- Telaire T3400 series refrigerant (A2L) leak sensor
Sensor (refrigerant leak detector) · Modbus register map
Amphenol Telaire T3400 series refrigerant (A2L) leak sensor Modbus register map
Updated 17 November 2026
The Telaire T3400 is an OEM thermal-conductivity refrigerant sensor for A2L leak detection systems in HVAC equipment, with an RS-485 Modbus RTU interface. All data are 16-bit holding registers: operating mode, leak flag, error bits, gas concentration in %LFL, temperature and humidity, plus address, leak threshold and identity registers. This map covers the published register set except the device marking string.
This page lists 13 Modbus registers for the Amphenol Telaire T3400 series refrigerant (A2L) leak sensor — 3 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Amphenol’s own free documentation (linked below) and checked against it.
- Manufacturer
- Amphenol
- Model
- Telaire T3400 series refrigerant (A2L) leak sensor
- Equipment type
- Sensor (refrigerant leak detector)
- Registers
- 13 (3 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 2400 baud, 8N2
- Documented addressing
- hexadecimal, 0-based
- Also known as
- Telaire T3400, T3400 R454B, T3400 R32
Integration notes: Amphenol Telaire T3400 series refrigerant (A2L) leak sensor
Talk to the sensor at 2400 baud, 8N2, address 1 by default; wait for operating mode 1 (measuring), then poll 0x0111 leak signal, 0x0112 errors and 0x0113 concentration.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 272 | Operating mode | UINT16 | Operating mode (startup/measuring) | Read |
| HR 273 | Leak signal | UINT16 | Leak signal | Read |
| HR 274 | Errors | BITMAP16 | Error flags | Read |
| HR 275 | Gas concentration | INT16 | Gas concentration %LFL | Read |
| HR 332 | Gas type | UINT16 | Configured gas type | Read |
Enable Modbus control & writes
Modbus RTU is the only interface; change the address by writing 0x0120 and then reset (write 1 to 0x0101) or power-cycle.
Byte order & addressing
- Default line settings are 2400 baud, 8 data bits, no parity, 2 stop bits.
- Concentration is in %LFL x 10, not ppm.
Network setup
- Wiring: pin 1 +5 Vdc (red), pin 2 ground (black), pin 3 B- (blue), pin 4 A+ (yellow).
Watch out for
- No measurements are available while the operating mode reads 0 (startup).
Amphenol Telaire T3400 series refrigerant (A2L) leak sensor Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 256doc 0x0100 | Register specification version | High byte major, low byte minor. | UINT16 | Read | ||||
| HR | 257doc 0x0101 | Device reset | Write 1 to reset the sensor. | UINT16 | Write | 1 = Reset | |||
| HR | 272doc 0x0110 | Operating mode | No measurements during startup. | UINT16 | Read | 0 = Startup; 1 = Measuring | |||
| HR | 273doc 0x0111 | Leak signal | Held 5 min (default) after concentration falls below threshold. | UINT16 | Read | 0 = No leak detected; 1 = Leak detected or hold period | |||
| HR | 274doc 0x0112 | Errors | Error flags. | BITMAP16 | Read | bit 0 = Internal error (measurement untrustworthy); bit 1 = Value out of limit (T, RH or concentration); bit 3 = Self-check failed; bit 4 = Dead (unrecoverable, replace sensor); bit 5 = Over lifetime limit | |||
| HR | 275doc 0x0113 | Gas concentration | 0-100 %LFL (clamped). | INT16 | × 0.1 | %LFL | Read | ||
| HR | 276doc 0x0114 | Sensor temperature | -40 to +125 °C. | INT16 | × 0.1 | °C | Read | ||
| HR | 277doc 0x0115 | Sensor humidity | 0-100 %RH. | INT16 | × 0.1 | %RH | Read | ||
| HR | 288doc 0x0120 | Device address | Modbus address 1-247 (default 1); applies after reset or power cycle. | UINT16 | Read/write | ||||
| HR | 292doc 0x0124 | Leak signal threshold | Concentration that triggers the leak signal. | UINT16 | × 0.1 | %LFL | Read/write | ||
| HR | 330doc 0x014A | Firmware version | High byte major, low byte minor. | UINT16 | Read | ||||
| HR | 332doc 0x014C | Gas type | Refrigerant the sensor is configured for. | UINT16 | Read | 0 = R32; 1 = R454B | |||
| HR | 334doc 0x14E | Lifetime counter | Elapsed lifetime. | UINT16 | days | Read |
Notes on this map
- The document is marked PROVISIONAL; check for a newer revision before deployment.
