Boiler (burner / boiler controller) · Modbus register map

Cleaver-Brooks CB Falcon hydronic / steam boiler control Modbus register map

Updated 17 November 2026

Short answer

The CB Falcon boiler control is a Modbus RTU slave on its two RS-485 ports. All data are 16-bit holding registers; this map covers the system and burner status block: digital I/O, limits, temperatures, setpoints, burner state, lockout and alarm codes, and sensor states.

This page lists 33 Modbus registers for the Cleaver-Brooks CB Falcon hydronic / steam boiler control — 1 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Cleaver-Brooks’s own free documentation (linked below) and checked against it.

Manufacturer
Cleaver-Brooks
Model
CB Falcon hydronic / steam boiler control
Equipment type
Boiler (burner / boiler controller)
Registers
33 (1 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
38400 baud, 8N1
Documented addressing
hexadecimal, 0-based
Also known as
CB Falcon, Falcon boiler control
Source document
CB Falcon Modbus Communication · 750-308 · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Cleaver-Brooks CB Falcon hydronic / steam boiler control

Integration in brief

Poll holding registers 0x0000-0x0034 with FC03 (up to 125 per read) for I/O, temperatures, setpoints, burner status and lockout code; temperatures are 0.1 °C. The Remote STAT register (0x002A) can create a heat demand.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 32Burner control statusUINT16Burner control statusRead
HR 34Lockout codeUINT16Lockout codeRead
HR 35Alarm reasonUINT16Alarm reasonRead
HR 7Outlet temperatureUINT16Outlet temperatureRead
HR 16Active CH setpointUINT16Active CH setpointRead
HR 2Digital I/OBITMAP16Digital I/ORead
HR 42Remote STATUINT16Remote STAT demandRead/write

Enable Modbus control & writes

Use the MB1 or MB2 RS-485 port; the Falcon answers on a single Modbus address.

Byte order & addressing

Network setup

Watch out for

Cleaver-Brooks CB Falcon hydronic / steam boiler control Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

