Teledyne Detcon Model X40 integrated alarm and control system (Modbus slave port) Modbus register map
Updated 17 November 2026
The X40 is a Teledyne Detcon gas detection controller that collects up to 32 wired or wireless sensors (CXT sensors, alarm stations, repeaters) and drives alarms. A Modbus RTU slave port lets a BMS or PLC read every channel: one register with the gas reading and one with alarm, fault, calibration, battery, decimal-point and device-type bits. This map lists all 64 registers.
This page lists 64 Modbus registers for the Teledyne Detcon Model X40 integrated alarm and control system (Modbus slave port) — 0 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Teledyne Detcon’s own free documentation (linked below) and checked against it.
- Manufacturer
- Teledyne Detcon
- Model
- Model X40 integrated alarm and control system (Modbus slave port)
- Equipment type
- Sensor controller (gas detection)
- Registers
- 64 (0 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 9600 baud, 8N1
- Documented addressing
- 0-based (the number printed is the address on the wire)
- Also known as
- X40-08-N4X, X40-32-N4X, X40-32-N1P, X40 controller
Integration notes: Teledyne Detcon Model X40 integrated alarm and control system (Modbus slave port)
Give each X40 its own slave address, poll at 9600 8N1 no faster than once per second, and read registers 0-63 (reading/status pairs per channel).
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 0 | Channel 1 reading | UINT16 | Channel 1 reading | Read |
| HR 1 | Channel 1 status | BITMAP16 | Channel 1 status (alarms, fault, decimals) | Read |
| HR 2 | Channel 2 reading | UINT16 | Channel 2 reading | Read |
| HR 3 | Channel 2 status | BITMAP16 | Channel 2 status | Read |
Enable Modbus control & writes
The manual describes no separate enable step for the slave port; give each X40 its own device address when several share one network.
Byte order & addressing
- Read the status register with every reading to get the decimal point.
- Minimum inter-poll delay 150 ms; response timeout at least 2000 ms; poll at most once per second.
Network setup
- 9600 baud, 8 data bits, no parity, 1 stop bit.
Watch out for
- A channel with type bits 000 is disabled; ignore its reading.
Teledyne Detcon Model X40 integrated alarm and control system (Modbus slave port) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 40000 | Channel 1 reading | Gas reading; divide per decimal-point bits 6-7 of the status register. | UINT16 | Read | ||||
| HR | 1doc 40001 | Channel 1 status | BITMAP16 | Read | bit 0 = Alarm 1; bit 1 = Alarm 2; bit 2 = Alarm 3; bit 3 = Sensor/alarm fault; bit 4 = In calibration (sensors only); bit 5 = Communication error; bit 6 = Decimal point bit 0 (01 = divide by 10); bit 7 = Decimal point bit 1 (10 = divide by 100); bit 8 = Smart battery pack present; bit 9 = Battery error; bit 10 = Low battery; bit 12 = Wireless network type (0 = 320, 1 = 300); bit 13 = Device type bit 0; bit 14 = Device type bit 1; bit 15 = Device type bit 2 | ||||
| HR | 2doc 40002 | Channel 2 reading | Gas reading; divide per decimal-point bits 6-7 of the status register. | UINT16 | Read | ||||
| HR | 3doc 40003 | Channel 2 status | BITMAP16 | Read | bit 0 = Alarm 1; bit 1 = Alarm 2; bit 2 = Alarm 3; bit 3 = Sensor/alarm fault; bit 4 = In calibration (sensors only); bit 5 = Communication error; bit 6 = Decimal point bit 0 (01 = divide by 10); bit 7 = Decimal point bit 1 (10 = divide by 100); bit 8 = Smart battery pack present; bit 9 = Battery error; bit 10 = Low battery; bit 12 = Wireless network type (0 = 320, 1 = 300); bit 13 = Device type bit 0; bit 14 = Device type bit 1; bit 15 = Device type bit 2 | ||||
