Main valve open
IR33doc 30034Boiler 10 status 1Boiler 10 = member 09.BITMAP16Readbit 1 = Blower running; bit 2 = Ignition alarm; bit 4 = High limit tripped; bit 7 = Software operator on; bit 8 = Header sensor not detected; bit 9 = Supply sensor not detected; bit 10 = Return sensor not detected; bit 11 = Outside sensor not detected; bit 13 = Combustion air damper open; bit 14 = Master boiler; bit 15 = Boiler detected
IR34doc 30035Boiler 10 status 2BITMAP16Readbit 0 = Disabled; bit 1 = Heat demand; bit 2 = Alarm; bit 3 = Failed; bit 4 = Member error; bit 5 = Boiler running; bit 6 = Pump running; bit 11 = Spare 4 (user) interlock closed; bit 13 = Water prove (flow) interlock closed; bit 15 = Main valve open
IR35doc 30036Boiler 11 status 1Boiler 11 = member 10.BITMAP16Readbit 1 = Blower running; bit 2 = Ignition alarm; bit 4 = High limit tripped; bit 7 = Software operator on; bit 8 = Header sensor not detected; bit 9 = Supply sensor not detected; bit 10 = Return sensor not detected; bit 11 = Outside sensor not detected; bit 13 = Combustion air damper open; bit 14 = Master boiler; bit 15 = Boiler detected
IR36doc 30037Boiler 11 status 2BITMAP16Readbit 0 = Disabled; bit 1 = Heat demand; bit 2 = Alarm; bit 3 = Failed; bit 4 = Member error; bit 5 = Boiler running; bit 6 = Pump running; bit 11 = Spare 4 (user) interlock closed; bit 13 = Water prove (flow) interlock closed; bit 15 = Main valve open
IR37doc 30038Boiler 12 status 1Boiler 12 = member 11.BITMAP16Readbit 1 = Blower running; bit 2 = Ignition alarm; bit 4 = High limit tripped; bit 7 = Software operator on; bit 8 = Header sensor not detected; bit 9 = Supply sensor not detected; bit 10 = Return sensor not detected; bit 11 = Outside sensor not detected; bit 13 = Combustion air damper open; bit 14 = Master boiler; bit 15 = Boiler detected
IR38doc 30039Boiler 12 status 2BITMAP16Readbit 0 = Disabled; bit 1 = Heat demand; bit 2 = Alarm; bit 3 = Failed; bit 4 = Member error; bit 5 = Boiler running; bit 6 = Pump running; bit 11 = Spare 4 (user) interlock closed; bit 13 = Water prove (flow) interlock closed; bit 15 = Main valve open
IR39doc 30040Boiler 13 status 1Boiler 13 = member 12.BITMAP16Readbit 1 = Blower running; bit 2 = Ignition alarm; bit 4 = High limit tripped; bit 7 = Software operator on; bit 8 = Header sensor not detected; bit 9 = Supply sensor not detected; bit 10 = Return sensor not detected; bit 11 = Outside sensor not detected; bit 13 = Combustion air damper open; bit 14 = Master boiler; bit 15 = Boiler detected
IR40doc 30041Boiler 13 status 2BITMAP16Readbit 0 = Disabled; bit 1 = Heat demand; bit 2 = Alarm; bit 3 = Failed; bit 4 = Member error; bit 5 = Boiler running; bit 6 = Pump running; bit 11 = Spare 4 (user) interlock closed; bit 13 = Water prove (flow) interlock closed; bit 15 = Main valve open
IR41doc 30042Boiler 14 status 1Boiler 14 = member 13.BITMAP16Readbit 1 = Blower running; bit 2 = Ignition alarm; bit 4 = High limit tripped; bit 7 = Software operator on; bit 8 = Header sensor not detected; bit 9 = Supply sensor not detected; bit 10 = Return sensor not detected; bit 11 = Outside sensor not detected; bit 13 = Combustion air damper open; bit 14 = Master boiler; bit 15 = Boiler detected
IR42doc 30043Boiler 14 status 2BITMAP16Readbit 0 = Disabled; bit 1 = Heat demand; bit 2 = Alarm; bit 3 = Failed; bit 4 = Member error; bit 5 = Boiler running; bit 6 = Pump running; bit 11 = Spare 4 (user) interlock closed; bit 13 = Water prove (flow) interlock closed; bit 15 = Main valve open
