- Copper-fin II / IIE boiler, water heater and pool heater (ModBus communication board)
Boiler · Modbus register map
Lochinvar Copper-fin II / IIE boiler, water heater and pool heater (ModBus communication board) Modbus register map
Updated 17 November 2026
Copper-fin II and IIE copper-tube boilers, water heaters and pool heaters talk Modbus RTU through Lochinvar's MTR-01 communication board on RS-485. The map uses coils for stage and tank-thermostat enables, discrete inputs for safety switches and outputs, input registers for temperatures, firing rate and status/blocking/lockout codes, and holding registers for configuration bits and BAS-supplied temperatures. All values are 16-bit; temperatures are degrees C x 10.
This page lists 56 Modbus registers for the Lochinvar Copper-fin II / IIE boiler, water heater and pool heater (ModBus communication board) — 12 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Lochinvar’s own free documentation (linked below) and checked against it.
- Manufacturer
- Lochinvar
- Model
- Copper-fin II / IIE boiler, water heater and pool heater (ModBus communication board)
- Equipment type
- Boiler
- Registers
- 56 (12 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Also known as
- Copper-fin II, Copper-fin IIE, CBX, CFX, CHX, CPX, C(F,H,P)X, Copperfin
Integration notes: Lochinvar Copper-fin II / IIE boiler, water heater and pool heater (ModBus communication board)
Set parameter H6 ModBus to Active, then write the configuration bits (40001) and enables (40002 or coils) and poll input registers 30009-30016 for temperatures, firing rate and status.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| CO 0 | Stage 1 Enable | BIT | Stage 1 enable | Read/write |
| IR 8 | Outlet temperature | INT16 | Outlet temperature | Read |
| IR 9 | Inlet temperature | INT16 | Inlet temperature | Read |
| IR 11 | Firing rate | UINT16 | Firing rate | Read |
| IR 13 | Status code | UINT16 | Status code | Read |
| IR 15 | Lockout code | UINT16 | Lockout code | Read |
| HR 0 | Configuration | BITMAP16 | Configuration bits | Read/write |
Enable Modbus control & writes
Set control parameter H6 ModBus to Active; address on dip switches 1-8, baud on switch 9 (0 = 9600, 1 = 19200), parity on switch 10 (0 = none with 2 stop bits, 1 = even with 1 stop bit).
Communication loss & watchdog
BAS-supplied temperatures must be refreshed within the H7 ModBus Time (1-255 s, default 10 s); other commands within 4 minutes, or the control reverts to its local inputs.
Byte order & addressing
- Re-send the configuration bits to 40001 before issuing commands.
- Rate (40003) is a plain percent integer.
Network setup
- RTU only.
- No parity uses two stop bits; even parity uses one.
Watch out for
- Lockout code 30016 changes constantly; trust it only when status code = 40.
Lochinvar Copper-fin II / IIE boiler, water heater and pool heater (ModBus communication board) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 0doc 00001 | Stage 1 Enable | BIT | Read/write | 0 = Off; 1 = On | ||||
| CO | 1doc 00002 | Stage 2 Enable | BIT | Read/write | 0 = Off; 1 = On | ||||
| CO | 2doc 00003 | Stage 3 Enable | BIT | Read/write | 0 = Off; 1 = On | ||||
| CO | 3doc 00004 | Stage 4 Enable | BIT | Read/write | 0 = Off; 1 = On | ||||
| CO | 4doc 00005 | Tank Thermostat | BIT | Read/write | 0 = Off; 1 = On | ||||
| DI | 0doc 10001 | High Limits | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 1doc 10002 | Flow Switch | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 2doc 10003 | Gas Pressure Switch | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 3doc 10004 | Louver Proving Switch | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 4doc 10005 | Air Pressure Switch | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 7doc 10008 | Flame 1 | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 8doc 10009 | Stage 1 On | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 9doc 10010 | Tank Thermostat | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 10doc 10011 | Stage 2 On | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 11doc 10012 | Stage 3 On | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 12doc 10013 | Stage 4 On | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 22doc 10023 | Flame 2 | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 23doc 10024 | Enable 2 | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 32doc 10033 | Runtime Contacts | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 33doc 10034 | Alarm Contacts | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 34doc 10035 | HTR Pump | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 35doc 10036 | DHW Pump | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 36doc 10037 | Louver Relay | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 37doc 10038 | Gas Valve 1 | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 38doc 10039 | System Pump | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 45doc 10046 | Gas Valve 2 | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 46doc 10047 | Gas Valve 3 | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 47doc 10048 | Gas Valve 4 | BIT | Read | 0 = Off; 1 = On | ||||
