Boiler (burner management / fuel-air ratio control) · Modbus register map
Fireye PPC4000 parallel positioning burner control (Modbus RTU) Modbus register map
Updated 17 November 2026
The PPC4000 is Fireye's parallel positioning fuel/air ratio control for burners. It is a Modbus RTU slave with holding registers only: a read-only block of status, counters, positions, raw sensor values and lockout history, and a small read/write block for burner on/off, low fire, lead/lag, auto/manual and manual modulation rate.
This page lists 76 Modbus registers for the Fireye PPC4000 parallel positioning burner control (Modbus RTU) — 5 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Fireye’s own free documentation (linked below) and checked against it.
- Manufacturer
- Fireye
- Model
- PPC4000 parallel positioning burner control (Modbus RTU)
- Equipment type
- Boiler (burner management / fuel-air ratio control)
- Registers
- 76 (5 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 8N1
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- ABCD high word first (big-endian)
- Firmware
- Engineering code EC08 or later
- Also known as
- PPC-4000, PPC4000, MOD-4001
Integration notes: Fireye PPC4000 parallel positioning burner control (Modbus RTU)
Poll the PPC4000 with FC03 at 8N1 and the baud rate chosen on the control (4800-57600). Read operational state, modulation rate and the active error; write 1/0 with FC06 to 41002 to turn the burner on or off.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 0 | Operational state | UINT16 | Operational state | Read |
| HR 8 | Current modulation rate | UINT16 | Modulation rate | Read |
| HR 191 | Current active error number | UINT16 | Active error number | Read |
| HR 4 | Burner on minutes | UINT32 ABCD | Burner on minutes | Read |
| HR 1001 | Burner control on/off | UINT16 | Burner on/off command | Read/write |
| HR 1004 | Burner control auto/manual | UINT16 | Auto/manual | Read/write |
| HR 1017 | Manual modulation rate | UINT16 | Manual modulation rate | Read/write |
Enable Modbus control & writes
Modbus is available on PPC4000 units with engineering code EC08 or later; the baud rate is selected in the PPC4000 menu.
Byte order & addressing
- Only FC03 (read) and FC06 (write single) are used.
- Register numbers are Modicon-style; subtract 40001.
- 32-bit counters are upper word first.
Network setup
- Serial format is fixed at 8 data bits, no parity, 1 stop bit; baud 4800-57600 is menu selectable.
- Set the slave address on the PPC4000.
Watch out for
- Manual modulation rate (41018) has no effect until auto/manual (41005) is set to manual.
Fireye PPC4000 parallel positioning burner control (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 40001 | Operational state | Current operating state number, 0-16. | UINT16 | Read | ||||
| HR | 2doc 40003 | System on minutes | 32-bit counter of controller operating minutes; upper word first. | UINT32 | ABCD | min | Read | ||
| HR | 4doc 40005 | Burner on minutes | 32-bit burner running minute counter; upper word first. | UINT32 | ABCD | min | Read | ||
| HR | 6doc 40007 | Completed burner cycles | 32-bit burner cycle counter; upper word first. | UINT32 | ABCD | Read | |||
| HR | 8doc 40009 | Current modulation rate | 0-100 %. | UINT16 | % | Read | |||
| HR | 9doc 40010 | Modulation mode | UINT16 | Read | 0 = Manual; 1 = Auto | ||||
| HR | 10doc 40011 | Internal temperature of the PPC4000 | In the configured temperature unit (C or F). | UINT16 | Read | ||||
