Sensor (gas detector) · Modbus register map
Senva TG series toxic/combustible gas monitor (RS-485 Modbus) Modbus register map
Updated 17 November 2026
The Senva TG is a wall-mount gas monitor with one or two gas sensors, a fan relay, an alarm relay and a buzzer, plus an RS-485 port that auto-detects BACnet MS/TP, Modbus RTU or Modbus ASCII. All data is in holding registers. This map covers communication setup, units, setpoints and hysteresis, sensor life and status, system state, relay and buzzer control, and the gas, temperature and supply-voltage readings with their statistics.
This page lists 79 Modbus registers for the Senva TG series toxic/combustible gas monitor (RS-485 Modbus) — 62 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Senva’s own free documentation (linked below) and checked against it.
- Manufacturer
- Senva
- Model
- TG series toxic/combustible gas monitor (RS-485 Modbus)
- Equipment type
- Sensor (gas detector)
- Registers
- 79 (62 writable)
- Transport
- Modbus RTU, Modbus ASCII
- Default unit ID
- Not stated
- Documented addressing
- 0-based (the number printed is the address on the wire)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- Senva TG, TG series
Integration notes: Senva TG series toxic/combustible gas monitor (RS-485 Modbus)
Connect the TG to the RS-485 bus and poll; it learns the protocol, baud and parity from traffic. Its address is 100 + the last two serial digits. Read R320 (gas 1), R170 (state) and R210/R230 (relays) with FC 03; floats are high word first.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 320 | Sensor 1 gas concentration | FLOAT32 ABCD | Sensor 1 gas concentration | Read |
| HR 330 | Sensor 2 gas concentration | FLOAT32 ABCD | Sensor 2 gas concentration | Read |
| HR 170 | Current system state | UINT16 | System state | Read |
| HR 210 | Fan relay | UINT16 | Fan relay | Read |
| HR 230 | Alarm relay | UINT16 | Alarm relay | Read |
| HR 158 | Sensor 1 life | INT16 | Sensor 1 remaining life | Read |
Enable Modbus control & writes
No setup needed: with Auto Protocol, Auto Baud and Auto Parity active (factory default) the TG adapts to the bus. Fix the settings via R122-R128 once the network is stable.
Byte order & addressing
- Addresses are raw (R320 = address 320).
- Floats and UINT32 are big-endian, high word first.
- Writing R124 turns auto-baud off and cannot be undone remotely if the new rate is wrong.
Network setup
- Default slave address = 100 + last two digits of the serial number.
- Auto baud 9600-115200; parity even/odd/none detected automatically.
Watch out for
- Writing 9699690 to R190 erases all configuration including the address.
- With Auto Reset Statistics on, every read of a min/max/average resets it.
Senva TG series toxic/combustible gas monitor (RS-485 Modbus) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 102doc R102 | Reset status | Reason for the last reset. | UINT16 | Read | 1 = Configuration reset; 3 = Power loss; 5 = Hardware watchdog | |||
| HR | 103doc R103 | Reset count | Lifetime count of firmware resets. | UINT16 | Read | ||||
| HR | 104doc R104 | Up time | Time since last reset. | UINT32 | ABCD | s | Read | ||
| HR | 111doc R111 | Identify device | LEDs light and LCD blinks the address while active. | UINT16 | Read/write | 0 = Inactive; 1 = Active | |||
| HR | 112doc R112 | Auto protocol | Default active. | UINT16 | Read/write | 0 = Inactive; 1 = Active | |||
| HR | 113doc R113 | Auto MAC (slave) address | Default active. | UINT16 | Read/write | 0 = Inactive; 1 = Active | |||
| HR | 114doc R114 | Auto baud rate | Default active. | UINT16 | Read/write | 0 = Inactive; 1 = Active | |||
| HR | 115doc R115 | Auto parity | Default active. | UINT16 | Read/write | 0 = Inactive; 1 = Active | |||
| HR | 116doc R116 | Auto data bits | Default active. | UINT16 | Read/write | 0 = Inactive; 1 = Active | |||
| HR | 117doc R117 | Auto stop bits | Default active. | UINT16 | Read/write | 0 = Inactive; 1 = Active | |||
