  4. TG series toxic/combustible gas monitor (RS-485 Modbus)

Sensor (gas detector) · Modbus register map

Senva TG series toxic/combustible gas monitor (RS-485 Modbus) Modbus register map

Updated 17 November 2026

Short answer

The Senva TG is a wall-mount gas monitor with one or two gas sensors, a fan relay, an alarm relay and a buzzer, plus an RS-485 port that auto-detects BACnet MS/TP, Modbus RTU or Modbus ASCII. All data is in holding registers. This map covers communication setup, units, setpoints and hysteresis, sensor life and status, system state, relay and buzzer control, and the gas, temperature and supply-voltage readings with their statistics.

This page lists 79 Modbus registers for the Senva TG series toxic/combustible gas monitor (RS-485 Modbus) — 62 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Senva’s own free documentation (linked below) and checked against it.

Manufacturer
Senva
Model
TG series toxic/combustible gas monitor (RS-485 Modbus)
Equipment type
Sensor (gas detector)
Registers
79 (62 writable)
Transport
Modbus RTU, Modbus ASCII
Default unit ID
Not stated
Documented addressing
0-based (the number printed is the address on the wire)
32-bit word order
ABCD high word first (big-endian)
Also known as
Senva TG, TG series
Source document
TG Modbus Protocol Guide · 154-0036-0A · rev. 2020-02-07 · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Senva TG series toxic/combustible gas monitor (RS-485 Modbus)

Integration in brief

Connect the TG to the RS-485 bus and poll; it learns the protocol, baud and parity from traffic. Its address is 100 + the last two serial digits. Read R320 (gas 1), R170 (state) and R210/R230 (relays) with FC 03; floats are high word first.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 320Sensor 1 gas concentrationFLOAT32 ABCDSensor 1 gas concentrationRead
HR 330Sensor 2 gas concentrationFLOAT32 ABCDSensor 2 gas concentrationRead
HR 170Current system stateUINT16System stateRead
HR 210Fan relayUINT16Fan relayRead
HR 230Alarm relayUINT16Alarm relayRead
HR 158Sensor 1 lifeINT16Sensor 1 remaining lifeRead

Enable Modbus control & writes

No setup needed: with Auto Protocol, Auto Baud and Auto Parity active (factory default) the TG adapts to the bus. Fix the settings via R122-R128 once the network is stable.

Byte order & addressing

Network setup

Watch out for

Senva TG series toxic/combustible gas monitor (RS-485 Modbus) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

