- VLT HVAC Basic Drive FC 101 (Modbus RTU)
Variable frequency drive (HVAC fans and pumps) · Modbus register map
Danfoss VLT HVAC Basic Drive FC 101 (Modbus RTU) Modbus register map
Updated 17 November 2026
The FC 101 is Danfoss's basic HVAC drive for fans and pumps with a built-in RS-485 port that can run Modbus RTU. Control and status words are exchanged as coils (control bits 1-16, status bits 33-48), and every drive parameter is a holding register at ten times its parameter number. This map lists the control/status coils, the communication parameters, the main readouts and the alarm/warning words.
This page lists 86 Modbus registers for the Danfoss VLT HVAC Basic Drive FC 101 (Modbus RTU) — 30 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Danfoss’s own free documentation (linked below) and checked against it.
- Manufacturer
- Danfoss
- Model
- VLT HVAC Basic Drive FC 101 (Modbus RTU)
- Equipment type
- Variable frequency drive (HVAC fans and pumps)
- Registers
- 86 (30 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 19200 baud
- Documented addressing
- derived from parameter numbers
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- FC101, FC-101, VLT HVAC Basic Drive FC 101, VLT HVAC Basic
Integration notes: Danfoss VLT HVAC Basic Drive FC 101 (Modbus RTU)
Set 8-30 = Modbus RTU and the port settings, make sure 8-02 is FC port, then write the 16 control bits (coils 1-16) and the reference (coils 17-32) with function 15 and read status coils 33-48. Read readouts from the 16-xx registers at parameter number x 10, minus 1 on the wire.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| CO 6 | CTW bit 6 (coil 7) | BIT | CTW bit 6: start / ramp stop | Read/write |
| CO 10 | CTW bit 10 (coil 11) | BIT | CTW bit 10: data valid | Read/write |
| CO 43 | STW bit 11 (coil 44) | BIT | Running | Read |
| CO 35 | STW bit 3 (coil 36) | BIT | Alarm | Read |
| HR 16129 | 16-13 Frequency | UINT32 ABCD | 16-13 Frequency | Read |
| HR 16139 | 16-14 Motor current | UINT16 | 16-14 Motor current | Read |
| HR 16899 | 16-90 Alarm word | UINT32 ABCD | 16-90 Alarm word | Read |
Enable Modbus control & writes
8-30 Protocol = [2] Modbus RTU, 8-31 Address 1-247, 8-32 Baud Rate (2400-115200; 19200 is the Modbus RTU default), 8-33 Parity/Stop Bits. 8-02 Control Source must be [1] FC port (the default) and 8-01 Control Site decides whether digital inputs, the control word or both are used.
Communication loss & watchdog
8-03 Control Timeout Time (0.1-6500 s) and 8-04 Control Timeout Function (default Off; Freeze output, Stop, Jogging, Max. speed, Stop and trip, N2 override release) act when the control word stops being updated.
Byte order & addressing
- Control word bit 10 (coil 11) must be 1 or the drive ignores the control word.
- Parameter writes go to RAM only unless coil 65 is 1.
Network setup
- 8-35 Minimum Response Delay can be raised for slow masters or converters.
- Array parameters need the index written to holding register 9 first.
Watch out for
- Register numbers in the manual are 1-based; subtract 1 in the request.
