Boiler (burner / boiler controller) · Modbus register map
Cleaver-Brooks CB Falcon hydronic / steam boiler control Modbus register map
Updated 17 November 2026
The CB Falcon boiler control is a Modbus RTU slave on its two RS-485 ports. All data are 16-bit holding registers; this map covers the system and burner status block: digital I/O, limits, temperatures, setpoints, burner state, lockout and alarm codes, and sensor states.
This page lists 33 Modbus registers for the Cleaver-Brooks CB Falcon hydronic / steam boiler control — 1 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Cleaver-Brooks’s own free documentation (linked below) and checked against it.
- Manufacturer
- Cleaver-Brooks
- Model
- CB Falcon hydronic / steam boiler control
- Equipment type
- Boiler (burner / boiler controller)
- Registers
- 33 (1 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 38400 baud, 8N1
- Documented addressing
- hexadecimal, 0-based
- Also known as
- CB Falcon, Falcon boiler control
- Source document
- CB Falcon Modbus Communication · 750-308 · unofficial copy
Integration notes: Cleaver-Brooks CB Falcon hydronic / steam boiler control
Poll holding registers 0x0000-0x0034 with FC03 (up to 125 per read) for I/O, temperatures, setpoints, burner status and lockout code; temperatures are 0.1 °C. The Remote STAT register (0x002A) can create a heat demand.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 32 | Burner control status | UINT16 | Burner control status | Read |
| HR 34 | Lockout code | UINT16 | Lockout code | Read |
| HR 35 | Alarm reason | UINT16 | Alarm reason | Read |
| HR 7 | Outlet temperature | UINT16 | Outlet temperature | Read |
| HR 16 | Active CH setpoint | UINT16 | Active CH setpoint | Read |
| HR 2 | Digital I/O | BITMAP16 | Digital I/O | Read |
| HR 42 | Remote STAT | UINT16 | Remote STAT demand | Read/write |
Enable Modbus control & writes
Use the MB1 or MB2 RS-485 port; the Falcon answers on a single Modbus address.
Byte order & addressing
- Temperatures are always Celsius x10.
- 0x8FFF = sensor not configured.
- Variable-length items must be read on their own.
Network setup
- RTU 38400 8N1 per the manual.
- Writes: up to 20 registers; reads: up to 125.
Watch out for
- Reading 0x0000 clears it, so a second master will miss change flags.
Cleaver-Brooks CB Falcon hydronic / steam boiler control Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 0000 | Status change | Groups with new status; cleared when read. | BITMAP16 | Read | bit 0 = Active lockout; bit 1 = Burner control status; bit 2 = Sensor status; bit 3 = Demand & modulation status; bit 4 = CH status; bit 5 = DHW status; bit 6 = Pump status; bit 7 = Statistics; bit 8 = Lead Lag status; bit 9 = Lockout history; bit 10 = Alert log | |||
| HR | 2doc 0002 | Digital I/O | BITMAP16 | Read | bit 0 = Pump A; bit 1 = Pump B; bit 2 = Pump C; bit 3 = Blower motor / HSI; bit 4 = External ignition; bit 5 = Pilot valve; bit 6 = Main valve; bit 7 = Alarm; bit 8 = Interlock (ILK); bit 9 = Pre-ignition interlock (PII); bit 10 = Load control input (LCI); bit 11 = Low fire switch (LFS); bit 12 = High fire switch (HFS); bit 13 = STAT (demand); bit 14 = Time of day; bit 15 = Safety relay | ||||
| HR | 3doc 0003 | Annunciation I/O | Only when annunciation is enabled. | BITMAP16 | Read | bit 0 = Annunciator 1 / IAS; bit 1 = Annunciator 2; bit 2 = Annunciator 3; bit 3 = Annunciator 4; bit 4 = Annunciator 5; bit 5 = Annunciator 6; bit 6 = Annunciator 7 / HFS; bit 7 = Annunciator 8 / LFS | |||
