Boiler (electric) · Modbus register map

Lochinvar Lectrus KEB electric boilers / water heaters 0015-0150 (Modbus communication board) Modbus register map

Updated 17 November 2026

Short answer

Lochinvar's Lectrus KEB electric boilers expose Modbus RTU through an RS-485 communication board. The BAS writes a configuration word, an enable word, a rate or setpoint command and optional remote temperatures; it reads safety-switch and pump states, outlet/inlet temperatures, modulation rate, pump speeds, cascade power and status/blocking/lockout codes.

This page lists 36 Modbus registers for the Lochinvar Lectrus KEB electric boilers / water heaters 0015-0150 (Modbus communication board) — 9 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Lochinvar’s own free documentation (linked below) and checked against it.

Manufacturer
Lochinvar
Model
Lectrus KEB electric boilers / water heaters 0015-0150 (Modbus communication board)
Equipment type
Boiler (electric)
Registers
36 (9 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Also known as
Lectrus, KEB0015, KEB0150, KEB 0015-0150, MODB-I-O-KEB, Lochinvar Lectrus
Source document
Modbus and BACnet Communication Instructions - Models KEB 0015-0150 · MODB-I-O-KEB 100389961_2000844370 Rev A
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Lochinvar Lectrus KEB electric boilers / water heaters 0015-0150 (Modbus communication board)

Integration in brief

Set address, baud and parity on the board DIP switches, set the control mode in the installer menu (code 5309, CONTROL MODES), then write 40001 and the commands: enable only = 40001 0x0001 + 40002 0x0001; enable + rate = 40001 0x0005 + 40002 0x0001 + 40003; rate only = 40001 0x0004 + 40003. Monitor 30009-30016.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 0ConfigurationBITMAP16Configuration bitsRead/write
HR 1BV 0-4UINT16Enable commandRead/write
HR 20-10 BMSUINT16Rate (%) or setpoint commandRead/write
IR 8Outlet TemperatureUINT16Outlet temperatureRead
IR 11Modulation RateUINT16Modulation rateRead
IR 13Boiler Status CodeUINT16Status codeRead
IR 14Boiler Blocking CodeUINT16Blocking codeRead
IR 15Boiler Lockout CodeUINT16Lockout codeRead

Enable Modbus control & writes

Installer menu (hold LEFT SELECT [MENU] 5 s, code 5309) > CONTROL MODES: set BMS to ACTIVE for rate/setpoint control or BMS TSTAT to ACTIVE for remote DHW, and choose BMS TYPE (POWER or SETPOINT). Re-send 40001 before each command.

Communication loss & watchdog

MODBUS T/O in CONTROL MODES, 5-120 s (default 10 s): BAS-supplied temperatures/0-10 V values must be refreshed within it. Other commands must be refreshed at least every 4 minutes or the boiler reverts to its own inputs.

Byte order & addressing

Network setup

Watch out for

Lochinvar Lectrus KEB electric boilers / water heaters 0015-0150 (Modbus communication board) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