| HR | 4doc 40004 | Channel 3 reading | Gas reading; divide per decimal-point bits 6-7 of the status register. | UINT16 | Read | ||||
| HR | 5doc 40005 | Channel 3 status | BITMAP16 | Read | bit 0 = Alarm 1; bit 1 = Alarm 2; bit 2 = Alarm 3; bit 3 = Sensor/alarm fault; bit 4 = In calibration (sensors only); bit 5 = Communication error; bit 6 = Decimal point bit 0 (01 = divide by 10); bit 7 = Decimal point bit 1 (10 = divide by 100); bit 8 = Smart battery pack present; bit 9 = Battery error; bit 10 = Low battery; bit 12 = Wireless network type (0 = 320, 1 = 300); bit 13 = Device type bit 0; bit 14 = Device type bit 1; bit 15 = Device type bit 2 | ||||
| HR | 6doc 40006 | Channel 4 reading | Gas reading; divide per decimal-point bits 6-7 of the status register. | UINT16 | Read | ||||
| HR | 7doc 40007 | Channel 4 status | BITMAP16 | Read | bit 0 = Alarm 1; bit 1 = Alarm 2; bit 2 = Alarm 3; bit 3 = Sensor/alarm fault; bit 4 = In calibration (sensors only); bit 5 = Communication error; bit 6 = Decimal point bit 0 (01 = divide by 10); bit 7 = Decimal point bit 1 (10 = divide by 100); bit 8 = Smart battery pack present; bit 9 = Battery error; bit 10 = Low battery; bit 12 = Wireless network type (0 = 320, 1 = 300); bit 13 = Device type bit 0; bit 14 = Device type bit 1; bit 15 = Device type bit 2 | ||||
| HR | 8doc 40008 | Channel 5 reading | Gas reading; divide per decimal-point bits 6-7 of the status register. | UINT16 | Read | ||||
| HR | 9doc 40009 | Channel 5 status | BITMAP16 | Read | bit 0 = Alarm 1; bit 1 = Alarm 2; bit 2 = Alarm 3; bit 3 = Sensor/alarm fault; bit 4 = In calibration (sensors only); bit 5 = Communication error; bit 6 = Decimal point bit 0 (01 = divide by 10); bit 7 = Decimal point bit 1 (10 = divide by 100); bit 8 = Smart battery pack present; bit 9 = Battery error; bit 10 = Low battery; bit 12 = Wireless network type (0 = 320, 1 = 300); bit 13 = Device type bit 0; bit 14 = Device type bit 1; bit 15 = Device type bit 2 | ||||
| HR | 10doc 40010 | Channel 6 reading | Gas reading; divide per decimal-point bits 6-7 of the status register. | UINT16 | Read | ||||
| HR | 11doc 40011 | Channel 6 status | BITMAP16 | Read | bit 0 = Alarm 1; bit 1 = Alarm 2; bit 2 = Alarm 3; bit 3 = Sensor/alarm fault; bit 4 = In calibration (sensors only); bit 5 = Communication error; bit 6 = Decimal point bit 0 (01 = divide by 10); bit 7 = Decimal point bit 1 (10 = divide by 100); bit 8 = Smart battery pack present; bit 9 = Battery error; bit 10 = Low battery; bit 12 = Wireless network type (0 = 320, 1 = 300); bit 13 = Device type bit 0; bit 14 = Device type bit 1; bit 15 = Device type bit 2 | ||||
| HR | 12doc 40012 | Channel 7 reading | Gas reading; divide per decimal-point bits 6-7 of the status register. | UINT16 | Read | ||||
| HR | 13doc 40013 | Channel 7 status | BITMAP16 | Read | bit 0 = Alarm 1; bit 1 = Alarm 2; bit 2 = Alarm 3; bit 3 = Sensor/alarm fault; bit 4 = In calibration (sensors only); bit 5 = Communication error; bit 6 = Decimal point bit 0 (01 = divide by 10); bit 7 = Decimal point bit 1 (10 = divide by 100); bit 8 = Smart battery pack present; bit 9 = Battery error; bit 10 = Low battery; bit 12 = Wireless network type (0 = 320, 1 = 300); bit 13 = Device type bit 0; bit 14 = Device type bit 1; bit 15 = Device type bit 2 | ||||
| HR | 14doc 40014 | Channel 8 reading | Gas reading; divide per decimal-point bits 6-7 of the status register. | UINT16 | Read | ||||
| HR | 15doc 40015 | Channel 8 status | BITMAP16 | Read | bit 0 = Alarm 1; bit 1 = Alarm 2; bit 2 = Alarm 3; bit 3 = Sensor/alarm fault; bit 4 = In calibration (sensors only); bit 5 = Communication error; bit 6 = Decimal point bit 0 (01 = divide by 10); bit 7 = Decimal point bit 1 (10 = divide by 100); bit 8 = Smart battery pack present; bit 9 = Battery error; bit 10 = Low battery; bit 12 = Wireless network type (0 = 320, 1 = 300); bit 13 = Device type bit 0; bit 14 = Device type bit 1; bit 15 = Device type bit 2 | ||||