IR43doc 30044Boiler 15 status 1Boiler 15 = member 14.BITMAP16Readbit 1 = Blower running; bit 2 = Ignition alarm; bit 4 = High limit tripped; bit 7 = Software operator on; bit 8 = Header sensor not detected; bit 9 = Supply sensor not detected; bit 10 = Return sensor not detected; bit 11 = Outside sensor not detected; bit 13 = Combustion air damper open; bit 14 = Master boiler; bit 15 = Boiler detected
IR44doc 30045Boiler 15 status 2BITMAP16Readbit 0 = Disabled; bit 1 = Heat demand; bit 2 = Alarm; bit 3 = Failed; bit 4 = Member error; bit 5 = Boiler running; bit 6 = Pump running; bit 11 = Spare 4 (user) interlock closed; bit 13 = Water prove (flow) interlock closed; bit 15 = Main valve open
IR45doc 30046Boiler 16 status 1Boiler 16 = member 15.BITMAP16Readbit 1 = Blower running; bit 2 = Ignition alarm; bit 4 = High limit tripped; bit 7 = Software operator on; bit 8 = Header sensor not detected; bit 9 = Supply sensor not detected; bit 10 = Return sensor not detected; bit 11 = Outside sensor not detected; bit 13 = Combustion air damper open; bit 14 = Master boiler; bit 15 = Boiler detected
IR46doc 30047Boiler 16 status 2BITMAP16Readbit 0 = Disabled; bit 1 = Heat demand; bit 2 = Alarm; bit 3 = Failed; bit 4 = Member error; bit 5 = Boiler running; bit 6 = Pump running; bit 11 = Spare 4 (user) interlock closed; bit 13 = Water prove (flow) interlock closed; bit 15 = Main valve open
IR47doc 30048Boiler 01 runtimeUINT32ABCDsRead
IR49doc 30050Boiler 02 runtimeUINT32ABCDsRead
IR51doc 30052Boiler 03 runtimeUINT32ABCDsRead
IR53doc 30054Boiler 04 runtimeUINT32ABCDsRead
IR55doc 30056Boiler 05 runtimeUINT32ABCDsRead
IR57doc 30058Boiler 06 runtimeUINT32ABCDsRead
IR59doc 30060Boiler 07 runtimeUINT32ABCDsRead
IR61doc 30062Boiler 08 runtimeUINT32ABCDsRead
IR63doc 30064Boiler 09 runtimeUINT32ABCDsRead
IR65doc 30066Boiler 10 runtimeUINT32ABCDsRead
IR67doc 30068Boiler 11 runtimeUINT32ABCDsRead
IR69doc 30070Boiler 12 runtimeUINT32ABCDsRead
IR71doc 30072Boiler 13 runtimeUINT32ABCDsRead
IR73doc 30074Boiler 14 runtimeUINT32ABCDsRead
IR75doc 30076Boiler 15 runtimeUINT32ABCDsRead
IR77doc 30078Boiler 16 runtimeUINT32ABCDsRead
IR79doc 30080Boiler 01 status 3BITMAP16Readbit 0 = AA high fire input; bit 1 = Heat demand input (local override); bit 2 = 4-20 mA remote enable input
IR80doc 30081Boiler 02 status 3BITMAP16Readbit 0 = AA high fire input; bit 1 = Heat demand input (local override); bit 2 = 4-20 mA remote enable input
IR81doc 30082Boiler 03 status 3BITMAP16Readbit 0 = AA high fire input; bit 1 = Heat demand input (local override); bit 2 = 4-20 mA remote enable input
IR82doc 30083Boiler 04 status 3BITMAP16Readbit 0 = AA high fire input; bit 1 = Heat demand input (local override); bit 2 = 4-20 mA remote enable input
IR83doc 30084Boiler 05 status 3BITMAP16Readbit 0 = AA high fire input; bit 1 = Heat demand input (local override); bit 2 = 4-20 mA remote enable input
IR84doc 30085Boiler 06 status 3BITMAP16Readbit 0 = AA high fire input; bit 1 = Heat demand input (local override); bit 2 = 4-20 mA remote enable input
IR85doc 30086Boiler 07 status 3BITMAP16Readbit 0 = AA high fire input; bit 1 = Heat demand input (local override); bit 2 = 4-20 mA remote enable input
IR86doc 30087Boiler 08 status 3BITMAP16Readbit 0 = AA high fire input; bit 1 = Heat demand input (local override); bit 2 = 4-20 mA remote enable input
IR87doc 30088Boiler 09 status 3BITMAP16Readbit 0 = AA high fire input; bit 1 = Heat demand input (local override); bit 2 = 4-20 mA remote enable input