Danfoss VLT HVAC Basic Drive FC 101 (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 0doc 1 | CTW bit 0 (coil 1) | Preset reference LSB. | BIT | Read/write | ||||
| CO | 1doc 2 | CTW bit 1 (coil 2) | Preset reference MSB. | BIT | Read/write | ||||
| CO | 2doc 3 | CTW bit 2 (coil 3) | 0 = DC brake, 1 = no DC brake. | BIT | Read/write | ||||
| CO | 3doc 4 | CTW bit 3 (coil 4) | 0 = coast stop, 1 = no coast stop. | BIT | Read/write | ||||
| CO | 4doc 5 | CTW bit 4 (coil 5) | 0 = quick stop, 1 = no quick stop. | BIT | Read/write | ||||
| CO | 5doc 6 | CTW bit 5 (coil 6) | 0 = freeze frequency, 1 = no freeze. | BIT | Read/write | ||||
| CO | 6doc 7 | CTW bit 6 (coil 7) | 0 = ramp stop, 1 = start. | BIT | Read/write | ||||
| CO | 7doc 8 | CTW bit 7 (coil 8) | 1 = reset. | BIT | Read/write | ||||
| CO | 8doc 9 | CTW bit 8 (coil 9) | 1 = jog. | BIT | Read/write | ||||
| CO | 9doc 10 | CTW bit 9 (coil 10) | 0 = ramp 1, 1 = ramp 2. | BIT | Read/write | ||||
| CO | 10doc 11 | CTW bit 10 (coil 11) | 1 = data valid. | BIT | Read/write | ||||
| CO | 11doc 12 | CTW bit 11 (coil 12) | 1 = relay 1 on. | BIT | Read/write | ||||
| CO | 12doc 13 | CTW bit 12 (coil 13) | 1 = relay 2 on. | BIT | Read/write | ||||
| CO | 13doc 14 | CTW bit 13 (coil 14) | Set-up select LSB. | BIT | Read/write | ||||
| CO | 15doc 16 | CTW bit 15 (coil 16) | 1 = reversing. | BIT | Read/write | ||||
| CO | 32doc 33 | STW bit 0 (coil 33) | 1 = control ready. | BIT | Read | ||||
| CO | 33doc 34 | STW bit 1 (coil 34) | 1 = drive ready. | BIT | Read | ||||
| CO | 34doc 35 | STW bit 2 (coil 35) | 0 = coasting stop, 1 = safety closed. | BIT | Read | ||||
| CO | 35doc 36 | STW bit 3 (coil 36) | 1 = alarm. | BIT | Read | ||||
| CO | 39doc 40 | STW bit 7 (coil 40) | 1 = warning. | BIT | Read | ||||
| CO | 40doc 41 | STW bit 8 (coil 41) | 1 = at reference. | BIT | Read | ||||
| CO | 41doc 42 | STW bit 9 (coil 42) | 0 = hand mode, 1 = auto mode. | BIT | Read | ||||
| CO | 42doc 43 | STW bit 10 (coil 43) | 1 = in frequency range. | BIT | Read | ||||
| CO | 43doc 44 | STW bit 11 (coil 44) | 0 = stopped, 1 = running. | BIT | Read | ||||
| CO | 45doc 46 | STW bit 13 (coil 46) | 1 = voltage warning. | BIT | Read | ||||
| CO | 46doc 47 | STW bit 14 (coil 47) | 1 = current limit. | BIT | Read | ||||
| CO | 47doc 48 | STW bit 15 (coil 48) | 1 = thermal warning. | BIT | Read | ||||
| CO | 64doc 65 | Parameter write control | 0 = writes go to RAM, 1 = RAM and EEPROM. | BIT | Read/write | ||||
| HR | 6doc 7 | Last error code | Error from the parameter database. | UINT16 | Read | ||||
| HR | 7doc 8 | Last error register | Register where the last error happened. | UINT16 | Read | ||||
| HR | 8doc 9 | Index pointer (IND) | Sub-index for array parameters. | UINT16 | Read/write | ||||
| HR | 3019doc 3020 | 3-02 Minimum Reference | INT32 | ABCD | × 0.001 | Read/write | |||
| HR | 3029doc 3030 | 3-03 Maximum Reference | INT32 | ABCD | × 0.001 | Read/write | |||