| HR | 16doc 40016 | Channel 9 reading | Gas reading; divide per decimal-point bits 6-7 of the status register. | UINT16 | Read | ||||
| HR | 17doc 40017 | Channel 9 status | BITMAP16 | Read | bit 0 = Alarm 1; bit 1 = Alarm 2; bit 2 = Alarm 3; bit 3 = Sensor/alarm fault; bit 4 = In calibration (sensors only); bit 5 = Communication error; bit 6 = Decimal point bit 0 (01 = divide by 10); bit 7 = Decimal point bit 1 (10 = divide by 100); bit 8 = Smart battery pack present; bit 9 = Battery error; bit 10 = Low battery; bit 12 = Wireless network type (0 = 320, 1 = 300); bit 13 = Device type bit 0; bit 14 = Device type bit 1; bit 15 = Device type bit 2 | ||||
| HR | 18doc 40018 | Channel 10 reading | Gas reading; divide per decimal-point bits 6-7 of the status register. | UINT16 | Read | ||||
| HR | 19doc 40019 | Channel 10 status | BITMAP16 | Read | bit 0 = Alarm 1; bit 1 = Alarm 2; bit 2 = Alarm 3; bit 3 = Sensor/alarm fault; bit 4 = In calibration (sensors only); bit 5 = Communication error; bit 6 = Decimal point bit 0 (01 = divide by 10); bit 7 = Decimal point bit 1 (10 = divide by 100); bit 8 = Smart battery pack present; bit 9 = Battery error; bit 10 = Low battery; bit 12 = Wireless network type (0 = 320, 1 = 300); bit 13 = Device type bit 0; bit 14 = Device type bit 1; bit 15 = Device type bit 2 | ||||
| HR | 20doc 40020 | Channel 11 reading | Gas reading; divide per decimal-point bits 6-7 of the status register. | UINT16 | Read | ||||
| HR | 21doc 40021 | Channel 11 status | BITMAP16 | Read | bit 0 = Alarm 1; bit 1 = Alarm 2; bit 2 = Alarm 3; bit 3 = Sensor/alarm fault; bit 4 = In calibration (sensors only); bit 5 = Communication error; bit 6 = Decimal point bit 0 (01 = divide by 10); bit 7 = Decimal point bit 1 (10 = divide by 100); bit 8 = Smart battery pack present; bit 9 = Battery error; bit 10 = Low battery; bit 12 = Wireless network type (0 = 320, 1 = 300); bit 13 = Device type bit 0; bit 14 = Device type bit 1; bit 15 = Device type bit 2 | ||||
| HR | 22doc 40022 | Channel 12 reading | Gas reading; divide per decimal-point bits 6-7 of the status register. | UINT16 | Read | ||||
| HR | 23doc 40023 | Channel 12 status | BITMAP16 | Read | bit 0 = Alarm 1; bit 1 = Alarm 2; bit 2 = Alarm 3; bit 3 = Sensor/alarm fault; bit 4 = In calibration (sensors only); bit 5 = Communication error; bit 6 = Decimal point bit 0 (01 = divide by 10); bit 7 = Decimal point bit 1 (10 = divide by 100); bit 8 = Smart battery pack present; bit 9 = Battery error; bit 10 = Low battery; bit 12 = Wireless network type (0 = 320, 1 = 300); bit 13 = Device type bit 0; bit 14 = Device type bit 1; bit 15 = Device type bit 2 | ||||
| HR | 24doc 40024 | Channel 13 reading | Gas reading; divide per decimal-point bits 6-7 of the status register. | UINT16 | Read | ||||
| HR | 25doc 40025 | Channel 13 status | BITMAP16 | Read | bit 0 = Alarm 1; bit 1 = Alarm 2; bit 2 = Alarm 3; bit 3 = Sensor/alarm fault; bit 4 = In calibration (sensors only); bit 5 = Communication error; bit 6 = Decimal point bit 0 (01 = divide by 10); bit 7 = Decimal point bit 1 (10 = divide by 100); bit 8 = Smart battery pack present; bit 9 = Battery error; bit 10 = Low battery; bit 12 = Wireless network type (0 = 320, 1 = 300); bit 13 = Device type bit 0; bit 14 = Device type bit 1; bit 15 = Device type bit 2 | ||||
| HR | 26doc 40026 | Channel 14 reading | Gas reading; divide per decimal-point bits 6-7 of the status register. | UINT16 | Read | ||||