| IR | 0doc 30001 | Discrete inputs 1-16 (packed) | Packed copy of the discrete inputs; bit order not stated. | UINT16 | Read | ||||
| IR | 1doc 30002 | Discrete inputs 17-32 (packed) | UINT16 | Read | |||||
| IR | 2doc 30003 | Discrete inputs 33-48 (packed) | UINT16 | Read | |||||
| IR | 4doc 30005 | System pump speed | UINT16 | % | Read | ||||
| IR | 5doc 30006 | Cascade total power | UINT16 | % | Read | ||||
| IR | 6doc 30007 | Cascade current power | UINT16 | % | Read | ||||
| IR | 8doc 30009 | Outlet temperature | INT16 | × 0.1 | °C | Read | |||
| IR | 9doc 30010 | Inlet temperature | INT16 | × 0.1 | °C | Read | |||
| IR | 10doc 30011 | Pool temperature | INT16 | × 0.1 | °C | Read | |||
| IR | 11doc 30012 | Firing rate | UINT16 | % | Read | ||||
| IR | 13doc 30014 | Status code | UINT16 | Read | 2 = Heat demand blocked: high absolute outlet temperature; 3 = Heat demand blocked: high absolute flue temperature; 4 = Heat demand blocked: high absolute delta T; 8 = Heat demand blocked: low 24 VAC; 9 = Outdoor shutdown; 10 = Blocked: boiler switched off at display; 12 = Blocked: no correct cascade communication; 16 = Service function; 19 = DHW function, storage tank; 21 = SH heat demand from room thermostat; 22 = SH heat demand from boiler management system; 23 = SH heat demand from cascade; 30 = Heat demand from freeze protection; 32 = DHW pump delay; 33 = SH pump delay; 34 = No heat function (after pump delay); 40 = Lockout; 32764 = Busy updating status; 32765 = DHW blocked: no tank sensor; 32766 = Burner control(s) manually shut down; 32767 = Code not present | ||||
| IR | 14doc 30015 | Blocking code | UINT16 | Read | 0 = No blocking; 1 = SH blocking; 2 = Low 24 VAC supply; 3 = General block; 4 = MRHL open; 5 = Boiler switched off (display); 6 = Wrong cascade communication; 7 = High delta T; 8 = High flue temperature; 9 = High outlet temperature; 10 = Service blocking; 12 = DHW blocking, high outlet temperature; 13 = Anti-cycling time; 14 = Storage tank demand blocked, fan problem; 15 = No system sensor with leader control; 16 = Fan speed limited, high outlet temperature; 17 = Fan minimum decreased, low flame current; 18 = Max fan speed limited, high delta T; 19 = Max fan speed limited, high flue temperature; 32767 = Code not present | ||||
| IR | 15doc 30016 | Lockout code | Only meaningful when the status code is 40 (lockout). | UINT16 | Read | ||||
| IR | 26doc 30027 | Lockout code leader | UINT16 | Read | |||||
| IR | 27doc 30028 | Lockout code member 1 | UINT16 | Read | |||||
| IR | 28doc 30029 | Lockout code member 2 | UINT16 | Read | |||||
| IR | 29doc 30030 | Lockout code member 3 | UINT16 | Read | |||||
| IR | 30doc 30031 | Lockout code member 4 | UINT16 | Read | |||||
| IR | 31doc 30032 | Lockout code member 5 | UINT16 | Read | |||||
| IR | 32doc 30033 | Lockout code member 6 | UINT16 | Read | |||||
| IR | 33doc 30034 | Lockout code member 7 | UINT16 | Read | |||||
| HR | 0doc 40001 | Configuration | Set bit = take that value from the BAS, not the local input. | BITMAP16 | Read/write | bit 0 = Boiler enable; bit 1 = Tank thermostat; bit 2 = Rate command / 0-10 V input / set point command; bit 3 = Tank set point; bit 4 = System supply temperature; bit 5 = Outdoor temperature; bit 6 = Tank temperature; bit 7 = System return temperature | |||
| HR | 1doc 40002 | Coils | Enable bits written by the BAS; meaning depends on control mode (e.g. 0x0001 = Enable 1). | UINT16 | Read/write | ||||
| HR | 2doc 40003 | 0-10 V input / rate command / set point command | Percent written as a plain integer, e.g. 49 = 0x31. | UINT16 | % | Read/write | |||
| HR | 4doc 40005 | Tank temperature (from BAS) | INT16 | × 0.1 | °C | Read/write | |||
| HR | 5doc 40006 | Outdoor temperature (from BAS) | INT16 | × 0.1 | °C | Read/write | |||
| HR | 6doc 40007 | System supply temperature (from BAS) | INT16 | × 0.1 | °C | Read/write | |||
| HR | 7doc 40008 | System return temperature (from BAS) | INT16 | × 0.1 | °C | Read/write |
Notes on this map
- Temperatures: the conversion section says temperatures pass in degrees C with the decimal value divided by 10 (worked examples: 26.7 C sent as 267, 683 read as 68.3 C), so scale 0.1 is used.
