- TempTrac water heater electronic controller (Modbus RTU)
Boiler (water heater controller) · Modbus register map
PVI Industries TempTrac water heater electronic controller (Modbus RTU) Modbus register map
Updated 17 November 2026
TempTrac is PVI's electronic operating control for its water heaters. It is a Modbus RTU slave on 2-wire RS-485 at a fixed 9600 8N1 and uses only holding registers (FC03/06/16, up to 5 registers per request). This map covers the registers PVI lists for typical BMS use: probe temperatures, set point, modulation rate, burner hours, relay status, alarms and the on/off command.
This page lists 10 Modbus registers for the PVI Industries TempTrac water heater electronic controller (Modbus RTU) — 4 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from PVI Industries’s own free documentation (linked below) and checked against it.
- Manufacturer
- PVI Industries
- Model
- TempTrac water heater electronic controller (Modbus RTU)
- Equipment type
- Boiler (water heater controller)
- Registers
- 10 (4 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 9600 baud, 8N1
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Also known as
- TempTrac, PV500-42
Integration notes: PVI Industries TempTrac water heater electronic controller (Modbus RTU)
Poll 9600 8N1 with FC03, no more than 5 registers per request. Read probe 1 (40257), relay status (42050) and alarms (43329); write the set point at 40769 and turn the heater on/off by writing 257/1 to 41281.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 256 | Probe 1 temperature (TP1) | INT16 | Probe 1 temperature | Read |
| HR 768 | Set point 1 (St1) | INT16 | Set point 1 | Read/write |
| HR 2049 | Relay status | BITMAP16 | Relay / burner status | Read |
| HR 3328 | Alarm register | BITMAP16 | Alarm flags | Read |
| HR 1280 | Control command (on/off) | UINT16 | On/off command | Write |
| HR 848 | Working hours relay 1 (ou1) | UINT16 | Burner hours | Read/write |
Enable Modbus control & writes
Modbus RTU is available through the XJ485 serial interface (TTL to RS-485) connected to the TempTrac's programming port.
Byte order & addressing
- Maximum 5 registers per read or write.
- Register numbers are Modicon-style; subtract 40001.
- 41281 is write-only; reading it returns invalid data.
Network setup
- Fixed serial settings: 9600 baud, 8 data bits, no parity, 1 stop bit (not adjustable).
- Set the slave address (1-247) on the keypad; each unit on the bus needs its own address.
- Leave at least 500 ms before a retry. The controller has no bias resistors; bias the line at the master.
Watch out for
- Reading probe 2 or 3 returns an exception when that probe is disabled.
- In OFF the display shows OFF and outputs are open, but temperatures can still be read.
PVI Industries TempTrac water heater electronic controller (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 256doc 40257 | Probe 1 temperature (TP1) | Operating probe that set point St1 controls to; degrees F. | INT16 | °F | Read | |||
| HR | 258doc 40259 | Probe 2 temperature (TP2) | Returns an exception if probe 2 is disabled. | INT16 | °F | Read | |||
| HR | 260doc 40261 | Probe 3 temperature (TP3) | Returns an exception if probe 3 is disabled. | INT16 | °F | Read | |||
| HR | 262doc 40263 | Modulation rate output | Firmware 0.5 only: 4-20 mA modulation output, 0-100 % (0 = low fire on most units). | UINT16 | % | Read | |||
| HR | 768doc 40769 | Set point 1 (St1) | Main system set point. | INT16 | °F | Read/write | |||
| HR | 848doc 40849 | Working hours relay 1 (ou1) | Burner run hours, rolls over at 9999. | UINT16 | h | Read/write | |||
| HR | 857doc 40858 | Serial address (Adr) | Modbus slave address 1-247. | UINT16 | Read/write | ||||
| HR | 1280doc 41281 | Control command (on/off) | Write-only command word; 257 = ON, 1 = OFF. Reads are invalid. | UINT16 | Write | 1 = Off; 8 = Keypad unlock; 257 = On; 2056 = Keypad lock; 4112 = Silence buzzer | |||
| HR | 2049doc 42050 | Relay status | Relay 1 bit = call for heat (burner on). | BITMAP16 | Read | bit 0 = Relay 1 (burner on); bit 1 = Relay 2; bit 2 = Relay 3 | |||
| HR | 3328doc 43329 | Alarm register | Bit meanings listed are the firmware 0.5 rows; on firmware 0.3, bit 12 flags input 2/3 alarms. | BITMAP16 | Read | bit 0 = Low temperature alarm (LA); bit 1 = High temperature alarm (HA); bit 2 = Probe 1 error; bit 8 = Probe 2 error; bit 9 = Probe 3 error; bit 10 = Alarm 1 (input 1); bit 11 = Alarm 2 (lockout, input 2); bit 12 = Alarm 3 (lockout, alarm on any failure); bit 13 = Maintenance relay 1; bit 14 = Maintenance relay 2; bit 15 = Maintenance relay 3 |
Notes on this map
- PVI does not host this manual publicly that we could find; this copy is served by a controls distributor and is the unaltered PVI document (PVI Industries footer, document number on every page).
