- Home
- Modbus register maps
- Mestek
- KNSLM boiler control (KN2 / KN4 / rAy series)
Boiler · Modbus register map
Mestek KNSLM boiler control (KN2 / KN4 / rAy series) Modbus register map
Updated 17 November 2026
The KNSLM is the boiler control named in this Mestek register list for the KN2, KN4 and rAy series; one connected (master) boiler can report on up to 15 member boilers. Over Modbus a BMS sets heat demand, system and outdoor-reset setpoints and the clock through holding registers, and reads header, supply, return and outdoor temperatures plus per-boiler status flags, runtimes, cycle counts and modulation through input registers.
This page lists 192 Modbus registers for the Mestek KNSLM boiler control (KN2 / KN4 / rAy series) — 17 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Mestek’s own free documentation (linked below) and checked against it.
- Manufacturer
- Mestek
- Model
- KNSLM boiler control (KN2 / KN4 / rAy series)
- Equipment type
- Boiler
- Registers
- 192 (17 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- ABCD high word first (big-endian)
- Firmware
- V1.10 list; some registers 2.70+
- Also known as
- KNSLM, KN2, KN4, rAy
Integration notes: Mestek KNSLM boiler control (KN2 / KN4 / rAy series)
Write the system setpoint (40003) and heat demand (40001), and keep reloading the setpoint timer (40002) so the boiler does not fall back to its local setpoint. Poll input registers 30001-30006 for system temperatures and the boiler status blocks for alarms.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 0 | Heat demand | UINT16 | Heat demand | Read/write |
| HR 1 | Setpoint timer | UINT16 | Setpoint failsafe timer | Read/write |
| HR 2 | System setpoint | UINT16 | System setpoint | Read/write |
| IR 2 | Header / system temperature | INT16 | Header temperature | Read |
| IR 3 | Supply temperature | INT16 | Supply temperature | Read |
| IR 4 | Return temperature | INT16 | Return temperature | Read |
| IR 16 | Boiler 01 status 2 | BITMAP16 | Master boiler status 2 (alarm / failed / running) | Read |
| IR 239 | Operating setpoint | INT16 | Active operating setpoint | Read |
Enable Modbus control & writes
Not described in this register list; set up Modbus in the boiler control as per the boiler manual.
Communication loss & watchdog
Setpoint timer 40002: if it counts down to zero the control assumes the BMS has failed and reloads its saved local setpoint. Writing any read/write register reloads it to 60 s if it is below 60 (firmware 2.70+; older firmware only on a setpoint write).
Byte order & addressing
- Writing the clock is a two-step operation: load 40010-40016, then write 1 to 40017.
Watch out for
- Temperatures are in °F with 0.01 resolution for the system sensors but whole °F for setpoints and DHW values.
Mestek KNSLM boiler control (KN2 / KN4 / rAy series) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 0doc 30001 | Boilers on | Number of boilers running, 0-16. | UINT16 | Read | ||||
| IR | 2doc 30003 | Header / system temperature | INT16 | × 0.01 | °F | Read | |||
| IR | 3doc 30004 | Supply temperature | INT16 | × 0.01 | °F | Read | |||
| IR | 4doc 30005 | Return temperature | INT16 | × 0.01 | °F | Read | |||
| IR | 5doc 30006 | Outside air temperature | INT16 | × 0.01 | °F | Read | |||
| IR | 6doc 30007 | Spare 1 raw A/D | INT16 | Read | |||||
| IR | 7doc 30008 | Spare 2 raw A/D | INT16 | Read | |||||
| IR | 8doc 30009 | Clock month | 0 = January ... 11 = December. | UINT16 | Read | ||||
| IR | 9doc 30010 | Clock day | UINT16 | Read | |||||
| IR | 10doc 30011 | Clock year | 0-99. | UINT16 | Read | ||||
| IR | 11doc 30012 | Clock hour | UINT16 | Read | |||||
| IR | 12doc 30013 | Clock minute | UINT16 | Read | |||||
| IR | 13doc 30014 | Clock second | UINT16 | Read | |||||
| IR | 14doc 30015 | Clock weekday | 1 = Monday ... 7 = Sunday. | UINT16 | Read | ||||
| IR | 15doc 30016 | Boiler 01 status 1 | Boiler 1 = master. | BITMAP16 | Read | bit 1 = Blower running; bit 2 = Ignition alarm; bit 4 = High limit tripped; bit 7 = Software operator on; bit 8 = Header sensor not detected; bit 9 = Supply sensor not detected; bit 10 = Return sensor not detected; bit 11 = Outside sensor not detected; bit 13 = Combustion air damper open; bit 14 = Master boiler; bit 15 = Boiler detected | |||
| IR | 16doc 30017 | Boiler 01 status 2 | BITMAP16 | Read | bit 0 = Disabled; bit 1 = Heat demand; bit 2 = Alarm; bit 3 = Failed; bit 4 = Member error; bit 5 = Boiler running; bit 6 = Pump running; bit 11 = Spare 4 (user) interlock closed; bit 13 = Water prove (flow) interlock closed; bit 15 = Main valve open | ||||
| IR | 17doc 30018 | Boiler 02 status 1 | Boiler 2 = member 01. | BITMAP16 | Read | bit 1 = Blower running; bit 2 = Ignition alarm; bit 4 = High limit tripped; bit 7 = Software operator on; bit 8 = Header sensor not detected; bit 9 = Supply sensor not detected; bit 10 = Return sensor not detected; bit 11 = Outside sensor not detected; bit 13 = Combustion air damper open; bit 14 = Master boiler; bit 15 = Boiler detected | |||
