- Lectrus KEB electric boilers / water heaters 0015-0150 (Modbus communication board)
Boiler (electric) · Modbus register map
Lochinvar Lectrus KEB electric boilers / water heaters 0015-0150 (Modbus communication board) Modbus register map
Updated 17 November 2026
Lochinvar's Lectrus KEB electric boilers expose Modbus RTU through an RS-485 communication board. The BAS writes a configuration word, an enable word, a rate or setpoint command and optional remote temperatures; it reads safety-switch and pump states, outlet/inlet temperatures, modulation rate, pump speeds, cascade power and status/blocking/lockout codes.
This page lists 36 Modbus registers for the Lochinvar Lectrus KEB electric boilers / water heaters 0015-0150 (Modbus communication board) — 9 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Lochinvar’s own free documentation (linked below) and checked against it.
- Manufacturer
- Lochinvar
- Model
- Lectrus KEB electric boilers / water heaters 0015-0150 (Modbus communication board)
- Equipment type
- Boiler (electric)
- Registers
- 36 (9 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Also known as
- Lectrus, KEB0015, KEB0150, KEB 0015-0150, MODB-I-O-KEB, Lochinvar Lectrus
Integration notes: Lochinvar Lectrus KEB electric boilers / water heaters 0015-0150 (Modbus communication board)
Set address, baud and parity on the board DIP switches, set the control mode in the installer menu (code 5309, CONTROL MODES), then write 40001 and the commands: enable only = 40001 0x0001 + 40002 0x0001; enable + rate = 40001 0x0005 + 40002 0x0001 + 40003; rate only = 40001 0x0004 + 40003. Monitor 30009-30016.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 0 | Configuration | BITMAP16 | Configuration bits | Read/write |
| HR 1 | BV 0-4 | UINT16 | Enable command | Read/write |
| HR 2 | 0-10 BMS | UINT16 | Rate (%) or setpoint command | Read/write |
| IR 8 | Outlet Temperature | UINT16 | Outlet temperature | Read |
| IR 11 | Modulation Rate | UINT16 | Modulation rate | Read |
| IR 13 | Boiler Status Code | UINT16 | Status code | Read |
| IR 14 | Boiler Blocking Code | UINT16 | Blocking code | Read |
| IR 15 | Boiler Lockout Code | UINT16 | Lockout code | Read |
Enable Modbus control & writes
Installer menu (hold LEFT SELECT [MENU] 5 s, code 5309) > CONTROL MODES: set BMS to ACTIVE for rate/setpoint control or BMS TSTAT to ACTIVE for remote DHW, and choose BMS TYPE (POWER or SETPOINT). Re-send 40001 before each command.
Communication loss & watchdog
MODBUS T/O in CONTROL MODES, 5-120 s (default 10 s): BAS-supplied temperatures/0-10 V values must be refreshed within it. Other commands must be refreshed at least every 4 minutes or the boiler reverts to its own inputs.
Byte order & addressing
- Modicon addressing: 30009 is input register 8 on the wire.
- Temperatures are degrees C x 10 with DIP switch 8 OFF.
- A setpoint sent through 40003 is the 0-10 V equivalent percentage interpolated from the BMS low/high setpoint parameters, not degrees.
- Read the lockout code only when the status code is 40.
Network setup
- DIP switches 1-7: Modbus address (maximum 127).
- DIP switch 8: OFF = Celsius, ON = Fahrenheit.
- DIP switch 9: 0 = 9600 baud, 1 = 19200 baud.
- DIP switch 10: 0 = no parity with 2 stop bits, 1 = even parity with 1 stop bit.
- RTU only; check 120 ohm termination.
Watch out for
- Board LED D7: 1 s bright / 1 s dim = normal; 1.5 s on / 0.5 s off = no Modbus traffic; 0.5 s on / 1.5 s off = no burner-control communication.
