Lochinvar Copper-fin II / IIE boiler, water heater and pool heater (ModBus communication board) Modbus register map

Updated 17 November 2026

Short answer

Copper-fin II and IIE copper-tube boilers, water heaters and pool heaters talk Modbus RTU through Lochinvar's MTR-01 communication board on RS-485. The map uses coils for stage and tank-thermostat enables, discrete inputs for safety switches and outputs, input registers for temperatures, firing rate and status/blocking/lockout codes, and holding registers for configuration bits and BAS-supplied temperatures. All values are 16-bit; temperatures are degrees C x 10.

This page lists 56 Modbus registers for the Lochinvar Copper-fin II / IIE boiler, water heater and pool heater (ModBus communication board) — 12 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Lochinvar’s own free documentation (linked below) and checked against it.

Manufacturer
Lochinvar
Model
Copper-fin II / IIE boiler, water heater and pool heater (ModBus communication board)
Equipment type
Boiler
Registers
56 (12 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Also known as
Copper-fin II, Copper-fin IIE, CBX, CFX, CHX, CPX, C(F,H,P)X, Copperfin
Source document
Copper-fin II/IIE Boiler, Water Heater and Pool Heater - ModBus and BACnet Communication Instructions · 100160882_2000001229 Rev G · rev. 2026-01
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Lochinvar Copper-fin II / IIE boiler, water heater and pool heater (ModBus communication board)

Integration in brief

Set parameter H6 ModBus to Active, then write the configuration bits (40001) and enables (40002 or coils) and poll input registers 30009-30016 for temperatures, firing rate and status.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
CO 0Stage 1 EnableBITStage 1 enableRead/write
IR 8Outlet temperatureINT16Outlet temperatureRead
IR 9Inlet temperatureINT16Inlet temperatureRead
IR 11Firing rateUINT16Firing rateRead
IR 13Status codeUINT16Status codeRead
IR 15Lockout codeUINT16Lockout codeRead
HR 0ConfigurationBITMAP16Configuration bitsRead/write

Enable Modbus control & writes

Set control parameter H6 ModBus to Active; address on dip switches 1-8, baud on switch 9 (0 = 9600, 1 = 19200), parity on switch 10 (0 = none with 2 stop bits, 1 = even with 1 stop bit).

Communication loss & watchdog

BAS-supplied temperatures must be refreshed within the H7 ModBus Time (1-255 s, default 10 s); other commands within 4 minutes, or the control reverts to its local inputs.

Byte order & addressing

Network setup

Watch out for

Lochinvar Copper-fin II / IIE boiler, water heater and pool heater (ModBus communication board) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