| IR | 18doc 30019 | Boiler 02 status 2 | BITMAP16 | Read | bit 0 = Disabled; bit 1 = Heat demand; bit 2 = Alarm; bit 3 = Failed; bit 4 = Member error; bit 5 = Boiler running; bit 6 = Pump running; bit 11 = Spare 4 (user) interlock closed; bit 13 = Water prove (flow) interlock closed; bit 15 = Main valve open | ||||
| IR | 19doc 30020 | Boiler 03 status 1 | Boiler 3 = member 02. | BITMAP16 | Read | bit 1 = Blower running; bit 2 = Ignition alarm; bit 4 = High limit tripped; bit 7 = Software operator on; bit 8 = Header sensor not detected; bit 9 = Supply sensor not detected; bit 10 = Return sensor not detected; bit 11 = Outside sensor not detected; bit 13 = Combustion air damper open; bit 14 = Master boiler; bit 15 = Boiler detected | |||
| IR | 20doc 30021 | Boiler 03 status 2 | BITMAP16 | Read | bit 0 = Disabled; bit 1 = Heat demand; bit 2 = Alarm; bit 3 = Failed; bit 4 = Member error; bit 5 = Boiler running; bit 6 = Pump running; bit 11 = Spare 4 (user) interlock closed; bit 13 = Water prove (flow) interlock closed; bit 15 = Main valve open | ||||
| IR | 21doc 30022 | Boiler 04 status 1 | Boiler 4 = member 03. | BITMAP16 | Read | bit 1 = Blower running; bit 2 = Ignition alarm; bit 4 = High limit tripped; bit 7 = Software operator on; bit 8 = Header sensor not detected; bit 9 = Supply sensor not detected; bit 10 = Return sensor not detected; bit 11 = Outside sensor not detected; bit 13 = Combustion air damper open; bit 14 = Master boiler; bit 15 = Boiler detected | |||
| IR | 22doc 30023 | Boiler 04 status 2 | BITMAP16 | Read | bit 0 = Disabled; bit 1 = Heat demand; bit 2 = Alarm; bit 3 = Failed; bit 4 = Member error; bit 5 = Boiler running; bit 6 = Pump running; bit 11 = Spare 4 (user) interlock closed; bit 13 = Water prove (flow) interlock closed; bit 15 = Main valve open | ||||
| IR | 23doc 30024 | Boiler 05 status 1 | Boiler 5 = member 04. | BITMAP16 | Read | bit 1 = Blower running; bit 2 = Ignition alarm; bit 4 = High limit tripped; bit 7 = Software operator on; bit 8 = Header sensor not detected; bit 9 = Supply sensor not detected; bit 10 = Return sensor not detected; bit 11 = Outside sensor not detected; bit 13 = Combustion air damper open; bit 14 = Master boiler; bit 15 = Boiler detected | |||
| IR | 24doc 30025 | Boiler 05 status 2 | BITMAP16 | Read | bit 0 = Disabled; bit 1 = Heat demand; bit 2 = Alarm; bit 3 = Failed; bit 4 = Member error; bit 5 = Boiler running; bit 6 = Pump running; bit 11 = Spare 4 (user) interlock closed; bit 13 = Water prove (flow) interlock closed; bit 15 = Main valve open | ||||
| IR | 25doc 30026 | Boiler 06 status 1 | Boiler 6 = member 05. | BITMAP16 | Read | bit 1 = Blower running; bit 2 = Ignition alarm; bit 4 = High limit tripped; bit 7 = Software operator on; bit 8 = Header sensor not detected; bit 9 = Supply sensor not detected; bit 10 = Return sensor not detected; bit 11 = Outside sensor not detected; bit 13 = Combustion air damper open; bit 14 = Master boiler; bit 15 = Boiler detected | |||
| IR | 26doc 30027 | Boiler 06 status 2 | BITMAP16 | Read | bit 0 = Disabled; bit 1 = Heat demand; bit 2 = Alarm; bit 3 = Failed; bit 4 = Member error; bit 5 = Boiler running; bit 6 = Pump running; bit 11 = Spare 4 (user) interlock closed; bit 13 = Water prove (flow) interlock closed; bit 15 = Main valve open | ||||
| IR | 27doc 30028 | Boiler 07 status 1 | Boiler 7 = member 06. | BITMAP16 | Read | bit 1 = Blower running; bit 2 = Ignition alarm; bit 4 = High limit tripped; bit 7 = Software operator on; bit 8 = Header sensor not detected; bit 9 = Supply sensor not detected; bit 10 = Return sensor not detected; bit 11 = Outside sensor not detected; bit 13 = Combustion air damper open; bit 14 = Master boiler; bit 15 = Boiler detected | |||
| IR | 28doc 30029 | Boiler 07 status 2 | BITMAP16 | Read | bit 0 = Disabled; bit 1 = Heat demand; bit 2 = Alarm; bit 3 = Failed; bit 4 = Member error; bit 5 = Boiler running; bit 6 = Pump running; bit 11 = Spare 4 (user) interlock closed; bit 13 = Water prove (flow) interlock closed; bit 15 = Main valve open | ||||
| IR | 29doc 30030 | Boiler 08 status 1 | Boiler 8 = member 07. | BITMAP16 | Read | bit 1 = Blower running; bit 2 = Ignition alarm; bit 4 = High limit tripped; bit 7 = Software operator on; bit 8 = Header sensor not detected; bit 9 = Supply sensor not detected; bit 10 = Return sensor not detected; bit 11 = Outside sensor not detected; bit 13 = Combustion air damper open; bit 14 = Master boiler; bit 15 = Boiler detected | |||
| IR | 30doc 30031 | Boiler 08 status 2 | BITMAP16 | Read | bit 0 = Disabled; bit 1 = Heat demand; bit 2 = Alarm; bit 3 = Failed; bit 4 = Member error; bit 5 = Boiler running; bit 6 = Pump running; bit 11 = Spare 4 (user) interlock closed; bit 13 = Water prove (flow) interlock closed; bit 15 = Main valve open | ||||
| IR | 31doc 30032 | Boiler 09 status 1 | Boiler 9 = member 08. | BITMAP16 | Read | bit 1 = Blower running; bit 2 = Ignition alarm; bit 4 = High limit tripped; bit 7 = Software operator on; bit 8 = Header sensor not detected; bit 9 = Supply sensor not detected; bit 10 = Return sensor not detected; bit 11 = Outside sensor not detected; bit 13 = Combustion air damper open; bit 14 = Master boiler; bit 15 = Boiler detected | |||