36 of 36 shown
Lochinvar Lectrus KEB electric boilers / water heaters 0015-0150 (Modbus communication board) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
CO0doc 00001Boiler EnableEnable command from the BAS.BITRead/write0 = Off; 1 = On
CO4doc 00005DHW EnableDHW (tank thermostat) demand from the BAS.BITRead/write0 = Off; 1 = On
DI1doc 10002Flow SwitchBITRead0 = Off; 1 = On
DI2doc 10003Low Pressure SwitchBITRead0 = Off; 1 = On
DI3doc 10004External Low Water Cut OffBITRead0 = Off; 1 = On
DI4doc 10005Low Water Cut Off / Manual Reset High LimitBITRead0 = Off; 1 = On
DI6doc 10007Auto Reset High LimitBITRead0 = Off; 1 = On
DI8doc 10009SH EnableBITRead0 = Off; 1 = On
DI9doc 10010DHW EnableBITRead0 = Off; 1 = On
DI32doc 10033Run-time ContactsBITRead0 = Off; 1 = On
DI33doc 10034Alarm ContactsBITRead0 = Off; 1 = On
DI34doc 10035Boiler PumpBITRead0 = Off; 1 = On
DI35doc 10036DHW PumpBITRead0 = Off; 1 = On
DI36doc 10037Low Water Cut Off EnableBITRead0 = Off; 1 = On
DI37doc 10038Safety Monitor RelayBITRead0 = Off; 1 = On
DI38doc 10039System PumpBITRead0 = Off; 1 = On
IR0doc 30001Discrete Inputs 1-15Packed copy of discrete inputs 1-15.UINT16Read
IR1doc 30002Discrete Inputs 16-31Packed copy of discrete inputs 16-31.UINT16Read
IR2doc 30003Discrete Inputs 32-47Packed copy of discrete inputs 32-47.UINT16Read
IR4doc 30005System Pump Speed0-100 %.UINT16%Read
IR5doc 30006Cascade Total PowerTotal cascade capacity (100-800 %).UINT16%Read
IR6doc 30007Cascade Current PowerCurrent cascade output (0-800 %).UINT16%Read
IR8doc 30009Outlet TemperatureRaw is degrees C x 10 (manual example: 683 = 68.3 C).UINT16× 0.1°CRead
IR9doc 30010Inlet TemperatureINT16× 0.1°CRead
IR11doc 30012Modulation Rate0-100 %.UINT16%Read
IR12doc 30013Boiler Pump Speed0-100 %.UINT16%Read
IR13doc 30014Boiler Status CodeWhat the boiler is doing; 40 = lockout.UINT16Read2 = Heat demand blocked: high absolute outlet temperature; 4 = Heat demand blocked: high absolute delta T (outlet - inlet); 8 = Heat demand blocked: low 24 VDC; 10 = Blocked: boiler switched off at the display; 16 = Service function; 19 = DHW function, storage tank; 21 = Heat demand from input sensor; 22 = Heat demand from boiler management system; 23 = Heat demand from cascade; 30 = Heat demand from freeze protection; 32 = DHW pump delay; 33 = Boiler pump delay; 34 = No heat function (after pump delay); 40 = Lockout; 32767 = Code not present
IR14doc 30015Boiler Blocking CodeWhy heat demand is blocked.UINT16Read2 = Low 24 VDC supply; 5 = Boiler switched off (display ENTER switch); 7 = High delta T; 9 = High outlet temperature; 13 = Anti-cycling time; 18 = Power limited: high delta T
IR15doc 30016Boiler Lockout CodeOnly valid while the status code is 40.UINT16Read166 = EEPROM: auto reset high limit; 167 = EEPROM: auxiliary alarm contact; 168 = EEPROM: flow switch open; 169 = EEPROM: water pressure; 170 = EEPROM: external low water cut-off; 179 = Sensor 2 (inlet) fault; 180 = Sensor 2 (inlet) missing; 192 = Sensor 1 (outlet) fault; 193 = Sensor 1 (outlet) error; 230 = EEPROM: main control board error; 235 = EEPROM: LWCO / manual reset high limit; 237 = EEPROM: monitor relay not working properly; 241 = Low water cut-off recycling; 242 = Auxiliary alarm contact recycling; 243 = Flow switch recycling; 244 = Water pressure recycling
HR0doc 40001ConfigurationSelects which values the BAS supplies instead of the boiler's own inputs.BITMAP16Read/writebit 0 = Boiler Enable from BAS; bit 1 = DHW Enable from BAS; bit 2 = 0-10V BMS input from BAS; bit 3 = Tank Setpoint from BAS; bit 4 = System Supply Temperature from BAS; bit 5 = Outdoor Temperature from BAS; bit 6 = Tank Temperature from BAS
HR1doc 40002BV 0-4Command word ('Coils / BV'); manual examples: 0x0001 enables, 0x0008 = tank thermostat, 0x0000 disables.UINT16Read/write
HR2doc 400030-10 BMSRate command: modulation % or setpoint, per the BMS Type setting (0-100).UINT16%Read/write
HR4doc 40005Tank TemperatureTank temperature supplied by the BAS (0-130 C).UINT16× 0.1°CRead/write
HR5doc 40006Outdoor TemperatureOutdoor temperature supplied by the BAS (-40 to 60 C).INT16× 0.1°CRead/write
HR6doc 40007System Supply TemperatureSystem supply temperature supplied by the BAS.INT16× 0.1°CRead/write
HR7doc 40008DHW Recirculation TemperatureDHW recirculation temperature supplied by the BAS.INT16× 0.1°CRead/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Lochinvar Lectrus KEB electric boilers / water heaters 0015-0150 (Modbus communication board)

What Modbus registers does the Lochinvar Lectrus KEB electric boilers / water heaters 0015-0150 (Modbus communication board) have?

This map lists 36 registers: 2 coils, 14 discrete inputs, 13 input registers, 7 holding registers. 9 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Lochinvar Lectrus KEB electric boilers / water heaters 0015-0150 (Modbus communication board) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Addresses are printed Modicon-style (00001, 10001, 30001, 40001). Subtract the table base and 1 for the wire address; the manual's exception-code text confirms PDU addresses start at 0.

What are the minimum Modbus registers to integrate the Lochinvar Lectrus KEB electric boilers / water heaters 0015-0150 (Modbus communication board)?

Start with HR 0 Configuration (Configuration bits); HR 1 BV 0-4 (Enable command); HR 2 0-10 BMS (Rate (%) or setpoint command); IR 8 Outlet Temperature (Outlet temperature); IR 11 Modulation Rate (Modulation rate); IR 13 Boiler Status Code (Status code); IR 14 Boiler Blocking Code (Blocking code); IR 15 Boiler Lockout Code (Lockout code).

How do I enable Modbus control of the Lochinvar Lectrus KEB electric boilers / water heaters 0015-0150 (Modbus communication board)?

Installer menu (hold LEFT SELECT [MENU] 5 s, code 5309) > CONTROL MODES: set BMS to ACTIVE for rate/setpoint control or BMS TSTAT to ACTIVE for remote DHW, and choose BMS TYPE (POWER or SETPOINT). Re-send 40001 before each command.

What happens when the Lochinvar Lectrus KEB electric boilers / water heaters 0015-0150 (Modbus communication board) loses Modbus communication?

MODBUS T/O in CONTROL MODES, 5-120 s (default 10 s): BAS-supplied temperatures/0-10 V values must be refreshed within it. Other commands must be refreshed at least every 4 minutes or the boiler reverts to its own inputs.

Where is the official Lochinvar Lectrus KEB electric boilers / water heaters 0015-0150 (Modbus communication board) Modbus documentation?

The source is Modbus and BACnet Communication Instructions - Models KEB 0015-0150 (MODB-I-O-KEB 100389961_2000844370 Rev A), published free by Lochinvar at https://assets.lochinvar.com/damroot/Original/10017/MODB-I-O-KEB_100389961_2000844370_Rev_A_(63600).pdf.