Sensor (fixed gas detector) · Modbus register map

Teledyne Detcon Model CX-IR infrared combustible gas sensor (Modbus RTU) Modbus register map

Updated 17 November 2026

Short answer

The CX-IR is an infrared combustible gas sensor from Teledyne Detcon with a 4-20 mA output and a Modbus RTU RS-485 port. The holding registers give the range, gas reading in %LEL, span level, sensor life, fault bits and calibration control, plus optional smart-battery registers in the 48199-48206 block. This map covers the documented registers except temperature and voltage.

This page lists 16 Modbus registers for the Teledyne Detcon Model CX-IR infrared combustible gas sensor (Modbus RTU) — 5 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Teledyne Detcon’s own free documentation (linked below) and checked against it.

Manufacturer
Teledyne Detcon
Model
Model CX-IR infrared combustible gas sensor (Modbus RTU)
Equipment type
Sensor (fixed gas detector)
Registers
16 (5 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
9600 baud, 8N1
Documented addressing
0-based (the number printed is the address on the wire)
Also known as
CX-IR, Detcon CX-IR
Source document
CX-IR Instruction Manual · Document #4428, Rev. 1.9 · rev. 2022-03-14
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Teledyne Detcon Model CX-IR infrared combustible gas sensor (Modbus RTU)

Integration in brief

Set a unique Modbus ID (hex) in the magnet menu, wire RS-485 at 9600 8N1 and poll holding registers 0-7 with function 03.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 2Gas readingUINT16Gas reading %LELRead
HR 5Sensor faultsBITMAP16Fault bitsRead
HR 1RangeUINT16RangeRead/write
HR 4Sensor lifeUINT16Sensor lifeRead
HR 8204StatusBITMAP16Battery statusRead

Enable Modbus control & writes

The manual describes no separate enable step; set the ID with Set Modbus ID (01-FF hex, default 01).

Byte order & addressing

Network setup

Watch out for

Teledyne Detcon Model CX-IR infrared combustible gas sensor (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

16 of 16 shown
Teledyne Detcon Model CX-IR infrared combustible gas sensor (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 40000Device typeReads 42 for a CX-IR.UINT16Read42 = CX-IR
HR1doc 40001RangeDetectable range.UINT16%LELRead/write
HR2doc 40002Gas readingCurrent gas reading.UINT16%LELRead
HR3doc 40003Calibration levelAutoSpan gas level.UINT16%LELRead/write
HR4doc 40004Sensor lifeUINT16%Read
HR5doc 40005Sensor faultsBITMAP16Readbit 0 = Global fault; bit 1 = AutoSpan fault; bit 2 = Temperature fault; bit 5 = Memory fault; bit 6 = Processor fault; bit 7 = Sensor fault; bit 9 = Clearing fault; bit 11 = Range fault; bit 12 = Zero fault; bit 14 = Calibration mode
HR6doc 40006Sensor modelReads 3 (IR).UINT16Read
HR7doc 40007Days since calibrationUINT16daysRead
HR11doc 40011Gas factorSee the gas factor menu in the manual.UINT16Read/write
HR14doc 40014Range divisorUINT16Read
HR15doc 40015Calibration enable/statusUINT16Read/write
HR16doc 40016-40021Gas type/units stringASCII text set at the factory.STRING[12]Read
HR8199doc 48199Battery lifeSmart battery life remaining, 0-100.UINT16%Read
HR8200doc 48200Battery life in minutesCaps at 65535 (about 45.5 days).UINT16minRead
HR8204doc 48204StatusBattery detect and battery fault flags.BITMAP16Readbit 4 = Battery detected; bit 5 = Battery fault
HR8206doc 48206Battery read error countWrite 0 to clear.UINT16Read/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Teledyne Detcon Model CX-IR infrared combustible gas sensor (Modbus RTU)

What Modbus registers does the Teledyne Detcon Model CX-IR infrared combustible gas sensor (Modbus RTU) have?

This map lists 16 registers: 16 holding registers. 5 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Teledyne Detcon Model CX-IR infrared combustible gas sensor (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are printed with a leading 4 starting at 40000 (device type), so 40002 is wire address 2 and 48204 is wire address 8204.

What are the minimum Modbus registers to integrate the Teledyne Detcon Model CX-IR infrared combustible gas sensor (Modbus RTU)?

Start with HR 2 Gas reading (Gas reading %LEL); HR 5 Sensor faults (Fault bits); HR 1 Range (Range); HR 4 Sensor life (Sensor life); HR 8204 Status (Battery status).

How do I enable Modbus control of the Teledyne Detcon Model CX-IR infrared combustible gas sensor (Modbus RTU)?

The manual describes no separate enable step; set the ID with Set Modbus ID (01-FF hex, default 01).

Where is the official Teledyne Detcon Model CX-IR infrared combustible gas sensor (Modbus RTU) Modbus documentation?

The source is CX-IR Instruction Manual (Document #4428, Rev. 1.9), revision 2022-03-14, published free by Teledyne Detcon at https://www.teledynegasandflamedetection.com/en-us/products/docs/areagas-cx-smart-ir-usermanual-english.pdf.

More Teledyne Detcon Modbus register maps

Other gas detectors register maps

All gas detectors Modbus register maps →

Source: CX-IR Instruction Manual · Document #4428, Rev. 1.9 · rev. 2022-03-14. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.