Boiler (burner management / fuel-air ratio control) · Modbus register map

Fireye PPC4000 parallel positioning burner control (Modbus RTU) Modbus register map

Updated 17 November 2026

Short answer

The PPC4000 is Fireye's parallel positioning fuel/air ratio control for burners. It is a Modbus RTU slave with holding registers only: a read-only block of status, counters, positions, raw sensor values and lockout history, and a small read/write block for burner on/off, low fire, lead/lag, auto/manual and manual modulation rate.

This page lists 76 Modbus registers for the Fireye PPC4000 parallel positioning burner control (Modbus RTU) — 5 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Fireye’s own free documentation (linked below) and checked against it.

Manufacturer
Fireye
Model
PPC4000 parallel positioning burner control (Modbus RTU)
Equipment type
Boiler (burner management / fuel-air ratio control)
Registers
76 (5 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
8N1
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
ABCD high word first (big-endian)
Firmware
Engineering code EC08 or later
Also known as
PPC-4000, PPC4000, MOD-4001
Source document
PPC4000 Modbus Communications · MOD-4001 · rev. 2012-09-13 · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Fireye PPC4000 parallel positioning burner control (Modbus RTU)

Integration in brief

Poll the PPC4000 with FC03 at 8N1 and the baud rate chosen on the control (4800-57600). Read operational state, modulation rate and the active error; write 1/0 with FC06 to 41002 to turn the burner on or off.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 0Operational stateUINT16Operational stateRead
HR 8Current modulation rateUINT16Modulation rateRead
HR 191Current active error numberUINT16Active error numberRead
HR 4Burner on minutesUINT32 ABCDBurner on minutesRead
HR 1001Burner control on/offUINT16Burner on/off commandRead/write
HR 1004Burner control auto/manualUINT16Auto/manualRead/write
HR 1017Manual modulation rateUINT16Manual modulation rateRead/write

Enable Modbus control & writes

Modbus is available on PPC4000 units with engineering code EC08 or later; the baud rate is selected in the PPC4000 menu.

Byte order & addressing

Network setup

Watch out for

Fireye PPC4000 parallel positioning burner control (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