| HR | 27doc 40027 | Channel 14 status | BITMAP16 | Read | bit 0 = Alarm 1; bit 1 = Alarm 2; bit 2 = Alarm 3; bit 3 = Sensor/alarm fault; bit 4 = In calibration (sensors only); bit 5 = Communication error; bit 6 = Decimal point bit 0 (01 = divide by 10); bit 7 = Decimal point bit 1 (10 = divide by 100); bit 8 = Smart battery pack present; bit 9 = Battery error; bit 10 = Low battery; bit 12 = Wireless network type (0 = 320, 1 = 300); bit 13 = Device type bit 0; bit 14 = Device type bit 1; bit 15 = Device type bit 2 | ||||
| HR | 28doc 40028 | Channel 15 reading | Gas reading; divide per decimal-point bits 6-7 of the status register. | UINT16 | Read | ||||
| HR | 29doc 40029 | Channel 15 status | BITMAP16 | Read | bit 0 = Alarm 1; bit 1 = Alarm 2; bit 2 = Alarm 3; bit 3 = Sensor/alarm fault; bit 4 = In calibration (sensors only); bit 5 = Communication error; bit 6 = Decimal point bit 0 (01 = divide by 10); bit 7 = Decimal point bit 1 (10 = divide by 100); bit 8 = Smart battery pack present; bit 9 = Battery error; bit 10 = Low battery; bit 12 = Wireless network type (0 = 320, 1 = 300); bit 13 = Device type bit 0; bit 14 = Device type bit 1; bit 15 = Device type bit 2 | ||||
| HR | 30doc 40030 | Channel 16 reading | Gas reading; divide per decimal-point bits 6-7 of the status register. | UINT16 | Read | ||||
| HR | 31doc 40031 | Channel 16 status | BITMAP16 | Read | bit 0 = Alarm 1; bit 1 = Alarm 2; bit 2 = Alarm 3; bit 3 = Sensor/alarm fault; bit 4 = In calibration (sensors only); bit 5 = Communication error; bit 6 = Decimal point bit 0 (01 = divide by 10); bit 7 = Decimal point bit 1 (10 = divide by 100); bit 8 = Smart battery pack present; bit 9 = Battery error; bit 10 = Low battery; bit 12 = Wireless network type (0 = 320, 1 = 300); bit 13 = Device type bit 0; bit 14 = Device type bit 1; bit 15 = Device type bit 2 | ||||
| HR | 32doc 40032 | Channel 17 reading | Gas reading; divide per decimal-point bits 6-7 of the status register. | UINT16 | Read | ||||
| HR | 33doc 40033 | Channel 17 status | BITMAP16 | Read | bit 0 = Alarm 1; bit 1 = Alarm 2; bit 2 = Alarm 3; bit 3 = Sensor/alarm fault; bit 4 = In calibration (sensors only); bit 5 = Communication error; bit 6 = Decimal point bit 0 (01 = divide by 10); bit 7 = Decimal point bit 1 (10 = divide by 100); bit 8 = Smart battery pack present; bit 9 = Battery error; bit 10 = Low battery; bit 12 = Wireless network type (0 = 320, 1 = 300); bit 13 = Device type bit 0; bit 14 = Device type bit 1; bit 15 = Device type bit 2 | ||||
| HR | 34doc 40034 | Channel 18 reading | Gas reading; divide per decimal-point bits 6-7 of the status register. | UINT16 | Read | ||||
| HR | 35doc 40035 | Channel 18 status | BITMAP16 | Read | bit 0 = Alarm 1; bit 1 = Alarm 2; bit 2 = Alarm 3; bit 3 = Sensor/alarm fault; bit 4 = In calibration (sensors only); bit 5 = Communication error; bit 6 = Decimal point bit 0 (01 = divide by 10); bit 7 = Decimal point bit 1 (10 = divide by 100); bit 8 = Smart battery pack present; bit 9 = Battery error; bit 10 = Low battery; bit 12 = Wireless network type (0 = 320, 1 = 300); bit 13 = Device type bit 0; bit 14 = Device type bit 1; bit 15 = Device type bit 2 | ||||
| HR | 36doc 40036 | Channel 19 reading | Gas reading; divide per decimal-point bits 6-7 of the status register. | UINT16 | Read | ||||
| HR | 37doc 40037 | Channel 19 status | BITMAP16 | Read | bit 0 = Alarm 1; bit 1 = Alarm 2; bit 2 = Alarm 3; bit 3 = Sensor/alarm fault; bit 4 = In calibration (sensors only); bit 5 = Communication error; bit 6 = Decimal point bit 0 (01 = divide by 10); bit 7 = Decimal point bit 1 (10 = divide by 100); bit 8 = Smart battery pack present; bit 9 = Battery error; bit 10 = Low battery; bit 12 = Wireless network type (0 = 320, 1 = 300); bit 13 = Device type bit 0; bit 14 = Device type bit 1; bit 15 = Device type bit 2 | ||||
