Easy Modbus
  1. Home
  2. Modbus register maps
  3. PVI Industries
  4. TempTrac water heater electronic controller (Modbus RTU)

Boiler (water heater controller) · Modbus register map

PVI Industries TempTrac water heater electronic controller (Modbus RTU) Modbus register map

Updated 17 November 2026

Short answer

TempTrac is PVI's electronic operating control for its water heaters. It is a Modbus RTU slave on 2-wire RS-485 at a fixed 9600 8N1 and uses only holding registers (FC03/06/16, up to 5 registers per request). This map covers the registers PVI lists for typical BMS use: probe temperatures, set point, modulation rate, burner hours, relay status, alarms and the on/off command.

This page lists 10 Modbus registers for the PVI Industries TempTrac water heater electronic controller (Modbus RTU) — 4 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from PVI Industries’s own free documentation (linked below) and checked against it.

Manufacturer
PVI Industries
Model
TempTrac water heater electronic controller (Modbus RTU)
Equipment type
Boiler (water heater controller)
Registers
10 (4 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
9600 baud, 8N1
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Also known as
TempTrac, PV500-42
Source document
MODBUS-RTU Applied to the TempTrac Control · PV500-42 06/2014 · rev. 2014-06 · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: PVI Industries TempTrac water heater electronic controller (Modbus RTU)

Integration in brief

Poll 9600 8N1 with FC03, no more than 5 registers per request. Read probe 1 (40257), relay status (42050) and alarms (43329); write the set point at 40769 and turn the heater on/off by writing 257/1 to 41281.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 256Probe 1 temperature (TP1)INT16Probe 1 temperatureRead
HR 768Set point 1 (St1)INT16Set point 1Read/write
HR 2049Relay statusBITMAP16Relay / burner statusRead
HR 3328Alarm registerBITMAP16Alarm flagsRead
HR 1280Control command (on/off)UINT16On/off commandWrite
HR 848Working hours relay 1 (ou1)UINT16Burner hoursRead/write

Enable Modbus control & writes

Modbus RTU is available through the XJ485 serial interface (TTL to RS-485) connected to the TempTrac's programming port.

Byte order & addressing

Network setup

Watch out for

PVI Industries TempTrac water heater electronic controller (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

10 of 10 shown
PVI Industries TempTrac water heater electronic controller (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR256doc 40257Probe 1 temperature (TP1)Operating probe that set point St1 controls to; degrees F.INT16°FRead
HR258doc 40259Probe 2 temperature (TP2)Returns an exception if probe 2 is disabled.INT16°FRead
HR260doc 40261Probe 3 temperature (TP3)Returns an exception if probe 3 is disabled.INT16°FRead
HR262doc 40263Modulation rate outputFirmware 0.5 only: 4-20 mA modulation output, 0-100 % (0 = low fire on most units).UINT16%Read
HR768doc 40769Set point 1 (St1)Main system set point.INT16°FRead/write
HR848doc 40849Working hours relay 1 (ou1)Burner run hours, rolls over at 9999.UINT16hRead/write
HR857doc 40858Serial address (Adr)Modbus slave address 1-247.UINT16Read/write
HR1280doc 41281Control command (on/off)Write-only command word; 257 = ON, 1 = OFF. Reads are invalid.UINT16Write1 = Off; 8 = Keypad unlock; 257 = On; 2056 = Keypad lock; 4112 = Silence buzzer
HR2049doc 42050Relay statusRelay 1 bit = call for heat (burner on).BITMAP16Readbit 0 = Relay 1 (burner on); bit 1 = Relay 2; bit 2 = Relay 3
HR3328doc 43329Alarm registerBit meanings listed are the firmware 0.5 rows; on firmware 0.3, bit 12 flags input 2/3 alarms.BITMAP16Readbit 0 = Low temperature alarm (LA); bit 1 = High temperature alarm (HA); bit 2 = Probe 1 error; bit 8 = Probe 2 error; bit 9 = Probe 3 error; bit 10 = Alarm 1 (input 1); bit 11 = Alarm 2 (lockout, input 2); bit 12 = Alarm 3 (lockout, alarm on any failure); bit 13 = Maintenance relay 1; bit 14 = Maintenance relay 2; bit 15 = Maintenance relay 3

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the PVI Industries TempTrac water heater electronic controller (Modbus RTU)

What Modbus registers does the PVI Industries TempTrac water heater electronic controller (Modbus RTU) have?

This map lists 10 registers: 10 holding registers. 4 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the PVI Industries TempTrac water heater electronic controller (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual uses register numbers: holding register 40001 is address 0 on the wire, so subtract 40001 (40769 -> 768). Coils are numbered from 00001 the same way, so coil 513 is wire address 512.

What are the minimum Modbus registers to integrate the PVI Industries TempTrac water heater electronic controller (Modbus RTU)?

Start with HR 256 Probe 1 temperature (TP1) (Probe 1 temperature); HR 768 Set point 1 (St1) (Set point 1); HR 2049 Relay status (Relay / burner status); HR 3328 Alarm register (Alarm flags); HR 1280 Control command (on/off) (On/off command); HR 848 Working hours relay 1 (ou1) (Burner hours).

How do I enable Modbus control of the PVI Industries TempTrac water heater electronic controller (Modbus RTU)?

Modbus RTU is available through the XJ485 serial interface (TTL to RS-485) connected to the TempTrac's programming port.

Where is the official PVI Industries TempTrac water heater electronic controller (Modbus RTU) Modbus documentation?

The source is MODBUS-RTU Applied to the TempTrac Control (PV500-42 06/2014), revision 2014-06. PVI Industries doesn't publish it on its own website, so this map was re-typed from a free copy at https://www.ccontrols.com/support/dp/PV500-42.pdf. It may be an older revision, so check it against the live unit.

More PVI Industries Modbus register maps

Other boilers & water heaters register maps

All boilers & water heaters Modbus register maps →

Source: MODBUS-RTU Applied to the TempTrac Control · PV500-42 06/2014 · rev. 2014-06 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.