CO2Meter CM500 CO2 sensor / controller (RS-485 Modbus RTU) Modbus register map

Updated 17 November 2026

Short answer

The CM500 is a CO2 sensor and controller with an RS-485 port that speaks Modbus RTU using FC03 reads and FC06 writes. Readings are single 16-bit registers. The shared register sheet also lists other gas, particulate and RTC registers that only answer on units fitted with those sensors.

This page lists 13 Modbus registers for the CO2Meter CM500 CO2 sensor / controller (RS-485 Modbus RTU) — 3 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from CO2Meter’s own free documentation (linked below) and checked against it.

Manufacturer
CO2Meter
Model
CM500 CO2 sensor / controller (RS-485 Modbus RTU)
Equipment type
Sensor (CO2 / gas)
Registers
13 (3 writable)
Transport
Modbus RTU
Default unit ID
104
Default serial
19200 baud, 8N1
Documented addressing
hexadecimal, 0-based
Also known as
CM500, CO2Meter CM500
Source document
CM500 RS-485 Modbus RTU protocol (RS485 Communications Modbus Protocol) · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: CO2Meter CM500 CO2 sensor / controller (RS-485 Modbus RTU)

Integration in brief

Poll 19200 8N1 at address 104 (0x68) with FC03 and read register 0x14 for CO2 in ppm. Change address, baud or parity with FC06 and power-cycle the sensor.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 20CO2UINT16CO2 ppmRead
HR 0Slave addressUINT16Slave addressRead/write
HR 1Baud rateUINT16Baud rate codeRead/write
HR 2UART parity / framingUINT16Parity codeRead/write

Enable Modbus control & writes

Modbus RTU is the RS-485 interface's protocol; no enable step is described.

Byte order & addressing

Network setup

Watch out for

CO2Meter CM500 CO2 sensor / controller (RS-485 Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

13 of 13 shown
CO2Meter CM500 CO2 sensor / controller (RS-485 Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 00HSlave address1-249; 250 (0xFA) is reserved for broadcast. Stored in EEPROM.UINT16Read/write
HR1doc 01HBaud rateTakes effect after a power cycle.UINT16Read/write0 = 38400; 1 = 19200 (default); 2 = 9600; 3 = 4800
HR2doc 02HUART parity / framingTakes effect after a power cycle.UINT16Read/write0 = N82; 1 = N81 (default); 2 = E81; 3 = O81
HR19doc 13HNH3Whole ppm (only on units with this sensor).UINT16ppmRead
HR20doc 14HCO2Whole ppm; the manual's example reads 0x0318 = 792 ppm.UINT16ppmRead
HR21doc 15HCOWhole ppm (only on units with this sensor).UINT16ppmRead
HR22doc 16HVOCWhole ppb (only on units with this sensor).UINT16ppbRead
HR23doc 17HPM2.5Only on units with this sensor.UINT16µg/m³Read
HR24doc 18HPM10Only on units with this sensor.UINT16µg/m³Read
HR30doc 1EHRTC yearUINT16Read
HR31doc 1FHRTC month-dayPacking not described.UINT16Read
HR32doc 20HRTC hour-minutePacking not described.UINT16Read
HR33doc 21HRTC secondsUINT16Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the CO2Meter CM500 CO2 sensor / controller (RS-485 Modbus RTU)

What Modbus registers does the CO2Meter CM500 CO2 sensor / controller (RS-485 Modbus RTU) have?

This map lists 13 registers: 13 holding registers. 3 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the CO2Meter CM500 CO2 sensor / controller (RS-485 Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are listed as hex addresses sent unchanged in the request; the examples read CO2 with start address 0x0014 (table row 14H).

What are the minimum Modbus registers to integrate the CO2Meter CM500 CO2 sensor / controller (RS-485 Modbus RTU)?

Start with HR 20 CO2 (CO2 ppm); HR 0 Slave address (Slave address); HR 1 Baud rate (Baud rate code); HR 2 UART parity / framing (Parity code).

How do I enable Modbus control of the CO2Meter CM500 CO2 sensor / controller (RS-485 Modbus RTU)?

Modbus RTU is the RS-485 interface's protocol; no enable step is described.

Where is the official CO2Meter CM500 CO2 sensor / controller (RS-485 Modbus RTU) Modbus documentation?

The source is CM500 RS-485 Modbus RTU protocol (RS485 Communications Modbus Protocol). CO2Meter doesn't publish it on its own website, so this map was re-typed from a free copy at https://cdn.shopify.com/s/files/1/0019/5952/files/CO2Meter-CM500-RS-485-Modbus-RTU-protocol.pdf. It may be an older revision, so check it against the live unit.

Other gas detectors register maps

All gas detectors Modbus register maps →

Source: CM500 RS-485 Modbus RTU protocol (RS485 Communications Modbus Protocol) · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.