Easy Modbus
  1. Home
  2. Modbus register maps
  3. Gas detectors

Equipment type

Gas detectors Modbus register maps

Updated 19 November 2026

23 gas detectors register maps from 13 manufacturers: Amphenol, Analytical Technology (ATI), CO2Meter, Danfoss, Gas Detection Australia, Honeywell, New Cosmos Electric, RLE Technologies, Senva, Teledyne Analytical Instruments, Teledyne Detcon, Teledyne Oldham Simtronics, Teracom.

23 of 23 shown

Gas detectors: default communication settings

Factory defaults as the manufacturer documents them. Change one setting at a time on site and write down what you changed. Word order applies to 32-bit values; the addressing column says how the manufacturer prints register numbers (every map on this site also gives the 0-based wire address).

ModelTransportUnit IDSerialWord orderDocumented addressingRegisters
Telaire T3400 series refrigerant (A2L) leak sensorRTU12400 baud, 8N216-bit onlyhex 0-based13
D12 / F12 gas transmitter (H10, catalytic bead, wet H2S sensors) Modbus interfaceRTU19600 baud, 8N1CDABModicon29
CM500 CO2 sensor / controller (RS-485 Modbus RTU)RTU10419200 baud, 8N116-bit onlyhex 0-based13
Gas Detection Units GD Basic / Premium / Heavy Duty (Modbus RTU)RTUNot stated19200 baud, 8E116-bit only0-based88
GDA 4022RTUNot stated9600 baud, 8N116-bit onlyModicon29
Midas gas detector (Modbus/TCP)TCPNot stated-16-bit onlyModicon16
Midas S2 extractive gas transmitter (Modbus/TCP)TCPNot stated-16-bit onlyModicon14
PS-7-M series extractive pump gas detector (Modbus RTU / TCP)RTU/TCPNot stated9600 baud, 8N116-bit onlyModicon30
PS-8 series extractive gas detector (Modbus TCP)TCPNot stated-16-bit onlyModicon117
Falcon F200 environment and leak monitoring appliance (Modbus TCP)TCPNot stated-16-bit onlyModicon71
TG series toxic/combustible gas monitor (RS-485 Modbus)RTU/ASCIINot stated-ABCD0-based79
7500 / 7600 infrared gas analyzer (Modbus RTU)RTUNot stated9600 baud, 8N116-bit onlyModicon43
Model CX-IR infrared combustible gas sensor (Modbus RTU)RTU19600 baud, 8N116-bit only0-based16
Model DM-700 electrochemical toxic gas / oxygen sensor (RS-485 Modbus)RTU19600 baud, 8N116-bit only0-based16
Model FP-624D MicroSafe combustible gas sensor (RS-485 Modbus)RTU19600 baud, 8N116-bit only0-based13
Model FP-700 catalytic bead combustible gas sensor (RS-485 Modbus)RTU19600 baud, 8N116-bit only0-based16
Model IR-700 infrared combustible / CO2 gas sensor (RS-485 Modbus)RTU19600 baud, 8N116-bit only0-based16
Model PI-700 photoionization (PID) VOC sensor (RS-485 Modbus)RTU19600 baud, 8N116-bit only0-based16
Model TP-700 MOS (metal oxide) H2S sensor (RS-485 Modbus)RTU19600 baud, 8N116-bit only0-based15
Model X40 integrated alarm and control system (Modbus slave port)RTUNot stated9600 baud, 8N116-bit only0-based64
OLCT 700 / OLCT 710 FP catalytic bead combustible gas detector (RS-485 Modbus)RTU19600 baud, 8N116-bit only0-based16
OLCT 700 / OLCT 710 IR infrared combustible / CO2 gas detector (RS-485 Modbus)RTU19600 baud, 8N116-bit only0-based16
TSF400-4 water-leak detector with Modbus RTURTU119200 baud, 8E116-bit onlyModicon13