| HR | 118doc R118 | Buzzer override | Forces the buzzer regardless of state. | UINT16 | Read/write | 0 = Inactive; 1 = Active | |||
| HR | 122doc R122 | RS485 protocol | UINT16 | Read/write | 1 = Auto; 2 = BACnet; 3 = Modbus RTU; 4 = Modbus ASCII; 5 = BACnet and Modbus RTU; 6 = BACnet and Modbus ASCII; 7 = Modbus RTU and ASCII; 8 = Any protocol | ||||
| HR | 123doc R123 | Slave address | 1-254 (use 1-247); also answers to 255. | UINT16 | Read/write | ||||
| HR | 124doc R124 | RS485 baud rate | 1200-460800. Writing turns auto baud off; no remote way back. | UINT32 | ABCD | Read/write | |||
| HR | 126doc R126 | RS485 parity | UINT16 | Read/write | 1 = Auto; 2 = No parity; 3 = Odd parity; 4 = Even parity | ||||
| HR | 127doc R127 | RS485 data bits | UINT16 | Read/write | 1 = Auto; 2 = 7 bits; 3 = 8 bits | ||||
| HR | 128doc R128 | RS485 stop bits | UINT16 | Read/write | 1 = Auto; 2 = 1 bit; 3 = 1.5 bits; 4 = 2 bits | ||||
| HR | 133doc R133 | Temperature units | Default °F. | UINT16 | Read/write | 1 = Degrees Fahrenheit; 2 = Degrees Celsius | |||
| HR | 134doc R134 | Smoothed temperature response time | Default 30 s. | UINT16 | s | Read/write | |||
| HR | 135doc R135 | Gas 1 response time | Default 10 s. | UINT16 | s | Read/write | |||
| HR | 136doc R136 | Gas 2 response time | Default 10 s. | UINT16 | s | Read/write | |||
| HR | 150doc R150 | Sensor 1 warning setpoint | Gas level for the Warning state. | FLOAT32 | ABCD | Read/write | |||
| HR | 152doc R152 | Sensor 1 alarm setpoint | Gas level for the Alarm state. | FLOAT32 | ABCD | Read/write | |||
| HR | 154doc R154 | Sensor 1 hysteresis | Default 0. | FLOAT32 | ABCD | Read/write | |||
| HR | 158doc R158 | Sensor 1 life | Remaining sensor life; starts at 1825. | INT16 | days | Read | |||
| HR | 160doc R160 | Sensor 2 warning setpoint | Default 1.0 ppm. | FLOAT32 | ABCD | Read/write | |||
| HR | 162doc R162 | Sensor 2 alarm setpoint | Default 3.0 ppm. | FLOAT32 | ABCD | Read/write | |||
| HR | 164doc R164 | Sensor 2 hysteresis | Default 0. | FLOAT32 | ABCD | Read/write | |||
| HR | 168doc R168 | Sensor 2 life | Remaining sensor life; starts at 1825. | INT16 | days | Read | |||
| HR | 170doc R170 | Current system state | UINT16 | Read | 1 = Normal; 2 = Warning; 3 = Alarm; 4 = Extended alarm | ||||
| HR | 190doc R190 | System configuration reset | Write 9699690 to restore factory defaults (address and serial settings too). | UINT32 | ABCD | Write | |||
| HR | 192doc R192 | System statistics reset | Write 4765089 to reset min/max/average statistics. | UINT32 | ABCD | Write | |||
| HR | 195doc R195 | Auto reset statistics | When active, reading a statistic also resets it. | UINT16 | Read/write | 0 = Inactive; 1 = Active | |||
| HR | 196doc R196 | Sensor 1 pulse status | Pulse health check for electrochemical sensors. | UINT16 | Read/write | 0 = Inactive; 1 = Active | |||
| HR | 197doc R197 | Sensor 2 pulse status | Pulse health check for electrochemical sensors. | UINT16 | Read/write | 0 = Inactive; 1 = Active | |||
| HR | 200doc R200 | Sensor 1 sensor status | UINT16 | Read/write | 0 = No fault detected; 1 = No sensor; 2 = Over range; 3 = Under range; 7 = Unreliable other | ||||
| HR | 201doc R201 | Sensor 2 sensor status | Value coding printed inconsistently in the source (see notes). | UINT16 | Read/write | ||||
| HR | 210doc R210 | Fan relay | UINT16 | Read | 1 = Inactive; 2 = Active | ||||
| HR | 211doc R211 | Fan relay override | UINT16 | Read/write | 1 = System; 2 = Inactive; 3 = Active | ||||
| HR | 212doc R212 | Fan maximum off time | 0 = ignored. | UINT32 | ABCD | s | Read/write | ||
| HR | 214doc R214 | Fan minimum on time | Default 60 s. | UINT32 | ABCD | s | Read/write | ||
| HR | 216doc R216 | Fan minimum off time | Default 60 s. | UINT32 | ABCD | s | Read/write | ||
| HR | 218doc R218 | Fan state count | Transitions since restart; write 0 to reset. | UINT32 | ABCD | Read/write | |||