33 of 33 shown
Cleaver-Brooks CB Falcon hydronic / steam boiler control Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 0000Status changeGroups with new status; cleared when read.BITMAP16Readbit 0 = Active lockout; bit 1 = Burner control status; bit 2 = Sensor status; bit 3 = Demand & modulation status; bit 4 = CH status; bit 5 = DHW status; bit 6 = Pump status; bit 7 = Statistics; bit 8 = Lead Lag status; bit 9 = Lockout history; bit 10 = Alert log
HR2doc 0002Digital I/OBITMAP16Readbit 0 = Pump A; bit 1 = Pump B; bit 2 = Pump C; bit 3 = Blower motor / HSI; bit 4 = External ignition; bit 5 = Pilot valve; bit 6 = Main valve; bit 7 = Alarm; bit 8 = Interlock (ILK); bit 9 = Pre-ignition interlock (PII); bit 10 = Load control input (LCI); bit 11 = Low fire switch (LFS); bit 12 = High fire switch (HFS); bit 13 = STAT (demand); bit 14 = Time of day; bit 15 = Safety relay
HR3doc 0003Annunciation I/OOnly when annunciation is enabled.BITMAP16Readbit 0 = Annunciator 1 / IAS; bit 1 = Annunciator 2; bit 2 = Annunciator 3; bit 3 = Annunciator 4; bit 4 = Annunciator 5; bit 5 = Annunciator 6; bit 6 = Annunciator 7 / HFS; bit 7 = Annunciator 8 / LFS
HR4doc 0004LimitsBITMAP16Readbit 0 = Outlet high limit; bit 1 = DHW high limit; bit 2 = Stack limit; bit 3 = Delta T inlet/outlet limit; bit 4 = Delta T exchanger/outlet limit; bit 5 = Delta T inlet/exchanger limit; bit 6 = Inversion inlet/outlet limit; bit 7 = Inversion exchanger/outlet limit; bit 8 = Inversion inlet/exchanger limit; bit 9 = Outlet T-rise limit; bit 10 = Exchanger T-rise limit; bit 11 = Heat exchanger high limit
HR6doc 0006Demand sourceUINT16Read0 = Unknown; 1 = No source demand; 2 = CH; 3 = DHW; 4 = Lead Lag slave; 5 = Lead Lag master; 6 = CH frost protection; 7 = DHW frost protection; 8 = No demand, burner switch off; 9 = DHW storage; 11 = Warm weather shutdown
HR7doc 0007Outlet temperatureOutlet (S3S4) or outlet limit (S3) sensor; 0.1 °C units, always Celsius; 0x8FFF = not configured.UINT16× 0.1°CRead
HR9doc 0009Fan speedUINT16rpmRead
HR10doc 000AFlame signal0.01 V or 0.01 A steps depending on flame sensor, 0-50.00.UINT16× 0.01V or ARead
HR11doc 000BInlet temperature (S1)0.1 °C units, always Celsius; 0x8FFF = not configured.UINT16× 0.1°CRead
HR12doc 000CDHW temperatureDHW (S6S7) or DHW limit (S6) sensor; 0.1 °C units, always Celsius; 0x8FFF = not configured.UINT16× 0.1°CRead
HR14doc 000EStack temperatureStack (S8S9) or stack limit (S8) sensor; 0.1 °C units, always Celsius; 0x8FFF = not configured.UINT16× 0.1°CRead
HR16doc 0010Active CH setpoint0.1 °C units, always Celsius; 0x8FFF = not configured.UINT16× 0.1°CRead
HR17doc 0011Active DHW setpoint0.1 °C units, always Celsius; 0x8FFF = not configured.UINT16× 0.1°CRead
HR18doc 0012Active Lead Lag setpoint0.1 °C units, always Celsius; 0x8FFF = not configured.UINT16× 0.1°CRead
HR19doc 0013Register access statusUINT16Read0 = No register writes allowed; 1 = Installer writes allowed; 2 = OEM writes allowed; 3 = All writes allowed
HR20doc 0014Steam pressure0-150 psi.UINT16× 0.1psiRead
HR22doc 0016Active CH pressure setpointUINT16× 0.1psiRead
HR32doc 0020Burner control statusUINT16Read0 = Disabled; 1 = Locked out; 4 = Anti-short cycle; 5 = Unconfigured safety data; 34 = Standby Hold; 35 = Standby Delay; 48 = Normal Standby; 49 = Preparing; 50 = Ignition; 51 = Firing; 52 = Postpurge
HR33doc 0021Burner control stateSequence state code; see the manual's Table 11.UINT16Read
HR34doc 0022Lockout code0 = no lockout, else code 1-4096 per Table 8.UINT16Read
HR35doc 0023Alarm reasonUINT16Read0 = None; 1 = Lockout (see lockout code); 2 = Alert; 3 = Other
HR38doc 0026Sequence timeRunning time of the timed burner step.UINT16sRead
HR39doc 0027Delay timeRunning delay in delayed or hold state.UINT16sRead
HR40doc 0028Hold codeReason for burner hold, same codes as lockouts.UINT16Read
HR41doc 0029Burner control flagsBITMAP16Readbit 0 = Flame detected
HR42doc 002ARemote STATUINT16Read/write0 = No remote STAT demand; 1 = Remote STAT demand
HR46doc 002EOutlet operation sensor (S4) stateUINT16Read0 = None; 1 = Normal; 2 = Open; 3 = Shorted; 4 = Outside high range; 5 = Outside low range; 6 = Not reliable
HR47doc 002FDHW operation sensor (S7) stateUINT16Read0 = None; 1 = Normal; 2 = Open; 3 = Shorted; 4 = Outside high range; 5 = Outside low range; 6 = Not reliable
HR48doc 0030Outlet limit sensor (S3) stateUINT16Read0 = None; 1 = Normal; 2 = Open; 3 = Shorted; 4 = Outside high range; 5 = Outside low range; 6 = Not reliable
HR49doc 0031Inlet sensor (S1) stateUINT16Read0 = None; 1 = Normal; 2 = Open; 3 = Shorted; 4 = Outside high range; 5 = Outside low range; 6 = Not reliable
HR50doc 0032DHW limit sensor stateUINT16Read0 = None; 1 = Normal; 2 = Open; 3 = Shorted; 4 = Outside high range; 5 = Outside low range; 6 = Not reliable
HR51doc 0033Stack limit sensor (S8) stateUINT16Read0 = None; 1 = Normal; 2 = Open; 3 = Shorted; 4 = Outside high range; 5 = Outside low range; 6 = Not reliable
HR52doc 0034S5 sensor stateUINT16Read0 = None; 1 = Normal; 2 = Open; 3 = Shorted; 4 = Outside high range; 5 = Outside low range; 6 = Not reliable

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Cleaver-Brooks CB Falcon hydronic / steam boiler control

What Modbus registers does the Cleaver-Brooks CB Falcon hydronic / steam boiler control have?

This map lists 33 registers: 33 holding registers. 1 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Cleaver-Brooks CB Falcon hydronic / steam boiler control Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Table 4 lists each register as a hex address and its decimal equivalent, starting at 0000 (Status change). These are the protocol addresses: register 0x0022 (decimal 34) is sent as 34.

What are the minimum Modbus registers to integrate the Cleaver-Brooks CB Falcon hydronic / steam boiler control?

Start with HR 32 Burner control status (Burner control status); HR 34 Lockout code (Lockout code); HR 35 Alarm reason (Alarm reason); HR 7 Outlet temperature (Outlet temperature); HR 16 Active CH setpoint (Active CH setpoint); HR 2 Digital I/O (Digital I/O); HR 42 Remote STAT (Remote STAT demand).

How do I enable Modbus control of the Cleaver-Brooks CB Falcon hydronic / steam boiler control?

Use the MB1 or MB2 RS-485 port; the Falcon answers on a single Modbus address.

Where is the official Cleaver-Brooks CB Falcon hydronic / steam boiler control Modbus documentation?

The source is CB Falcon Modbus Communication (750-308). Cleaver-Brooks doesn't publish it on its own website, so this map was re-typed from a free copy at https://www.ccontrols.com/support/dp/750-308FalconModbus.pdf. It may be an older revision, so check it against the live unit.

Other boilers & water heaters register maps

All boilers & water heaters Modbus register maps →

Source: CB Falcon Modbus Communication · 750-308 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.