| HR | 38doc 40038 | Channel 20 reading | Gas reading; divide per decimal-point bits 6-7 of the status register. | UINT16 | Read | ||||
| HR | 39doc 40039 | Channel 20 status | BITMAP16 | Read | bit 0 = Alarm 1; bit 1 = Alarm 2; bit 2 = Alarm 3; bit 3 = Sensor/alarm fault; bit 4 = In calibration (sensors only); bit 5 = Communication error; bit 6 = Decimal point bit 0 (01 = divide by 10); bit 7 = Decimal point bit 1 (10 = divide by 100); bit 8 = Smart battery pack present; bit 9 = Battery error; bit 10 = Low battery; bit 12 = Wireless network type (0 = 320, 1 = 300); bit 13 = Device type bit 0; bit 14 = Device type bit 1; bit 15 = Device type bit 2 | ||||
| HR | 40doc 40040 | Channel 21 reading | Gas reading; divide per decimal-point bits 6-7 of the status register. | UINT16 | Read | ||||
| HR | 41doc 40041 | Channel 21 status | BITMAP16 | Read | bit 0 = Alarm 1; bit 1 = Alarm 2; bit 2 = Alarm 3; bit 3 = Sensor/alarm fault; bit 4 = In calibration (sensors only); bit 5 = Communication error; bit 6 = Decimal point bit 0 (01 = divide by 10); bit 7 = Decimal point bit 1 (10 = divide by 100); bit 8 = Smart battery pack present; bit 9 = Battery error; bit 10 = Low battery; bit 12 = Wireless network type (0 = 320, 1 = 300); bit 13 = Device type bit 0; bit 14 = Device type bit 1; bit 15 = Device type bit 2 | ||||
| HR | 42doc 40042 | Channel 22 reading | Gas reading; divide per decimal-point bits 6-7 of the status register. | UINT16 | Read | ||||
| HR | 43doc 40043 | Channel 22 status | BITMAP16 | Read | bit 0 = Alarm 1; bit 1 = Alarm 2; bit 2 = Alarm 3; bit 3 = Sensor/alarm fault; bit 4 = In calibration (sensors only); bit 5 = Communication error; bit 6 = Decimal point bit 0 (01 = divide by 10); bit 7 = Decimal point bit 1 (10 = divide by 100); bit 8 = Smart battery pack present; bit 9 = Battery error; bit 10 = Low battery; bit 12 = Wireless network type (0 = 320, 1 = 300); bit 13 = Device type bit 0; bit 14 = Device type bit 1; bit 15 = Device type bit 2 | ||||
| HR | 44doc 40044 | Channel 23 reading | Gas reading; divide per decimal-point bits 6-7 of the status register. | UINT16 | Read | ||||
| HR | 45doc 40045 | Channel 23 status | BITMAP16 | Read | bit 0 = Alarm 1; bit 1 = Alarm 2; bit 2 = Alarm 3; bit 3 = Sensor/alarm fault; bit 4 = In calibration (sensors only); bit 5 = Communication error; bit 6 = Decimal point bit 0 (01 = divide by 10); bit 7 = Decimal point bit 1 (10 = divide by 100); bit 8 = Smart battery pack present; bit 9 = Battery error; bit 10 = Low battery; bit 12 = Wireless network type (0 = 320, 1 = 300); bit 13 = Device type bit 0; bit 14 = Device type bit 1; bit 15 = Device type bit 2 | ||||
| HR | 46doc 40046 | Channel 24 reading | Gas reading; divide per decimal-point bits 6-7 of the status register. | UINT16 | Read | ||||
| HR | 47doc 40047 | Channel 24 status | BITMAP16 | Read | bit 0 = Alarm 1; bit 1 = Alarm 2; bit 2 = Alarm 3; bit 3 = Sensor/alarm fault; bit 4 = In calibration (sensors only); bit 5 = Communication error; bit 6 = Decimal point bit 0 (01 = divide by 10); bit 7 = Decimal point bit 1 (10 = divide by 100); bit 8 = Smart battery pack present; bit 9 = Battery error; bit 10 = Low battery; bit 12 = Wireless network type (0 = 320, 1 = 300); bit 13 = Device type bit 0; bit 14 = Device type bit 1; bit 15 = Device type bit 2 | ||||
| HR | 48doc 40048 | Channel 25 reading | Gas reading; divide per decimal-point bits 6-7 of the status register. | UINT16 | Read | ||||