IR88doc 30089Boiler 10 status 3BITMAP16Readbit 0 = AA high fire input; bit 1 = Heat demand input (local override); bit 2 = 4-20 mA remote enable input
IR89doc 30090Boiler 11 status 3BITMAP16Readbit 0 = AA high fire input; bit 1 = Heat demand input (local override); bit 2 = 4-20 mA remote enable input
IR90doc 30091Boiler 12 status 3BITMAP16Readbit 0 = AA high fire input; bit 1 = Heat demand input (local override); bit 2 = 4-20 mA remote enable input
IR91doc 30092Boiler 13 status 3BITMAP16Readbit 0 = AA high fire input; bit 1 = Heat demand input (local override); bit 2 = 4-20 mA remote enable input
IR92doc 30093Boiler 14 status 3BITMAP16Readbit 0 = AA high fire input; bit 1 = Heat demand input (local override); bit 2 = 4-20 mA remote enable input
IR93doc 30094Boiler 15 status 3BITMAP16Readbit 0 = AA high fire input; bit 1 = Heat demand input (local override); bit 2 = 4-20 mA remote enable input
IR94doc 30095Boiler 16 status 3BITMAP16Readbit 0 = AA high fire input; bit 1 = Heat demand input (local override); bit 2 = 4-20 mA remote enable input
IR95doc 30096Boiler 01 supply temperatureIf the sensor is present (status 2).INT16× 0.01°FRead
IR96doc 30097Boiler 02 supply temperatureIf the sensor is present (status 2).INT16× 0.01°FRead
IR97doc 30098Boiler 03 supply temperatureIf the sensor is present (status 2).INT16× 0.01°FRead
IR98doc 30099Boiler 04 supply temperatureIf the sensor is present (status 2).INT16× 0.01°FRead
IR99doc 30100Boiler 05 supply temperatureIf the sensor is present (status 2).INT16× 0.01°FRead
IR100doc 30101Boiler 06 supply temperatureIf the sensor is present (status 2).INT16× 0.01°FRead
IR101doc 30102Boiler 07 supply temperatureIf the sensor is present (status 2).INT16× 0.01°FRead
IR102doc 30103Boiler 08 supply temperatureIf the sensor is present (status 2).INT16× 0.01°FRead
IR103doc 30104Boiler 09 supply temperatureIf the sensor is present (status 2).INT16× 0.01°FRead
IR104doc 30105Boiler 10 supply temperatureIf the sensor is present (status 2).INT16× 0.01°FRead
IR105doc 30106Boiler 11 supply temperatureIf the sensor is present (status 2).INT16× 0.01°FRead
IR106doc 30107Boiler 12 supply temperatureIf the sensor is present (status 2).INT16× 0.01°FRead
IR107doc 30108Boiler 13 supply temperatureIf the sensor is present (status 2).INT16× 0.01°FRead
IR108doc 30109Boiler 14 supply temperatureIf the sensor is present (status 2).INT16× 0.01°FRead
IR109doc 30110Boiler 15 supply temperatureIf the sensor is present (status 2).INT16× 0.01°FRead
IR110doc 30111Boiler 16 supply temperatureIf the sensor is present (status 2).INT16× 0.01°FRead
IR111doc 30112Boiler 01 return temperatureIf the sensor is present (status 2).INT16× 0.01°FRead
IR112doc 30113Boiler 02 return temperatureIf the sensor is present (status 2).INT16× 0.01°FRead
IR113doc 30114Boiler 03 return temperatureIf the sensor is present (status 2).INT16× 0.01°FRead
IR114doc 30115Boiler 04 return temperatureIf the sensor is present (status 2).INT16× 0.01°FRead
IR115doc 30116Boiler 05 return temperatureIf the sensor is present (status 2).INT16× 0.01°FRead
IR116doc 30117Boiler 06 return temperatureIf the sensor is present (status 2).INT16× 0.01°FRead
IR117doc 30118Boiler 07 return temperatureIf the sensor is present (status 2).INT16× 0.01°FRead
IR118doc 30119Boiler 08 return temperatureIf the sensor is present (status 2).INT16× 0.01°FRead
IR119doc 30120Boiler 09 return temperatureIf the sensor is present (status 2).INT16× 0.01°FRead