| IR | 32doc 30033 | Boiler 09 status 2 | BITMAP16 | Read | bit 0 = Disabled; bit 1 = Heat demand; bit 2 = Alarm; bit 3 = Failed; bit 4 = Member error; bit 5 = Boiler running; bit 6 = Pump running; bit 11 = Spare 4 (user) interlock closed; bit 13 = Water prove (flow) interlock closed; bit 15 = Main valve open | ||||
| IR | 33doc 30034 | Boiler 10 status 1 | Boiler 10 = member 09. | BITMAP16 | Read | bit 1 = Blower running; bit 2 = Ignition alarm; bit 4 = High limit tripped; bit 7 = Software operator on; bit 8 = Header sensor not detected; bit 9 = Supply sensor not detected; bit 10 = Return sensor not detected; bit 11 = Outside sensor not detected; bit 13 = Combustion air damper open; bit 14 = Master boiler; bit 15 = Boiler detected | |||
| IR | 34doc 30035 | Boiler 10 status 2 | BITMAP16 | Read | bit 0 = Disabled; bit 1 = Heat demand; bit 2 = Alarm; bit 3 = Failed; bit 4 = Member error; bit 5 = Boiler running; bit 6 = Pump running; bit 11 = Spare 4 (user) interlock closed; bit 13 = Water prove (flow) interlock closed; bit 15 = Main valve open | ||||
| IR | 35doc 30036 | Boiler 11 status 1 | Boiler 11 = member 10. | BITMAP16 | Read | bit 1 = Blower running; bit 2 = Ignition alarm; bit 4 = High limit tripped; bit 7 = Software operator on; bit 8 = Header sensor not detected; bit 9 = Supply sensor not detected; bit 10 = Return sensor not detected; bit 11 = Outside sensor not detected; bit 13 = Combustion air damper open; bit 14 = Master boiler; bit 15 = Boiler detected | |||
| IR | 36doc 30037 | Boiler 11 status 2 | BITMAP16 | Read | bit 0 = Disabled; bit 1 = Heat demand; bit 2 = Alarm; bit 3 = Failed; bit 4 = Member error; bit 5 = Boiler running; bit 6 = Pump running; bit 11 = Spare 4 (user) interlock closed; bit 13 = Water prove (flow) interlock closed; bit 15 = Main valve open | ||||
| IR | 37doc 30038 | Boiler 12 status 1 | Boiler 12 = member 11. | BITMAP16 | Read | bit 1 = Blower running; bit 2 = Ignition alarm; bit 4 = High limit tripped; bit 7 = Software operator on; bit 8 = Header sensor not detected; bit 9 = Supply sensor not detected; bit 10 = Return sensor not detected; bit 11 = Outside sensor not detected; bit 13 = Combustion air damper open; bit 14 = Master boiler; bit 15 = Boiler detected | |||
| IR | 38doc 30039 | Boiler 12 status 2 | BITMAP16 | Read | bit 0 = Disabled; bit 1 = Heat demand; bit 2 = Alarm; bit 3 = Failed; bit 4 = Member error; bit 5 = Boiler running; bit 6 = Pump running; bit 11 = Spare 4 (user) interlock closed; bit 13 = Water prove (flow) interlock closed; bit 15 = Main valve open | ||||
| IR | 39doc 30040 | Boiler 13 status 1 | Boiler 13 = member 12. | BITMAP16 | Read | bit 1 = Blower running; bit 2 = Ignition alarm; bit 4 = High limit tripped; bit 7 = Software operator on; bit 8 = Header sensor not detected; bit 9 = Supply sensor not detected; bit 10 = Return sensor not detected; bit 11 = Outside sensor not detected; bit 13 = Combustion air damper open; bit 14 = Master boiler; bit 15 = Boiler detected | |||
| IR | 40doc 30041 | Boiler 13 status 2 | BITMAP16 | Read | bit 0 = Disabled; bit 1 = Heat demand; bit 2 = Alarm; bit 3 = Failed; bit 4 = Member error; bit 5 = Boiler running; bit 6 = Pump running; bit 11 = Spare 4 (user) interlock closed; bit 13 = Water prove (flow) interlock closed; bit 15 = Main valve open | ||||
| IR | 41doc 30042 | Boiler 14 status 1 | Boiler 14 = member 13. | BITMAP16 | Read | bit 1 = Blower running; bit 2 = Ignition alarm; bit 4 = High limit tripped; bit 7 = Software operator on; bit 8 = Header sensor not detected; bit 9 = Supply sensor not detected; bit 10 = Return sensor not detected; bit 11 = Outside sensor not detected; bit 13 = Combustion air damper open; bit 14 = Master boiler; bit 15 = Boiler detected | |||
| IR | 42doc 30043 | Boiler 14 status 2 | BITMAP16 | Read | bit 0 = Disabled; bit 1 = Heat demand; bit 2 = Alarm; bit 3 = Failed; bit 4 = Member error; bit 5 = Boiler running; bit 6 = Pump running; bit 11 = Spare 4 (user) interlock closed; bit 13 = Water prove (flow) interlock closed; bit 15 = Main valve open | ||||
| IR | 43doc 30044 | Boiler 15 status 1 | Boiler 15 = member 14. | BITMAP16 | Read | bit 1 = Blower running; bit 2 = Ignition alarm; bit 4 = High limit tripped; bit 7 = Software operator on; bit 8 = Header sensor not detected; bit 9 = Supply sensor not detected; bit 10 = Return sensor not detected; bit 11 = Outside sensor not detected; bit 13 = Combustion air damper open; bit 14 = Master boiler; bit 15 = Boiler detected | |||
| IR | 44doc 30045 | Boiler 15 status 2 | BITMAP16 | Read | bit 0 = Disabled; bit 1 = Heat demand; bit 2 = Alarm; bit 3 = Failed; bit 4 = Member error; bit 5 = Boiler running; bit 6 = Pump running; bit 11 = Spare 4 (user) interlock closed; bit 13 = Water prove (flow) interlock closed; bit 15 = Main valve open | ||||