| HR | 49doc 40049 | Channel 25 status | BITMAP16 | Read | bit 0 = Alarm 1; bit 1 = Alarm 2; bit 2 = Alarm 3; bit 3 = Sensor/alarm fault; bit 4 = In calibration (sensors only); bit 5 = Communication error; bit 6 = Decimal point bit 0 (01 = divide by 10); bit 7 = Decimal point bit 1 (10 = divide by 100); bit 8 = Smart battery pack present; bit 9 = Battery error; bit 10 = Low battery; bit 12 = Wireless network type (0 = 320, 1 = 300); bit 13 = Device type bit 0; bit 14 = Device type bit 1; bit 15 = Device type bit 2 | ||||
| HR | 50doc 40050 | Channel 26 reading | Gas reading; divide per decimal-point bits 6-7 of the status register. | UINT16 | Read | ||||
| HR | 51doc 40051 | Channel 26 status | BITMAP16 | Read | bit 0 = Alarm 1; bit 1 = Alarm 2; bit 2 = Alarm 3; bit 3 = Sensor/alarm fault; bit 4 = In calibration (sensors only); bit 5 = Communication error; bit 6 = Decimal point bit 0 (01 = divide by 10); bit 7 = Decimal point bit 1 (10 = divide by 100); bit 8 = Smart battery pack present; bit 9 = Battery error; bit 10 = Low battery; bit 12 = Wireless network type (0 = 320, 1 = 300); bit 13 = Device type bit 0; bit 14 = Device type bit 1; bit 15 = Device type bit 2 | ||||
| HR | 52doc 40052 | Channel 27 reading | Gas reading; divide per decimal-point bits 6-7 of the status register. | UINT16 | Read | ||||
| HR | 53doc 40053 | Channel 27 status | BITMAP16 | Read | bit 0 = Alarm 1; bit 1 = Alarm 2; bit 2 = Alarm 3; bit 3 = Sensor/alarm fault; bit 4 = In calibration (sensors only); bit 5 = Communication error; bit 6 = Decimal point bit 0 (01 = divide by 10); bit 7 = Decimal point bit 1 (10 = divide by 100); bit 8 = Smart battery pack present; bit 9 = Battery error; bit 10 = Low battery; bit 12 = Wireless network type (0 = 320, 1 = 300); bit 13 = Device type bit 0; bit 14 = Device type bit 1; bit 15 = Device type bit 2 | ||||
| HR | 54doc 40054 | Channel 28 reading | Gas reading; divide per decimal-point bits 6-7 of the status register. | UINT16 | Read | ||||
| HR | 55doc 40055 | Channel 28 status | BITMAP16 | Read | bit 0 = Alarm 1; bit 1 = Alarm 2; bit 2 = Alarm 3; bit 3 = Sensor/alarm fault; bit 4 = In calibration (sensors only); bit 5 = Communication error; bit 6 = Decimal point bit 0 (01 = divide by 10); bit 7 = Decimal point bit 1 (10 = divide by 100); bit 8 = Smart battery pack present; bit 9 = Battery error; bit 10 = Low battery; bit 12 = Wireless network type (0 = 320, 1 = 300); bit 13 = Device type bit 0; bit 14 = Device type bit 1; bit 15 = Device type bit 2 | ||||
| HR | 56doc 40056 | Channel 29 reading | Gas reading; divide per decimal-point bits 6-7 of the status register. | UINT16 | Read | ||||
| HR | 57doc 40057 | Channel 29 status | BITMAP16 | Read | bit 0 = Alarm 1; bit 1 = Alarm 2; bit 2 = Alarm 3; bit 3 = Sensor/alarm fault; bit 4 = In calibration (sensors only); bit 5 = Communication error; bit 6 = Decimal point bit 0 (01 = divide by 10); bit 7 = Decimal point bit 1 (10 = divide by 100); bit 8 = Smart battery pack present; bit 9 = Battery error; bit 10 = Low battery; bit 12 = Wireless network type (0 = 320, 1 = 300); bit 13 = Device type bit 0; bit 14 = Device type bit 1; bit 15 = Device type bit 2 | ||||
| HR | 58doc 40058 | Channel 30 reading | Gas reading; divide per decimal-point bits 6-7 of the status register. | UINT16 | Read | ||||
| HR | 59doc 40059 | Channel 30 status | BITMAP16 | Read | bit 0 = Alarm 1; bit 1 = Alarm 2; bit 2 = Alarm 3; bit 3 = Sensor/alarm fault; bit 4 = In calibration (sensors only); bit 5 = Communication error; bit 6 = Decimal point bit 0 (01 = divide by 10); bit 7 = Decimal point bit 1 (10 = divide by 100); bit 8 = Smart battery pack present; bit 9 = Battery error; bit 10 = Low battery; bit 12 = Wireless network type (0 = 320, 1 = 300); bit 13 = Device type bit 0; bit 14 = Device type bit 1; bit 15 = Device type bit 2 | ||||
| HR | 60doc 40060 | Channel 31 reading | Gas reading; divide per decimal-point bits 6-7 of the status register. | UINT16 | Read | ||||