| HR | 220doc R220 | Fan total active time | Since restart; write 0 to reset. | UINT32 | ABCD | s | Read/write | ||
| HR | 230doc R230 | Alarm relay | Value coding printed inconsistently in the source (see notes). | UINT16 | Read | ||||
| HR | 231doc R231 | Alarm relay override | UINT16 | Read/write | 1 = System; 2 = Inactive; 3 = Active | ||||
| HR | 232doc R232 | Alarm maximum off time | 0 = ignored. | UINT32 | ABCD | s | Read/write | ||
| HR | 234doc R234 | Alarm minimum on time | Default 60 s. | UINT32 | ABCD | s | Read/write | ||
| HR | 236doc R236 | Alarm minimum off time | Default 60 s. | UINT32 | ABCD | s | Read/write | ||
| HR | 238doc R238 | Alarm state count | Transitions since restart; write 0 to reset. | UINT32 | ABCD | Read/write | |||
| HR | 240doc R240 | Alarm total active time | Since restart; write 0 to reset. | UINT32 | ABCD | s | Read/write | ||
| HR | 250doc R250 | Alarm buzzer | UINT16 | Read | 1 = Inactive; 2 = Active | ||||
| HR | 251doc R251 | Alarm buzzer override | UINT16 | Read/write | 1 = System; 2 = Inactive; 3 = Active | ||||
| HR | 252doc R252 | Buzzer delay | Delay after entering Alarm; default 1800 s. | UINT32 | ABCD | s | Read/write | ||
| HR | 254doc R254 | Buzzer minimum on time | Default 0 s. | UINT32 | ABCD | s | Read/write | ||
| HR | 256doc R256 | Buzzer minimum off time | Default 0 s. | UINT32 | ABCD | s | Read/write | ||
| HR | 258doc R258 | Buzzer state count | Transitions since restart; write 0 to reset. | UINT32 | ABCD | Read/write | |||
| HR | 260doc R260 | Buzzer total active time | Since restart; write 0 to reset. | UINT32 | ABCD | s | Read/write | ||
| HR | 278doc R278 | Location string | Up to 31 characters, null terminated; appended to Server ID. | STRING[32] | Read/write | ||||
| HR | 310doc R310 | Temperature | Primary reading. Units per R133 (default °F); thermistor models only. | FLOAT32 | ABCD | Read | |||
| HR | 312doc R312 | Temperature - instantaneous | FLOAT32 | ABCD | Read | ||||
| HR | 314doc R314 | Temperature - minimum | Write 0 to reset. | FLOAT32 | ABCD | Read/write | |||
| HR | 316doc R316 | Temperature - maximum | Write 0 to reset. | FLOAT32 | ABCD | Read/write | |||
| HR | 318doc R318 | Temperature - average | Write 0 to reset. | FLOAT32 | ABCD | Read/write | |||
| HR | 320doc R320 | Sensor 1 gas concentration | Primary reading. | FLOAT32 | ABCD | Read | |||
| HR | 322doc R322 | Sensor 1 gas concentration - smoothed | FLOAT32 | ABCD | Read | ||||
| HR | 324doc R324 | Sensor 1 gas concentration - minimum | Write 0 to reset. | FLOAT32 | ABCD | Read/write | |||
| HR | 326doc R326 | Sensor 1 gas concentration - maximum | Write 0 to reset. | FLOAT32 | ABCD | Read/write | |||
| HR | 328doc R328 | Sensor 1 gas concentration - average | Write 0 to reset. | FLOAT32 | ABCD | Read/write | |||
| HR | 330doc R330 | Sensor 2 gas concentration | Primary reading. | FLOAT32 | ABCD | Read | |||
| HR | 332doc R332 | Sensor 2 gas concentration - smoothed | FLOAT32 | ABCD | Read | ||||
| HR | 334doc R334 | Sensor 2 gas concentration - minimum | Write 0 to reset. | FLOAT32 | ABCD | Read/write | |||
| HR | 336doc R336 | Sensor 2 gas concentration - maximum | Write 0 to reset. | FLOAT32 | ABCD | Read/write | |||
| HR | 338doc R338 | Sensor 2 gas concentration - average | Write 0 to reset. | FLOAT32 | ABCD | Read/write | |||
| HR | 380doc R380 | Power supply voltage | Primary reading. | FLOAT32 | ABCD | V | Read | ||
| HR | 382doc R382 | Power supply voltage - instantaneous | FLOAT32 | ABCD | V | Read | |||
| HR | 384doc R384 | Power supply voltage - minimum | Write 0 to reset. | FLOAT32 | ABCD | V | Read/write | ||
| HR | 386doc R386 | Power supply voltage - maximum | Write 0 to reset. | FLOAT32 | ABCD | V | Read/write | ||
| HR | 388doc R388 | Power supply voltage - average | Write 0 to reset. | FLOAT32 | ABCD | V | Read/write |
Notes on this map
- Source host: the unaltered Senva guide hosted by a distributor; we did not find it on Senva's own site.