| IR | 45doc 30046 | Boiler 16 status 1 | Boiler 16 = member 15. | BITMAP16 | Read | bit 1 = Blower running; bit 2 = Ignition alarm; bit 4 = High limit tripped; bit 7 = Software operator on; bit 8 = Header sensor not detected; bit 9 = Supply sensor not detected; bit 10 = Return sensor not detected; bit 11 = Outside sensor not detected; bit 13 = Combustion air damper open; bit 14 = Master boiler; bit 15 = Boiler detected | |||
| IR | 46doc 30047 | Boiler 16 status 2 | BITMAP16 | Read | bit 0 = Disabled; bit 1 = Heat demand; bit 2 = Alarm; bit 3 = Failed; bit 4 = Member error; bit 5 = Boiler running; bit 6 = Pump running; bit 11 = Spare 4 (user) interlock closed; bit 13 = Water prove (flow) interlock closed; bit 15 = Main valve open | ||||
| IR | 47doc 30048 | Boiler 01 runtime | UINT32 | ABCD | s | Read | |||
| IR | 49doc 30050 | Boiler 02 runtime | UINT32 | ABCD | s | Read | |||
| IR | 51doc 30052 | Boiler 03 runtime | UINT32 | ABCD | s | Read | |||
| IR | 53doc 30054 | Boiler 04 runtime | UINT32 | ABCD | s | Read | |||
| IR | 55doc 30056 | Boiler 05 runtime | UINT32 | ABCD | s | Read | |||
| IR | 57doc 30058 | Boiler 06 runtime | UINT32 | ABCD | s | Read | |||
| IR | 59doc 30060 | Boiler 07 runtime | UINT32 | ABCD | s | Read | |||
| IR | 61doc 30062 | Boiler 08 runtime | UINT32 | ABCD | s | Read | |||
| IR | 63doc 30064 | Boiler 09 runtime | UINT32 | ABCD | s | Read | |||
| IR | 65doc 30066 | Boiler 10 runtime | UINT32 | ABCD | s | Read | |||
| IR | 67doc 30068 | Boiler 11 runtime | UINT32 | ABCD | s | Read | |||
| IR | 69doc 30070 | Boiler 12 runtime | UINT32 | ABCD | s | Read | |||
| IR | 71doc 30072 | Boiler 13 runtime | UINT32 | ABCD | s | Read | |||
| IR | 73doc 30074 | Boiler 14 runtime | UINT32 | ABCD | s | Read | |||
| IR | 75doc 30076 | Boiler 15 runtime | UINT32 | ABCD | s | Read | |||
| IR | 77doc 30078 | Boiler 16 runtime | UINT32 | ABCD | s | Read | |||
| IR | 79doc 30080 | Boiler 01 status 3 | BITMAP16 | Read | bit 0 = AA high fire input; bit 1 = Heat demand input (local override); bit 2 = 4-20 mA remote enable input | ||||
| IR | 80doc 30081 | Boiler 02 status 3 | BITMAP16 | Read | bit 0 = AA high fire input; bit 1 = Heat demand input (local override); bit 2 = 4-20 mA remote enable input | ||||
| IR | 81doc 30082 | Boiler 03 status 3 | BITMAP16 | Read | bit 0 = AA high fire input; bit 1 = Heat demand input (local override); bit 2 = 4-20 mA remote enable input | ||||
| IR | 82doc 30083 | Boiler 04 status 3 | BITMAP16 | Read | bit 0 = AA high fire input; bit 1 = Heat demand input (local override); bit 2 = 4-20 mA remote enable input | ||||
| IR | 83doc 30084 | Boiler 05 status 3 | BITMAP16 | Read | bit 0 = AA high fire input; bit 1 = Heat demand input (local override); bit 2 = 4-20 mA remote enable input | ||||
| IR | 84doc 30085 | Boiler 06 status 3 | BITMAP16 | Read | bit 0 = AA high fire input; bit 1 = Heat demand input (local override); bit 2 = 4-20 mA remote enable input | ||||
| IR | 85doc 30086 | Boiler 07 status 3 | BITMAP16 | Read | bit 0 = AA high fire input; bit 1 = Heat demand input (local override); bit 2 = 4-20 mA remote enable input | ||||
| IR | 86doc 30087 | Boiler 08 status 3 | BITMAP16 | Read | bit 0 = AA high fire input; bit 1 = Heat demand input (local override); bit 2 = 4-20 mA remote enable input | ||||
| IR | 87doc 30088 | Boiler 09 status 3 | BITMAP16 | Read | bit 0 = AA high fire input; bit 1 = Heat demand input (local override); bit 2 = 4-20 mA remote enable input | ||||
| IR | 88doc 30089 | Boiler 10 status 3 | BITMAP16 | Read | bit 0 = AA high fire input; bit 1 = Heat demand input (local override); bit 2 = 4-20 mA remote enable input | ||||
| IR | 89doc 30090 | Boiler 11 status 3 | BITMAP16 | Read | bit 0 = AA high fire input; bit 1 = Heat demand input (local override); bit 2 = 4-20 mA remote enable input | ||||
| IR | 90doc 30091 | Boiler 12 status 3 | BITMAP16 | Read | bit 0 = AA high fire input; bit 1 = Heat demand input (local override); bit 2 = 4-20 mA remote enable input | ||||
| IR | 91doc 30092 | Boiler 13 status 3 | BITMAP16 | Read | bit 0 = AA high fire input; bit 1 = Heat demand input (local override); bit 2 = 4-20 mA remote enable input | ||||
| IR | 92doc 30093 | Boiler 14 status 3 | BITMAP16 | Read | bit 0 = AA high fire input; bit 1 = Heat demand input (local override); bit 2 = 4-20 mA remote enable input | ||||
| IR | 93doc 30094 | Boiler 15 status 3 | BITMAP16 | Read | bit 0 = AA high fire input; bit 1 = Heat demand input (local override); bit 2 = 4-20 mA remote enable input | ||||
| IR | 94doc 30095 | Boiler 16 status 3 | BITMAP16 | Read | bit 0 = AA high fire input; bit 1 = Heat demand input (local override); bit 2 = 4-20 mA remote enable input | ||||
| IR | 95doc 30096 | Boiler 01 supply temperature | If the sensor is present (status 2). | INT16 | × 0.01 | °F | Read | ||
| IR | 96doc 30097 | Boiler 02 supply temperature | If the sensor is present (status 2). | INT16 | × 0.01 | °F | Read | ||
| IR | 97doc 30098 | Boiler 03 supply temperature | If the sensor is present (status 2). | INT16 | × 0.01 | °F | Read | ||
| IR | 98doc 30099 | Boiler 04 supply temperature | If the sensor is present (status 2). | INT16 | × 0.01 | °F | Read | ||
| IR | 99doc 30100 | Boiler 05 supply temperature | If the sensor is present (status 2). | INT16 | × 0.01 | °F | Read | ||