- Left out: System/Cascade set point (30004), Outlet set point (30008) and Pool set point (40004). The map prints a 0.5 resolution for these while the conversion section says temperature data is C x 10, so their scaling is not settled.
- Registers with a negative published minimum (inlet, pool, tank, outdoor, supply/return temperatures) are typed INT16; the manual only says 16-bit word. Outlet temperature is also typed INT16 for consistency with the other temperatures.
- Status codes are also listed for input register 30023 and blocking codes for 30024 in the troubleshooting section, but those registers are not in the memory map, so they are not listed.
- The lockout code list is in the manual (p. 25); 30016 changes during operation and should be read only when the status code is 40.
- The BACnet section says dip switch 8 selects C or F; in the ModBus section switch 8 is an address bit (value 128). Units here assume C, as in the conversion examples.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Lochinvar Copper-fin II / IIE boiler, water heater and pool heater (ModBus communication board)
What Modbus registers does the Lochinvar Copper-fin II / IIE boiler, water heater and pool heater (ModBus communication board) have?
This map lists 56 registers: 5 coils, 23 discrete inputs, 21 input registers, 7 holding registers. 12 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Lochinvar Copper-fin II / IIE boiler, water heater and pool heater (ModBus communication board) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Addresses are printed Modicon-style (00001 coils, 10001 discrete inputs, 30001 input registers, 40001 holding registers). Subtract the table base and 1 for the wire address; the exception-code text describes PDU addresses starting at 0.
What are the minimum Modbus registers to integrate the Lochinvar Copper-fin II / IIE boiler, water heater and pool heater (ModBus communication board)?
Start with CO 0 Stage 1 Enable (Stage 1 enable); IR 8 Outlet temperature (Outlet temperature); IR 9 Inlet temperature (Inlet temperature); IR 11 Firing rate (Firing rate); IR 13 Status code (Status code); IR 15 Lockout code (Lockout code); HR 0 Configuration (Configuration bits).
How do I enable Modbus control of the Lochinvar Copper-fin II / IIE boiler, water heater and pool heater (ModBus communication board)?
Set control parameter H6 ModBus to Active; address on dip switches 1-8, baud on switch 9 (0 = 9600, 1 = 19200), parity on switch 10 (0 = none with 2 stop bits, 1 = even with 1 stop bit).
What happens when the Lochinvar Copper-fin II / IIE boiler, water heater and pool heater (ModBus communication board) loses Modbus communication?
BAS-supplied temperatures must be refreshed within the H7 ModBus Time (1-255 s, default 10 s); other commands within 4 minutes, or the control reverts to its local inputs.
Where is the official Lochinvar Copper-fin II / IIE boiler, water heater and pool heater (ModBus communication board) Modbus documentation?
The source is Copper-fin II/IIE Boiler, Water Heater and Pool Heater - ModBus and BACnet Communication Instructions (100160882_2000001229 Rev G), revision 2026-01, published free by Lochinvar at https://assets.lochinvar.com/damroot/Original/10017/C(F,H,P)X-MODB_100160882_2000001229_REV%20G_(69837).pdf.
More Lochinvar Modbus register maps
- Boiler (commercial water heater)
Lochinvar Armor 1250-4000 commercial water heaters, Series 100 & 101 (Modbus communication board)
Lochinvar Armor water heaters, models 1250-4000, Series 100 and 101, with the SMART SYSTEM control and Modbus/BACnet communication board, per 100305786_2000558371 Rev C.
Also known as: Armor 1250, Armor 1500, Armor 2000, Armor 2500, Armor 3000, Armor 3500, Armor 4000, AWH, AWH1250, AWH4000, SMART SYSTEM - Boiler
Lochinvar Crest / Crest with Hellcat boilers (ModBus communication board)
Lochinvar Crest FB/OF 751-6001 and FCB1000-6000 (including Crest with Hellcat) with the ModBus communication board.