IR120doc 30121Boiler 10 return temperatureIf the sensor is present (status 2).INT16× 0.01°FRead
IR121doc 30122Boiler 11 return temperatureIf the sensor is present (status 2).INT16× 0.01°FRead
IR122doc 30123Boiler 12 return temperatureIf the sensor is present (status 2).INT16× 0.01°FRead
IR123doc 30124Boiler 13 return temperatureIf the sensor is present (status 2).INT16× 0.01°FRead
IR124doc 30125Boiler 14 return temperatureIf the sensor is present (status 2).INT16× 0.01°FRead
IR125doc 30126Boiler 15 return temperatureIf the sensor is present (status 2).INT16× 0.01°FRead
IR126doc 30127Boiler 16 return temperatureIf the sensor is present (status 2).INT16× 0.01°FRead
IR127doc 30128Boiler 01 cyclesUINT32ABCDRead
IR129doc 30130Boiler 02 cyclesUINT32ABCDRead
IR131doc 30132Boiler 03 cyclesUINT32ABCDRead
IR133doc 30134Boiler 04 cyclesUINT32ABCDRead
IR135doc 30136Boiler 05 cyclesUINT32ABCDRead
IR137doc 30138Boiler 06 cyclesUINT32ABCDRead
IR139doc 30140Boiler 07 cyclesUINT32ABCDRead
IR141doc 30142Boiler 08 cyclesUINT32ABCDRead
IR143doc 30144Boiler 09 cyclesUINT32ABCDRead
IR145doc 30146Boiler 10 cyclesUINT32ABCDRead
IR147doc 30148Boiler 11 cyclesUINT32ABCDRead
IR149doc 30150Boiler 12 cyclesUINT32ABCDRead
IR151doc 30152Boiler 13 cyclesUINT32ABCDRead
IR153doc 30154Boiler 14 cyclesUINT32ABCDRead
IR155doc 30156Boiler 15 cyclesUINT32ABCDRead
IR157doc 30158Boiler 16 cyclesUINT32ABCDRead
IR159doc 30160Boiler 01 status 4Firmware 2.70+.BITMAP16Readbit 0 = DHW sensor enabled; bit 1 = Damper prove; bit 3 = Blower fault; bit 4 = Blocked inlet; bit 5 = Blocked flue; bit 6 = DHW input; bit 7 = Low fire input; bit 8 = DHW fault; bit 9 = DHW sensor not detected; bit 11 = Operating limit clamp
IR160doc 30161Boiler 02 status 4Firmware 2.70+.BITMAP16Readbit 0 = DHW sensor enabled; bit 1 = Damper prove; bit 3 = Blower fault; bit 4 = Blocked inlet; bit 5 = Blocked flue; bit 6 = DHW input; bit 7 = Low fire input; bit 8 = DHW fault; bit 9 = DHW sensor not detected; bit 11 = Operating limit clamp
IR161doc 30162Boiler 03 status 4Firmware 2.70+.BITMAP16Readbit 0 = DHW sensor enabled; bit 1 = Damper prove; bit 3 = Blower fault; bit 4 = Blocked inlet; bit 5 = Blocked flue; bit 6 = DHW input; bit 7 = Low fire input; bit 8 = DHW fault; bit 9 = DHW sensor not detected; bit 11 = Operating limit clamp
IR162doc 30163Boiler 04 status 4Firmware 2.70+.BITMAP16Readbit 0 = DHW sensor enabled; bit 1 = Damper prove; bit 3 = Blower fault; bit 4 = Blocked inlet; bit 5 = Blocked flue; bit 6 = DHW input; bit 7 = Low fire input; bit 8 = DHW fault; bit 9 = DHW sensor not detected; bit 11 = Operating limit clamp
IR163doc 30164Boiler 05 status 4Firmware 2.70+.BITMAP16Readbit 0 = DHW sensor enabled; bit 1 = Damper prove; bit 3 = Blower fault; bit 4 = Blocked inlet; bit 5 = Blocked flue; bit 6 = DHW input; bit 7 = Low fire input; bit 8 = DHW fault; bit 9 = DHW sensor not detected; bit 11 = Operating limit clamp
IR164doc 30165Boiler 06 status 4Firmware 2.70+.BITMAP16Readbit 0 = DHW sensor enabled; bit 1 = Damper prove; bit 3 = Blower fault; bit 4 = Blocked inlet; bit 5 = Blocked flue; bit 6 = DHW input; bit 7 = Low fire input; bit 8 = DHW fault; bit 9 = DHW sensor not detected; bit 11 = Operating limit clamp
IR165doc 30166Boiler 07 status 4Firmware 2.70+.BITMAP16Readbit 0 = DHW sensor enabled; bit 1 = Damper prove; bit 3 = Blower fault; bit 4 = Blocked inlet; bit 5 = Blocked flue; bit 6 = DHW input; bit 7 = Low fire input; bit 8 = DHW fault; bit 9 = DHW sensor not detected; bit 11 = Operating limit clamp