| IR | 100doc 30101 | Boiler 06 supply temperature | If the sensor is present (status 2). | INT16 | × 0.01 | °F | Read | ||
| IR | 101doc 30102 | Boiler 07 supply temperature | If the sensor is present (status 2). | INT16 | × 0.01 | °F | Read | ||
| IR | 102doc 30103 | Boiler 08 supply temperature | If the sensor is present (status 2). | INT16 | × 0.01 | °F | Read | ||
| IR | 103doc 30104 | Boiler 09 supply temperature | If the sensor is present (status 2). | INT16 | × 0.01 | °F | Read | ||
| IR | 104doc 30105 | Boiler 10 supply temperature | If the sensor is present (status 2). | INT16 | × 0.01 | °F | Read | ||
| IR | 105doc 30106 | Boiler 11 supply temperature | If the sensor is present (status 2). | INT16 | × 0.01 | °F | Read | ||
| IR | 106doc 30107 | Boiler 12 supply temperature | If the sensor is present (status 2). | INT16 | × 0.01 | °F | Read | ||
| IR | 107doc 30108 | Boiler 13 supply temperature | If the sensor is present (status 2). | INT16 | × 0.01 | °F | Read | ||
| IR | 108doc 30109 | Boiler 14 supply temperature | If the sensor is present (status 2). | INT16 | × 0.01 | °F | Read | ||
| IR | 109doc 30110 | Boiler 15 supply temperature | If the sensor is present (status 2). | INT16 | × 0.01 | °F | Read | ||
| IR | 110doc 30111 | Boiler 16 supply temperature | If the sensor is present (status 2). | INT16 | × 0.01 | °F | Read | ||
| IR | 111doc 30112 | Boiler 01 return temperature | If the sensor is present (status 2). | INT16 | × 0.01 | °F | Read | ||
| IR | 112doc 30113 | Boiler 02 return temperature | If the sensor is present (status 2). | INT16 | × 0.01 | °F | Read | ||
| IR | 113doc 30114 | Boiler 03 return temperature | If the sensor is present (status 2). | INT16 | × 0.01 | °F | Read | ||
| IR | 114doc 30115 | Boiler 04 return temperature | If the sensor is present (status 2). | INT16 | × 0.01 | °F | Read | ||
| IR | 115doc 30116 | Boiler 05 return temperature | If the sensor is present (status 2). | INT16 | × 0.01 | °F | Read | ||
| IR | 116doc 30117 | Boiler 06 return temperature | If the sensor is present (status 2). | INT16 | × 0.01 | °F | Read | ||
| IR | 117doc 30118 | Boiler 07 return temperature | If the sensor is present (status 2). | INT16 | × 0.01 | °F | Read | ||
| IR | 118doc 30119 | Boiler 08 return temperature | If the sensor is present (status 2). | INT16 | × 0.01 | °F | Read | ||
| IR | 119doc 30120 | Boiler 09 return temperature | If the sensor is present (status 2). | INT16 | × 0.01 | °F | Read | ||
| IR | 120doc 30121 | Boiler 10 return temperature | If the sensor is present (status 2). | INT16 | × 0.01 | °F | Read | ||
| IR | 121doc 30122 | Boiler 11 return temperature | If the sensor is present (status 2). | INT16 | × 0.01 | °F | Read | ||
| IR | 122doc 30123 | Boiler 12 return temperature | If the sensor is present (status 2). | INT16 | × 0.01 | °F | Read | ||
| IR | 123doc 30124 | Boiler 13 return temperature | If the sensor is present (status 2). | INT16 | × 0.01 | °F | Read | ||
| IR | 124doc 30125 | Boiler 14 return temperature | If the sensor is present (status 2). | INT16 | × 0.01 | °F | Read | ||
| IR | 125doc 30126 | Boiler 15 return temperature | If the sensor is present (status 2). | INT16 | × 0.01 | °F | Read | ||
| IR | 126doc 30127 | Boiler 16 return temperature | If the sensor is present (status 2). | INT16 | × 0.01 | °F | Read | ||
| IR | 127doc 30128 | Boiler 01 cycles | UINT32 | ABCD | Read | ||||
| IR | 129doc 30130 | Boiler 02 cycles | UINT32 | ABCD | Read | ||||
| IR | 131doc 30132 | Boiler 03 cycles | UINT32 | ABCD | Read | ||||
| IR | 133doc 30134 | Boiler 04 cycles | UINT32 | ABCD | Read | ||||
| IR | 135doc 30136 | Boiler 05 cycles | UINT32 | ABCD | Read | ||||
| IR | 137doc 30138 | Boiler 06 cycles | UINT32 | ABCD | Read | ||||
| IR | 139doc 30140 | Boiler 07 cycles | UINT32 | ABCD | Read | ||||
| IR | 141doc 30142 | Boiler 08 cycles | UINT32 | ABCD | Read | ||||
| IR | 143doc 30144 | Boiler 09 cycles | UINT32 | ABCD | Read | ||||
| IR | 145doc 30146 | Boiler 10 cycles | UINT32 | ABCD | Read | ||||
| IR | 147doc 30148 | Boiler 11 cycles | UINT32 | ABCD | Read | ||||
| IR | 149doc 30150 | Boiler 12 cycles | UINT32 | ABCD | Read | ||||
| IR | 151doc 30152 | Boiler 13 cycles | UINT32 | ABCD | Read | ||||
| IR | 153doc 30154 | Boiler 14 cycles | UINT32 | ABCD | Read | ||||
| IR | 155doc 30156 | Boiler 15 cycles | UINT32 | ABCD | Read | ||||
| IR | 157doc 30158 | Boiler 16 cycles | UINT32 | ABCD | Read | ||||
| IR | 159doc 30160 | Boiler 01 status 4 | Firmware 2.70+. | BITMAP16 | Read | bit 0 = DHW sensor enabled; bit 1 = Damper prove; bit 3 = Blower fault; bit 4 = Blocked inlet; bit 5 = Blocked flue; bit 6 = DHW input; bit 7 = Low fire input; bit 8 = DHW fault; bit 9 = DHW sensor not detected; bit 11 = Operating limit clamp | |||
| IR | 160doc 30161 | Boiler 02 status 4 | Firmware 2.70+. | BITMAP16 | Read | bit 0 = DHW sensor enabled; bit 1 = Damper prove; bit 3 = Blower fault; bit 4 = Blocked inlet; bit 5 = Blocked flue; bit 6 = DHW input; bit 7 = Low fire input; bit 8 = DHW fault; bit 9 = DHW sensor not detected; bit 11 = Operating limit clamp | |||