56 of 56 shown
Lochinvar Copper-fin II / IIE boiler, water heater and pool heater (ModBus communication board) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
CO0doc 00001Stage 1 EnableBITRead/write0 = Off; 1 = On
CO1doc 00002Stage 2 EnableBITRead/write0 = Off; 1 = On
CO2doc 00003Stage 3 EnableBITRead/write0 = Off; 1 = On
CO3doc 00004Stage 4 EnableBITRead/write0 = Off; 1 = On
CO4doc 00005Tank ThermostatBITRead/write0 = Off; 1 = On
DI0doc 10001High LimitsBITRead0 = Off; 1 = On
DI1doc 10002Flow SwitchBITRead0 = Off; 1 = On
DI2doc 10003Gas Pressure SwitchBITRead0 = Off; 1 = On
DI3doc 10004Louver Proving SwitchBITRead0 = Off; 1 = On
DI4doc 10005Air Pressure SwitchBITRead0 = Off; 1 = On
DI7doc 10008Flame 1BITRead0 = Off; 1 = On
DI8doc 10009Stage 1 OnBITRead0 = Off; 1 = On
DI9doc 10010Tank ThermostatBITRead0 = Off; 1 = On
DI10doc 10011Stage 2 OnBITRead0 = Off; 1 = On
DI11doc 10012Stage 3 OnBITRead0 = Off; 1 = On
DI12doc 10013Stage 4 OnBITRead0 = Off; 1 = On
DI22doc 10023Flame 2BITRead0 = Off; 1 = On
DI23doc 10024Enable 2BITRead0 = Off; 1 = On
DI32doc 10033Runtime ContactsBITRead0 = Off; 1 = On
DI33doc 10034Alarm ContactsBITRead0 = Off; 1 = On
DI34doc 10035HTR PumpBITRead0 = Off; 1 = On
DI35doc 10036DHW PumpBITRead0 = Off; 1 = On
DI36doc 10037Louver RelayBITRead0 = Off; 1 = On
DI37doc 10038Gas Valve 1BITRead0 = Off; 1 = On
DI38doc 10039System PumpBITRead0 = Off; 1 = On
DI45doc 10046Gas Valve 2BITRead0 = Off; 1 = On
DI46doc 10047Gas Valve 3BITRead0 = Off; 1 = On
DI47doc 10048Gas Valve 4BITRead0 = Off; 1 = On
IR0doc 30001Discrete inputs 1-16 (packed)Packed copy of the discrete inputs; bit order not stated.UINT16Read
IR1doc 30002Discrete inputs 17-32 (packed)UINT16Read
IR2doc 30003Discrete inputs 33-48 (packed)UINT16Read
IR4doc 30005System pump speedUINT16%Read
IR5doc 30006Cascade total powerUINT16%Read
IR6doc 30007Cascade current powerUINT16%Read
IR8doc 30009Outlet temperatureINT16× 0.1°CRead
IR9doc 30010Inlet temperatureINT16× 0.1°CRead
IR10doc 30011Pool temperatureINT16× 0.1°CRead
IR11doc 30012Firing rateUINT16%Read
IR13doc 30014Status codeUINT16Read2 = Heat demand blocked: high absolute outlet temperature; 3 = Heat demand blocked: high absolute flue temperature; 4 = Heat demand blocked: high absolute delta T; 8 = Heat demand blocked: low 24 VAC; 9 = Outdoor shutdown; 10 = Blocked: boiler switched off at display; 12 = Blocked: no correct cascade communication; 16 = Service function; 19 = DHW function, storage tank; 21 = SH heat demand from room thermostat; 22 = SH heat demand from boiler management system; 23 = SH heat demand from cascade; 30 = Heat demand from freeze protection; 32 = DHW pump delay; 33 = SH pump delay; 34 = No heat function (after pump delay); 40 = Lockout; 32764 = Busy updating status; 32765 = DHW blocked: no tank sensor; 32766 = Burner control(s) manually shut down; 32767 = Code not present
IR14doc 30015Blocking codeUINT16Read0 = No blocking; 1 = SH blocking; 2 = Low 24 VAC supply; 3 = General block; 4 = MRHL open; 5 = Boiler switched off (display); 6 = Wrong cascade communication; 7 = High delta T; 8 = High flue temperature; 9 = High outlet temperature; 10 = Service blocking; 12 = DHW blocking, high outlet temperature; 13 = Anti-cycling time; 14 = Storage tank demand blocked, fan problem; 15 = No system sensor with leader control; 16 = Fan speed limited, high outlet temperature; 17 = Fan minimum decreased, low flame current; 18 = Max fan speed limited, high delta T; 19 = Max fan speed limited, high flue temperature; 32767 = Code not present
IR15doc 30016Lockout codeOnly meaningful when the status code is 40 (lockout).UINT16Read
IR26doc 30027Lockout code leaderUINT16Read
IR27doc 30028Lockout code member 1UINT16Read
IR28doc 30029Lockout code member 2UINT16Read
IR29doc 30030Lockout code member 3UINT16Read
IR30doc 30031Lockout code member 4UINT16Read
IR31doc 30032Lockout code member 5UINT16Read
IR32doc 30033Lockout code member 6UINT16Read
IR33doc 30034Lockout code member 7UINT16Read
HR0doc 40001ConfigurationSet bit = take that value from the BAS, not the local input.BITMAP16Read/writebit 0 = Boiler enable; bit 1 = Tank thermostat; bit 2 = Rate command / 0-10 V input / set point command; bit 3 = Tank set point; bit 4 = System supply temperature; bit 5 = Outdoor temperature; bit 6 = Tank temperature; bit 7 = System return temperature
HR1doc 40002CoilsEnable bits written by the BAS; meaning depends on control mode (e.g. 0x0001 = Enable 1).UINT16Read/write
HR2doc 400030-10 V input / rate command / set point commandPercent written as a plain integer, e.g. 49 = 0x31.UINT16%Read/write
HR4doc 40005Tank temperature (from BAS)INT16× 0.1°CRead/write
HR5doc 40006Outdoor temperature (from BAS)INT16× 0.1°CRead/write
HR6doc 40007System supply temperature (from BAS)INT16× 0.1°CRead/write
HR7doc 40008System return temperature (from BAS)INT16× 0.1°CRead/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Lochinvar Copper-fin II / IIE boiler, water heater and pool heater (ModBus communication board)

What Modbus registers does the Lochinvar Copper-fin II / IIE boiler, water heater and pool heater (ModBus communication board) have?

This map lists 56 registers: 5 coils, 23 discrete inputs, 21 input registers, 7 holding registers. 12 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Lochinvar Copper-fin II / IIE boiler, water heater and pool heater (ModBus communication board) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Addresses are printed Modicon-style (00001 coils, 10001 discrete inputs, 30001 input registers, 40001 holding registers). Subtract the table base and 1 for the wire address; the exception-code text describes PDU addresses starting at 0.

What are the minimum Modbus registers to integrate the Lochinvar Copper-fin II / IIE boiler, water heater and pool heater (ModBus communication board)?

Start with CO 0 Stage 1 Enable (Stage 1 enable); IR 8 Outlet temperature (Outlet temperature); IR 9 Inlet temperature (Inlet temperature); IR 11 Firing rate (Firing rate); IR 13 Status code (Status code); IR 15 Lockout code (Lockout code); HR 0 Configuration (Configuration bits).

How do I enable Modbus control of the Lochinvar Copper-fin II / IIE boiler, water heater and pool heater (ModBus communication board)?

Set control parameter H6 ModBus to Active; address on dip switches 1-8, baud on switch 9 (0 = 9600, 1 = 19200), parity on switch 10 (0 = none with 2 stop bits, 1 = even with 1 stop bit).

What happens when the Lochinvar Copper-fin II / IIE boiler, water heater and pool heater (ModBus communication board) loses Modbus communication?

BAS-supplied temperatures must be refreshed within the H7 ModBus Time (1-255 s, default 10 s); other commands within 4 minutes, or the control reverts to its local inputs.

Where is the official Lochinvar Copper-fin II / IIE boiler, water heater and pool heater (ModBus communication board) Modbus documentation?

The source is Copper-fin II/IIE Boiler, Water Heater and Pool Heater - ModBus and BACnet Communication Instructions (100160882_2000001229 Rev G), revision 2026-01, published free by Lochinvar at https://assets.lochinvar.com/damroot/Original/10017/C(F,H,P)X-MODB_100160882_2000001229_REV%20G_(69837).pdf.

More Lochinvar Modbus register maps

Other boilers & water heaters register maps

All boilers & water heaters Modbus register maps →

Source: Copper-fin II/IIE Boiler, Water Heater and Pool Heater - ModBus and BACnet Communication Instructions · 100160882_2000001229 Rev G · rev. 2026-01. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.