79 of 79 shown
Senva TG series toxic/combustible gas monitor (RS-485 Modbus) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR102doc R102Reset statusReason for the last reset.UINT16Read1 = Configuration reset; 3 = Power loss; 5 = Hardware watchdog
HR103doc R103Reset countLifetime count of firmware resets.UINT16Read
HR104doc R104Up timeTime since last reset.UINT32ABCDsRead
HR111doc R111Identify deviceLEDs light and LCD blinks the address while active.UINT16Read/write0 = Inactive; 1 = Active
HR112doc R112Auto protocolDefault active.UINT16Read/write0 = Inactive; 1 = Active
HR113doc R113Auto MAC (slave) addressDefault active.UINT16Read/write0 = Inactive; 1 = Active
HR114doc R114Auto baud rateDefault active.UINT16Read/write0 = Inactive; 1 = Active
HR115doc R115Auto parityDefault active.UINT16Read/write0 = Inactive; 1 = Active
HR116doc R116Auto data bitsDefault active.UINT16Read/write0 = Inactive; 1 = Active
HR117doc R117Auto stop bitsDefault active.UINT16Read/write0 = Inactive; 1 = Active
HR118doc R118Buzzer overrideForces the buzzer regardless of state.UINT16Read/write0 = Inactive; 1 = Active
HR122doc R122RS485 protocolUINT16Read/write1 = Auto; 2 = BACnet; 3 = Modbus RTU; 4 = Modbus ASCII; 5 = BACnet and Modbus RTU; 6 = BACnet and Modbus ASCII; 7 = Modbus RTU and ASCII; 8 = Any protocol
HR123doc R123Slave address1-254 (use 1-247); also answers to 255.UINT16Read/write
HR124doc R124RS485 baud rate1200-460800. Writing turns auto baud off; no remote way back.UINT32ABCDRead/write
HR126doc R126RS485 parityUINT16Read/write1 = Auto; 2 = No parity; 3 = Odd parity; 4 = Even parity
HR127doc R127RS485 data bitsUINT16Read/write1 = Auto; 2 = 7 bits; 3 = 8 bits
HR128doc R128RS485 stop bitsUINT16Read/write1 = Auto; 2 = 1 bit; 3 = 1.5 bits; 4 = 2 bits
HR133doc R133Temperature unitsDefault °F.UINT16Read/write1 = Degrees Fahrenheit; 2 = Degrees Celsius
HR134doc R134Smoothed temperature response timeDefault 30 s.UINT16sRead/write
HR135doc R135Gas 1 response timeDefault 10 s.UINT16sRead/write
HR136doc R136Gas 2 response timeDefault 10 s.UINT16sRead/write
HR150doc R150Sensor 1 warning setpointGas level for the Warning state.FLOAT32ABCDRead/write
HR152doc R152Sensor 1 alarm setpointGas level for the Alarm state.FLOAT32ABCDRead/write
HR154doc R154Sensor 1 hysteresisDefault 0.FLOAT32ABCDRead/write
HR158doc R158Sensor 1 lifeRemaining sensor life; starts at 1825.INT16daysRead
HR160doc R160Sensor 2 warning setpointDefault 1.0 ppm.FLOAT32ABCDRead/write
HR162doc R162Sensor 2 alarm setpointDefault 3.0 ppm.FLOAT32ABCDRead/write
HR164doc R164Sensor 2 hysteresisDefault 0.FLOAT32ABCDRead/write
HR168doc R168Sensor 2 lifeRemaining sensor life; starts at 1825.INT16daysRead
HR170doc R170Current system stateUINT16Read1 = Normal; 2 = Warning; 3 = Alarm; 4 = Extended alarm
HR190doc R190System configuration resetWrite 9699690 to restore factory defaults (address and serial settings too).UINT32ABCDWrite
HR192doc R192System statistics resetWrite 4765089 to reset min/max/average statistics.UINT32ABCDWrite
HR195doc R195Auto reset statisticsWhen active, reading a statistic also resets it.UINT16Read/write0 = Inactive; 1 = Active
HR196doc R196Sensor 1 pulse statusPulse health check for electrochemical sensors.UINT16Read/write0 = Inactive; 1 = Active
HR197doc R197Sensor 2 pulse statusPulse health check for electrochemical sensors.UINT16Read/write0 = Inactive; 1 = Active
HR200doc R200Sensor 1 sensor statusUINT16Read/write0 = No fault detected; 1 = No sensor; 2 = Over range; 3 = Under range; 7 = Unreliable other
HR201doc R201Sensor 2 sensor statusValue coding printed inconsistently in the source (see notes).UINT16Read/write
HR210doc R210Fan relayUINT16Read1 = Inactive; 2 = Active
HR211doc R211Fan relay overrideUINT16Read/write1 = System; 2 = Inactive; 3 = Active
HR212doc R212Fan maximum off time0 = ignored.UINT32ABCDsRead/write
HR214doc R214Fan minimum on timeDefault 60 s.UINT32ABCDsRead/write
HR216doc R216Fan minimum off timeDefault 60 s.UINT32ABCDsRead/write
HR218doc R218Fan state countTransitions since restart; write 0 to reset.UINT32ABCDRead/write
HR220doc R220Fan total active timeSince restart; write 0 to reset.UINT32ABCDsRead/write
HR230doc R230Alarm relayValue coding printed inconsistently in the source (see notes).UINT16Read
HR231doc R231Alarm relay overrideUINT16Read/write1 = System; 2 = Inactive; 3 = Active
HR232doc R232Alarm maximum off time0 = ignored.UINT32ABCDsRead/write
HR234doc R234Alarm minimum on timeDefault 60 s.UINT32ABCDsRead/write
HR236doc R236Alarm minimum off timeDefault 60 s.UINT32ABCDsRead/write
HR238doc R238Alarm state countTransitions since restart; write 0 to reset.UINT32ABCDRead/write
HR240doc R240Alarm total active timeSince restart; write 0 to reset.UINT32ABCDsRead/write
HR250doc R250Alarm buzzerUINT16Read1 = Inactive; 2 = Active
HR251doc R251Alarm buzzer overrideUINT16Read/write1 = System; 2 = Inactive; 3 = Active
HR252doc R252Buzzer delayDelay after entering Alarm; default 1800 s.UINT32ABCDsRead/write
HR254doc R254Buzzer minimum on timeDefault 0 s.UINT32ABCDsRead/write
HR256doc R256Buzzer minimum off timeDefault 0 s.UINT32ABCDsRead/write
HR258doc R258Buzzer state countTransitions since restart; write 0 to reset.UINT32ABCDRead/write
HR260doc R260Buzzer total active timeSince restart; write 0 to reset.UINT32ABCDsRead/write
HR278doc R278Location stringUp to 31 characters, null terminated; appended to Server ID.STRING[32]Read/write
HR310doc R310TemperaturePrimary reading. Units per R133 (default °F); thermistor models only.FLOAT32ABCDRead
HR312doc R312Temperature - instantaneousFLOAT32ABCDRead
HR314doc R314Temperature - minimumWrite 0 to reset.FLOAT32ABCDRead/write
HR316doc R316Temperature - maximumWrite 0 to reset.FLOAT32ABCDRead/write
HR318doc R318Temperature - averageWrite 0 to reset.FLOAT32ABCDRead/write
HR320doc R320Sensor 1 gas concentrationPrimary reading.FLOAT32ABCDRead
HR322doc R322Sensor 1 gas concentration - smoothedFLOAT32ABCDRead
HR324doc R324Sensor 1 gas concentration - minimumWrite 0 to reset.FLOAT32ABCDRead/write
HR326doc R326Sensor 1 gas concentration - maximumWrite 0 to reset.FLOAT32ABCDRead/write
HR328doc R328Sensor 1 gas concentration - averageWrite 0 to reset.FLOAT32ABCDRead/write
HR330doc R330Sensor 2 gas concentrationPrimary reading.FLOAT32ABCDRead
HR332doc R332Sensor 2 gas concentration - smoothedFLOAT32ABCDRead
HR334doc R334Sensor 2 gas concentration - minimumWrite 0 to reset.FLOAT32ABCDRead/write
HR336doc R336Sensor 2 gas concentration - maximumWrite 0 to reset.FLOAT32ABCDRead/write
HR338doc R338Sensor 2 gas concentration - averageWrite 0 to reset.FLOAT32ABCDRead/write
HR380doc R380Power supply voltagePrimary reading.FLOAT32ABCDVRead
HR382doc R382Power supply voltage - instantaneousFLOAT32ABCDVRead
HR384doc R384Power supply voltage - minimumWrite 0 to reset.FLOAT32ABCDVRead/write
HR386doc R386Power supply voltage - maximumWrite 0 to reset.FLOAT32ABCDVRead/write
HR388doc R388Power supply voltage - averageWrite 0 to reset.FLOAT32ABCDVRead/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Senva TG series toxic/combustible gas monitor (RS-485 Modbus)

