- Gas Detection Units GD Basic / Premium / Heavy Duty (Modbus RTU)
Sensor (refrigerant / toxic gas detector) · Modbus register map
Danfoss Gas Detection Units GD Basic / Premium / Heavy Duty (Modbus RTU) Modbus register map
Updated 17 November 2026
Danfoss GD gas detection units (refrigerant, ammonia, CO2 and other gases) answer as Modbus RTU slaves on their RS-485 terminals. This map covers the per-sensor block (gas type, range, divisor, current and average value, error, alarm and relay bits, thresholds) and the operating-data block (production data, maintenance counters, extremes), plus the address-change register.
This page lists 88 Modbus registers for the Danfoss Gas Detection Units GD Basic / Premium / Heavy Duty (Modbus RTU) — 1 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Danfoss’s own free documentation (linked below) and checked against it.
- Manufacturer
- Danfoss
- Model
- Gas Detection Units GD Basic / Premium / Heavy Duty (Modbus RTU)
- Equipment type
- Sensor (refrigerant / toxic gas detector)
- Registers
- 88 (1 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 19200 baud, 8E1
- Documented addressing
- 0-based (the number printed is the address on the wire)
- Also known as
- GDA, GDC, GDHC, GDHF, GDH, GD Basic, GD Premium, GD Heavy Duty
Integration notes: Danfoss Gas Detection Units GD Basic / Premium / Heavy Duty (Modbus RTU)
Read the sensor block at 40 (12 registers per sensor, up to 48 in one request) and divide the current value by the divisor register. Alarm and relay states are bit fields in the same block.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 40 | Gas type, sensor 1 | UINT16 | Gas type of sensor 1 | Read |
| HR 42 | Divisor, sensor 1 | UINT16 | Divisor needed to scale sensor 1 values | Read |
| HR 43 | Current value, sensor 1 | INT16 | Sensor 1 current gas value | Read |
| HR 45 | Error, sensor 1 | UINT16 | Sensor 1 error word | Read |
| HR 46 | Alarm status, sensor 1 | BITMAP16 | Sensor 1 alarm 1-4 bits | Read |
| HR 47 | Relays and digital inputs (sensor 1 block) | BITMAP16 | Relay and digital input states | Read |
Enable Modbus control & writes
The RS-485 Modbus port (Bus A / Bus B terminals) is always a slave at 19200 baud, 8 data bits, even parity, 1 stop bit. The slave address can be changed by writing the new address to register 333 with function 16.
Byte order & addressing
- Only function 03 reads are supported; nothing can be written with function 06, and function 16 is accepted only for the address-change register 333.
- The compact block (not listed here) must be read as exactly 10 words starting at address 0.
Network setup
- Poll each unit no faster than every 100 ms; with poll intervals under 550 ms, add at least one pause longer than 550 ms per polling cycle.
Watch out for
- Changing the address with register 333 readdresses every device sharing the old address, so only one device with that address may be on the bus.