Also known as: Crest, Crest FB751-6001, Crest OF751-6001, Crest FCB1000-6000, Hellcat, MTR-01 - Boiler / water heater
Lochinvar Knight / Armor / Wall Mount boilers (ModBus communication board)
Knight 81-286, Knight XL 400-1000, Armor 151-1000, Outdoor Knight/Knight XL/Armor, AQUAS 400-801, FTXL 400-1000, Wall Mount 51-211, Wall Hung 55-399, Wall Mount Armor 125-200 and Shield 125-500 with the Lochinvar ModBus communication board.
Also known as: Knight, Knight XL, Outdoor Knight, Outdoor Knight XL, Armor, Outdoor Armor, Wall Mount Armor, Knight Wall Mount, Knight Wall Hung, AQUAS, FTXL, Shield - Boiler (electric)
Lochinvar Lectrus KEB electric boilers / water heaters 0015-0150 (Modbus communication board)
Lochinvar Lectrus KEB 0015-0150 electric boilers/water heaters with the Modbus/BACnet communication board, per MODB-I-O-KEB Rev A.
Also known as: Lectrus, KEB0015, KEB0150, KEB 0015-0150, MODB-I-O-KEB, Lochinvar Lectrus - Boiler
Lochinvar Power-fin PBX / PFX boilers and water heaters 502-1302, 1501-2001 (Modbus communication board)
Lochinvar Power-fin PB/PF 'X' models 502-1302 and 1501-2001 with the SMART SYSTEM control and Modbus/BACnet communication board, per PBX-PFX-MODB Rev D.
Also known as: Power-fin, Power-Fin, PBX502, PBX1302, PBX1501, PBX2001, PFX502, PFX2001, PBX-PFX-MODB, SMART SYSTEM - Boiler
Lochinvar SYNC condensing boilers / water heaters 1.0, 1.3, 1.5 (Modbus communication board)
Lochinvar SYNC 1.0 / 1.3 / 1.5 dual-module boilers and water heaters with the Modbus/BACnet communication board, per SYNC-MODB Rev L.
Also known as: SYNC 1.0, SYNC 1.3, SYNC 1.5, SYNC, Lochinvar SYNC, SYNC-MODB
Other boilers & water heaters register maps
- Boiler controller
Patterson-Kelley NURO boiler controller (Modbus BMS port)
Patterson-Kelley NURO boiler control, Modbus register map from Appendix A of the NURO Advanced Users Guide.
Also known as: Patterson-Kelley NURO, Harsco Industrial Patterson-Kelley NURO - Boiler (burner / boiler controller)
Cleaver-Brooks CB Falcon hydronic / steam boiler control
Cleaver-Brooks CB Falcon boiler controls on the MB1 or MB2 Modbus port, per manual 750-308.
Also known as: CB Falcon, Falcon boiler control - Boiler
Weil-McLain Unity 2 control (ECO Tec 80-199, SVF 500/600 boilers)
Weil-McLain boilers with the Unity 2 control (ECO Tec 80/110/150/199 wall-mount and combi, SVF 500/600), per Modbus supplement 550-100-266/1023.
Also known as: ECO Tec 80, ECO Tec 110, ECO Tec 150, ECO Tec 199, ECO Tec Combi, SVF 500, SVF 600, Unity2 - Boiler
Mestek KNSLM boiler control (KN2 / KN4 / rAy series)
KNSLM boiler control (KN2/KN4/rAy series), register list V1.10; registers marked 2.70+ need firmware 2.70 or later.
Also known as: KNSLM, KN2, KN4, rAy - Boiler
Buderus SSB condensing boilers (built-in Modbus RTU)
Buderus SSB series condensing boilers (Bosch Thermotechnology, North America) using the Modbus terminals on the boiler's internal terminal strip, per installation instructions 6720818450 (2015/10).
Also known as: SSB, Buderus SSB boiler, Bosch SSB, 6720818450 - Boiler (water heater controller)
PVI Industries XR10CX water heater digital operating controller (Modbus RTU)
PVI XR10CX digital operating controls on RS-485 Modbus RTU, per PVI manual PV500-67 (06/2014).
Also known as: XR10CX, PV500-67
All boilers & water heaters Modbus register maps →
Source: Copper-fin II/IIE Boiler, Water Heater and Pool Heater - ModBus and BACnet Communication Instructions · 100160882_2000001229 Rev G · rev. 2026-01. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.