| IR | 161doc 30162 | Boiler 03 status 4 | Firmware 2.70+. | BITMAP16 | Read | bit 0 = DHW sensor enabled; bit 1 = Damper prove; bit 3 = Blower fault; bit 4 = Blocked inlet; bit 5 = Blocked flue; bit 6 = DHW input; bit 7 = Low fire input; bit 8 = DHW fault; bit 9 = DHW sensor not detected; bit 11 = Operating limit clamp | |||
| IR | 162doc 30163 | Boiler 04 status 4 | Firmware 2.70+. | BITMAP16 | Read | bit 0 = DHW sensor enabled; bit 1 = Damper prove; bit 3 = Blower fault; bit 4 = Blocked inlet; bit 5 = Blocked flue; bit 6 = DHW input; bit 7 = Low fire input; bit 8 = DHW fault; bit 9 = DHW sensor not detected; bit 11 = Operating limit clamp | |||
| IR | 163doc 30164 | Boiler 05 status 4 | Firmware 2.70+. | BITMAP16 | Read | bit 0 = DHW sensor enabled; bit 1 = Damper prove; bit 3 = Blower fault; bit 4 = Blocked inlet; bit 5 = Blocked flue; bit 6 = DHW input; bit 7 = Low fire input; bit 8 = DHW fault; bit 9 = DHW sensor not detected; bit 11 = Operating limit clamp | |||
| IR | 164doc 30165 | Boiler 06 status 4 | Firmware 2.70+. | BITMAP16 | Read | bit 0 = DHW sensor enabled; bit 1 = Damper prove; bit 3 = Blower fault; bit 4 = Blocked inlet; bit 5 = Blocked flue; bit 6 = DHW input; bit 7 = Low fire input; bit 8 = DHW fault; bit 9 = DHW sensor not detected; bit 11 = Operating limit clamp | |||
| IR | 165doc 30166 | Boiler 07 status 4 | Firmware 2.70+. | BITMAP16 | Read | bit 0 = DHW sensor enabled; bit 1 = Damper prove; bit 3 = Blower fault; bit 4 = Blocked inlet; bit 5 = Blocked flue; bit 6 = DHW input; bit 7 = Low fire input; bit 8 = DHW fault; bit 9 = DHW sensor not detected; bit 11 = Operating limit clamp | |||
| IR | 166doc 30167 | Boiler 08 status 4 | Firmware 2.70+. | BITMAP16 | Read | bit 0 = DHW sensor enabled; bit 1 = Damper prove; bit 3 = Blower fault; bit 4 = Blocked inlet; bit 5 = Blocked flue; bit 6 = DHW input; bit 7 = Low fire input; bit 8 = DHW fault; bit 9 = DHW sensor not detected; bit 11 = Operating limit clamp | |||
| IR | 167doc 30168 | Boiler 09 status 4 | Firmware 2.70+. | BITMAP16 | Read | bit 0 = DHW sensor enabled; bit 1 = Damper prove; bit 3 = Blower fault; bit 4 = Blocked inlet; bit 5 = Blocked flue; bit 6 = DHW input; bit 7 = Low fire input; bit 8 = DHW fault; bit 9 = DHW sensor not detected; bit 11 = Operating limit clamp | |||
| IR | 168doc 30169 | Boiler 10 status 4 | Firmware 2.70+. | BITMAP16 | Read | bit 0 = DHW sensor enabled; bit 1 = Damper prove; bit 3 = Blower fault; bit 4 = Blocked inlet; bit 5 = Blocked flue; bit 6 = DHW input; bit 7 = Low fire input; bit 8 = DHW fault; bit 9 = DHW sensor not detected; bit 11 = Operating limit clamp | |||
| IR | 169doc 30170 | Boiler 11 status 4 | Firmware 2.70+. | BITMAP16 | Read | bit 0 = DHW sensor enabled; bit 1 = Damper prove; bit 3 = Blower fault; bit 4 = Blocked inlet; bit 5 = Blocked flue; bit 6 = DHW input; bit 7 = Low fire input; bit 8 = DHW fault; bit 9 = DHW sensor not detected; bit 11 = Operating limit clamp | |||
| IR | 170doc 30171 | Boiler 12 status 4 | Firmware 2.70+. | BITMAP16 | Read | bit 0 = DHW sensor enabled; bit 1 = Damper prove; bit 3 = Blower fault; bit 4 = Blocked inlet; bit 5 = Blocked flue; bit 6 = DHW input; bit 7 = Low fire input; bit 8 = DHW fault; bit 9 = DHW sensor not detected; bit 11 = Operating limit clamp | |||
| IR | 171doc 30172 | Boiler 13 status 4 | Firmware 2.70+. | BITMAP16 | Read | bit 0 = DHW sensor enabled; bit 1 = Damper prove; bit 3 = Blower fault; bit 4 = Blocked inlet; bit 5 = Blocked flue; bit 6 = DHW input; bit 7 = Low fire input; bit 8 = DHW fault; bit 9 = DHW sensor not detected; bit 11 = Operating limit clamp | |||
| IR | 172doc 30173 | Boiler 14 status 4 | Firmware 2.70+. | BITMAP16 | Read | bit 0 = DHW sensor enabled; bit 1 = Damper prove; bit 3 = Blower fault; bit 4 = Blocked inlet; bit 5 = Blocked flue; bit 6 = DHW input; bit 7 = Low fire input; bit 8 = DHW fault; bit 9 = DHW sensor not detected; bit 11 = Operating limit clamp | |||
| IR | 173doc 30174 | Boiler 15 status 4 | Firmware 2.70+. | BITMAP16 | Read | bit 0 = DHW sensor enabled; bit 1 = Damper prove; bit 3 = Blower fault; bit 4 = Blocked inlet; bit 5 = Blocked flue; bit 6 = DHW input; bit 7 = Low fire input; bit 8 = DHW fault; bit 9 = DHW sensor not detected; bit 11 = Operating limit clamp | |||
| IR | 174doc 30175 | Boiler 16 status 4 | Firmware 2.70+. | BITMAP16 | Read | bit 0 = DHW sensor enabled; bit 1 = Damper prove; bit 3 = Blower fault; bit 4 = Blocked inlet; bit 5 = Blocked flue; bit 6 = DHW input; bit 7 = Low fire input; bit 8 = DHW fault; bit 9 = DHW sensor not detected; bit 11 = Operating limit clamp | |||
| IR | 207doc 30208 | Boiler 01 DHW temperature | If available; firmware 2.70+. | INT16 | °F | Read | |||
| IR | 208doc 30209 | Boiler 02 DHW temperature | If available; firmware 2.70+. | INT16 | °F | Read | |||
| IR | 209doc 30210 | Boiler 03 DHW temperature | If available; firmware 2.70+. | INT16 | °F | Read | |||
| IR | 210doc 30211 | Boiler 04 DHW temperature | If available; firmware 2.70+. | INT16 | °F | Read | |||