IR166doc 30167Boiler 08 status 4Firmware 2.70+.BITMAP16Readbit 0 = DHW sensor enabled; bit 1 = Damper prove; bit 3 = Blower fault; bit 4 = Blocked inlet; bit 5 = Blocked flue; bit 6 = DHW input; bit 7 = Low fire input; bit 8 = DHW fault; bit 9 = DHW sensor not detected; bit 11 = Operating limit clamp
IR167doc 30168Boiler 09 status 4Firmware 2.70+.BITMAP16Readbit 0 = DHW sensor enabled; bit 1 = Damper prove; bit 3 = Blower fault; bit 4 = Blocked inlet; bit 5 = Blocked flue; bit 6 = DHW input; bit 7 = Low fire input; bit 8 = DHW fault; bit 9 = DHW sensor not detected; bit 11 = Operating limit clamp
IR168doc 30169Boiler 10 status 4Firmware 2.70+.BITMAP16Readbit 0 = DHW sensor enabled; bit 1 = Damper prove; bit 3 = Blower fault; bit 4 = Blocked inlet; bit 5 = Blocked flue; bit 6 = DHW input; bit 7 = Low fire input; bit 8 = DHW fault; bit 9 = DHW sensor not detected; bit 11 = Operating limit clamp
IR169doc 30170Boiler 11 status 4Firmware 2.70+.BITMAP16Readbit 0 = DHW sensor enabled; bit 1 = Damper prove; bit 3 = Blower fault; bit 4 = Blocked inlet; bit 5 = Blocked flue; bit 6 = DHW input; bit 7 = Low fire input; bit 8 = DHW fault; bit 9 = DHW sensor not detected; bit 11 = Operating limit clamp
IR170doc 30171Boiler 12 status 4Firmware 2.70+.BITMAP16Readbit 0 = DHW sensor enabled; bit 1 = Damper prove; bit 3 = Blower fault; bit 4 = Blocked inlet; bit 5 = Blocked flue; bit 6 = DHW input; bit 7 = Low fire input; bit 8 = DHW fault; bit 9 = DHW sensor not detected; bit 11 = Operating limit clamp
IR171doc 30172Boiler 13 status 4Firmware 2.70+.BITMAP16Readbit 0 = DHW sensor enabled; bit 1 = Damper prove; bit 3 = Blower fault; bit 4 = Blocked inlet; bit 5 = Blocked flue; bit 6 = DHW input; bit 7 = Low fire input; bit 8 = DHW fault; bit 9 = DHW sensor not detected; bit 11 = Operating limit clamp
IR172doc 30173Boiler 14 status 4Firmware 2.70+.BITMAP16Readbit 0 = DHW sensor enabled; bit 1 = Damper prove; bit 3 = Blower fault; bit 4 = Blocked inlet; bit 5 = Blocked flue; bit 6 = DHW input; bit 7 = Low fire input; bit 8 = DHW fault; bit 9 = DHW sensor not detected; bit 11 = Operating limit clamp
IR173doc 30174Boiler 15 status 4Firmware 2.70+.BITMAP16Readbit 0 = DHW sensor enabled; bit 1 = Damper prove; bit 3 = Blower fault; bit 4 = Blocked inlet; bit 5 = Blocked flue; bit 6 = DHW input; bit 7 = Low fire input; bit 8 = DHW fault; bit 9 = DHW sensor not detected; bit 11 = Operating limit clamp
IR174doc 30175Boiler 16 status 4Firmware 2.70+.BITMAP16Readbit 0 = DHW sensor enabled; bit 1 = Damper prove; bit 3 = Blower fault; bit 4 = Blocked inlet; bit 5 = Blocked flue; bit 6 = DHW input; bit 7 = Low fire input; bit 8 = DHW fault; bit 9 = DHW sensor not detected; bit 11 = Operating limit clamp
IR207doc 30208Boiler 01 DHW temperatureIf available; firmware 2.70+.INT16°FRead
IR208doc 30209Boiler 02 DHW temperatureIf available; firmware 2.70+.INT16°FRead
IR209doc 30210Boiler 03 DHW temperatureIf available; firmware 2.70+.INT16°FRead
IR210doc 30211Boiler 04 DHW temperatureIf available; firmware 2.70+.INT16°FRead
IR211doc 30212Boiler 05 DHW temperatureIf available; firmware 2.70+.INT16°FRead
IR212doc 30213Boiler 06 DHW temperatureIf available; firmware 2.70+.INT16°FRead
IR213doc 30214Boiler 07 DHW temperatureIf available; firmware 2.70+.INT16°FRead
IR214doc 30215Boiler 08 DHW temperatureIf available; firmware 2.70+.INT16°FRead
IR215doc 30216Boiler 09 DHW temperatureIf available; firmware 2.70+.INT16°FRead