Danfoss Gas Detection Units GD Basic / Premium / Heavy Duty (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 40 | Gas type, sensor 1 | Gas type code (code table in the guide). | UINT16 | Read | ||||
| HR | 41 | Measuring range, sensor 1 | Full-scale range as a plain integer. | UINT16 | Read | ||||
| HR | 42 | Divisor, sensor 1 | Divide values and thresholds of this sensor by this number. | UINT16 | Read | ||||
| HR | 43 | Current value, sensor 1 | Gas reading x divisor; divide by register 42. | INT16 | Read | ||||
| HR | 44 | Average value, sensor 1 | Average reading x divisor; divide by register 42. | INT16 | Read | ||||
| HR | 45 | Error, sensor 1 | Bit-coded error word; codes listed in the guide. | UINT16 | Read | ||||
| HR | 46 | Alarm status, sensor 1 | BITMAP16 | Read | bit 4 = Alarm 1; bit 5 = Alarm 2; bit 6 = Alarm 3; bit 7 = Alarm 4; bit 12 = Alarm 1 self-hold (latched); bit 13 = Alarm 2 self-hold (latched); bit 14 = Alarm 3 self-hold (latched); bit 15 = Alarm 4 self-hold (latched) | ||||
| HR | 47 | Relays and digital inputs (sensor 1 block) | BITMAP16 | Read | bit 0 = Relay 1; bit 1 = Relay 2; bit 2 = Relay 3; bit 3 = Relay 4; bit 4 = Relay 5; bit 8 = Digital input 1; bit 9 = Digital input 2 | ||||
| HR | 48 | Alarm threshold 1, sensor 1 | Threshold x divisor; divide by register 42. | UINT16 | Read | ||||
| HR | 49 | Alarm threshold 2, sensor 1 | Threshold x divisor; divide by register 42. | UINT16 | Read | ||||
| HR | 50 | Alarm threshold 3, sensor 1 | Threshold x divisor; divide by register 42. | UINT16 | Read | ||||
| HR | 51 | Alarm threshold 4, sensor 1 | Threshold x divisor; divide by register 42. | UINT16 | Read | ||||
| HR | 52 | Gas type, sensor 2 | Gas type code (code table in the guide). | UINT16 | Read | ||||
| HR | 53 | Measuring range, sensor 2 | Full-scale range as a plain integer. | UINT16 | Read | ||||
| HR | 54 | Divisor, sensor 2 | Divide values and thresholds of this sensor by this number. | UINT16 | Read | ||||
| HR | 55 | Current value, sensor 2 | Gas reading x divisor; divide by register 54. | INT16 | Read | ||||
| HR | 56 | Average value, sensor 2 | Average reading x divisor; divide by register 54. | INT16 | Read | ||||
| HR | 57 | Error, sensor 2 | Bit-coded error word; codes listed in the guide. | UINT16 | Read | ||||
| HR | 58 | Alarm status, sensor 2 | BITMAP16 | Read | bit 4 = Alarm 1; bit 5 = Alarm 2; bit 6 = Alarm 3; bit 7 = Alarm 4; bit 12 = Alarm 1 self-hold (latched); bit 13 = Alarm 2 self-hold (latched); bit 14 = Alarm 3 self-hold (latched); bit 15 = Alarm 4 self-hold (latched) | ||||
| HR | 59 | Relays and digital inputs (sensor 2 block) | BITMAP16 | Read | bit 0 = Relay 1; bit 1 = Relay 2; bit 2 = Relay 3; bit 3 = Relay 4; bit 4 = Relay 5; bit 8 = Digital input 1; bit 9 = Digital input 2 | ||||
| HR | 60 | Alarm threshold 1, sensor 2 | Threshold x divisor; divide by register 54. | UINT16 | Read | ||||
| HR | 61 | Alarm threshold 2, sensor 2 | Threshold x divisor; divide by register 54. | UINT16 | Read | ||||
| HR | 62 | Alarm threshold 3, sensor 2 | Threshold x divisor; divide by register 54. | UINT16 | Read | ||||
| HR | 63 | Alarm threshold 4, sensor 2 | Threshold x divisor; divide by register 54. | UINT16 | Read | ||||
| HR | 64 | Gas type, sensor 3 | Gas type code (code table in the guide). | UINT16 | Read | ||||
| HR | 65 | Measuring range, sensor 3 | Full-scale range as a plain integer. | UINT16 | Read | ||||
| HR | 66 | Divisor, sensor 3 | Divide values and thresholds of this sensor by this number. | UINT16 | Read | ||||
| HR | 67 | Current value, sensor 3 | Gas reading x divisor; divide by register 66. | INT16 | Read | ||||
| HR | 68 | Average value, sensor 3 | Average reading x divisor; divide by register 66. | INT16 | Read | ||||
