- Model CX-IR infrared combustible gas sensor (Modbus RTU)
Sensor (fixed gas detector) · Modbus register map
Teledyne Detcon Model CX-IR infrared combustible gas sensor (Modbus RTU) Modbus register map
Updated 17 November 2026
The CX-IR is an infrared combustible gas sensor from Teledyne Detcon with a 4-20 mA output and a Modbus RTU RS-485 port. The holding registers give the range, gas reading in %LEL, span level, sensor life, fault bits and calibration control, plus optional smart-battery registers in the 48199-48206 block. This map covers the documented registers except temperature and voltage.
This page lists 16 Modbus registers for the Teledyne Detcon Model CX-IR infrared combustible gas sensor (Modbus RTU) — 5 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Teledyne Detcon’s own free documentation (linked below) and checked against it.
- Manufacturer
- Teledyne Detcon
- Model
- Model CX-IR infrared combustible gas sensor (Modbus RTU)
- Equipment type
- Sensor (fixed gas detector)
- Registers
- 16 (5 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 9600 baud, 8N1
- Documented addressing
- 0-based (the number printed is the address on the wire)
- Also known as
- CX-IR, Detcon CX-IR
Integration notes: Teledyne Detcon Model CX-IR infrared combustible gas sensor (Modbus RTU)
Set a unique Modbus ID (hex) in the magnet menu, wire RS-485 at 9600 8N1 and poll holding registers 0-7 with function 03.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 2 | Gas reading | UINT16 | Gas reading %LEL | Read |
| HR 5 | Sensor faults | BITMAP16 | Fault bits | Read |
| HR 1 | Range | UINT16 | Range | Read/write |
| HR 4 | Sensor life | UINT16 | Sensor life | Read |
| HR 8204 | Status | BITMAP16 | Battery status | Read |
Enable Modbus control & writes
The manual describes no separate enable step; set the ID with Set Modbus ID (01-FF hex, default 01).
Byte order & addressing
- 40000 = wire address 0; the battery block sits at 8199-8206.
- Bump tests do not change the Modbus gas reading.
Network setup
- 9600 baud, 8 data bits, no parity, 1 stop bit.
Watch out for
- Bit 14 of 40005 is set while in calibration mode.
Teledyne Detcon Model CX-IR infrared combustible gas sensor (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 40000 | Device type | Reads 42 for a CX-IR. | UINT16 | Read | 42 = CX-IR | |||
| HR | 1doc 40001 | Range | Detectable range. | UINT16 | %LEL | Read/write | |||
| HR | 2doc 40002 | Gas reading | Current gas reading. | UINT16 | %LEL | Read | |||
| HR | 3doc 40003 | Calibration level | AutoSpan gas level. | UINT16 | %LEL | Read/write | |||
| HR | 4doc 40004 | Sensor life | UINT16 | % | Read | ||||
| HR | 5doc 40005 | Sensor faults | BITMAP16 | Read | bit 0 = Global fault; bit 1 = AutoSpan fault; bit 2 = Temperature fault; bit 5 = Memory fault; bit 6 = Processor fault; bit 7 = Sensor fault; bit 9 = Clearing fault; bit 11 = Range fault; bit 12 = Zero fault; bit 14 = Calibration mode | ||||
| HR | 6doc 40006 | Sensor model | Reads 3 (IR). | UINT16 | Read | ||||
| HR | 7doc 40007 | Days since calibration | UINT16 | days | Read | ||||
| HR | 11doc 40011 | Gas factor | See the gas factor menu in the manual. | UINT16 | Read/write | ||||
| HR | 14doc 40014 | Range divisor | UINT16 | Read | |||||
| HR | 15doc 40015 | Calibration enable/status | UINT16 | Read/write | |||||
| HR | 16doc 40016-40021 | Gas type/units string | ASCII text set at the factory. | STRING[12] | Read | ||||
| HR | 8199doc 48199 | Battery life | Smart battery life remaining, 0-100. | UINT16 | % | Read | |||
| HR | 8200doc 48200 | Battery life in minutes | Caps at 65535 (about 45.5 days). | UINT16 | min | Read | |||
| HR | 8204doc 48204 | Status | Battery detect and battery fault flags. | BITMAP16 | Read | bit 4 = Battery detected; bit 5 = Battery fault | |||
| HR | 8206doc 48206 | Battery read error count | Write 0 to clear. | UINT16 | Read/write |
Notes on this map
- Left out: 40010 sensor temperature (°C, no data type or sign given) and 48205 battery/input voltage (unit volts but no scale given). Reserved registers 40008-40009 and 40012-40013 are skipped.
- The gas reading is listed in %LEL. A range divisor register exists (40014) but the manual does not say how it applies, so no scale is set.
- Calibration enable/status codes are not listed in the CX-IR manual.
- Supported functions: 03, 06 and 16. Writes to read-only registers are acknowledged but ignored.
- Battery registers only work with a Detcon smart battery pack; check bit 4 of 48204 first. Battery status refreshes about every 60 s.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Teledyne Detcon Model CX-IR infrared combustible gas sensor (Modbus RTU)
What Modbus registers does the Teledyne Detcon Model CX-IR infrared combustible gas sensor (Modbus RTU) have?
This map lists 16 registers: 16 holding registers. 5 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Teledyne Detcon Model CX-IR infrared combustible gas sensor (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are printed with a leading 4 starting at 40000 (device type), so 40002 is wire address 2 and 48204 is wire address 8204.
What are the minimum Modbus registers to integrate the Teledyne Detcon Model CX-IR infrared combustible gas sensor (Modbus RTU)?
Start with HR 2 Gas reading (Gas reading %LEL); HR 5 Sensor faults (Fault bits); HR 1 Range (Range); HR 4 Sensor life (Sensor life); HR 8204 Status (Battery status).