IR216doc 30217Boiler 10 DHW temperatureIf available; firmware 2.70+.INT16°FRead
IR217doc 30218Boiler 11 DHW temperatureIf available; firmware 2.70+.INT16°FRead
IR218doc 30219Boiler 12 DHW temperatureIf available; firmware 2.70+.INT16°FRead
IR219doc 30220Boiler 13 DHW temperatureIf available; firmware 2.70+.INT16°FRead
IR220doc 30221Boiler 14 DHW temperatureIf available; firmware 2.70+.INT16°FRead
IR221doc 30222Boiler 15 DHW temperatureIf available; firmware 2.70+.INT16°FRead
IR222doc 30223Boiler 16 DHW temperatureIf available; firmware 2.70+.INT16°FRead
IR223doc 30224Boiler 01 running modulationDisplayed running modulation, 0-100.INT16Read
IR224doc 30225Boiler 02 running modulationDisplayed running modulation, 0-100.INT16Read
IR225doc 30226Boiler 03 running modulationDisplayed running modulation, 0-100.INT16Read
IR226doc 30227Boiler 04 running modulationDisplayed running modulation, 0-100.INT16Read
IR227doc 30228Boiler 05 running modulationDisplayed running modulation, 0-100.INT16Read
IR228doc 30229Boiler 06 running modulationDisplayed running modulation, 0-100.INT16Read
IR229doc 30230Boiler 07 running modulationDisplayed running modulation, 0-100.INT16Read
IR230doc 30231Boiler 08 running modulationDisplayed running modulation, 0-100.INT16Read
IR231doc 30232Boiler 09 running modulationDisplayed running modulation, 0-100.INT16Read
IR232doc 30233Boiler 10 running modulationDisplayed running modulation, 0-100.INT16Read
IR233doc 30234Boiler 11 running modulationDisplayed running modulation, 0-100.INT16Read
IR234doc 30235Boiler 12 running modulationDisplayed running modulation, 0-100.INT16Read
IR235doc 30236Boiler 13 running modulationDisplayed running modulation, 0-100.INT16Read
IR236doc 30237Boiler 14 running modulationDisplayed running modulation, 0-100.INT16Read
IR237doc 30238Boiler 15 running modulationDisplayed running modulation, 0-100.INT16Read
IR238doc 30239Boiler 16 running modulationDisplayed running modulation, 0-100.INT16Read
IR239doc 30240Operating setpointActive setpoint: heating, DHW, outdoor reset or 4-20 mA; 40-220 °F.INT16°FRead
HR0doc 40001Heat demandUINT16Read/write0 = No heat demand; 1 = Heat demand
HR1doc 40002Setpoint timerBMS failsafe countdown; at zero the boiler reverts to its saved local setpoint.UINT16sRead/write
HR2doc 40003System setpoint40-220 °F (8-bit value).UINT16°FRead/write
HR3doc 40004Outdoor reset enableUINT16Read/write0 = Disabled; 1 = Enabled
HR4doc 40005Outdoor reset shutdown setpointOutdoor temperature at which the boiler shuts down, 40-100 °F.UINT16°FRead/write
HR5doc 40006Reset water temp at high outdoor temp60-150 °F.UINT16°FRead/write
HR6doc 40007Reset high outdoor air temp50-90 °F.UINT16°FRead/write
HR7doc 40008Reset water temp at low outdoor temp70-220 °F.UINT16°FRead/write
HR9doc 40010Set clock month0 = January ... 11 = December.UINT16Read/write
HR10doc 40011Set clock day1-31.UINT16Read/write
HR11doc 40012Set clock year0-99.UINT16Read/write
HR12doc 40013Set clock hour0-23.UINT16Read/write
HR13doc 40014Set clock minute0-59.UINT16Read/write
HR14doc 40015Set clock second0-59.UINT16Read/write
HR15doc 40016Set clock weekday1 = Monday ... 7 = Sunday.UINT16Read/write
HR16doc 40017Set clock commandLoad 40010-40016 first, then write 1.UINT16Read/write0 = No action; 1 = Write clock
HR17doc 40018DHW setpoint40-200 °F; firmware 2.70+.INT16°FRead/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Mestek KNSLM boiler control (KN2 / KN4 / rAy series)