| HR | 69 | Error, sensor 3 | Bit-coded error word; codes listed in the guide. | UINT16 | Read | ||||
| HR | 70 | Alarm status, sensor 3 | BITMAP16 | Read | bit 4 = Alarm 1; bit 5 = Alarm 2; bit 6 = Alarm 3; bit 7 = Alarm 4; bit 12 = Alarm 1 self-hold (latched); bit 13 = Alarm 2 self-hold (latched); bit 14 = Alarm 3 self-hold (latched); bit 15 = Alarm 4 self-hold (latched) | ||||
| HR | 71 | Relays and digital inputs (sensor 3 block) | BITMAP16 | Read | bit 0 = Relay 1; bit 1 = Relay 2; bit 2 = Relay 3; bit 3 = Relay 4; bit 4 = Relay 5; bit 8 = Digital input 1; bit 9 = Digital input 2 | ||||
| HR | 72 | Alarm threshold 1, sensor 3 | Threshold x divisor; divide by register 66. | UINT16 | Read | ||||
| HR | 73 | Alarm threshold 2, sensor 3 | Threshold x divisor; divide by register 66. | UINT16 | Read | ||||
| HR | 74 | Alarm threshold 3, sensor 3 | Threshold x divisor; divide by register 66. | UINT16 | Read | ||||
| HR | 75 | Alarm threshold 4, sensor 3 | Threshold x divisor; divide by register 66. | UINT16 | Read | ||||
| HR | 200 | Manufacturing day and month, sensor 1 | Hex coded: high byte day, low byte month. | UINT16 | Read | ||||
| HR | 201 | Manufacturing year, sensor 1 | UINT16 | Read | |||||
| HR | 202 | Serial number, sensor 1 | UINT16 | Read | |||||
| HR | 203 | Unit type, sensor 1 | UINT16 | Read | 1 = Sensor head; 2 = Basic / Premium unit; 3 = Gas detection controller | ||||
| HR | 204 | Operating days, sensor 1 | UINT16 | days | Read | ||||
| HR | 205 | Days until next maintenance, sensor 1 | Negative = maintenance overdue. | INT16 | days | Read | |||
| HR | 206 | Operating days at last calibration, sensor 1 | UINT16 | days | Read | ||||
| HR | 207 | Maintenance interval, sensor 1 | UINT16 | days | Read | ||||
| HR | 208 | Days left in previous maintenance period, sensor 1 | UINT16 | days | Read | ||||
| HR | 209 | Sensor sensitivity, sensor 1 | 100 % = new sensor. | UINT16 | % | Read | |||
| HR | 210 | Calibrations performed, sensor 1 | UINT16 | Read | |||||
| HR | 211 | Calibration tool serial number, sensor 1 | UINT16 | Read | |||||
| HR | 212 | Calibration tool ID number, sensor 1 | UINT16 | Read | |||||
| HR | 213 | Long-term average gas concentration, sensor 1 | UINT16 | Read | |||||
| HR | 214 | Highest gas concentration measured, sensor 1 | INT16 | Read | |||||
| HR | 215 | Lowest temperature measured, sensor 1 | INT16 | Read | |||||
| HR | 216 | Highest temperature measured, sensor 1 | INT16 | Read | |||||
| HR | 218 | Manufacturing day and month, sensor 2 | Hex coded: high byte day, low byte month. | UINT16 | Read | ||||
| HR | 219 | Manufacturing year, sensor 2 | UINT16 | Read | |||||
| HR | 220 | Serial number, sensor 2 | UINT16 | Read | |||||
| HR | 221 | Unit type, sensor 2 | UINT16 | Read | 1 = Sensor head; 2 = Basic / Premium unit; 3 = Gas detection controller | ||||
| HR | 222 | Operating days, sensor 2 | UINT16 | days | Read | ||||
| HR | 223 | Days until next maintenance, sensor 2 | Negative = maintenance overdue. | INT16 | days | Read | |||
| HR | 224 | Operating days at last calibration, sensor 2 | UINT16 | days | Read | ||||
| HR | 225 | Maintenance interval, sensor 2 | UINT16 | days | Read | ||||
| HR | 226 | Days left in previous maintenance period, sensor 2 | UINT16 | days | Read | ||||
| HR | 227 | Sensor sensitivity, sensor 2 | 100 % = new sensor. | UINT16 | % | Read | |||
| HR | 228 | Calibrations performed, sensor 2 | UINT16 | Read | |||||
| HR | 229 | Calibration tool serial number, sensor 2 | UINT16 | Read | |||||
| HR | 230 | Calibration tool ID number, sensor 2 | UINT16 | Read | |||||
| HR | 231 | Long-term average gas concentration, sensor 2 | UINT16 | Read | |||||
| HR | 232 | Highest gas concentration measured, sensor 2 | INT16 | Read | |||||