| HR | 61doc 40061 | Channel 31 status | BITMAP16 | Read | bit 0 = Alarm 1; bit 1 = Alarm 2; bit 2 = Alarm 3; bit 3 = Sensor/alarm fault; bit 4 = In calibration (sensors only); bit 5 = Communication error; bit 6 = Decimal point bit 0 (01 = divide by 10); bit 7 = Decimal point bit 1 (10 = divide by 100); bit 8 = Smart battery pack present; bit 9 = Battery error; bit 10 = Low battery; bit 12 = Wireless network type (0 = 320, 1 = 300); bit 13 = Device type bit 0; bit 14 = Device type bit 1; bit 15 = Device type bit 2 | ||||
| HR | 62doc 40062 | Channel 32 reading | Gas reading; divide per decimal-point bits 6-7 of the status register. | UINT16 | Read | ||||
| HR | 63doc 40063 | Channel 32 status | BITMAP16 | Read | bit 0 = Alarm 1; bit 1 = Alarm 2; bit 2 = Alarm 3; bit 3 = Sensor/alarm fault; bit 4 = In calibration (sensors only); bit 5 = Communication error; bit 6 = Decimal point bit 0 (01 = divide by 10); bit 7 = Decimal point bit 1 (10 = divide by 100); bit 8 = Smart battery pack present; bit 9 = Battery error; bit 10 = Low battery; bit 12 = Wireless network type (0 = 320, 1 = 300); bit 13 = Device type bit 0; bit 14 = Device type bit 1; bit 15 = Device type bit 2 |
Notes on this map
- Readings carry no fixed scale: status bits 7-6 give the decimal point (00 = none, 01 = divide by 10, 10 = divide by 100, 11 = undefined, treat as none).
- Status bits 15-13 give the device type on that channel: 000 disabled, 001 CXT sensor, 010 alarm station, 011 SmartHMI, 100 repeater, 101 sensor, 110/111 undefined (sensor).
- Bits 4, 6 and 7 are only active for sensor devices. Bit 11 is not used.
- The manual does not name the function code; the 4xxxx register numbers indicate holding registers (function 03).
- The slave address is set in the controller menu; no default is stated in this section.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Teledyne Detcon Model X40 integrated alarm and control system (Modbus slave port)
What Modbus registers does the Teledyne Detcon Model X40 integrated alarm and control system (Modbus slave port) have?
This map lists 64 registers: 64 holding registers. 0 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Teledyne Detcon Model X40 integrated alarm and control system (Modbus slave port) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Table 4 numbers the registers from 40000 (channel 1 reading), so the digits after the leading 4 are the wire address: channel n reading = 2(n-1), status = 2(n-1)+1.
What are the minimum Modbus registers to integrate the Teledyne Detcon Model X40 integrated alarm and control system (Modbus slave port)?
Start with HR 0 Channel 1 reading (Channel 1 reading); HR 1 Channel 1 status (Channel 1 status (alarms, fault, decimals)); HR 2 Channel 2 reading (Channel 2 reading); HR 3 Channel 2 status (Channel 2 status).
How do I enable Modbus control of the Teledyne Detcon Model X40 integrated alarm and control system (Modbus slave port)?
The manual describes no separate enable step for the slave port; give each X40 its own device address when several share one network.
Where is the official Teledyne Detcon Model X40 integrated alarm and control system (Modbus slave port) Modbus documentation?
The source is X40 Instruction Manual (Document #3672, Rev. 3.8), revision 2023-01-18, published free by Teledyne Detcon at https://www.teledynegasandflamedetection.com/en-us/Products/docs/controllers-x40-usermanual-english.pdf.
More Teledyne Detcon Modbus register maps
- Sensor (fixed gas detector)
Teledyne Detcon Model CX-IR infrared combustible gas sensor (Modbus RTU)
Teledyne Detcon CX-IR wired infrared gas sensors (RS-485 Modbus RTU and 4-20 mA), instruction manual Document #4428 Rev. 1.9.
