- Midas S2 extractive gas transmitter (Modbus/TCP)
Sensor (extractive gas detector) · Modbus register map
Honeywell Midas S2 extractive gas transmitter (Modbus/TCP) Modbus register map
Updated 17 November 2026
The Midas S2 is a Honeywell pumped single-point gas transmitter for toxic, flammable and oxygen gases. Its Ethernet port is a Modbus/TCP server: holding registers 40001-40122 give a packed status word, the gas reading, decimal point and units, temperature, cell life, flow, alarm and fault flags. This map covers the 16-bit registers; float, time and text registers are left out.
This page lists 14 Modbus registers for the Honeywell Midas S2 extractive gas transmitter (Modbus/TCP) — 0 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Honeywell’s own free documentation (linked below) and checked against it.
- Manufacturer
- Honeywell
- Model
- Midas S2 extractive gas transmitter (Modbus/TCP)
- Equipment type
- Sensor (extractive gas detector)
- Registers
- 14 (0 writable)
- Transport
- Modbus TCP
- Default unit ID
- Not stated
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Also known as
- Midas S2, MIDAS-S2, Midas S2 gas detector
Integration notes: Honeywell Midas S2 extractive gas transmitter (Modbus/TCP)
Connect to the Midas S2 IP and read holding registers 0-17 with function 03; gas = 40005 / 10^(40007 bits 0-2).
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 4 | Gas concentration integer (CONC) | UINT16 | Gas concentration | Read |
| HR 6 | Decimal point and units (DPUN) | UINT16 | Decimal point and units | Read |
| HR 0 | Status (STTS) | BITMAP16 | Status and alarms | Read |
| HR 17 | Fault status (FSI) | BITMAP16 | Fault flags | Read |
| HR 10 | Sample flow (FLOW) | UINT16 | Sample flow | Read |
| HR 8 | Cell life remaining (CLRH) | UINT16 | Cell life | Read |
Enable Modbus control & writes
Modbus/TCP is part of the Ethernet interface; set the network address in the transmitter setup.
Byte order & addressing
- Gas reading is in ppm for ppm and ppb gases, otherwise in display units.
- In bump test mode the Modbus outputs are not inhibited.
Network setup
- Ethernet or PoE.
- Modbus TCP has no authentication; isolate it on a secure network.
- Factory default IP address is 192.168.0.14; without DHCP, put the PC on the same subnet.
Watch out for
- Read 40007 together with 40005 to apply the right decimal point.
Honeywell Midas S2 extractive gas transmitter (Modbus/TCP) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 40001 | Status (STTS) | Bits 0-3 monitoring state, bits 4-5 fault state; flags below. | BITMAP16 | Read | bit 6 = Alarm 1 active; bit 7 = Alarm 2 active; bit 8 = Relay 1 energized; bit 9 = Relay 2 energized; bit 10 = Relay 3 energized; bit 11 = Heartbeat (toggles every second); bit 12 = Relays under remote Modbus/TCP control; bit 13 = Last zero calibration succeeded; bit 14 = Last span calibration succeeded | |||
| HR | 1doc 40002 | Gas selection (GASS) | Low byte gas ID, high byte cartridge type. | UINT16 | Read | ||||
| HR | 4doc 40005 | Gas concentration integer (CONC) | Divide by 10^decimal (40007 bits 0-2); ppm for ppm/ppb gases. | UINT16 | Read | ||||
| HR | 5doc 40006 | Most important active fault number (NOFT) | Fault code; see the troubleshooting table in the manual. | UINT16 | Read | ||||
| HR | 6doc 40007 | Decimal point and units (DPUN) | Bits 0-2 decimals; high byte units: 1 ppm, 2 ppb, 4 %vol, 8 %LEL, 16 mA. | UINT16 | Read | ||||
| HR | 7doc 40008 | Temperature (TEMP) | INT16 | °C | Read | ||||
| HR | 8doc 40009 | Cell life remaining (CLRH) | UINT16 | h | Read | ||||
| HR | 9doc 40010 | Heartbeat counter (HRTB) | Low 16 bits of time in seconds. | UINT16 | s | Read | |||
| HR | 10doc 40011 | Sample flow (FLOW) | UINT16 | cc/min | Read | ||||
| HR | 16doc 40017 | Alarm status (ASI) | BITMAP16 | Read | bit 0 = Alarm 1 active; bit 1 = Alarm 2 active | ||||
| HR | 17doc 40018 | Fault status (FSI) | BITMAP16 | Read | bit 0 = Maintenance fault; bit 1 = Instrument fault; bit 2 = Flow fault; bit 3 = Internal communication fault; bit 4 = Pyrolyzer fault; bit 5 = Sensor fault; bit 6 = Range over fault | ||||
| HR | 62doc 40063 | Transmitter serial number prefix | First four digits of the S-number as a decimal value. | UINT16 | Read | ||||
| HR | 63doc 40064 | Transmitter serial number suffix | Last digits of the S-number as a decimal value. | UINT16 | Read | ||||
| HR | 80doc 40081 | Mode status (MSI) | BITMAP16 | Read | bit 0 = Warm-up; bit 1 = Monitor mode; bit 2 = Test mode; bit 3 = Maintenance mode |
Notes on this map
- Left out: float registers (concentration 40003-40004, alarm thresholds 40013-40016, high scale 40019-40020). The manual only says floats are "little-endian or Intel format", which does not pin down the word order on the wire.
- Left out: 32-bit UNIX time registers 40061-40062, 40065-40068 (word order not stated) and the ASCII serial-number and gas-name registers (character order within a register not stated).