| HR | 11doc 40012 | Current profile commission point | Profile point the control is running at (P0-P23). | UINT16 | Read | ||||
| HR | 12doc 40013 | Current calculated CO2 value | Scaling not stated in the manual. | UINT16 | Read | ||||
| HR | 13doc 40014 | PPC4000 model | UINT16 | Read | 0 = PPC-4000 only; 1 = PPC-4000 with internal flame safeguard | ||||
| HR | 14doc 40015 | Current selected profile | 1-4. | UINT16 | Read | ||||
| HR | 15doc 40016 | Commissioned points in current profile | 0-24. | UINT16 | Read | ||||
| HR | 17doc 40018 | Current digital input values | Present state of digital inputs 1-10 (1-16 on flame safeguard versions). | UINT16 | Read | ||||
| HR | 21doc 40022 | VFD 1 actual position | 0-1000. | UINT16 | × 0.1 | Read | |||
| HR | 22doc 40023 | VFD 1 commanded position | 0-1000. | UINT16 | × 0.1 | Read | |||
| HR | 23doc 40024 | VFD 2 actual position | 0-1000. | UINT16 | × 0.1 | Read | |||
| HR | 24doc 40025 | VFD 2 commanded position | 0-1000. | UINT16 | × 0.1 | Read | |||
| HR | 25doc 40026 | Current running efficiency | 0-100 %. | UINT16 | % | Read | |||
| HR | 26doc 40027 | Current O2 target value | In tenths of a percent. | UINT16 | × 0.1 | % | Read | ||
| HR | 51doc 40052 | Calibration constant | 819-860 counts; used to convert raw sensor values (see notes). | UINT16 | Read | ||||
| HR | 59doc 40060 | Sensor 1 raw value | Raw A/D reading of the primary sensor. | UINT16 | Read | ||||
| HR | 60doc 40061 | Sensor 2 raw value | Raw A/D reading of auxiliary sensor 1. | UINT16 | Read | ||||
| HR | 61doc 40062 | Sensor 3 raw value | Raw A/D reading of auxiliary sensor 2. | UINT16 | Read | ||||
| HR | 65doc 40066 | Sensor 4 raw value | Raw only; no calibration constant. | UINT16 | Read | ||||
| HR | 66doc 40067 | Sensor 5 raw value | Raw only; no calibration constant. | UINT16 | Read | ||||
| HR | 79doc 40080 | Servo 1 current position | UINT16 | Read | |||||
| HR | 88doc 40089 | Servo 2 current position | UINT16 | Read | |||||
| HR | 97doc 40098 | Servo 3 current position | UINT16 | Read | |||||
| HR | 106doc 40107 | Servo 4 current position | UINT16 | Read | |||||
| HR | 115doc 40116 | Servo 5 current position | UINT16 | Read | |||||
| HR | 124doc 40125 | Servo 6 current position | UINT16 | Read | |||||
| HR | 133doc 40134 | Servo 7 current position | UINT16 | Read | |||||
| HR | 142doc 40143 | Servo 8 current position | UINT16 | Read | |||||
| HR | 151doc 40152 | Servo 9 current position | UINT16 | Read | |||||
| HR | 160doc 40161 | Servo 10 current position | UINT16 | Read | |||||
| HR | 190doc 40191 | Lockout history pointer | Low byte = number of the next lockout entry. | UINT16 | Read | ||||
| HR | 191doc 40192 | Current active error number | 0 = no active error, otherwise the PPC4000 error code. | UINT16 | Read | ||||
| HR | 192doc 40193 | Total errors detected | Stored lockout count. | UINT16 | Read | ||||
| HR | 193doc 40194 | Fault 1 (most recent) profile/state | High byte = profile position, low byte = operational state at the fault. | UINT16 | Read | ||||
| HR | 194doc 40195 | Fault 1 error code | UINT16 | Read | |||||
| HR | 195doc 40196 | Fault 1 time | High byte = minutes, low byte = seconds. | UINT16 | Read | ||||
| HR | 196doc 40197 | Fault 1 date (day/hour) | High byte = day of month, low byte = hour. | UINT16 | Read | ||||
| HR | 197doc 40198 | Fault 1 date (weekday/month) | High byte = weekday (0 = Sunday), low byte = month. | UINT16 | Read | ||||
| HR | 198doc 40199 | Fault 1 year | UINT16 | Read | |||||
| HR | 264doc 40265 | Sensor 1 set point value | UINT16 | Read | |||||
| HR | 265doc 40266 | Sensor 1 cut-in value | UINT16 | Read | |||||