Lochinvar Lectrus KEB electric boilers / water heaters 0015-0150 (Modbus communication board) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 0doc 00001 | Boiler Enable | Enable command from the BAS. | BIT | Read/write | 0 = Off; 1 = On | |||
| CO | 4doc 00005 | DHW Enable | DHW (tank thermostat) demand from the BAS. | BIT | Read/write | 0 = Off; 1 = On | |||
| DI | 1doc 10002 | Flow Switch | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 2doc 10003 | Low Pressure Switch | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 3doc 10004 | External Low Water Cut Off | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 4doc 10005 | Low Water Cut Off / Manual Reset High Limit | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 6doc 10007 | Auto Reset High Limit | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 8doc 10009 | SH Enable | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 9doc 10010 | DHW Enable | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 32doc 10033 | Run-time Contacts | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 33doc 10034 | Alarm Contacts | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 34doc 10035 | Boiler Pump | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 35doc 10036 | DHW Pump | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 36doc 10037 | Low Water Cut Off Enable | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 37doc 10038 | Safety Monitor Relay | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 38doc 10039 | System Pump | BIT | Read | 0 = Off; 1 = On | ||||
| IR | 0doc 30001 | Discrete Inputs 1-15 | Packed copy of discrete inputs 1-15. | UINT16 | Read | ||||
| IR | 1doc 30002 | Discrete Inputs 16-31 | Packed copy of discrete inputs 16-31. | UINT16 | Read | ||||
| IR | 2doc 30003 | Discrete Inputs 32-47 | Packed copy of discrete inputs 32-47. | UINT16 | Read | ||||
| IR | 4doc 30005 | System Pump Speed | 0-100 %. | UINT16 | % | Read | |||
| IR | 5doc 30006 | Cascade Total Power | Total cascade capacity (100-800 %). | UINT16 | % | Read | |||
| IR | 6doc 30007 | Cascade Current Power | Current cascade output (0-800 %). | UINT16 | % | Read | |||
| IR | 8doc 30009 | Outlet Temperature | Raw is degrees C x 10 (manual example: 683 = 68.3 C). | UINT16 | × 0.1 | °C | Read | ||
| IR | 9doc 30010 | Inlet Temperature | INT16 | × 0.1 | °C | Read | |||
| IR | 11doc 30012 | Modulation Rate | 0-100 %. | UINT16 | % | Read | |||
| IR | 12doc 30013 | Boiler Pump Speed | 0-100 %. | UINT16 | % | Read | |||
| IR | 13doc 30014 | Boiler Status Code | What the boiler is doing; 40 = lockout. | UINT16 | Read | 2 = Heat demand blocked: high absolute outlet temperature; 4 = Heat demand blocked: high absolute delta T (outlet - inlet); 8 = Heat demand blocked: low 24 VDC; 10 = Blocked: boiler switched off at the display; 16 = Service function; 19 = DHW function, storage tank; 21 = Heat demand from input sensor; 22 = Heat demand from boiler management system; 23 = Heat demand from cascade; 30 = Heat demand from freeze protection; 32 = DHW pump delay; 33 = Boiler pump delay; 34 = No heat function (after pump delay); 40 = Lockout; 32767 = Code not present | |||
| IR | 14doc 30015 | Boiler Blocking Code | Why heat demand is blocked. | UINT16 | Read | 2 = Low 24 VDC supply; 5 = Boiler switched off (display ENTER switch); 7 = High delta T; 9 = High outlet temperature; 13 = Anti-cycling time; 18 = Power limited: high delta T | |||
| IR | 15doc 30016 | Boiler Lockout Code | Only valid while the status code is 40. | UINT16 | Read | 166 = EEPROM: auto reset high limit; 167 = EEPROM: auxiliary alarm contact; 168 = EEPROM: flow switch open; 169 = EEPROM: water pressure; 170 = EEPROM: external low water cut-off; 179 = Sensor 2 (inlet) fault; 180 = Sensor 2 (inlet) missing; 192 = Sensor 1 (outlet) fault; 193 = Sensor 1 (outlet) error; 230 = EEPROM: main control board error; 235 = EEPROM: LWCO / manual reset high limit; 237 = EEPROM: monitor relay not working properly; 241 = Low water cut-off recycling; 242 = Auxiliary alarm contact recycling; 243 = Flow switch recycling; 244 = Water pressure recycling | |||
| HR | 0doc 40001 | Configuration | Selects which values the BAS supplies instead of the boiler's own inputs. | BITMAP16 | Read/write | bit 0 = Boiler Enable from BAS; bit 1 = DHW Enable from BAS; bit 2 = 0-10V BMS input from BAS; bit 3 = Tank Setpoint from BAS; bit 4 = System Supply Temperature from BAS; bit 5 = Outdoor Temperature from BAS; bit 6 = Tank Temperature from BAS | |||
| HR | 1doc 40002 | BV 0-4 | Command word ('Coils / BV'); manual examples: 0x0001 enables, 0x0008 = tank thermostat, 0x0000 disables. | UINT16 | Read/write | ||||
| HR | 2doc 40003 | 0-10 BMS | Rate command: modulation % or setpoint, per the BMS Type setting (0-100). | UINT16 | % | Read/write | |||
| HR | 4doc 40005 | Tank Temperature | Tank temperature supplied by the BAS (0-130 C). | UINT16 | × 0.1 | °C | Read/write | ||
| HR | 5doc 40006 | Outdoor Temperature | Outdoor temperature supplied by the BAS (-40 to 60 C). | INT16 | × 0.1 | °C | Read/write | ||
| HR | 6doc 40007 | System Supply Temperature | System supply temperature supplied by the BAS. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 7doc 40008 | DHW Recirculation Temperature | DHW recirculation temperature supplied by the BAS. | INT16 | × 0.1 | °C | Read/write |
Notes on this map
- Temperatures: the conversion section says the boiler passes temperatures in degrees C and the value must be divided by 10 (examples: 26.7 C sent as 267; outlet 683 = 68.3 C). Scale 0.1 is applied to the registers with 0.1 resolution in the map, assuming DIP switch 8 is OFF (Celsius).
