- CM500 CO2 sensor / controller (RS-485 Modbus RTU)
Sensor (CO2 / gas) · Modbus register map
CO2Meter CM500 CO2 sensor / controller (RS-485 Modbus RTU) Modbus register map
Updated 17 November 2026
The CM500 is a CO2 sensor and controller with an RS-485 port that speaks Modbus RTU using FC03 reads and FC06 writes. Readings are single 16-bit registers. The shared register sheet also lists other gas, particulate and RTC registers that only answer on units fitted with those sensors.
This page lists 13 Modbus registers for the CO2Meter CM500 CO2 sensor / controller (RS-485 Modbus RTU) — 3 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from CO2Meter’s own free documentation (linked below) and checked against it.
- Manufacturer
- CO2Meter
- Model
- CM500 CO2 sensor / controller (RS-485 Modbus RTU)
- Equipment type
- Sensor (CO2 / gas)
- Registers
- 13 (3 writable)
- Transport
- Modbus RTU
- Default unit ID
- 104
- Default serial
- 19200 baud, 8N1
- Documented addressing
- hexadecimal, 0-based
- Also known as
- CM500, CO2Meter CM500
Integration notes: CO2Meter CM500 CO2 sensor / controller (RS-485 Modbus RTU)
Poll 19200 8N1 at address 104 (0x68) with FC03 and read register 0x14 for CO2 in ppm. Change address, baud or parity with FC06 and power-cycle the sensor.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 20 | CO2 | UINT16 | CO2 ppm | Read |
| HR 0 | Slave address | UINT16 | Slave address | Read/write |
| HR 1 | Baud rate | UINT16 | Baud rate code | Read/write |
| HR 2 | UART parity / framing | UINT16 | Parity code | Read/write |
Enable Modbus control & writes
Modbus RTU is the RS-485 interface's protocol; no enable step is described.
Byte order & addressing
- Only FC03 and FC06 are supported.
- Baud and parity changes need a power cycle.
Network setup
- Defaults: 19200 baud, 8 data bits, no parity, 1 stop bit.
Watch out for
- Address 250 (0xFA) is broadcast; do not assign it to a sensor.
CO2Meter CM500 CO2 sensor / controller (RS-485 Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 00H | Slave address | 1-249; 250 (0xFA) is reserved for broadcast. Stored in EEPROM. | UINT16 | Read/write | ||||
| HR | 1doc 01H | Baud rate | Takes effect after a power cycle. | UINT16 | Read/write | 0 = 38400; 1 = 19200 (default); 2 = 9600; 3 = 4800 | |||
| HR | 2doc 02H | UART parity / framing | Takes effect after a power cycle. | UINT16 | Read/write | 0 = N82; 1 = N81 (default); 2 = E81; 3 = O81 | |||
| HR | 19doc 13H | NH3 | Whole ppm (only on units with this sensor). | UINT16 | ppm | Read | |||
| HR | 20doc 14H | CO2 | Whole ppm; the manual's example reads 0x0318 = 792 ppm. | UINT16 | ppm | Read | |||
| HR | 21doc 15H | CO | Whole ppm (only on units with this sensor). | UINT16 | ppm | Read | |||
| HR | 22doc 16H | VOC | Whole ppb (only on units with this sensor). | UINT16 | ppb | Read | |||
| HR | 23doc 17H | PM2.5 | Only on units with this sensor. | UINT16 | µg/m³ | Read | |||
| HR | 24doc 18H | PM10 | Only on units with this sensor. | UINT16 | µg/m³ | Read | |||
| HR | 30doc 1EH | RTC year | UINT16 | Read | |||||
| HR | 31doc 1FH | RTC month-day | Packing not described. | UINT16 | Read | ||||
| HR | 32doc 20H | RTC hour-minute | Packing not described. | UINT16 | Read | ||||
| HR | 33doc 21H | RTC seconds | UINT16 | Read |
Notes on this map
- The sheet is served from a Shopify file CDN (cdn.shopify.com) used by CO2Meter's store, not from a CO2Meter-branded host, so it is marked unofficial.
- Note 1 on page 2 says the CO2 start address is 0x0B, but the register table and both example frames use 0x14; 0x14 is used here.