| HR | 4doc 0004 | Limits | BITMAP16 | Read | bit 0 = Outlet high limit; bit 1 = DHW high limit; bit 2 = Stack limit; bit 3 = Delta T inlet/outlet limit; bit 4 = Delta T exchanger/outlet limit; bit 5 = Delta T inlet/exchanger limit; bit 6 = Inversion inlet/outlet limit; bit 7 = Inversion exchanger/outlet limit; bit 8 = Inversion inlet/exchanger limit; bit 9 = Outlet T-rise limit; bit 10 = Exchanger T-rise limit; bit 11 = Heat exchanger high limit | ||||
| HR | 6doc 0006 | Demand source | UINT16 | Read | 0 = Unknown; 1 = No source demand; 2 = CH; 3 = DHW; 4 = Lead Lag slave; 5 = Lead Lag master; 6 = CH frost protection; 7 = DHW frost protection; 8 = No demand, burner switch off; 9 = DHW storage; 11 = Warm weather shutdown | ||||
| HR | 7doc 0007 | Outlet temperature | Outlet (S3S4) or outlet limit (S3) sensor; 0.1 °C units, always Celsius; 0x8FFF = not configured. | UINT16 | × 0.1 | °C | Read | ||
| HR | 9doc 0009 | Fan speed | UINT16 | rpm | Read | ||||
| HR | 10doc 000A | Flame signal | 0.01 V or 0.01 A steps depending on flame sensor, 0-50.00. | UINT16 | × 0.01 | V or A | Read | ||
| HR | 11doc 000B | Inlet temperature (S1) | 0.1 °C units, always Celsius; 0x8FFF = not configured. | UINT16 | × 0.1 | °C | Read | ||
| HR | 12doc 000C | DHW temperature | DHW (S6S7) or DHW limit (S6) sensor; 0.1 °C units, always Celsius; 0x8FFF = not configured. | UINT16 | × 0.1 | °C | Read | ||
| HR | 14doc 000E | Stack temperature | Stack (S8S9) or stack limit (S8) sensor; 0.1 °C units, always Celsius; 0x8FFF = not configured. | UINT16 | × 0.1 | °C | Read | ||
| HR | 16doc 0010 | Active CH setpoint | 0.1 °C units, always Celsius; 0x8FFF = not configured. | UINT16 | × 0.1 | °C | Read | ||
| HR | 17doc 0011 | Active DHW setpoint | 0.1 °C units, always Celsius; 0x8FFF = not configured. | UINT16 | × 0.1 | °C | Read | ||
| HR | 18doc 0012 | Active Lead Lag setpoint | 0.1 °C units, always Celsius; 0x8FFF = not configured. | UINT16 | × 0.1 | °C | Read | ||
| HR | 19doc 0013 | Register access status | UINT16 | Read | 0 = No register writes allowed; 1 = Installer writes allowed; 2 = OEM writes allowed; 3 = All writes allowed | ||||
| HR | 20doc 0014 | Steam pressure | 0-150 psi. | UINT16 | × 0.1 | psi | Read | ||
| HR | 22doc 0016 | Active CH pressure setpoint | UINT16 | × 0.1 | psi | Read | |||
| HR | 32doc 0020 | Burner control status | UINT16 | Read | 0 = Disabled; 1 = Locked out; 4 = Anti-short cycle; 5 = Unconfigured safety data; 34 = Standby Hold; 35 = Standby Delay; 48 = Normal Standby; 49 = Preparing; 50 = Ignition; 51 = Firing; 52 = Postpurge | ||||
| HR | 33doc 0021 | Burner control state | Sequence state code; see the manual's Table 11. | UINT16 | Read | ||||
| HR | 34doc 0022 | Lockout code | 0 = no lockout, else code 1-4096 per Table 8. | UINT16 | Read | ||||
| HR | 35doc 0023 | Alarm reason | UINT16 | Read | 0 = None; 1 = Lockout (see lockout code); 2 = Alert; 3 = Other | ||||
| HR | 38doc 0026 | Sequence time | Running time of the timed burner step. | UINT16 | s | Read | |||
| HR | 39doc 0027 | Delay time | Running delay in delayed or hold state. | UINT16 | s | Read | |||
| HR | 40doc 0028 | Hold code | Reason for burner hold, same codes as lockouts. | UINT16 | Read | ||||