76 of 76 shown
Fireye PPC4000 parallel positioning burner control (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 40001Operational stateCurrent operating state number, 0-16.UINT16Read
HR2doc 40003System on minutes32-bit counter of controller operating minutes; upper word first.UINT32ABCDminRead
HR4doc 40005Burner on minutes32-bit burner running minute counter; upper word first.UINT32ABCDminRead
HR6doc 40007Completed burner cycles32-bit burner cycle counter; upper word first.UINT32ABCDRead
HR8doc 40009Current modulation rate0-100 %.UINT16%Read
HR9doc 40010Modulation modeUINT16Read0 = Manual; 1 = Auto
HR10doc 40011Internal temperature of the PPC4000In the configured temperature unit (C or F).UINT16Read
HR11doc 40012Current profile commission pointProfile point the control is running at (P0-P23).UINT16Read
HR12doc 40013Current calculated CO2 valueScaling not stated in the manual.UINT16Read
HR13doc 40014PPC4000 modelUINT16Read0 = PPC-4000 only; 1 = PPC-4000 with internal flame safeguard
HR14doc 40015Current selected profile1-4.UINT16Read
HR15doc 40016Commissioned points in current profile0-24.UINT16Read
HR17doc 40018Current digital input valuesPresent state of digital inputs 1-10 (1-16 on flame safeguard versions).UINT16Read
HR21doc 40022VFD 1 actual position0-1000.UINT16× 0.1Read
HR22doc 40023VFD 1 commanded position0-1000.UINT16× 0.1Read
HR23doc 40024VFD 2 actual position0-1000.UINT16× 0.1Read
HR24doc 40025VFD 2 commanded position0-1000.UINT16× 0.1Read
HR25doc 40026Current running efficiency0-100 %.UINT16%Read
HR26doc 40027Current O2 target valueIn tenths of a percent.UINT16× 0.1%Read
HR51doc 40052Calibration constant819-860 counts; used to convert raw sensor values (see notes).UINT16Read
HR59doc 40060Sensor 1 raw valueRaw A/D reading of the primary sensor.UINT16Read
HR60doc 40061Sensor 2 raw valueRaw A/D reading of auxiliary sensor 1.UINT16Read
HR61doc 40062Sensor 3 raw valueRaw A/D reading of auxiliary sensor 2.UINT16Read
HR65doc 40066Sensor 4 raw valueRaw only; no calibration constant.UINT16Read
HR66doc 40067Sensor 5 raw valueRaw only; no calibration constant.UINT16Read
HR79doc 40080Servo 1 current positionUINT16Read
HR88doc 40089Servo 2 current positionUINT16Read
HR97doc 40098Servo 3 current positionUINT16Read
HR106doc 40107Servo 4 current positionUINT16Read
HR115doc 40116Servo 5 current positionUINT16Read
HR124doc 40125Servo 6 current positionUINT16Read
HR133doc 40134Servo 7 current positionUINT16Read
HR142doc 40143Servo 8 current positionUINT16Read
HR151doc 40152Servo 9 current positionUINT16Read
HR160doc 40161Servo 10 current positionUINT16Read
HR190doc 40191Lockout history pointerLow byte = number of the next lockout entry.UINT16Read
HR191doc 40192Current active error number0 = no active error, otherwise the PPC4000 error code.UINT16Read
HR192doc 40193Total errors detectedStored lockout count.UINT16Read
HR193doc 40194Fault 1 (most recent) profile/stateHigh byte = profile position, low byte = operational state at the fault.UINT16Read
HR194doc 40195Fault 1 error codeUINT16Read
HR195doc 40196Fault 1 timeHigh byte = minutes, low byte = seconds.UINT16Read
HR196doc 40197Fault 1 date (day/hour)High byte = day of month, low byte = hour.UINT16Read
HR197doc 40198Fault 1 date (weekday/month)High byte = weekday (0 = Sunday), low byte = month.UINT16Read
HR198doc 40199Fault 1 yearUINT16Read
HR264doc 40265Sensor 1 set point valueUINT16Read
HR265doc 40266Sensor 1 cut-in valueUINT16Read
HR266doc 40267Sensor 1 cut-out valueUINT16Read
HR268doc 40269Sensor 1 margin alarm valueUINT16Read
HR269doc 40270Sensor 1 limit alarm valueUINT16Read
HR272doc 40273Sensor 2 set point valueUINT16Read
HR273doc 40274Sensor 2 cut-in valueUINT16Read
HR274doc 40275Sensor 2 cut-out valueUINT16Read
HR276doc 40277Sensor 2 margin alarm valueUINT16Read
HR277doc 40278Sensor 2 limit alarm valueUINT16Read
HR280doc 40281Sensor 3 set point valueUINT16Read
HR281doc 40282Sensor 3 cut-in valueUINT16Read
HR282doc 40283Sensor 3 cut-out valueUINT16Read
HR284doc 40285Sensor 3 margin alarm valueUINT16Read
HR285doc 40286Sensor 3 limit alarm valueUINT16Read
HR288doc 40289Sensor 4 set point valueUINT16Read
HR289doc 40290Sensor 4 cut-in valueUINT16Read
HR290doc 40291Sensor 4 cut-out valueUINT16Read
HR292doc 40293Sensor 4 margin alarm valueUINT16Read
HR293doc 40294Sensor 4 limit alarm valueUINT16Read
HR296doc 40297Sensor 5 set point valueUINT16Read
HR297doc 40298Sensor 5 cut-in valueUINT16Read
HR298doc 40299Sensor 5 cut-out valueUINT16Read
HR300doc 40301Sensor 5 margin alarm valueUINT16Read
HR301doc 40302Sensor 5 limit alarm valueUINT16Read
HR346doc 40347PCV set point string20-character text.STRING[20]Read
HR356doc 40357PCV measured value string20-character text.STRING[20]Read
HR1001doc 41002Burner control on/offWrite 1 to turn the burner on.UINT16Read/write0 = False; 1 = True
HR1002doc 41003Burner control low fireWrite 1 to hold low fire.UINT16Read/write0 = False; 1 = True
HR1003doc 41004Burner control lead/lagWrite 1 to make this unit the sequence master (when sequencing is enabled).UINT16Read/write0 = False; 1 = True
HR1004doc 41005Burner control auto/manualWrite 1 for automatic modulation.UINT16Read/write0 = False; 1 = True
HR1017doc 41018Manual modulation rateUsed only in manual modulation mode.UINT16Read/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Fireye PPC4000 parallel positioning burner control (Modbus RTU)

What Modbus registers does the Fireye PPC4000 parallel positioning burner control (Modbus RTU) have?

This map lists 76 registers: 76 holding registers. 5 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Fireye PPC4000 parallel positioning burner control (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The bulletin prints holding register numbers from 40001 next to the message address actually sent (40001 = address 00, 41002 = 1001). Subtract 40001 for the wire address.

What byte order does the Fireye PPC4000 parallel positioning burner control (Modbus RTU) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Fireye PPC4000 parallel positioning burner control (Modbus RTU)?

Start with HR 0 Operational state (Operational state); HR 8 Current modulation rate (Modulation rate); HR 191 Current active error number (Active error number); HR 4 Burner on minutes (Burner on minutes); HR 1001 Burner control on/off (Burner on/off command); HR 1004 Burner control auto/manual (Auto/manual); HR 1017 Manual modulation rate (Manual modulation rate).

How do I enable Modbus control of the Fireye PPC4000 parallel positioning burner control (Modbus RTU)?

Modbus is available on PPC4000 units with engineering code EC08 or later; the baud rate is selected in the PPC4000 menu.

Where is the official Fireye PPC4000 parallel positioning burner control (Modbus RTU) Modbus documentation?

The source is PPC4000 Modbus Communications (MOD-4001), revision 2012-09-13. Fireye doesn't publish it on its own website, so this map was re-typed from a free copy at https://www.ccontrols.com/support/dp/MOD-4001.pdf. It may be an older revision, so check it against the live unit.