- Default slave address is printed as 0x068 (104). The examples use 0xFA, which the sheet reserves for broadcast.
- Left out: O2, ambient temperature, barometer, RH, dew point and battery voltage (12H, 19H-1DH). The sheet only shows display formats such as 'xx.xx%', not the register scaling.
- Writable RTC registers (78H-7BH) are left out because their layout is not described.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the CO2Meter CM500 CO2 sensor / controller (RS-485 Modbus RTU)
What Modbus registers does the CO2Meter CM500 CO2 sensor / controller (RS-485 Modbus RTU) have?
This map lists 13 registers: 13 holding registers. 3 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the CO2Meter CM500 CO2 sensor / controller (RS-485 Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are listed as hex addresses sent unchanged in the request; the examples read CO2 with start address 0x0014 (table row 14H).
What are the minimum Modbus registers to integrate the CO2Meter CM500 CO2 sensor / controller (RS-485 Modbus RTU)?
Start with HR 20 CO2 (CO2 ppm); HR 0 Slave address (Slave address); HR 1 Baud rate (Baud rate code); HR 2 UART parity / framing (Parity code).
How do I enable Modbus control of the CO2Meter CM500 CO2 sensor / controller (RS-485 Modbus RTU)?
Modbus RTU is the RS-485 interface's protocol; no enable step is described.
Where is the official CO2Meter CM500 CO2 sensor / controller (RS-485 Modbus RTU) Modbus documentation?
The source is CM500 RS-485 Modbus RTU protocol (RS485 Communications Modbus Protocol). CO2Meter doesn't publish it on its own website, so this map was re-typed from a free copy at https://cdn.shopify.com/s/files/1/0019/5952/files/CO2Meter-CM500-RS-485-Modbus-RTU-protocol.pdf. It may be an older revision, so check it against the live unit.
Other gas detectors register maps
- Sensor (environmental / leak monitor)
RLE Technologies Falcon F200 environment and leak monitoring appliance (Modbus TCP)
RLE Falcon F200 with firmware 4100.1 or later; register guide v06.21.
Also known as: F200, Falcon F200 - Sensor (fixed gas detector)
Teledyne Detcon Model IR-700 infrared combustible / CO2 gas sensor (RS-485 Modbus)
Teledyne Detcon IR-700 smart sensors with the 4-20 mA and RS-485 Modbus outputs, instruction manual Document #3169, Rev. 4.9.
Also known as: IR-700, Detcon IR-700, Teledyne Detcon IR-700 - Sensor (refrigerant leak detector)
Amphenol Telaire T3400 series refrigerant (A2L) leak sensor
Amphenol Telaire T3400 series refrigerant sensors (R454B / R32) with RS-485 Modbus RTU, user instructions AS-T63381B (04/2025, marked provisional).
Also known as: Telaire T3400, T3400 R454B, T3400 R32 - Sensor (fixed gas detector)
New Cosmos Electric PS-7-M series extractive pump gas detector (Modbus RTU / TCP)
New Cosmos PS-7-M series extractive pump gas detectors (main unit with base unit) over RS-485 Modbus RTU or Ethernet Modbus TCP, communication specifications guide GAE-159-01.
Also known as: PS-7-M, PS-7 - Sensor (fixed gas detector)
Teledyne Detcon Model FP-624D MicroSafe combustible gas sensor (RS-485 Modbus)
Teledyne Detcon FP-624D MicroSafe catalytic LEL sensor with 4-20 mA, relays and RS-485 Modbus RTU, instruction manual Document #3598 Rev. 1.7.
Also known as: FP-624D, MicroSafe FP-624D, Detcon FP-624D - Sensor (fixed gas detector)
Teledyne Oldham Simtronics OLCT 700 / OLCT 710 IR infrared combustible / CO2 gas detector (RS-485 Modbus)
Teledyne Oldham Simtronics OLCT 700 and OLCT 710 IR detectors with 4-20 mA and RS-485 Modbus RTU, manual NP700IRIMEN Revision E.0.
Also known as: OLCT 700 IR, OLCT 710 IR, Oldham OLCT 700 IR, 700 IR series
All gas detectors Modbus register maps →
Source: CM500 RS-485 Modbus RTU protocol (RS485 Communications Modbus Protocol) · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.