- XR10CX water heater digital operating controller (Modbus RTU)
Boiler (water heater controller) · Modbus register map
PVI Industries XR10CX water heater digital operating controller (Modbus RTU) Modbus register map
Updated 17 November 2026
The XR10CX is a digital operating control used on PVI water heaters. It is a Modbus RTU slave on 2-wire RS-485 at a fixed 9600 8N1, with a handful of holding registers for temperature and set points and output coils for on/off, keypad lock, alarms and the call-for-heat relay.
This page lists 22 Modbus registers for the PVI Industries XR10CX water heater digital operating controller (Modbus RTU) — 9 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from PVI Industries’s own free documentation (linked below) and checked against it.
- Manufacturer
- PVI Industries
- Model
- XR10CX water heater digital operating controller (Modbus RTU)
- Equipment type
- Boiler (water heater controller)
- Registers
- 22 (9 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 9600 baud, 8N1
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Also known as
- XR10CX, PV500-67
Integration notes: PVI Industries XR10CX water heater digital operating controller (Modbus RTU)
Poll 9600 8N1. Read probe 1 at 40257 and the set point at 40864 with FC03; read status coils 513-545 with FC01, and switch the control on/off with coil 513.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 256 | Probe 1 temperature (PRB1) | INT16 | Probe 1 temperature | Read |
| HR 863 | System set point (Set) | INT16 | System set point | Read/write |
| CO 542 | Relay call for heat | BIT | Call for heat relay | Read |
| CO 537 | Any-alarm (can be muted) | BIT | Any-alarm | Read |
| CO 512 | On/off for control | BIT | On/off for control | Read/write |
| CO 520 | Probe 1 error | BIT | Probe 1 error | Read |
Enable Modbus control & writes
Modbus RTU is available through the XJ485 serial interface connected to the XR10CX programming port.
Byte order & addressing
- Maximum 5 registers per request.
- Register and coil numbers are Modicon-style; subtract 40001 for registers and 1 for coils.
- Coils can be read up to 80 at a time but written only one at a time.
Network setup
- Fixed serial settings: 9600 baud, 8 data bits, no parity, 1 stop bit (not adjustable).
- Set the slave address (1-247) on the keypad; each unit on the bus needs its own address.
- Leave at least 500 ms before a retry. The controller has no bias resistors; bias the line at the master.
Watch out for
- In OFF the display shows OFF and outputs are open, but temperatures can still be read.
PVI Industries XR10CX water heater digital operating controller (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 512doc 513 | On/off for control | Enables or disables the controller. | BIT | Read/write | ||||
| CO | 515doc 516 | Keypad lock | BIT | Read/write | |||||
| CO | 516doc 517 | Mute buzzer and any-alarm | BIT | Read/write | |||||
| CO | 519doc 520 | Digital input pin 9 | BIT | Read | |||||
| CO | 520doc 521 | Probe 1 error | BIT | Read | |||||
| CO | 521doc 522 | Probe 2 error | BIT | Read | |||||
| CO | 522doc 523 | Probe 3 error | BIT | Read | |||||
| CO | 523doc 524 | Probe 4 error | BIT | Read | |||||
| CO | 524doc 525 | High temperature alarm Pb1 | BIT | Read | |||||
| CO | 525doc 526 | Low temperature alarm Pb1 | BIT | Read | |||||
| CO | 528doc 529 | Alarm from external input | BIT | Read | |||||
| CO | 531doc 532 | EEPROM failure | BIT | Read | |||||
| CO | 537doc 538 | Any-alarm (can be muted) | BIT | Read | |||||
| CO | 542doc 543 | Relay call for heat | On = burner signal on. | BIT | Read | ||||
| CO | 544doc 545 | Buzzer on with external or high alarm | BIT | Read | |||||
| HR | 256doc 40257 | Probe 1 temperature (PRB1) | Operating probe; degrees F. | INT16 | °F | Read | |||
| HR | 768doc 40769 | Differential (HY) | UINT16 | Read/write | |||||
| HR | 829doc 40830 | Temperature alarm delay (ALd) | UINT16 | Read/write | |||||
| HR | 830doc 40831 | Temperature alarm delay at startup (dAo) | UINT16 | Read/write | |||||
| HR | 846doc 40847 | Digital input alarm delay (did) | 0-255 min. | UINT16 | min | Read/write | |||
| HR | 851doc 40852 | Modbus address (Adr) | 1-247. | UINT16 | Read/write | ||||
| HR | 863doc 40864 | System set point (Set) | Main set point. | INT16 | °F | Read/write |
Notes on this map
- PVI does not host this manual publicly that we could find; this copy is served by a controls distributor and is the unaltered PVI document (PVI Industries footer, document number on every page).