| HR | 266doc 40267 | Sensor 1 cut-out value | UINT16 | Read | |||||
| HR | 268doc 40269 | Sensor 1 margin alarm value | UINT16 | Read | |||||
| HR | 269doc 40270 | Sensor 1 limit alarm value | UINT16 | Read | |||||
| HR | 272doc 40273 | Sensor 2 set point value | UINT16 | Read | |||||
| HR | 273doc 40274 | Sensor 2 cut-in value | UINT16 | Read | |||||
| HR | 274doc 40275 | Sensor 2 cut-out value | UINT16 | Read | |||||
| HR | 276doc 40277 | Sensor 2 margin alarm value | UINT16 | Read | |||||
| HR | 277doc 40278 | Sensor 2 limit alarm value | UINT16 | Read | |||||
| HR | 280doc 40281 | Sensor 3 set point value | UINT16 | Read | |||||
| HR | 281doc 40282 | Sensor 3 cut-in value | UINT16 | Read | |||||
| HR | 282doc 40283 | Sensor 3 cut-out value | UINT16 | Read | |||||
| HR | 284doc 40285 | Sensor 3 margin alarm value | UINT16 | Read | |||||
| HR | 285doc 40286 | Sensor 3 limit alarm value | UINT16 | Read | |||||
| HR | 288doc 40289 | Sensor 4 set point value | UINT16 | Read | |||||
| HR | 289doc 40290 | Sensor 4 cut-in value | UINT16 | Read | |||||
| HR | 290doc 40291 | Sensor 4 cut-out value | UINT16 | Read | |||||
| HR | 292doc 40293 | Sensor 4 margin alarm value | UINT16 | Read | |||||
| HR | 293doc 40294 | Sensor 4 limit alarm value | UINT16 | Read | |||||
| HR | 296doc 40297 | Sensor 5 set point value | UINT16 | Read | |||||
| HR | 297doc 40298 | Sensor 5 cut-in value | UINT16 | Read | |||||
| HR | 298doc 40299 | Sensor 5 cut-out value | UINT16 | Read | |||||
| HR | 300doc 40301 | Sensor 5 margin alarm value | UINT16 | Read | |||||
| HR | 301doc 40302 | Sensor 5 limit alarm value | UINT16 | Read | |||||
| HR | 346doc 40347 | PCV set point string | 20-character text. | STRING[20] | Read | ||||
| HR | 356doc 40357 | PCV measured value string | 20-character text. | STRING[20] | Read | ||||
| HR | 1001doc 41002 | Burner control on/off | Write 1 to turn the burner on. | UINT16 | Read/write | 0 = False; 1 = True | |||
| HR | 1002doc 41003 | Burner control low fire | Write 1 to hold low fire. | UINT16 | Read/write | 0 = False; 1 = True | |||
| HR | 1003doc 41004 | Burner control lead/lag | Write 1 to make this unit the sequence master (when sequencing is enabled). | UINT16 | Read/write | 0 = False; 1 = True | |||
| HR | 1004doc 41005 | Burner control auto/manual | Write 1 for automatic modulation. | UINT16 | Read/write | 0 = False; 1 = True | |||
| HR | 1017doc 41018 | Manual modulation rate | Used only in manual modulation mode. | UINT16 | Read/write |
Notes on this map
- Fireye's own copy of this bulletin was not reachable (the later MOD-4001-NXF4000_PPC4000 link on fireye.com returns 404); this copy is served by a controls distributor and is the unaltered Fireye bulletin.
- The three 32-bit counters are listed as an upper-16-bit register followed by a lower-16-bit register, so they read as ABCD UINT32.
- VFD positions are 0-1000 in tenths of a degree, so scale 0.1 gives degrees; servo positions and set point/alarm values have no stated scaling and are raw.
- Raw sensor conversion from the bulletin: value = ((raw / calibration constant - 0.2) / 0.8) * range + offset, using 40052 as the calibration constant and the range/offset of the fitted sensor (e.g. TS350: range 318, offset 32). Sensors 4 and 5 are raw only.
- Lockout history: only fault 1 (most recent) is listed; faults 2-10 follow at 40200-40253 in six-register groups with the same layout.
- O2 probe status and temperature registers (40036-40039) are left out; their meaning is in the separate O2 probe manual.