| HR | 41doc 0029 | Burner control flags | BITMAP16 | Read | bit 0 = Flame detected | ||||
| HR | 42doc 002A | Remote STAT | UINT16 | Read/write | 0 = No remote STAT demand; 1 = Remote STAT demand | ||||
| HR | 46doc 002E | Outlet operation sensor (S4) state | UINT16 | Read | 0 = None; 1 = Normal; 2 = Open; 3 = Shorted; 4 = Outside high range; 5 = Outside low range; 6 = Not reliable | ||||
| HR | 47doc 002F | DHW operation sensor (S7) state | UINT16 | Read | 0 = None; 1 = Normal; 2 = Open; 3 = Shorted; 4 = Outside high range; 5 = Outside low range; 6 = Not reliable | ||||
| HR | 48doc 0030 | Outlet limit sensor (S3) state | UINT16 | Read | 0 = None; 1 = Normal; 2 = Open; 3 = Shorted; 4 = Outside high range; 5 = Outside low range; 6 = Not reliable | ||||
| HR | 49doc 0031 | Inlet sensor (S1) state | UINT16 | Read | 0 = None; 1 = Normal; 2 = Open; 3 = Shorted; 4 = Outside high range; 5 = Outside low range; 6 = Not reliable | ||||
| HR | 50doc 0032 | DHW limit sensor state | UINT16 | Read | 0 = None; 1 = Normal; 2 = Open; 3 = Shorted; 4 = Outside high range; 5 = Outside low range; 6 = Not reliable | ||||
| HR | 51doc 0033 | Stack limit sensor (S8) state | UINT16 | Read | 0 = None; 1 = Normal; 2 = Open; 3 = Shorted; 4 = Outside high range; 5 = Outside low range; 6 = Not reliable | ||||
| HR | 52doc 0034 | S5 sensor state | UINT16 | Read | 0 = None; 1 = Normal; 2 = Open; 3 = Shorted; 4 = Outside high range; 5 = Outside low range; 6 = Not reliable |
Notes on this map
- Source is a copy of the Cleaver-Brooks manual hosted by Contemporary Controls; Cleaver-Brooks did not turn up a public copy in two searches.
- Serial format per Table 2: RTU, 38400 bps, 8 data bits, no parity, 1 stop bit.
- Temperatures are in 0.1 °C regardless of the display unit setting; 0x8FFF means the sensor is not configured. The manual types them as U16 while giving a range down to -40 °C and does not say how values below zero are coded. They are listed as UINT16 for boiler water, flue and setpoint values, which sit above 0 °C in service; treat any sub-zero reading with care. The S5 sensor temperature (0x000D) is left out because S5 is often an outdoor sensor where sub-zero values are routine.
- Left out: firing rate and other rate registers, whose unit (0.1 % or RPM) is chosen by the top bit; every 32-bit counter (cycle counts, run times), because the manual does not state their word order; the configuration change and extended status change registers; 4-20 mA inputs; and everything from 0x0035 on (CH/DHW/pump status, configuration, lead-lag, lockout history, alert log).
- Status change (0x0000) clears itself when read, so only one master should poll it.
- Writes need a password login in the Password register (0x00B1) for protected parameters; register 0x0013 shows the current write access.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Cleaver-Brooks CB Falcon hydronic / steam boiler control
What Modbus registers does the Cleaver-Brooks CB Falcon hydronic / steam boiler control have?
This map lists 33 registers: 33 holding registers. 1 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Cleaver-Brooks CB Falcon hydronic / steam boiler control Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Table 4 lists each register as a hex address and its decimal equivalent, starting at 0000 (Status change). These are the protocol addresses: register 0x0022 (decimal 34) is sent as 34.