What Modbus registers does the Mestek KNSLM boiler control (KN2 / KN4 / rAy series) have?

This map lists 192 registers: 175 input registers, 17 holding registers. 17 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Mestek KNSLM boiler control (KN2 / KN4 / rAy series) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are listed in Modicon form (40001 holding, 30001 input). Request 40001 as holding address 0 and 30001 as input address 0.

What byte order does the Mestek KNSLM boiler control (KN2 / KN4 / rAy series) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Mestek KNSLM boiler control (KN2 / KN4 / rAy series)?

Start with HR 0 Heat demand (Heat demand); HR 1 Setpoint timer (Setpoint failsafe timer); HR 2 System setpoint (System setpoint); IR 2 Header / system temperature (Header temperature); IR 3 Supply temperature (Supply temperature); IR 4 Return temperature (Return temperature); IR 16 Boiler 01 status 2 (Master boiler status 2 (alarm / failed / running)); IR 239 Operating setpoint (Active operating setpoint).

How do I enable Modbus control of the Mestek KNSLM boiler control (KN2 / KN4 / rAy series)?

Not described in this register list; set up Modbus in the boiler control as per the boiler manual.

What happens when the Mestek KNSLM boiler control (KN2 / KN4 / rAy series) loses Modbus communication?

Setpoint timer 40002: if it counts down to zero the control assumes the BMS has failed and reloads its saved local setpoint. Writing any read/write register reloads it to 60 s if it is below 60 (firmware 2.70+; older firmware only on a setpoint write).

Where is the official Mestek KNSLM boiler control (KN2 / KN4 / rAy series) Modbus documentation?

The source is KNSLM (KN2/KN4/rAy) Series Boiler - Modbus Registers (V1.10). Mestek doesn't publish it on its own website, so this map was re-typed from a free copy at https://www.ccontrols.com/support/dp/KNSLM.pdf. It may be an older revision, so check it against the live unit.

Other boilers & water heaters register maps

All boilers & water heaters Modbus register maps →

Source: KNSLM (KN2/KN4/rAy) Series Boiler - Modbus Registers · V1.10 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.