- Only the registers in section 4.2 'Typical parameters' and the clearly readable status/alarm rows are included; the long parameter list in Table 2 (pp. 10-14) did not extract cleanly and is left out.
- Temperatures are whole degrees F per section 4.2. The display resolution option (rES) applies only to Celsius; its effect on Modbus values is not documented, so Celsius operation is not covered here.
- Alarm bits follow the decimal values and bit numbers in the manual (bit 0 = 1). The manual's hex values for Alarm 2 (0x1000) and Alarm 3 (0x0800) disagree with their decimal values (2048, 4096); the decimal/bit numbers are used.
- Register 41281 also accepts keypad lock/unlock and buzzer-silence codes; PVI notes that only the on/off command is normally needed.
- Table 2 gives a hex base-0 address next to each register number (e.g. St1 0x300 = 40769), which confirms the 40001 = address 0 rule.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the PVI Industries TempTrac water heater electronic controller (Modbus RTU)
What Modbus registers does the PVI Industries TempTrac water heater electronic controller (Modbus RTU) have?
This map lists 10 registers: 10 holding registers. 4 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the PVI Industries TempTrac water heater electronic controller (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual uses register numbers: holding register 40001 is address 0 on the wire, so subtract 40001 (40769 -> 768). Coils are numbered from 00001 the same way, so coil 513 is wire address 512.
What are the minimum Modbus registers to integrate the PVI Industries TempTrac water heater electronic controller (Modbus RTU)?
Start with HR 256 Probe 1 temperature (TP1) (Probe 1 temperature); HR 768 Set point 1 (St1) (Set point 1); HR 2049 Relay status (Relay / burner status); HR 3328 Alarm register (Alarm flags); HR 1280 Control command (on/off) (On/off command); HR 848 Working hours relay 1 (ou1) (Burner hours).
How do I enable Modbus control of the PVI Industries TempTrac water heater electronic controller (Modbus RTU)?
Modbus RTU is available through the XJ485 serial interface (TTL to RS-485) connected to the TempTrac's programming port.
Where is the official PVI Industries TempTrac water heater electronic controller (Modbus RTU) Modbus documentation?
The source is MODBUS-RTU Applied to the TempTrac Control (PV500-42 06/2014), revision 2014-06. PVI Industries doesn't publish it on its own website, so this map was re-typed from a free copy at https://www.ccontrols.com/support/dp/PV500-42.pdf. It may be an older revision, so check it against the live unit.
More PVI Industries Modbus register maps
Other boilers & water heaters register maps
- Boiler (burner management / fuel-air ratio control)
Fireye PPC4000 parallel positioning burner control (Modbus RTU)
Fireye PPC4000 parallel positioning controls showing engineering code EC08 or later, per bulletin MOD-4001 (September 13, 2012). The later NXF4000 is not covered.
Also known as: PPC-4000, PPC4000, MOD-4001 - Boiler
Lochinvar Power-fin PBX / PFX boilers and water heaters 502-1302, 1501-2001 (Modbus communication board)
Lochinvar Power-fin PB/PF 'X' models 502-1302 and 1501-2001 with the SMART SYSTEM control and Modbus/BACnet communication board, per PBX-PFX-MODB Rev D.
Also known as: Power-fin, Power-Fin, PBX502, PBX1302, PBX1501, PBX2001, PFX502, PFX2001, PBX-PFX-MODB, SMART SYSTEM - Boiler / water heater controller
AERCO C-More Boiler Controller (Benchmark / KC series)
AERCO C-More boiler controllers (software 2.00 or later) used on Benchmark and KC Series boilers and water heaters, as a Modbus RTU slave.
Also known as: C-More, Benchmark, KC1000, KC Series, Benchmark boiler, Benchmark water heater - Boiler
Lochinvar Copper-fin II / IIE boiler, water heater and pool heater (ModBus communication board)
Lochinvar Copper-fin II/IIE boilers and water heaters 402-2072 and pool heaters 502-2072 with the MTR-01 ModBus board, per manual 100160882 Rev G.
Also known as: Copper-fin II, Copper-fin IIE, CBX, CFX, CHX, CPX, C(F,H,P)X, Copperfin - Boiler controller
Patterson-Kelley NURO boiler controller (Modbus BMS port)
Patterson-Kelley NURO boiler control, Modbus register map from Appendix A of the NURO Advanced Users Guide.
Also known as: Patterson-Kelley NURO, Harsco Industrial Patterson-Kelley NURO - Boiler (burner / boiler controller)
Cleaver-Brooks CB Falcon hydronic / steam boiler control
Cleaver-Brooks CB Falcon boiler controls on the MB1 or MB2 Modbus port, per manual 750-308.
Also known as: CB Falcon, Falcon boiler control
All boilers & water heaters Modbus register maps →
Source: MODBUS-RTU Applied to the TempTrac Control · PV500-42 06/2014 · rev. 2014-06 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.