Also known as: CX-IR, Detcon CX-IR - Sensor (fixed gas detector)
Teledyne Detcon Model DM-700 electrochemical toxic gas / oxygen sensor (RS-485 Modbus)
Teledyne Detcon DM-700 smart sensors with the 4-20 mA and RS-485 Modbus outputs, instruction manual Document #3207, Rev. 5.9.
Also known as: DM-700, Detcon DM-700, Teledyne Detcon DM-700 - Sensor (fixed gas detector)
Teledyne Detcon Model FP-624D MicroSafe combustible gas sensor (RS-485 Modbus)
Teledyne Detcon FP-624D MicroSafe catalytic LEL sensor with 4-20 mA, relays and RS-485 Modbus RTU, instruction manual Document #3598 Rev. 1.7.
Also known as: FP-624D, MicroSafe FP-624D, Detcon FP-624D - Sensor (fixed gas detector)
Teledyne Detcon Model FP-700 catalytic bead combustible gas sensor (RS-485 Modbus)
Teledyne Detcon FP-700 smart sensors with the 4-20 mA and RS-485 Modbus outputs, instruction manual Document #3168, Rev. 5.7.
Also known as: FP-700, Detcon FP-700, Teledyne Detcon FP-700 - Sensor (fixed gas detector)
Teledyne Detcon Model IR-700 infrared combustible / CO2 gas sensor (RS-485 Modbus)
Teledyne Detcon IR-700 smart sensors with the 4-20 mA and RS-485 Modbus outputs, instruction manual Document #3169, Rev. 4.9.
Also known as: IR-700, Detcon IR-700, Teledyne Detcon IR-700 - Sensor (fixed gas detector)
Teledyne Detcon Model PI-700 photoionization (PID) VOC sensor (RS-485 Modbus)
Teledyne Detcon PI-700 smart sensors with the 4-20 mA and RS-485 Modbus outputs, instruction manual Document #3228, Rev. 4.0.
Also known as: PI-700, Detcon PI-700, Teledyne Detcon PI-700 - Sensor (fixed gas detector)
Teledyne Detcon Model TP-700 MOS (metal oxide) H2S sensor (RS-485 Modbus)
Teledyne Detcon TP-700 smart sensors with the 4-20 mA and RS-485 Modbus outputs, instruction manual Document #3150, Rev. 4.6.
Also known as: TP-700, Detcon TP-700, Teledyne Detcon TP-700
Other gas detectors register maps
- Sensor (refrigerant / toxic gas detector)
Danfoss Gas Detection Units GD Basic / Premium / Heavy Duty (Modbus RTU)
Danfoss GD Basic, Premium and Heavy Duty gas detection units on their own RS-485 Modbus port (Part 2 of the guide). The gas detection controller's X-bus map in Part 1 is not included.
Also known as: GDA, GDC, GDHC, GDHF, GDH, GD Basic, GD Premium, GD Heavy Duty - Sensor (gas detector)
Senva TG series toxic/combustible gas monitor (RS-485 Modbus)
Senva TG series RS-485 gas monitors (one or two gas sensors, optional temperature), Modbus Protocol Guide 154-0036-0A (2020-02-07).
Also known as: Senva TG, TG series - Sensor (gas transmitter / gas detector)
Analytical Technology (ATI) D12 / F12 gas transmitter (H10, catalytic bead, wet H2S sensors) Modbus interface
ATI D12 and F12 transmitters with the Modbus option fitted to H10 toxic, catalytic bead or wet H2S sensors (Appendix table 4.1). IR-sensor D12s use a different table.
Also known as: D12, F12, D12 gas transmitter, F12 gas transmitter - Sensor (extractive gas detector)
New Cosmos Electric PS-8 series extractive gas detector (Modbus TCP)
New Cosmos PS-8 series pump-type gas detectors for semiconductor plants (up to 16 sensor channels) with Ethernet Modbus TCP, Instruction Manual for Communication GAE-180-00 (December 2024).
Also known as: PS-8, PS-8 series, New Cosmos PS-8 - Sensor (water leak detector)
Teracom TSF400-4 water-leak detector with Modbus RTU
TSF400-4 per the Teracom TSF400-4 user manual Revision R1.2.
Also known as: TSF400-4 - Sensor (extractive gas detector)
Honeywell Midas S2 extractive gas transmitter (Modbus/TCP)
Honeywell Midas S2 single-point extractive gas transmitters with Ethernet/PoE, user manual 3023M5001 Rev A, Modbus/TCP register map (Table 6-1).
Also known as: Midas S2, MIDAS-S2, Midas S2 gas detector
All gas detectors Modbus register maps →
Source: X40 Instruction Manual · Document #3672, Rev. 3.8 · rev. 2023-01-18. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.