- Error codes are listed in a separate Fireye publication; this bulletin does not explain the operational state numbers 0-16.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Fireye PPC4000 parallel positioning burner control (Modbus RTU)
What Modbus registers does the Fireye PPC4000 parallel positioning burner control (Modbus RTU) have?
This map lists 76 registers: 76 holding registers. 5 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Fireye PPC4000 parallel positioning burner control (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The bulletin prints holding register numbers from 40001 next to the message address actually sent (40001 = address 00, 41002 = 1001). Subtract 40001 for the wire address.
What byte order does the Fireye PPC4000 parallel positioning burner control (Modbus RTU) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Fireye PPC4000 parallel positioning burner control (Modbus RTU)?
Start with HR 0 Operational state (Operational state); HR 8 Current modulation rate (Modulation rate); HR 191 Current active error number (Active error number); HR 4 Burner on minutes (Burner on minutes); HR 1001 Burner control on/off (Burner on/off command); HR 1004 Burner control auto/manual (Auto/manual); HR 1017 Manual modulation rate (Manual modulation rate).
How do I enable Modbus control of the Fireye PPC4000 parallel positioning burner control (Modbus RTU)?
Modbus is available on PPC4000 units with engineering code EC08 or later; the baud rate is selected in the PPC4000 menu.
Where is the official Fireye PPC4000 parallel positioning burner control (Modbus RTU) Modbus documentation?
The source is PPC4000 Modbus Communications (MOD-4001), revision 2012-09-13. Fireye doesn't publish it on its own website, so this map was re-typed from a free copy at https://www.ccontrols.com/support/dp/MOD-4001.pdf. It may be an older revision, so check it against the live unit.
Other boilers & water heaters register maps
- Boiler
Lochinvar Power-fin PBX / PFX boilers and water heaters 502-1302, 1501-2001 (Modbus communication board)
Lochinvar Power-fin PB/PF 'X' models 502-1302 and 1501-2001 with the SMART SYSTEM control and Modbus/BACnet communication board, per PBX-PFX-MODB Rev D.
Also known as: Power-fin, Power-Fin, PBX502, PBX1302, PBX1501, PBX2001, PFX502, PFX2001, PBX-PFX-MODB, SMART SYSTEM - Boiler / water heater controller
AERCO C-More Boiler Controller (Benchmark / KC series)
AERCO C-More boiler controllers (software 2.00 or later) used on Benchmark and KC Series boilers and water heaters, as a Modbus RTU slave.
Also known as: C-More, Benchmark, KC1000, KC Series, Benchmark boiler, Benchmark water heater - Boiler
Lochinvar Copper-fin II / IIE boiler, water heater and pool heater (ModBus communication board)
Lochinvar Copper-fin II/IIE boilers and water heaters 402-2072 and pool heaters 502-2072 with the MTR-01 ModBus board, per manual 100160882 Rev G.
Also known as: Copper-fin II, Copper-fin IIE, CBX, CFX, CHX, CPX, C(F,H,P)X, Copperfin - Boiler controller
Patterson-Kelley NURO boiler controller (Modbus BMS port)
Patterson-Kelley NURO boiler control, Modbus register map from Appendix A of the NURO Advanced Users Guide.
Also known as: Patterson-Kelley NURO, Harsco Industrial Patterson-Kelley NURO - Boiler (burner / boiler controller)
Cleaver-Brooks CB Falcon hydronic / steam boiler control
Cleaver-Brooks CB Falcon boiler controls on the MB1 or MB2 Modbus port, per manual 750-308.
Also known as: CB Falcon, Falcon boiler control - Boiler (electric)
Lochinvar Lectrus KEB electric boilers / water heaters 0015-0150 (Modbus communication board)
Lochinvar Lectrus KEB 0015-0150 electric boilers/water heaters with the Modbus/BACnet communication board, per MODB-I-O-KEB Rev A.
Also known as: Lectrus, KEB0015, KEB0150, KEB 0015-0150, MODB-I-O-KEB, Lochinvar Lectrus
All boilers & water heaters Modbus register maps →
Source: PPC4000 Modbus Communications · MOD-4001 · rev. 2012-09-13 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.