- Temperatures are whole degrees F per section 4.2.
- The manual is inconsistent about coil 513: Table 2 lists it as a Read/Write coil, while section 4.2 says ON/OFF is written as 257/1 and calls it write-only. Treat it as a standard on/off coil and confirm on site.
- Units for the differential and alarm delays are not stated in the table.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the PVI Industries XR10CX water heater digital operating controller (Modbus RTU)
What Modbus registers does the PVI Industries XR10CX water heater digital operating controller (Modbus RTU) have?
This map lists 22 registers: 15 coils, 7 holding registers. 9 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the PVI Industries XR10CX water heater digital operating controller (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual uses register numbers: holding register 40001 is address 0 on the wire, so subtract 40001 (40769 -> 768). Coils are numbered from 00001 the same way, so coil 513 is wire address 512.
What are the minimum Modbus registers to integrate the PVI Industries XR10CX water heater digital operating controller (Modbus RTU)?
Start with HR 256 Probe 1 temperature (PRB1) (Probe 1 temperature); HR 863 System set point (Set) (System set point); CO 542 Relay call for heat (Call for heat relay); CO 537 Any-alarm (can be muted) (Any-alarm); CO 512 On/off for control (On/off for control); CO 520 Probe 1 error (Probe 1 error).
How do I enable Modbus control of the PVI Industries XR10CX water heater digital operating controller (Modbus RTU)?
Modbus RTU is available through the XJ485 serial interface connected to the XR10CX programming port.
Where is the official PVI Industries XR10CX water heater digital operating controller (Modbus RTU) Modbus documentation?
The source is MODBUS-RTU Applied to the XR10CX Control (PV500-67 06/2014), revision 2014-06. PVI Industries doesn't publish it on its own website, so this map was re-typed from a free copy at https://www.ccontrols.com/support/dp/PV500-67.pdf. It may be an older revision, so check it against the live unit.
More PVI Industries Modbus register maps
Other boilers & water heaters register maps
- Boiler controller
Honeywell SOLA hydronic boiler control (Modbus interface)
Honeywell SOLA (R7910/R7911) integrated boiler controls, status registers 0-173 of the SOLA Modbus Interface specification Rev 4.1.1 (2013-10-14). Used inside many OEM condensing boilers.
Also known as: R7910, R7911, Honeywell SOLA, SOLA ICP - Boiler
Lochinvar SYNC condensing boilers / water heaters 1.0, 1.3, 1.5 (Modbus communication board)
Lochinvar SYNC 1.0 / 1.3 / 1.5 dual-module boilers and water heaters with the Modbus/BACnet communication board, per SYNC-MODB Rev L.
Also known as: SYNC 1.0, SYNC 1.3, SYNC 1.5, SYNC, Lochinvar SYNC, SYNC-MODB - Boiler / heating system controller
Buderus Logamatic 5000 boiler and system controller (Modbus TCP, datapoint list 4.0)
Buderus Logamatic 5313 and 5311 (and the Bosch Control 8313/8311 equivalents) acting as master, firmware 1.3 or later with the 4.0 datapoint list; addresses for slave controllers differ.
Also known as: Logamatic 5313, Logamatic 5311, Bosch Control 8313, Bosch Control 8311, Control 8000, BCT 531, Logamatic 5000 Modbus - Boiler
Lochinvar Crest / Crest with Hellcat boilers (ModBus communication board)
Lochinvar Crest FB/OF 751-6001 and FCB1000-6000 (including Crest with Hellcat) with the ModBus communication board.
Also known as: Crest, Crest FB751-6001, Crest OF751-6001, Crest FCB1000-6000, Hellcat, MTR-01 - Boiler (burner management / fuel-air ratio control)
Fireye PPC4000 parallel positioning burner control (Modbus RTU)
Fireye PPC4000 parallel positioning controls showing engineering code EC08 or later, per bulletin MOD-4001 (September 13, 2012). The later NXF4000 is not covered.
Also known as: PPC-4000, PPC4000, MOD-4001 - Boiler
Lochinvar Power-fin PBX / PFX boilers and water heaters 502-1302, 1501-2001 (Modbus communication board)
Lochinvar Power-fin PB/PF 'X' models 502-1302 and 1501-2001 with the SMART SYSTEM control and Modbus/BACnet communication board, per PBX-PFX-MODB Rev D.
Also known as: Power-fin, Power-Fin, PBX502, PBX1302, PBX1501, PBX2001, PFX502, PFX2001, PBX-PFX-MODB, SMART SYSTEM
All boilers & water heaters Modbus register maps →
Source: MODBUS-RTU Applied to the XR10CX Control · PV500-67 06/2014 · rev. 2014-06 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.