- DIP switch 8 selects Celsius (OFF) or Fahrenheit (ON). The map shows Fahrenheit rows only for the setpoints; the manual does not say how the 0.1-resolution temperatures change with the switch ON, so keep it OFF when using this map.
- Left out: System/Cascade Setpoint (30004), Outlet Setpoint (30008) and Tank Setpoint (40004). They have 0.5 C (or 1.0/1.5 F) resolution in the map while the conversion text says C x 10, so their scaling is not settled.
- Signed types: inlet and BAS-supplied temperatures have negative minimums in the map and are listed as INT16; the manual itself only says 16-bit word.
- Input registers 30001-30003 are packed copies of the discrete inputs; the bit order is not stated, so they are UINT16. Use the discrete inputs instead.
- The manual repeats its unit-operation section twice (Control Modes 1-4 and Demand Configurations) with the same register values; the integration steps follow both.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Lochinvar Lectrus KEB electric boilers / water heaters 0015-0150 (Modbus communication board)
What Modbus registers does the Lochinvar Lectrus KEB electric boilers / water heaters 0015-0150 (Modbus communication board) have?
This map lists 36 registers: 2 coils, 14 discrete inputs, 13 input registers, 7 holding registers. 9 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Lochinvar Lectrus KEB electric boilers / water heaters 0015-0150 (Modbus communication board) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Addresses are printed Modicon-style (00001, 10001, 30001, 40001). Subtract the table base and 1 for the wire address; the manual's exception-code text confirms PDU addresses start at 0.
What are the minimum Modbus registers to integrate the Lochinvar Lectrus KEB electric boilers / water heaters 0015-0150 (Modbus communication board)?
Start with HR 0 Configuration (Configuration bits); HR 1 BV 0-4 (Enable command); HR 2 0-10 BMS (Rate (%) or setpoint command); IR 8 Outlet Temperature (Outlet temperature); IR 11 Modulation Rate (Modulation rate); IR 13 Boiler Status Code (Status code); IR 14 Boiler Blocking Code (Blocking code); IR 15 Boiler Lockout Code (Lockout code).
How do I enable Modbus control of the Lochinvar Lectrus KEB electric boilers / water heaters 0015-0150 (Modbus communication board)?
Installer menu (hold LEFT SELECT [MENU] 5 s, code 5309) > CONTROL MODES: set BMS to ACTIVE for rate/setpoint control or BMS TSTAT to ACTIVE for remote DHW, and choose BMS TYPE (POWER or SETPOINT). Re-send 40001 before each command.
What happens when the Lochinvar Lectrus KEB electric boilers / water heaters 0015-0150 (Modbus communication board) loses Modbus communication?
MODBUS T/O in CONTROL MODES, 5-120 s (default 10 s): BAS-supplied temperatures/0-10 V values must be refreshed within it. Other commands must be refreshed at least every 4 minutes or the boiler reverts to its own inputs.
Where is the official Lochinvar Lectrus KEB electric boilers / water heaters 0015-0150 (Modbus communication board) Modbus documentation?
The source is Modbus and BACnet Communication Instructions - Models KEB 0015-0150 (MODB-I-O-KEB 100389961_2000844370 Rev A), published free by Lochinvar at https://assets.lochinvar.com/damroot/Original/10017/MODB-I-O-KEB_100389961_2000844370_Rev_A_(63600).pdf.
More Lochinvar Modbus register maps
- Boiler (commercial water heater)
Lochinvar Armor 1250-4000 commercial water heaters, Series 100 & 101 (Modbus communication board)
Lochinvar Armor water heaters, models 1250-4000, Series 100 and 101, with the SMART SYSTEM control and Modbus/BACnet communication board, per 100305786_2000558371 Rev C.
Also known as: Armor 1250, Armor 1500, Armor 2000, Armor 2500, Armor 3000, Armor 3500, Armor 4000, AWH, AWH1250, AWH4000, SMART SYSTEM - Boiler
Lochinvar Copper-fin II / IIE boiler, water heater and pool heater (ModBus communication board)
Lochinvar Copper-fin II/IIE boilers and water heaters 402-2072 and pool heaters 502-2072 with the MTR-01 ModBus board, per manual 100160882 Rev G.
