Sensor (refrigerant / toxic gas detector) · Modbus register map

Danfoss Gas Detection Units GD Basic / Premium / Heavy Duty (Modbus RTU) Modbus register map

Updated 17 November 2026

Short answer

Danfoss GD gas detection units (refrigerant, ammonia, CO2 and other gases) answer as Modbus RTU slaves on their RS-485 terminals. This map covers the per-sensor block (gas type, range, divisor, current and average value, error, alarm and relay bits, thresholds) and the operating-data block (production data, maintenance counters, extremes), plus the address-change register.

This page lists 88 Modbus registers for the Danfoss Gas Detection Units GD Basic / Premium / Heavy Duty (Modbus RTU) — 1 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Danfoss’s own free documentation (linked below) and checked against it.

Manufacturer
Danfoss
Model
Gas Detection Units GD Basic / Premium / Heavy Duty (Modbus RTU)
Equipment type
Sensor (refrigerant / toxic gas detector)
Registers
88 (1 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
19200 baud, 8E1
Documented addressing
0-based (the number printed is the address on the wire)
Also known as
GDA, GDC, GDHC, GDHF, GDH, GD Basic, GD Premium, GD Heavy Duty
Source document
Danfoss Gas Detection - Modbus communication (User Guide) · BC283429059843en-000301 · rev. 2020-09
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Danfoss Gas Detection Units GD Basic / Premium / Heavy Duty (Modbus RTU)

Integration in brief

Read the sensor block at 40 (12 registers per sensor, up to 48 in one request) and divide the current value by the divisor register. Alarm and relay states are bit fields in the same block.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 40Gas type, sensor 1UINT16Gas type of sensor 1Read
HR 42Divisor, sensor 1UINT16Divisor needed to scale sensor 1 valuesRead
HR 43Current value, sensor 1INT16Sensor 1 current gas valueRead
HR 45Error, sensor 1UINT16Sensor 1 error wordRead
HR 46Alarm status, sensor 1BITMAP16Sensor 1 alarm 1-4 bitsRead
HR 47Relays and digital inputs (sensor 1 block)BITMAP16Relay and digital input statesRead

Enable Modbus control & writes

The RS-485 Modbus port (Bus A / Bus B terminals) is always a slave at 19200 baud, 8 data bits, even parity, 1 stop bit. The slave address can be changed by writing the new address to register 333 with function 16.

Byte order & addressing

Network setup

Watch out for

Danfoss Gas Detection Units GD Basic / Premium / Heavy Duty (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