How do I enable Modbus control of the Teledyne Detcon Model CX-IR infrared combustible gas sensor (Modbus RTU)?
The manual describes no separate enable step; set the ID with Set Modbus ID (01-FF hex, default 01).
Where is the official Teledyne Detcon Model CX-IR infrared combustible gas sensor (Modbus RTU) Modbus documentation?
The source is CX-IR Instruction Manual (Document #4428, Rev. 1.9), revision 2022-03-14, published free by Teledyne Detcon at https://www.teledynegasandflamedetection.com/en-us/products/docs/areagas-cx-smart-ir-usermanual-english.pdf.
More Teledyne Detcon Modbus register maps
- Sensor (fixed gas detector)
Teledyne Detcon Model DM-700 electrochemical toxic gas / oxygen sensor (RS-485 Modbus)
Teledyne Detcon DM-700 smart sensors with the 4-20 mA and RS-485 Modbus outputs, instruction manual Document #3207, Rev. 5.9.
Also known as: DM-700, Detcon DM-700, Teledyne Detcon DM-700 - Sensor (fixed gas detector)
Teledyne Detcon Model FP-624D MicroSafe combustible gas sensor (RS-485 Modbus)
Teledyne Detcon FP-624D MicroSafe catalytic LEL sensor with 4-20 mA, relays and RS-485 Modbus RTU, instruction manual Document #3598 Rev. 1.7.
Also known as: FP-624D, MicroSafe FP-624D, Detcon FP-624D - Sensor (fixed gas detector)
Teledyne Detcon Model FP-700 catalytic bead combustible gas sensor (RS-485 Modbus)
Teledyne Detcon FP-700 smart sensors with the 4-20 mA and RS-485 Modbus outputs, instruction manual Document #3168, Rev. 5.7.
Also known as: FP-700, Detcon FP-700, Teledyne Detcon FP-700 - Sensor (fixed gas detector)
Teledyne Detcon Model IR-700 infrared combustible / CO2 gas sensor (RS-485 Modbus)
Teledyne Detcon IR-700 smart sensors with the 4-20 mA and RS-485 Modbus outputs, instruction manual Document #3169, Rev. 4.9.
Also known as: IR-700, Detcon IR-700, Teledyne Detcon IR-700 - Sensor (fixed gas detector)
Teledyne Detcon Model PI-700 photoionization (PID) VOC sensor (RS-485 Modbus)
Teledyne Detcon PI-700 smart sensors with the 4-20 mA and RS-485 Modbus outputs, instruction manual Document #3228, Rev. 4.0.
Also known as: PI-700, Detcon PI-700, Teledyne Detcon PI-700 - Sensor (fixed gas detector)
Teledyne Detcon Model TP-700 MOS (metal oxide) H2S sensor (RS-485 Modbus)
Teledyne Detcon TP-700 smart sensors with the 4-20 mA and RS-485 Modbus outputs, instruction manual Document #3150, Rev. 4.6.
Also known as: TP-700, Detcon TP-700, Teledyne Detcon TP-700 - Sensor controller (gas detection)
Teledyne Detcon Model X40 integrated alarm and control system (Modbus slave port)
Teledyne Detcon X40 gas detection controllers (8 and 32 channel, N4X and N1P enclosures), instruction manual Document #3672 Rev. 3.8, slave port register map.
Also known as: X40-08-N4X, X40-32-N4X, X40-32-N1P, X40 controller
Other gas detectors register maps
- Sensor (refrigerant / toxic gas detector)
Danfoss Gas Detection Units GD Basic / Premium / Heavy Duty (Modbus RTU)
Danfoss GD Basic, Premium and Heavy Duty gas detection units on their own RS-485 Modbus port (Part 2 of the guide). The gas detection controller's X-bus map in Part 1 is not included.
Also known as: GDA, GDC, GDHC, GDHF, GDH, GD Basic, GD Premium, GD Heavy Duty - Sensor (gas detector)
Senva TG series toxic/combustible gas monitor (RS-485 Modbus)
Senva TG series RS-485 gas monitors (one or two gas sensors, optional temperature), Modbus Protocol Guide 154-0036-0A (2020-02-07).
Also known as: Senva TG, TG series - Sensor (gas transmitter / gas detector)
Analytical Technology (ATI) D12 / F12 gas transmitter (H10, catalytic bead, wet H2S sensors) Modbus interface
ATI D12 and F12 transmitters with the Modbus option fitted to H10 toxic, catalytic bead or wet H2S sensors (Appendix table 4.1). IR-sensor D12s use a different table.
Also known as: D12, F12, D12 gas transmitter, F12 gas transmitter - Sensor (extractive gas detector)
New Cosmos Electric PS-8 series extractive gas detector (Modbus TCP)
New Cosmos PS-8 series pump-type gas detectors for semiconductor plants (up to 16 sensor channels) with Ethernet Modbus TCP, Instruction Manual for Communication GAE-180-00 (December 2024).
Also known as: PS-8, PS-8 series, New Cosmos PS-8 - Sensor (water leak detector)
Teracom TSF400-4 water-leak detector with Modbus RTU
TSF400-4 per the Teracom TSF400-4 user manual Revision R1.2.
Also known as: TSF400-4 - Sensor (extractive gas detector)
Honeywell Midas S2 extractive gas transmitter (Modbus/TCP)
Honeywell Midas S2 single-point extractive gas transmitters with Ethernet/PoE, user manual 3023M5001 Rev A, Modbus/TCP register map (Table 6-1).
Also known as: Midas S2, MIDAS-S2, Midas S2 gas detector
All gas detectors Modbus register maps →
Source: CX-IR Instruction Manual · Document #4428, Rev. 1.9 · rev. 2022-03-14. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.