Sensor (extractive gas detector) · Modbus register map

Honeywell Midas S2 extractive gas transmitter (Modbus/TCP) Modbus register map

Updated 17 November 2026

Short answer

The Midas S2 is a Honeywell pumped single-point gas transmitter for toxic, flammable and oxygen gases. Its Ethernet port is a Modbus/TCP server: holding registers 40001-40122 give a packed status word, the gas reading, decimal point and units, temperature, cell life, flow, alarm and fault flags. This map covers the 16-bit registers; float, time and text registers are left out.

This page lists 14 Modbus registers for the Honeywell Midas S2 extractive gas transmitter (Modbus/TCP) — 0 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Honeywell’s own free documentation (linked below) and checked against it.

Manufacturer
Honeywell
Model
Midas S2 extractive gas transmitter (Modbus/TCP)
Equipment type
Sensor (extractive gas detector)
Registers
14 (0 writable)
Transport
Modbus TCP
Default unit ID
Not stated
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Also known as
Midas S2, MIDAS-S2, Midas S2 gas detector
Source document
Midas S2 Fixed single-point extractive gas transmitter User Manual · 3023M5001 Rev A · rev. 2023-08-31
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Honeywell Midas S2 extractive gas transmitter (Modbus/TCP)

Integration in brief

Connect to the Midas S2 IP and read holding registers 0-17 with function 03; gas = 40005 / 10^(40007 bits 0-2).

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 4Gas concentration integer (CONC)UINT16Gas concentrationRead
HR 6Decimal point and units (DPUN)UINT16Decimal point and unitsRead
HR 0Status (STTS)BITMAP16Status and alarmsRead
HR 17Fault status (FSI)BITMAP16Fault flagsRead
HR 10Sample flow (FLOW)UINT16Sample flowRead
HR 8Cell life remaining (CLRH)UINT16Cell lifeRead

Enable Modbus control & writes

Modbus/TCP is part of the Ethernet interface; set the network address in the transmitter setup.

Byte order & addressing

Network setup

Watch out for

Honeywell Midas S2 extractive gas transmitter (Modbus/TCP) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

14 of 14 shown
Honeywell Midas S2 extractive gas transmitter (Modbus/TCP) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 40001Status (STTS)Bits 0-3 monitoring state, bits 4-5 fault state; flags below.BITMAP16Readbit 6 = Alarm 1 active; bit 7 = Alarm 2 active; bit 8 = Relay 1 energized; bit 9 = Relay 2 energized; bit 10 = Relay 3 energized; bit 11 = Heartbeat (toggles every second); bit 12 = Relays under remote Modbus/TCP control; bit 13 = Last zero calibration succeeded; bit 14 = Last span calibration succeeded
HR1doc 40002Gas selection (GASS)Low byte gas ID, high byte cartridge type.UINT16Read
HR4doc 40005Gas concentration integer (CONC)Divide by 10^decimal (40007 bits 0-2); ppm for ppm/ppb gases.UINT16Read
HR5doc 40006Most important active fault number (NOFT)Fault code; see the troubleshooting table in the manual.UINT16Read
HR6doc 40007Decimal point and units (DPUN)Bits 0-2 decimals; high byte units: 1 ppm, 2 ppb, 4 %vol, 8 %LEL, 16 mA.UINT16Read
HR7doc 40008Temperature (TEMP)INT16°CRead
HR8doc 40009Cell life remaining (CLRH)UINT16hRead
HR9doc 40010Heartbeat counter (HRTB)Low 16 bits of time in seconds.UINT16sRead
HR10doc 40011Sample flow (FLOW)UINT16cc/minRead
HR16doc 40017Alarm status (ASI)BITMAP16Readbit 0 = Alarm 1 active; bit 1 = Alarm 2 active
HR17doc 40018Fault status (FSI)BITMAP16Readbit 0 = Maintenance fault; bit 1 = Instrument fault; bit 2 = Flow fault; bit 3 = Internal communication fault; bit 4 = Pyrolyzer fault; bit 5 = Sensor fault; bit 6 = Range over fault
HR62doc 40063Transmitter serial number prefixFirst four digits of the S-number as a decimal value.UINT16Read
HR63doc 40064Transmitter serial number suffixLast digits of the S-number as a decimal value.UINT16Read
HR80doc 40081Mode status (MSI)BITMAP16Readbit 0 = Warm-up; bit 1 = Monitor mode; bit 2 = Test mode; bit 3 = Maintenance mode

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Honeywell Midas S2 extractive gas transmitter (Modbus/TCP)

What Modbus registers does the Honeywell Midas S2 extractive gas transmitter (Modbus/TCP) have?

This map lists 14 registers: 14 holding registers. 0 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Honeywell Midas S2 extractive gas transmitter (Modbus/TCP) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The table lists reference addresses 40001-40122 (Modicon style), so 40001 (status) is wire address 0 and 40005 (gas reading) is wire address 4.

What are the minimum Modbus registers to integrate the Honeywell Midas S2 extractive gas transmitter (Modbus/TCP)?

Start with HR 4 Gas concentration integer (CONC) (Gas concentration); HR 6 Decimal point and units (DPUN) (Decimal point and units); HR 0 Status (STTS) (Status and alarms); HR 17 Fault status (FSI) (Fault flags); HR 10 Sample flow (FLOW) (Sample flow); HR 8 Cell life remaining (CLRH) (Cell life).

How do I enable Modbus control of the Honeywell Midas S2 extractive gas transmitter (Modbus/TCP)?

Modbus/TCP is part of the Ethernet interface; set the network address in the transmitter setup.

Where is the official Honeywell Midas S2 extractive gas transmitter (Modbus/TCP) Modbus documentation?

The source is Midas S2 Fixed single-point extractive gas transmitter User Manual (3023M5001 Rev A), revision 2023-08-31, published free by Honeywell at https://prod-edam.honeywell.com/content/dam/honeywell-edam/sps/hgas/en-us/products/high-tech-and-semiconductor/midass2/documents/hon-ia-dmc-3023m5001-midas-a-001-rev-a-midas-s2-um-en.pdf.

More Honeywell Modbus register maps

Other gas detectors register maps

All gas detectors Modbus register maps →

Source: Midas S2 Fixed single-point extractive gas transmitter User Manual · 3023M5001 Rev A · rev. 2023-08-31. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.