88 of 88 shown
Danfoss Gas Detection Units GD Basic / Premium / Heavy Duty (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR40Gas type, sensor 1Gas type code (code table in the guide).UINT16Read
HR41Measuring range, sensor 1Full-scale range as a plain integer.UINT16Read
HR42Divisor, sensor 1Divide values and thresholds of this sensor by this number.UINT16Read
HR43Current value, sensor 1Gas reading x divisor; divide by register 42.INT16Read
HR44Average value, sensor 1Average reading x divisor; divide by register 42.INT16Read
HR45Error, sensor 1Bit-coded error word; codes listed in the guide.UINT16Read
HR46Alarm status, sensor 1BITMAP16Readbit 4 = Alarm 1; bit 5 = Alarm 2; bit 6 = Alarm 3; bit 7 = Alarm 4; bit 12 = Alarm 1 self-hold (latched); bit 13 = Alarm 2 self-hold (latched); bit 14 = Alarm 3 self-hold (latched); bit 15 = Alarm 4 self-hold (latched)
HR47Relays and digital inputs (sensor 1 block)BITMAP16Readbit 0 = Relay 1; bit 1 = Relay 2; bit 2 = Relay 3; bit 3 = Relay 4; bit 4 = Relay 5; bit 8 = Digital input 1; bit 9 = Digital input 2
HR48Alarm threshold 1, sensor 1Threshold x divisor; divide by register 42.UINT16Read
HR49Alarm threshold 2, sensor 1Threshold x divisor; divide by register 42.UINT16Read
HR50Alarm threshold 3, sensor 1Threshold x divisor; divide by register 42.UINT16Read
HR51Alarm threshold 4, sensor 1Threshold x divisor; divide by register 42.UINT16Read
HR52Gas type, sensor 2Gas type code (code table in the guide).UINT16Read
HR53Measuring range, sensor 2Full-scale range as a plain integer.UINT16Read
HR54Divisor, sensor 2Divide values and thresholds of this sensor by this number.UINT16Read
HR55Current value, sensor 2Gas reading x divisor; divide by register 54.INT16Read
HR56Average value, sensor 2Average reading x divisor; divide by register 54.INT16Read
HR57Error, sensor 2Bit-coded error word; codes listed in the guide.UINT16Read
HR58Alarm status, sensor 2BITMAP16Readbit 4 = Alarm 1; bit 5 = Alarm 2; bit 6 = Alarm 3; bit 7 = Alarm 4; bit 12 = Alarm 1 self-hold (latched); bit 13 = Alarm 2 self-hold (latched); bit 14 = Alarm 3 self-hold (latched); bit 15 = Alarm 4 self-hold (latched)
HR59Relays and digital inputs (sensor 2 block)BITMAP16Readbit 0 = Relay 1; bit 1 = Relay 2; bit 2 = Relay 3; bit 3 = Relay 4; bit 4 = Relay 5; bit 8 = Digital input 1; bit 9 = Digital input 2
HR60Alarm threshold 1, sensor 2Threshold x divisor; divide by register 54.UINT16Read
HR61Alarm threshold 2, sensor 2Threshold x divisor; divide by register 54.UINT16Read
HR62Alarm threshold 3, sensor 2Threshold x divisor; divide by register 54.UINT16Read
HR63Alarm threshold 4, sensor 2Threshold x divisor; divide by register 54.UINT16Read
HR64Gas type, sensor 3Gas type code (code table in the guide).UINT16Read
HR65Measuring range, sensor 3Full-scale range as a plain integer.UINT16Read
HR66Divisor, sensor 3Divide values and thresholds of this sensor by this number.UINT16Read
HR67Current value, sensor 3Gas reading x divisor; divide by register 66.INT16Read
HR68Average value, sensor 3Average reading x divisor; divide by register 66.INT16Read
HR69Error, sensor 3Bit-coded error word; codes listed in the guide.UINT16Read
HR70Alarm status, sensor 3BITMAP16Readbit 4 = Alarm 1; bit 5 = Alarm 2; bit 6 = Alarm 3; bit 7 = Alarm 4; bit 12 = Alarm 1 self-hold (latched); bit 13 = Alarm 2 self-hold (latched); bit 14 = Alarm 3 self-hold (latched); bit 15 = Alarm 4 self-hold (latched)
HR71Relays and digital inputs (sensor 3 block)BITMAP16Readbit 0 = Relay 1; bit 1 = Relay 2; bit 2 = Relay 3; bit 3 = Relay 4; bit 4 = Relay 5; bit 8 = Digital input 1; bit 9 = Digital input 2
HR72Alarm threshold 1, sensor 3Threshold x divisor; divide by register 66.UINT16Read
HR73Alarm threshold 2, sensor 3Threshold x divisor; divide by register 66.UINT16Read
HR74Alarm threshold 3, sensor 3Threshold x divisor; divide by register 66.UINT16Read
HR75Alarm threshold 4, sensor 3Threshold x divisor; divide by register 66.UINT16Read
HR200Manufacturing day and month, sensor 1Hex coded: high byte day, low byte month.UINT16Read
HR201Manufacturing year, sensor 1UINT16Read
HR202Serial number, sensor 1UINT16Read
HR203Unit type, sensor 1UINT16Read1 = Sensor head; 2 = Basic / Premium unit; 3 = Gas detection controller
HR204Operating days, sensor 1UINT16daysRead
HR205Days until next maintenance, sensor 1Negative = maintenance overdue.INT16daysRead
HR206Operating days at last calibration, sensor 1UINT16daysRead
HR207Maintenance interval, sensor 1UINT16daysRead
HR208Days left in previous maintenance period, sensor 1UINT16daysRead
HR209Sensor sensitivity, sensor 1100 % = new sensor.UINT16%Read
HR210Calibrations performed, sensor 1UINT16Read
HR211Calibration tool serial number, sensor 1UINT16Read
HR212Calibration tool ID number, sensor 1UINT16Read
HR213Long-term average gas concentration, sensor 1UINT16Read
HR214Highest gas concentration measured, sensor 1INT16Read
HR215Lowest temperature measured, sensor 1INT16Read
HR216Highest temperature measured, sensor 1INT16Read
HR218Manufacturing day and month, sensor 2Hex coded: high byte day, low byte month.UINT16Read
HR219Manufacturing year, sensor 2UINT16Read
HR220Serial number, sensor 2UINT16Read
HR221Unit type, sensor 2UINT16Read1 = Sensor head; 2 = Basic / Premium unit; 3 = Gas detection controller
HR222Operating days, sensor 2UINT16daysRead
HR223Days until next maintenance, sensor 2Negative = maintenance overdue.INT16daysRead
HR224Operating days at last calibration, sensor 2UINT16daysRead
HR225Maintenance interval, sensor 2UINT16daysRead
HR226Days left in previous maintenance period, sensor 2UINT16daysRead
HR227Sensor sensitivity, sensor 2100 % = new sensor.UINT16%Read
HR228Calibrations performed, sensor 2UINT16Read
HR229Calibration tool serial number, sensor 2UINT16Read
HR230Calibration tool ID number, sensor 2UINT16Read
HR231Long-term average gas concentration, sensor 2UINT16Read
HR232Highest gas concentration measured, sensor 2INT16Read
HR233Lowest temperature measured, sensor 2INT16Read
HR234Highest temperature measured, sensor 2INT16Read
HR236Manufacturing day and month, sensor 3Hex coded: high byte day, low byte month.UINT16Read
HR237Manufacturing year, sensor 3UINT16Read
HR238Serial number, sensor 3UINT16Read
HR239Unit type, sensor 3UINT16Read1 = Sensor head; 2 = Basic / Premium unit; 3 = Gas detection controller
HR240Operating days, sensor 3UINT16daysRead
HR241Days until next maintenance, sensor 3Negative = maintenance overdue.INT16daysRead
HR242Operating days at last calibration, sensor 3UINT16daysRead
HR243Maintenance interval, sensor 3UINT16daysRead
HR244Days left in previous maintenance period, sensor 3UINT16daysRead
HR245Sensor sensitivity, sensor 3100 % = new sensor.UINT16%Read
HR246Calibrations performed, sensor 3UINT16Read
HR247Calibration tool serial number, sensor 3UINT16Read
HR248Calibration tool ID number, sensor 3UINT16Read
HR249Long-term average gas concentration, sensor 3UINT16Read
HR250Highest gas concentration measured, sensor 3INT16Read
HR251Lowest temperature measured, sensor 3INT16Read
HR252Highest temperature measured, sensor 3INT16Read
HR333Device address (write to readdress)Write the new slave address with function 16, length 1.UINT16Write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Danfoss Gas Detection Units GD Basic / Premium / Heavy Duty (Modbus RTU)