- Supported function codes: 03 (read), 06 (write single), 16 (write multiple). Registers are 16-bit, high byte first.
- Left out: 0x0140 device marking (String[20], 10 registers): the character order within registers is not stated.
- Error register bit 2 is not defined in the table.
- The printed address of the lifetime counter is '0x14E' (same as 0x014E).
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Amphenol Telaire T3400 series refrigerant (A2L) leak sensor
What Modbus registers does the Amphenol Telaire T3400 series refrigerant (A2L) leak sensor have?
This map lists 13 registers: 13 holding registers. 3 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Amphenol Telaire T3400 series refrigerant (A2L) leak sensor Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Register addresses are printed in hex and the frame description defines the register address as the starting position in the table, sent as one word, so 0x0113 (gas concentration) is requested as 275 decimal.
What are the minimum Modbus registers to integrate the Amphenol Telaire T3400 series refrigerant (A2L) leak sensor?
Start with HR 272 Operating mode (Operating mode (startup/measuring)); HR 273 Leak signal (Leak signal); HR 274 Errors (Error flags); HR 275 Gas concentration (Gas concentration %LFL); HR 332 Gas type (Configured gas type).
How do I enable Modbus control of the Amphenol Telaire T3400 series refrigerant (A2L) leak sensor?
Modbus RTU is the only interface; change the address by writing 0x0120 and then reset (write 1 to 0x0101) or power-cycle.
Where is the official Amphenol Telaire T3400 series refrigerant (A2L) leak sensor Modbus documentation?
The source is Telaire T3400 Series Refrigerant Sensor - User Instructions (AS-T63381B), revision 2025-04, published free by Amphenol at https://amphenol-sensors.com/hubfs/AS-T63381B-T3400-RefrigSensor-0425-web.pdf.
Other gas detectors register maps
- Sensor (fixed gas detector)
New Cosmos Electric PS-7-M series extractive pump gas detector (Modbus RTU / TCP)
New Cosmos PS-7-M series extractive pump gas detectors (main unit with base unit) over RS-485 Modbus RTU or Ethernet Modbus TCP, communication specifications guide GAE-159-01.
Also known as: PS-7-M, PS-7 - Sensor (fixed gas detector)
Teledyne Detcon Model FP-624D MicroSafe combustible gas sensor (RS-485 Modbus)
Teledyne Detcon FP-624D MicroSafe catalytic LEL sensor with 4-20 mA, relays and RS-485 Modbus RTU, instruction manual Document #3598 Rev. 1.7.
Also known as: FP-624D, MicroSafe FP-624D, Detcon FP-624D - Sensor (fixed gas detector)
Teledyne Oldham Simtronics OLCT 700 / OLCT 710 IR infrared combustible / CO2 gas detector (RS-485 Modbus)
Teledyne Oldham Simtronics OLCT 700 and OLCT 710 IR detectors with 4-20 mA and RS-485 Modbus RTU, manual NP700IRIMEN Revision E.0.
Also known as: OLCT 700 IR, OLCT 710 IR, Oldham OLCT 700 IR, 700 IR series - Sensor (extractive gas detector)
Honeywell Midas gas detector (Modbus/TCP)
Honeywell Midas extractive gas detectors (original Midas platform, software V1.08), user manual 3010M5000 revision 32, Appendix A Modbus/TCP interface.
Also known as: Midas, MIDAS gas detector - Sensor (fixed gas detector)
Teledyne Detcon Model CX-IR infrared combustible gas sensor (Modbus RTU)
Teledyne Detcon CX-IR wired infrared gas sensors (RS-485 Modbus RTU and 4-20 mA), instruction manual Document #4428 Rev. 1.9.
Also known as: CX-IR, Detcon CX-IR - Sensor controller (gas detection)
Teledyne Detcon Model X40 integrated alarm and control system (Modbus slave port)
Teledyne Detcon X40 gas detection controllers (8 and 32 channel, N4X and N1P enclosures), instruction manual Document #3672 Rev. 3.8, slave port register map.
Also known as: X40-08-N4X, X40-32-N4X, X40-32-N1P, X40 controller
All gas detectors Modbus register maps →
Source: Telaire T3400 Series Refrigerant Sensor - User Instructions · AS-T63381B · rev. 2025-04. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.