| HR | 233 | Lowest temperature measured, sensor 2 | INT16 | Read | |||||
| HR | 234 | Highest temperature measured, sensor 2 | INT16 | Read | |||||
| HR | 236 | Manufacturing day and month, sensor 3 | Hex coded: high byte day, low byte month. | UINT16 | Read | ||||
| HR | 237 | Manufacturing year, sensor 3 | UINT16 | Read | |||||
| HR | 238 | Serial number, sensor 3 | UINT16 | Read | |||||
| HR | 239 | Unit type, sensor 3 | UINT16 | Read | 1 = Sensor head; 2 = Basic / Premium unit; 3 = Gas detection controller | ||||
| HR | 240 | Operating days, sensor 3 | UINT16 | days | Read | ||||
| HR | 241 | Days until next maintenance, sensor 3 | Negative = maintenance overdue. | INT16 | days | Read | |||
| HR | 242 | Operating days at last calibration, sensor 3 | UINT16 | days | Read | ||||
| HR | 243 | Maintenance interval, sensor 3 | UINT16 | days | Read | ||||
| HR | 244 | Days left in previous maintenance period, sensor 3 | UINT16 | days | Read | ||||
| HR | 245 | Sensor sensitivity, sensor 3 | 100 % = new sensor. | UINT16 | % | Read | |||
| HR | 246 | Calibrations performed, sensor 3 | UINT16 | Read | |||||
| HR | 247 | Calibration tool serial number, sensor 3 | UINT16 | Read | |||||
| HR | 248 | Calibration tool ID number, sensor 3 | UINT16 | Read | |||||
| HR | 249 | Long-term average gas concentration, sensor 3 | UINT16 | Read | |||||
| HR | 250 | Highest gas concentration measured, sensor 3 | INT16 | Read | |||||
| HR | 251 | Lowest temperature measured, sensor 3 | INT16 | Read | |||||
| HR | 252 | Highest temperature measured, sensor 3 | INT16 | Read | |||||
| HR | 333 | Device address (write to readdress) | Write the new slave address with function 16, length 1. | UINT16 | Write |
Notes on this map
- Gas values are scaled per sensor: the divisor register (42/54/66) says what to divide the current value, average value and thresholds by (e.g. divisor 10 -> 1301 = 130.1). It depends on the measuring range, so it is read rather than fixed; scale is left at 1 here.
- The guide also offers a compact block: exactly 10 words read from address 0 (current and average value of sensors 1-3, then type + range words and a temperature word). It is left out because the guide does not say whether those words are signed or how the type, range and temperature words are encoded. Its gas values use a dynamic resolution: range under 10 -> value x 1000, 10-99 -> x 100, 100-999 -> x 10, 1000 and up -> x 1.
- On Heavy Duty units only sensor 1 is populated; the other sensor slots read 0. The sensor 2 operating-data block (218-235) is for Premium units; the guide also lists a third block (236-253), included here for completeness.
- The units of the gas reading follow the gas type code (ppm, %LEL, %Vol, °C, %rH, mbar...); the code table in the guide is printed in a layout that does not line codes up with gases reliably, so it is not transcribed.
- Error words are bit coded and can combine, e.g. 0x8001 sensor element error, 0x8002 ADC error, 0x8004 supply voltage, 0x8040 over-temperature, 0x8100 under-range, 0x8200 over-range, 0x0080 maintenance due.
- Units of the operating-data concentration and temperature extremes are not stated in the guide.
- Part 1 of the same guide (the Gas Detection Controller's X-bus map with blocks 1001-1096, 2001-2032 etc.) is a different device and is not in this file.
- Each sensor block can also be read as registers 40-51 from the next slave address up (unit address + 1 for sensor 2, + 2 for sensor 3); this map uses the single-address layout 40-75.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Danfoss Gas Detection Units GD Basic / Premium / Heavy Duty (Modbus RTU)
What Modbus registers does the Danfoss Gas Detection Units GD Basic / Premium / Heavy Duty (Modbus RTU) have?