| IR | 211doc 30212 | Boiler 05 DHW temperature | If available; firmware 2.70+. | INT16 | °F | Read | |||
| IR | 212doc 30213 | Boiler 06 DHW temperature | If available; firmware 2.70+. | INT16 | °F | Read | |||
| IR | 213doc 30214 | Boiler 07 DHW temperature | If available; firmware 2.70+. | INT16 | °F | Read | |||
| IR | 214doc 30215 | Boiler 08 DHW temperature | If available; firmware 2.70+. | INT16 | °F | Read | |||
| IR | 215doc 30216 | Boiler 09 DHW temperature | If available; firmware 2.70+. | INT16 | °F | Read | |||
| IR | 216doc 30217 | Boiler 10 DHW temperature | If available; firmware 2.70+. | INT16 | °F | Read | |||
| IR | 217doc 30218 | Boiler 11 DHW temperature | If available; firmware 2.70+. | INT16 | °F | Read | |||
| IR | 218doc 30219 | Boiler 12 DHW temperature | If available; firmware 2.70+. | INT16 | °F | Read | |||
| IR | 219doc 30220 | Boiler 13 DHW temperature | If available; firmware 2.70+. | INT16 | °F | Read | |||
| IR | 220doc 30221 | Boiler 14 DHW temperature | If available; firmware 2.70+. | INT16 | °F | Read | |||
| IR | 221doc 30222 | Boiler 15 DHW temperature | If available; firmware 2.70+. | INT16 | °F | Read | |||
| IR | 222doc 30223 | Boiler 16 DHW temperature | If available; firmware 2.70+. | INT16 | °F | Read | |||
| IR | 223doc 30224 | Boiler 01 running modulation | Displayed running modulation, 0-100. | INT16 | Read | ||||
| IR | 224doc 30225 | Boiler 02 running modulation | Displayed running modulation, 0-100. | INT16 | Read | ||||
| IR | 225doc 30226 | Boiler 03 running modulation | Displayed running modulation, 0-100. | INT16 | Read | ||||
| IR | 226doc 30227 | Boiler 04 running modulation | Displayed running modulation, 0-100. | INT16 | Read | ||||
| IR | 227doc 30228 | Boiler 05 running modulation | Displayed running modulation, 0-100. | INT16 | Read | ||||
| IR | 228doc 30229 | Boiler 06 running modulation | Displayed running modulation, 0-100. | INT16 | Read | ||||
| IR | 229doc 30230 | Boiler 07 running modulation | Displayed running modulation, 0-100. | INT16 | Read | ||||
| IR | 230doc 30231 | Boiler 08 running modulation | Displayed running modulation, 0-100. | INT16 | Read | ||||
| IR | 231doc 30232 | Boiler 09 running modulation | Displayed running modulation, 0-100. | INT16 | Read | ||||
| IR | 232doc 30233 | Boiler 10 running modulation | Displayed running modulation, 0-100. | INT16 | Read | ||||
| IR | 233doc 30234 | Boiler 11 running modulation | Displayed running modulation, 0-100. | INT16 | Read | ||||
| IR | 234doc 30235 | Boiler 12 running modulation | Displayed running modulation, 0-100. | INT16 | Read | ||||
| IR | 235doc 30236 | Boiler 13 running modulation | Displayed running modulation, 0-100. | INT16 | Read | ||||
| IR | 236doc 30237 | Boiler 14 running modulation | Displayed running modulation, 0-100. | INT16 | Read | ||||
| IR | 237doc 30238 | Boiler 15 running modulation | Displayed running modulation, 0-100. | INT16 | Read | ||||
| IR | 238doc 30239 | Boiler 16 running modulation | Displayed running modulation, 0-100. | INT16 | Read | ||||
| IR | 239doc 30240 | Operating setpoint | Active setpoint: heating, DHW, outdoor reset or 4-20 mA; 40-220 °F. | INT16 | °F | Read | |||
| HR | 0doc 40001 | Heat demand | UINT16 | Read/write | 0 = No heat demand; 1 = Heat demand | ||||
| HR | 1doc 40002 | Setpoint timer | BMS failsafe countdown; at zero the boiler reverts to its saved local setpoint. | UINT16 | s | Read/write | |||
| HR | 2doc 40003 | System setpoint | 40-220 °F (8-bit value). | UINT16 | °F | Read/write | |||
| HR | 3doc 40004 | Outdoor reset enable | UINT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 4doc 40005 | Outdoor reset shutdown setpoint | Outdoor temperature at which the boiler shuts down, 40-100 °F. | UINT16 | °F | Read/write | |||
| HR | 5doc 40006 | Reset water temp at high outdoor temp | 60-150 °F. | UINT16 | °F | Read/write | |||
| HR | 6doc 40007 | Reset high outdoor air temp | 50-90 °F. | UINT16 | °F | Read/write | |||
| HR | 7doc 40008 | Reset water temp at low outdoor temp | 70-220 °F. | UINT16 | °F | Read/write | |||
| HR | 9doc 40010 | Set clock month | 0 = January ... 11 = December. | UINT16 | Read/write | ||||
| HR | 10doc 40011 | Set clock day | 1-31. | UINT16 | Read/write | ||||
| HR | 11doc 40012 | Set clock year | 0-99. | UINT16 | Read/write | ||||
| HR | 12doc 40013 | Set clock hour | 0-23. | UINT16 | Read/write | ||||
| HR | 13doc 40014 | Set clock minute | 0-59. | UINT16 | Read/write | ||||
| HR | 14doc 40015 | Set clock second | 0-59. | UINT16 | Read/write | ||||
| HR | 15doc 40016 | Set clock weekday | 1 = Monday ... 7 = Sunday. | UINT16 | Read/write | ||||
| HR | 16doc 40017 | Set clock command | Load 40010-40016 first, then write 1. | UINT16 | Read/write | 0 = No action; 1 = Write clock | |||
| HR | 17doc 40018 | DHW setpoint | 40-200 °F; firmware 2.70+. | INT16 | °F | Read/write |
Notes on this map
- The register list is a Mestek, Inc. document; it names no other brand. No public copy on a Mestek site was found; the link is an unaltered copy hosted by a gateway supplier.