What Modbus registers does the Danfoss Gas Detection Units GD Basic / Premium / Heavy Duty (Modbus RTU) have?

This map lists 88 registers: 88 holding registers. 1 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Danfoss Gas Detection Units GD Basic / Premium / Heavy Duty (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide gives start addresses as they go in the request: the compact block is read from address 0 (impossible in 1-based numbering), the sensor block from 40 (shown as 28h) and operating data from 200. So register 43 is requested at address 43.

What are the minimum Modbus registers to integrate the Danfoss Gas Detection Units GD Basic / Premium / Heavy Duty (Modbus RTU)?

Start with HR 40 Gas type, sensor 1 (Gas type of sensor 1); HR 42 Divisor, sensor 1 (Divisor needed to scale sensor 1 values); HR 43 Current value, sensor 1 (Sensor 1 current gas value); HR 45 Error, sensor 1 (Sensor 1 error word); HR 46 Alarm status, sensor 1 (Sensor 1 alarm 1-4 bits); HR 47 Relays and digital inputs (sensor 1 block) (Relay and digital input states).

How do I enable Modbus control of the Danfoss Gas Detection Units GD Basic / Premium / Heavy Duty (Modbus RTU)?

The RS-485 Modbus port (Bus A / Bus B terminals) is always a slave at 19200 baud, 8 data bits, even parity, 1 stop bit. The slave address can be changed by writing the new address to register 333 with function 16.

Where is the official Danfoss Gas Detection Units GD Basic / Premium / Heavy Duty (Modbus RTU) Modbus documentation?

The source is Danfoss Gas Detection - Modbus communication (User Guide) (BC283429059843en-000301), revision 2020-09, published free by Danfoss at https://assets.danfoss.com/documents/latest/149624/BC283429059843en-000301.pdf.

More Danfoss Modbus register maps

Other gas detectors register maps

All gas detectors Modbus register maps →

Source: Danfoss Gas Detection - Modbus communication (User Guide) · BC283429059843en-000301 · rev. 2020-09. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.