This map lists 88 registers: 88 holding registers. 1 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Danfoss Gas Detection Units GD Basic / Premium / Heavy Duty (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide gives start addresses as they go in the request: the compact block is read from address 0 (impossible in 1-based numbering), the sensor block from 40 (shown as 28h) and operating data from 200. So register 43 is requested at address 43.
What are the minimum Modbus registers to integrate the Danfoss Gas Detection Units GD Basic / Premium / Heavy Duty (Modbus RTU)?
Start with HR 40 Gas type, sensor 1 (Gas type of sensor 1); HR 42 Divisor, sensor 1 (Divisor needed to scale sensor 1 values); HR 43 Current value, sensor 1 (Sensor 1 current gas value); HR 45 Error, sensor 1 (Sensor 1 error word); HR 46 Alarm status, sensor 1 (Sensor 1 alarm 1-4 bits); HR 47 Relays and digital inputs (sensor 1 block) (Relay and digital input states).
How do I enable Modbus control of the Danfoss Gas Detection Units GD Basic / Premium / Heavy Duty (Modbus RTU)?
The RS-485 Modbus port (Bus A / Bus B terminals) is always a slave at 19200 baud, 8 data bits, even parity, 1 stop bit. The slave address can be changed by writing the new address to register 333 with function 16.
Where is the official Danfoss Gas Detection Units GD Basic / Premium / Heavy Duty (Modbus RTU) Modbus documentation?
The source is Danfoss Gas Detection - Modbus communication (User Guide) (BC283429059843en-000301), revision 2020-09, published free by Danfoss at https://assets.danfoss.com/documents/latest/149624/BC283429059843en-000301.pdf.
More Danfoss Modbus register maps
- Thermostat / heating controller (district heating and HVAC)
Danfoss ECL Comfort 210 / 296 / 310 heating controller (Modbus RTU / TCP)
ECL Comfort 210, 296 and 310 controllers (and B versions) with any application key; many parameters depend on the loaded application.
Also known as: ECL Comfort 210, ECL Comfort 296, ECL Comfort 310, ECL Comfort 210B, ECL Comfort 310B, 087H3020, 087H3024, 087H3030, 087H3034, 087H3040, 087H3044, 087H3050, 087H3054 - Variable frequency drive
Danfoss iC2-Micro frequency converter (Modbus RTU)
Danfoss iC2-Micro frequency converters using the built-in RS-485 port with P 10.1.1 Protocol = [2] Modbus RTU and the FC control profile; Application Guide AB413939445838en-000401.
Also known as: iC2-Micro, iC2 Micro, Danfoss iC2 - Sensor / controller (CO2 condensing unit gateway)
Danfoss Optyma iCO2 gateway (OP-MPAM015 / OP-MPAM005)
Danfoss Optyma iCO2 CO2 condensing units (4.6 kW MT and 20 kW MT / 10 kW LT) through their Modbus gateway, software 1.0x.
Also known as: OP-MPAM015, OP-MPAM005, Optyma iCO2 4.6 kW MT, Optyma iCO2 20 kW MT / 10 kW LT - Variable frequency drive
Danfoss VLT AQUA Drive FC 202 (Modbus RTU)
VLT AQUA Drive FC 202 using the built-in RS-485 (FC) port with 8-30 Protocol = Modbus RTU and the FC control profile; parameter data checked against the software 5.4X programming guide.
Also known as: VLT AQUA Drive, FC202, FC-202, AQUA Drive FC 202 - Variable frequency drive
Danfoss VLT AutomationDrive FC 301/302 (Modbus RTU)
VLT AutomationDrive FC 301 and FC 302 (0.25-75 kW design guide; same scheme across sizes) using the built-in RS-485 (FC) port with 8-30 Protocol = Modbus RTU and the FC control profile; parameter data checked against the software 9.5x / 48.96 programming guide.
Also known as: VLT AutomationDrive, FC 301, FC301, FC302, FC-302, FC-301, FC 300 - Variable frequency drive
Danfoss VLT AutomationDrive FC 360 (Modbus RTU)
VLT AutomationDrive FC 360 on its built-in RS-485 port with 8-30 Protocol = Modbus RTU and the FC control profile.