- Runtime and cycle counters are two 16-bit registers, high word first: value = high x 65536 + low (ABCD).
- Several registers hold 8-bit or 1-bit values in a 16-bit register; they are listed as UINT16.
- Unsigned 8-bit values (setpoints, clock fields) are listed as UINT16; the list does not say which byte of the register holds them.
- Left out: the system modulation at 30002 (listed as 8-bit with scale 0.01 but range 0-100 %, which do not agree) and the low outdoor air temperature setpoint 40009 (8-bit signed; how it sits in the 16-bit register is not stated).
- Boiler 01 is the master (connected) boiler; boilers 02-16 are cascade members 01-15.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Mestek KNSLM boiler control (KN2 / KN4 / rAy series)
What Modbus registers does the Mestek KNSLM boiler control (KN2 / KN4 / rAy series) have?
This map lists 192 registers: 175 input registers, 17 holding registers. 17 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Mestek KNSLM boiler control (KN2 / KN4 / rAy series) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are listed in Modicon form (40001 holding, 30001 input). Request 40001 as holding address 0 and 30001 as input address 0.
What byte order does the Mestek KNSLM boiler control (KN2 / KN4 / rAy series) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Mestek KNSLM boiler control (KN2 / KN4 / rAy series)?
Start with HR 0 Heat demand (Heat demand); HR 1 Setpoint timer (Setpoint failsafe timer); HR 2 System setpoint (System setpoint); IR 2 Header / system temperature (Header temperature); IR 3 Supply temperature (Supply temperature); IR 4 Return temperature (Return temperature); IR 16 Boiler 01 status 2 (Master boiler status 2 (alarm / failed / running)); IR 239 Operating setpoint (Active operating setpoint).
How do I enable Modbus control of the Mestek KNSLM boiler control (KN2 / KN4 / rAy series)?
Not described in this register list; set up Modbus in the boiler control as per the boiler manual.
What happens when the Mestek KNSLM boiler control (KN2 / KN4 / rAy series) loses Modbus communication?
Setpoint timer 40002: if it counts down to zero the control assumes the BMS has failed and reloads its saved local setpoint. Writing any read/write register reloads it to 60 s if it is below 60 (firmware 2.70+; older firmware only on a setpoint write).
Where is the official Mestek KNSLM boiler control (KN2 / KN4 / rAy series) Modbus documentation?
The source is KNSLM (KN2/KN4/rAy) Series Boiler - Modbus Registers (V1.10). Mestek doesn't publish it on its own website, so this map was re-typed from a free copy at https://www.ccontrols.com/support/dp/KNSLM.pdf. It may be an older revision, so check it against the live unit.
Other boilers & water heaters register maps
- Boiler
Buderus SSB condensing boilers (built-in Modbus RTU)
Buderus SSB series condensing boilers (Bosch Thermotechnology, North America) using the Modbus terminals on the boiler's internal terminal strip, per installation instructions 6720818450 (2015/10).
Also known as: SSB, Buderus SSB boiler, Bosch SSB, 6720818450 - Boiler / water heater
Lochinvar Knight / Armor / Wall Mount boilers (ModBus communication board)
Knight 81-286, Knight XL 400-1000, Armor 151-1000, Outdoor Knight/Knight XL/Armor, AQUAS 400-801, FTXL 400-1000, Wall Mount 51-211, Wall Hung 55-399, Wall Mount Armor 125-200 and Shield 125-500 with the Lochinvar ModBus communication board.
Also known as: Knight, Knight XL, Outdoor Knight, Outdoor Knight XL, Armor, Outdoor Armor, Wall Mount Armor, Knight Wall Mount, Knight Wall Hung, AQUAS, FTXL, Shield - Boiler (water heater controller)
PVI Industries XR10CX water heater digital operating controller (Modbus RTU)
PVI XR10CX digital operating controls on RS-485 Modbus RTU, per PVI manual PV500-67 (06/2014).
Also known as: XR10CX, PV500-67 - Boiler controller
Honeywell SOLA hydronic boiler control (Modbus interface)
Honeywell SOLA (R7910/R7911) integrated boiler controls, status registers 0-173 of the SOLA Modbus Interface specification Rev 4.1.1 (2013-10-14). Used inside many OEM condensing boilers.
Also known as: R7910, R7911, Honeywell SOLA, SOLA ICP - Boiler
Lochinvar SYNC condensing boilers / water heaters 1.0, 1.3, 1.5 (Modbus communication board)
Lochinvar SYNC 1.0 / 1.3 / 1.5 dual-module boilers and water heaters with the Modbus/BACnet communication board, per SYNC-MODB Rev L.
Also known as: SYNC 1.0, SYNC 1.3, SYNC 1.5, SYNC, Lochinvar SYNC, SYNC-MODB - Boiler / heating system controller
Buderus Logamatic 5000 boiler and system controller (Modbus TCP, datapoint list 4.0)
Buderus Logamatic 5313 and 5311 (and the Bosch Control 8313/8311 equivalents) acting as master, firmware 1.3 or later with the 4.0 datapoint list; addresses for slave controllers differ.
Also known as: Logamatic 5313, Logamatic 5311, Bosch Control 8313, Bosch Control 8311, Control 8000, BCT 531, Logamatic 5000 Modbus
All boilers & water heaters Modbus register maps →
Source: KNSLM (KN2/KN4/rAy) Series Boiler - Modbus Registers · V1.10 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.