What Modbus registers does the Senva TG series toxic/combustible gas monitor (RS-485 Modbus) have?

This map lists 79 registers: 79 holding registers. 62 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Senva TG series toxic/combustible gas monitor (RS-485 Modbus) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide prints raw protocol addresses prefixed with R (R320 = address 320); in Modicon notation that is 40321. 'R320/21' is a 2-register value starting at 320.

What byte order does the Senva TG series toxic/combustible gas monitor (RS-485 Modbus) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Senva TG series toxic/combustible gas monitor (RS-485 Modbus)?

Start with HR 320 Sensor 1 gas concentration (Sensor 1 gas concentration); HR 330 Sensor 2 gas concentration (Sensor 2 gas concentration); HR 170 Current system state (System state); HR 210 Fan relay (Fan relay); HR 230 Alarm relay (Alarm relay); HR 158 Sensor 1 life (Sensor 1 remaining life).

How do I enable Modbus control of the Senva TG series toxic/combustible gas monitor (RS-485 Modbus)?

No setup needed: with Auto Protocol, Auto Baud and Auto Parity active (factory default) the TG adapts to the bus. Fix the settings via R122-R128 once the network is stable.

Where is the official Senva TG series toxic/combustible gas monitor (RS-485 Modbus) Modbus documentation?

The source is TG Modbus Protocol Guide (154-0036-0A), revision 2020-02-07. Senva doesn't publish it on its own website, so this map was re-typed from a free copy at https://www.zotsupply.com/content/PDFs/Senva/Gas%20Monitoring/154-0036-0A.pdf. It may be an older revision, so check it against the live unit.

More Senva Modbus register maps

Other gas detectors register maps

All gas detectors Modbus register maps →

Source: TG Modbus Protocol Guide · 154-0036-0A · rev. 2020-02-07 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.