Also known as: FC360, FC-360, VLT AutomationDrive FC 360 - Variable frequency drive
Danfoss VLT Compressor Drive CDS 803 (Modbus RTU)
VLT Compressor Drive CDS 803 (variable-speed compressor drive for HVAC/R) using the built-in RS-485 port with 8-30 Protocol = Modbus RTU; Modbus rules from Design Guide MG18N202 (software 1.20), parameter data from Programming Guide MG18P202 (software 2.0).
Also known as: CDS803, CDS-803, VLT Compressor Drive CDS 803 - Variable frequency drive (HVAC fans and pumps)
Danfoss VLT HVAC Basic Drive FC 101 (Modbus RTU)
VLT HVAC Basic Drive FC 101 on its built-in RS-485 port with 8-30 Protocol = Modbus RTU and the FC control profile.
Also known as: FC101, FC-101, VLT HVAC Basic Drive FC 101, VLT HVAC Basic - Variable frequency drive
Danfoss VLT HVAC Drive FC 102 (Modbus RTU)
VLT HVAC Drive FC 102 using the built-in RS-485 (FC) port with 8-30 Protocol = Modbus RTU and the FC control profile; parameter scaling checked against the software 7.61 programming guide.
Also known as: VLT HVAC Drive, FC102, FC-102 - Variable frequency drive
Danfoss VLT Micro Drive FC 51 (Modbus RTU)
VLT Micro Drive FC 51 on the built-in RS-485 port with 8-30 = Modbus, software 3.1x; registers per design guide MG02K402 and parameter data per programming guide MG02C702.
Also known as: FC 51, FC51, VLT Micro Drive, VLT Micro Drive FC 51 - Variable frequency drive
Danfoss VLT Midi Drive FC 280 (Modbus RTU)
VLT Midi Drive FC 280 on its built-in RS-485 port with 8-30 Protocol = Modbus RTU and the FC control profile.
Also known as: FC280, FC-280, VLT Midi Drive FC 280, VLT Midi Drive
Other gas detectors register maps
- Sensor (gas detector)
Senva TG series toxic/combustible gas monitor (RS-485 Modbus)
Senva TG series RS-485 gas monitors (one or two gas sensors, optional temperature), Modbus Protocol Guide 154-0036-0A (2020-02-07).
Also known as: Senva TG, TG series - Sensor (fixed gas detector)
Teledyne Detcon Model PI-700 photoionization (PID) VOC sensor (RS-485 Modbus)
Teledyne Detcon PI-700 smart sensors with the 4-20 mA and RS-485 Modbus outputs, instruction manual Document #3228, Rev. 4.0.
Also known as: PI-700, Detcon PI-700, Teledyne Detcon PI-700 - Sensor (gas transmitter / gas detector)
Analytical Technology (ATI) D12 / F12 gas transmitter (H10, catalytic bead, wet H2S sensors) Modbus interface
ATI D12 and F12 transmitters with the Modbus option fitted to H10 toxic, catalytic bead or wet H2S sensors (Appendix table 4.1). IR-sensor D12s use a different table.
Also known as: D12, F12, D12 gas transmitter, F12 gas transmitter - Sensor (extractive gas detector)
New Cosmos Electric PS-8 series extractive gas detector (Modbus TCP)
New Cosmos PS-8 series pump-type gas detectors for semiconductor plants (up to 16 sensor channels) with Ethernet Modbus TCP, Instruction Manual for Communication GAE-180-00 (December 2024).
Also known as: PS-8, PS-8 series, New Cosmos PS-8 - Sensor (fixed gas detector)
Teledyne Detcon Model FP-700 catalytic bead combustible gas sensor (RS-485 Modbus)
Teledyne Detcon FP-700 smart sensors with the 4-20 mA and RS-485 Modbus outputs, instruction manual Document #3168, Rev. 5.7.
Also known as: FP-700, Detcon FP-700, Teledyne Detcon FP-700 - Sensor (water leak detector)
Teracom TSF400-4 water-leak detector with Modbus RTU
TSF400-4 per the Teracom TSF400-4 user manual Revision R1.2.
Also known as: TSF400-4
All gas detectors Modbus register maps →
Source: Danfoss Gas Detection - Modbus communication (User Guide) · BC283429059843en-000301 · rev. 2020-09. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.