- Left out: user command registers 40021-40022 (CMD1 0x015E-0x0B5E with CMD2 0x3626 for reset, inhibit and relay control): the manual says only function 03 is supported, so how they are written is unclear.
- Status register 40001 packs numbers: bits 0-3 monitoring state (0 warm-up, 1 monitor, 2 alarms inhibited, 3 alarms and faults inhibited, 4 fully inhibited, 5 alarm/fault simulation, 6 bump test, 7 4-20 mA calibration, 8 other calibration); bits 4-5 fault state (0 none, 1 maintenance fault, 2 instrument fault).
- The manual mentions an older 40082 duplicate in the sensor serial list (typo for 40092); text registers are excluded anyway.
- Only function 03 (read holding registers) is supported.
- The manual does not state the TCP port; Modbus/TCP normally uses 502.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Honeywell Midas S2 extractive gas transmitter (Modbus/TCP)
What Modbus registers does the Honeywell Midas S2 extractive gas transmitter (Modbus/TCP) have?
This map lists 14 registers: 14 holding registers. 0 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Honeywell Midas S2 extractive gas transmitter (Modbus/TCP) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The table lists reference addresses 40001-40122 (Modicon style), so 40001 (status) is wire address 0 and 40005 (gas reading) is wire address 4.
What are the minimum Modbus registers to integrate the Honeywell Midas S2 extractive gas transmitter (Modbus/TCP)?
Start with HR 4 Gas concentration integer (CONC) (Gas concentration); HR 6 Decimal point and units (DPUN) (Decimal point and units); HR 0 Status (STTS) (Status and alarms); HR 17 Fault status (FSI) (Fault flags); HR 10 Sample flow (FLOW) (Sample flow); HR 8 Cell life remaining (CLRH) (Cell life).
How do I enable Modbus control of the Honeywell Midas S2 extractive gas transmitter (Modbus/TCP)?
Modbus/TCP is part of the Ethernet interface; set the network address in the transmitter setup.
Where is the official Honeywell Midas S2 extractive gas transmitter (Modbus/TCP) Modbus documentation?
The source is Midas S2 Fixed single-point extractive gas transmitter User Manual (3023M5001 Rev A), revision 2023-08-31, published free by Honeywell at https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/hgas/en-us/products/high-tech-and-semiconductor/midass2/documents/hon-ia-dmc-3023m5001-midas-a-001-rev-a-midas-s2-um-en.pdf.
More Honeywell Modbus register maps
- Sensor (extractive gas detector)
Honeywell Midas gas detector (Modbus/TCP)
Honeywell Midas extractive gas detectors (original Midas platform, software V1.08), user manual 3010M5000 revision 32, Appendix A Modbus/TCP interface.
Also known as: Midas, MIDAS gas detector - Boiler controller
Honeywell SOLA hydronic boiler control (Modbus interface)
Honeywell SOLA (R7910/R7911) integrated boiler controls, status registers 0-173 of the SOLA Modbus Interface specification Rev 4.1.1 (2013-10-14). Used inside many OEM condensing boilers.
Also known as: R7910, R7911, Honeywell SOLA, SOLA ICP
Other gas detectors register maps
- Sensor (fixed gas detector)
Teledyne Detcon Model DM-700 electrochemical toxic gas / oxygen sensor (RS-485 Modbus)
Teledyne Detcon DM-700 smart sensors with the 4-20 mA and RS-485 Modbus outputs, instruction manual Document #3207, Rev. 5.9.
Also known as: DM-700, Detcon DM-700, Teledyne Detcon DM-700 - Sensor (fixed gas detector)
Teledyne Oldham Simtronics OLCT 700 / OLCT 710 FP catalytic bead combustible gas detector (RS-485 Modbus)
Teledyne Oldham Simtronics OLCT 700 and OLCT 710 FP detectors with 4-20 mA and RS-485 Modbus RTU, manual NP700FPIMEN Revision E.0.
Also known as: OLCT 700 FP, OLCT 710 FP, Oldham OLCT 700 FP, 700 FP series - Gas detection controller (sensor)
Gas Detection Australia GDA 4022
Gas Detection Australia 4022 two-sensor gas detection controller, Modbus document 4022 V4.2 Rev 2.0 (16/11/2022).
Also known as: 4022 V4.2, GDA-4022 - Sensor (infrared gas analyzer)
Teledyne Analytical Instruments 7500 / 7600 infrared gas analyzer (Modbus RTU)
Teledyne 7500 and 7600 infrared gas analyzers with the Modbus communication function; channel registers CH1-CH8 apply to both models, CH9-CH12 to the 7600 only.
Also known as: Teledyne 7500, Teledyne 7600, Model 7500, Model 7600 - Sensor (fixed gas detector)
Teledyne Detcon Model TP-700 MOS (metal oxide) H2S sensor (RS-485 Modbus)
Teledyne Detcon TP-700 smart sensors with the 4-20 mA and RS-485 Modbus outputs, instruction manual Document #3150, Rev. 4.6.
Also known as: TP-700, Detcon TP-700, Teledyne Detcon TP-700 - Sensor (CO2 / gas)
CO2Meter CM500 CO2 sensor / controller (RS-485 Modbus RTU)
CO2Meter.com CM500 with the RS-485 Modbus RTU interface, per the vendor's 'RS485 Communications Modbus Protocol' sheet (no document number).
Also known as: CM500, CO2Meter CM500
All gas detectors Modbus register maps →
Source: Midas S2 Fixed single-point extractive gas transmitter User Manual · 3023M5001 Rev A · rev. 2023-08-31. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.