Also known as: Copper-fin II, Copper-fin IIE, CBX, CFX, CHX, CPX, C(F,H,P)X, Copperfin - Boiler
Lochinvar Crest / Crest with Hellcat boilers (ModBus communication board)
Lochinvar Crest FB/OF 751-6001 and FCB1000-6000 (including Crest with Hellcat) with the ModBus communication board.
Also known as: Crest, Crest FB751-6001, Crest OF751-6001, Crest FCB1000-6000, Hellcat, MTR-01 - Boiler / water heater
Lochinvar Knight / Armor / Wall Mount boilers (ModBus communication board)
Knight 81-286, Knight XL 400-1000, Armor 151-1000, Outdoor Knight/Knight XL/Armor, AQUAS 400-801, FTXL 400-1000, Wall Mount 51-211, Wall Hung 55-399, Wall Mount Armor 125-200 and Shield 125-500 with the Lochinvar ModBus communication board.
Also known as: Knight, Knight XL, Outdoor Knight, Outdoor Knight XL, Armor, Outdoor Armor, Wall Mount Armor, Knight Wall Mount, Knight Wall Hung, AQUAS, FTXL, Shield - Boiler
Lochinvar Power-fin PBX / PFX boilers and water heaters 502-1302, 1501-2001 (Modbus communication board)
Lochinvar Power-fin PB/PF 'X' models 502-1302 and 1501-2001 with the SMART SYSTEM control and Modbus/BACnet communication board, per PBX-PFX-MODB Rev D.
Also known as: Power-fin, Power-Fin, PBX502, PBX1302, PBX1501, PBX2001, PFX502, PFX2001, PBX-PFX-MODB, SMART SYSTEM - Boiler
Lochinvar SYNC condensing boilers / water heaters 1.0, 1.3, 1.5 (Modbus communication board)
Lochinvar SYNC 1.0 / 1.3 / 1.5 dual-module boilers and water heaters with the Modbus/BACnet communication board, per SYNC-MODB Rev L.
Also known as: SYNC 1.0, SYNC 1.3, SYNC 1.5, SYNC, Lochinvar SYNC, SYNC-MODB
Other boilers & water heaters register maps
- Boiler
Weil-McLain Unity 2 control (ECO Tec 80-199, SVF 500/600 boilers)
Weil-McLain boilers with the Unity 2 control (ECO Tec 80/110/150/199 wall-mount and combi, SVF 500/600), per Modbus supplement 550-100-266/1023.
Also known as: ECO Tec 80, ECO Tec 110, ECO Tec 150, ECO Tec 199, ECO Tec Combi, SVF 500, SVF 600, Unity2 - Boiler
Mestek KNSLM boiler control (KN2 / KN4 / rAy series)
KNSLM boiler control (KN2/KN4/rAy series), register list V1.10; registers marked 2.70+ need firmware 2.70 or later.
Also known as: KNSLM, KN2, KN4, rAy - Boiler
Buderus SSB condensing boilers (built-in Modbus RTU)
Buderus SSB series condensing boilers (Bosch Thermotechnology, North America) using the Modbus terminals on the boiler's internal terminal strip, per installation instructions 6720818450 (2015/10).
Also known as: SSB, Buderus SSB boiler, Bosch SSB, 6720818450 - Boiler (water heater controller)
PVI Industries XR10CX water heater digital operating controller (Modbus RTU)
PVI XR10CX digital operating controls on RS-485 Modbus RTU, per PVI manual PV500-67 (06/2014).
Also known as: XR10CX, PV500-67 - Boiler controller
Honeywell SOLA hydronic boiler control (Modbus interface)
Honeywell SOLA (R7910/R7911) integrated boiler controls, status registers 0-173 of the SOLA Modbus Interface specification Rev 4.1.1 (2013-10-14). Used inside many OEM condensing boilers.
Also known as: R7910, R7911, Honeywell SOLA, SOLA ICP - Boiler / heating system controller
Buderus Logamatic 5000 boiler and system controller (Modbus TCP, datapoint list 4.0)
Buderus Logamatic 5313 and 5311 (and the Bosch Control 8313/8311 equivalents) acting as master, firmware 1.3 or later with the 4.0 datapoint list; addresses for slave controllers differ.
Also known as: Logamatic 5313, Logamatic 5311, Bosch Control 8313, Bosch Control 8311, Control 8000, BCT 531, Logamatic 5000 Modbus
All boilers & water heaters Modbus register maps →
Source: Modbus and BACnet Communication Instructions - Models KEB 0015-0150 · MODB-I-O-KEB 100389961_2000844370 Rev A. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.