- Word order: the guide says UINT32 and FLOAT use two registers in full network byte order, MSB first, and gives UINT32 byte examples, so high word first (ABCD).
- BOOL registers are listed as UINT16 with 0/1 values. The default slave address is 100 plus the last two digits of the serial number; baud, parity and data bits are auto-detected by default.
- Gas concentrations are FLOAT values; the guide gives setpoint defaults in ppm but does not print a unit on the concentration registers.
- The source prints inconsistent value codes for R201 (4-8 for sensor 2 status) and R230 (4/5 for the alarm relay), so no value table is given for them.
- Left out: User Data R294-301 (free storage) and Sensor calibration registers mentioned but not listed (R156, R166).
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Senva TG series toxic/combustible gas monitor (RS-485 Modbus)
What Modbus registers does the Senva TG series toxic/combustible gas monitor (RS-485 Modbus) have?
This map lists 79 registers: 79 holding registers. 62 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Senva TG series toxic/combustible gas monitor (RS-485 Modbus) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide prints raw protocol addresses prefixed with R (R320 = address 320); in Modicon notation that is 40321. 'R320/21' is a 2-register value starting at 320.
What byte order does the Senva TG series toxic/combustible gas monitor (RS-485 Modbus) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Senva TG series toxic/combustible gas monitor (RS-485 Modbus)?
Start with HR 320 Sensor 1 gas concentration (Sensor 1 gas concentration); HR 330 Sensor 2 gas concentration (Sensor 2 gas concentration); HR 170 Current system state (System state); HR 210 Fan relay (Fan relay); HR 230 Alarm relay (Alarm relay); HR 158 Sensor 1 life (Sensor 1 remaining life).
How do I enable Modbus control of the Senva TG series toxic/combustible gas monitor (RS-485 Modbus)?
No setup needed: with Auto Protocol, Auto Baud and Auto Parity active (factory default) the TG adapts to the bus. Fix the settings via R122-R128 once the network is stable.
Where is the official Senva TG series toxic/combustible gas monitor (RS-485 Modbus) Modbus documentation?
The source is TG Modbus Protocol Guide (154-0036-0A), revision 2020-02-07. Senva doesn't publish it on its own website, so this map was re-typed from a free copy at https://www.zotsupply.com/content/PDFs/Senva/Gas%20Monitoring/154-0036-0A.pdf. It may be an older revision, so check it against the live unit.
More Senva Modbus register maps
Other gas detectors register maps
- Sensor (fixed gas detector)
Teledyne Detcon Model PI-700 photoionization (PID) VOC sensor (RS-485 Modbus)
Teledyne Detcon PI-700 smart sensors with the 4-20 mA and RS-485 Modbus outputs, instruction manual Document #3228, Rev. 4.0.
Also known as: PI-700, Detcon PI-700, Teledyne Detcon PI-700 - Sensor (gas transmitter / gas detector)
Analytical Technology (ATI) D12 / F12 gas transmitter (H10, catalytic bead, wet H2S sensors) Modbus interface
ATI D12 and F12 transmitters with the Modbus option fitted to H10 toxic, catalytic bead or wet H2S sensors (Appendix table 4.1). IR-sensor D12s use a different table.
Also known as: D12, F12, D12 gas transmitter, F12 gas transmitter - Sensor (extractive gas detector)
New Cosmos Electric PS-8 series extractive gas detector (Modbus TCP)
New Cosmos PS-8 series pump-type gas detectors for semiconductor plants (up to 16 sensor channels) with Ethernet Modbus TCP, Instruction Manual for Communication GAE-180-00 (December 2024).
Also known as: PS-8, PS-8 series, New Cosmos PS-8 - Sensor (fixed gas detector)
Teledyne Detcon Model FP-700 catalytic bead combustible gas sensor (RS-485 Modbus)
Teledyne Detcon FP-700 smart sensors with the 4-20 mA and RS-485 Modbus outputs, instruction manual Document #3168, Rev. 5.7.
Also known as: FP-700, Detcon FP-700, Teledyne Detcon FP-700 - Sensor (water leak detector)
Teracom TSF400-4 water-leak detector with Modbus RTU
TSF400-4 per the Teracom TSF400-4 user manual Revision R1.2.
Also known as: TSF400-4 - Sensor (extractive gas detector)
Honeywell Midas S2 extractive gas transmitter (Modbus/TCP)
Honeywell Midas S2 single-point extractive gas transmitters with Ethernet/PoE, user manual 3023M5001 Rev A, Modbus/TCP register map (Table 6-1).
Also known as: Midas S2, MIDAS-S2, Midas S2 gas detector
All gas detectors Modbus register maps →
Source: TG Modbus Protocol Guide · 154-0036-0A · rev. 2020-02-07 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.