What are the minimum Modbus registers to integrate the Cleaver-Brooks CB Falcon hydronic / steam boiler control?
Start with HR 32 Burner control status (Burner control status); HR 34 Lockout code (Lockout code); HR 35 Alarm reason (Alarm reason); HR 7 Outlet temperature (Outlet temperature); HR 16 Active CH setpoint (Active CH setpoint); HR 2 Digital I/O (Digital I/O); HR 42 Remote STAT (Remote STAT demand).
How do I enable Modbus control of the Cleaver-Brooks CB Falcon hydronic / steam boiler control?
Use the MB1 or MB2 RS-485 port; the Falcon answers on a single Modbus address.
Where is the official Cleaver-Brooks CB Falcon hydronic / steam boiler control Modbus documentation?
The source is CB Falcon Modbus Communication (750-308). Cleaver-Brooks doesn't publish it on its own website, so this map was re-typed from a free copy at https://www.ccontrols.com/support/dp/750-308FalconModbus.pdf. It may be an older revision, so check it against the live unit.
Other boilers & water heaters register maps
- Boiler (electric)
Lochinvar Lectrus KEB electric boilers / water heaters 0015-0150 (Modbus communication board)
Lochinvar Lectrus KEB 0015-0150 electric boilers/water heaters with the Modbus/BACnet communication board, per MODB-I-O-KEB Rev A.
Also known as: Lectrus, KEB0015, KEB0150, KEB 0015-0150, MODB-I-O-KEB, Lochinvar Lectrus - Boiler
Weil-McLain Unity 2 control (ECO Tec 80-199, SVF 500/600 boilers)
Weil-McLain boilers with the Unity 2 control (ECO Tec 80/110/150/199 wall-mount and combi, SVF 500/600), per Modbus supplement 550-100-266/1023.
Also known as: ECO Tec 80, ECO Tec 110, ECO Tec 150, ECO Tec 199, ECO Tec Combi, SVF 500, SVF 600, Unity2 - Boiler (commercial water heater)
Lochinvar Armor 1250-4000 commercial water heaters, Series 100 & 101 (Modbus communication board)
Lochinvar Armor water heaters, models 1250-4000, Series 100 and 101, with the SMART SYSTEM control and Modbus/BACnet communication board, per 100305786_2000558371 Rev C.
Also known as: Armor 1250, Armor 1500, Armor 2000, Armor 2500, Armor 3000, Armor 3500, Armor 4000, AWH, AWH1250, AWH4000, SMART SYSTEM - Boiler
Mestek KNSLM boiler control (KN2 / KN4 / rAy series)
KNSLM boiler control (KN2/KN4/rAy series), register list V1.10; registers marked 2.70+ need firmware 2.70 or later.
Also known as: KNSLM, KN2, KN4, rAy - Boiler
Buderus SSB condensing boilers (built-in Modbus RTU)
Buderus SSB series condensing boilers (Bosch Thermotechnology, North America) using the Modbus terminals on the boiler's internal terminal strip, per installation instructions 6720818450 (2015/10).
Also known as: SSB, Buderus SSB boiler, Bosch SSB, 6720818450 - Boiler / water heater
Lochinvar Knight / Armor / Wall Mount boilers (ModBus communication board)
Knight 81-286, Knight XL 400-1000, Armor 151-1000, Outdoor Knight/Knight XL/Armor, AQUAS 400-801, FTXL 400-1000, Wall Mount 51-211, Wall Hung 55-399, Wall Mount Armor 125-200 and Shield 125-500 with the Lochinvar ModBus communication board.
Also known as: Knight, Knight XL, Outdoor Knight, Outdoor Knight XL, Armor, Outdoor Armor, Wall Mount Armor, Knight Wall Mount, Knight Wall Hung, AQUAS, FTXL, Shield
All boilers & water heaters Modbus register maps →
Source: CB Falcon Modbus Communication · 750-308 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.