| HR | 3409doc 3410 | 3-41 Ramp 1 Ramp Up Time | UINT32 | ABCD | × 0.01 | s | Read/write | ||
| HR | 3419doc 3420 | 3-42 Ramp 1 Ramp Down Time | UINT32 | ABCD | × 0.01 | s | Read/write | ||
| HR | 8009doc 8010 | 8-01 Control Site | UINT16 | Read/write | 0 = Digital and ctrl. word; 1 = Digital only; 2 = Control word only | ||||
| HR | 8019doc 8020 | 8-02 Control Source | UINT16 | Read/write | 0 = None; 1 = FC port | ||||
| HR | 8029doc 8030 | 8-03 Control Timeout Time | 0.1-6500 s. | UINT16 | × 0.1 | s | Read/write | ||
| HR | 8039doc 8040 | 8-04 Control Timeout Function | UINT16 | Read/write | 0 = Off; 1 = Freeze output; 2 = Stop; 3 = Jogging; 4 = Max. speed; 5 = Stop and trip; 20 = N2 override release | ||||
| HR | 8299doc 8300 | 8-30 Protocol | UINT16 | Read/write | 0 = FC; 2 = Modbus RTU; 3 = Metasys N2; 4 = FLN; 5 = BACnet | ||||
| HR | 8309doc 8310 | 8-31 Address | 1-247 for Modbus. | UINT16 | Read/write | ||||
| HR | 8319doc 8320 | 8-32 Baud Rate | UINT16 | Read/write | 0 = 2400; 1 = 4800; 2 = 9600; 3 = 19200; 4 = 38400; 5 = 57600; 6 = 76800; 7 = 115200 | ||||
| HR | 8329doc 8330 | 8-33 Parity / Stop Bits | UINT16 | Read/write | 0 = Even parity, 1 stop bit; 1 = Odd parity, 1 stop bit; 2 = No parity, 1 stop bit; 3 = No parity, 2 stop bits | ||||
| HR | 8349doc 8350 | 8-35 Minimum Response Delay | UINT16 | × 0.001 | s | Read/write | |||
| HR | 14999doc 15000 | 15-00 Operating hours | UINT32 | ABCD | h | Read | |||
| HR | 15009doc 15010 | 15-01 Running hours | UINT32 | ABCD | h | Read | |||
| HR | 15019doc 15020 | 15-02 kWh counter | UINT32 | ABCD | kWh | Read | |||
| HR | 15029doc 15030 | 15-03 Power up's | UINT32 | ABCD | Read | ||||
| HR | 15039doc 15040 | 15-04 Over temp's | UINT16 | Read | |||||
| HR | 15049doc 15050 | 15-05 Over volt's | UINT16 | Read | |||||
| HR | 15999doc 16000 | 16-00 Control word | Control word as received. | UINT16 | Read | ||||
| HR | 16009doc 16010 | 16-01 Reference [unit] | INT32 | ABCD | × 0.001 | Read | |||
| HR | 16019doc 16020 | 16-02 Reference [%] | INT16 | × 0.1 | % | Read | |||
| HR | 16029doc 16030 | 16-03 Status word | Same bits as status coils 33-48. | UINT16 | Read | ||||
| HR | 16099doc 16100 | 16-10 Power [kW] | UINT32 | ABCD | × 0.001 | kW | Read | ||
| HR | 16109doc 16110 | 16-11 Power [hp] | UINT32 | ABCD | × 0.001 | hp | Read | ||
| HR | 16119doc 16120 | 16-12 Motor voltage | UINT32 | ABCD | × 0.1 | V | Read | ||
| HR | 16129doc 16130 | 16-13 Frequency | UINT32 | ABCD | × 0.1 | Hz | Read | ||
| HR | 16139doc 16140 | 16-14 Motor current | UINT16 | × 0.01 | A | Read | |||
| HR | 16149doc 16150 | 16-15 Frequency [%] | UINT16 | × 0.1 | % | Read | |||
| HR | 16159doc 16160 | 16-16 Torque [Nm] | INT32 | ABCD | Nm | Read | |||
| HR | 16169doc 16170 | 16-17 Speed [RPM] | INT32 | ABCD | RPM | Read | |||
| HR | 16179doc 16180 | 16-18 Motor thermal | UINT16 | % | Read | ||||
| HR | 16219doc 16220 | 16-22 Torque [%] | INT16 | % | Read | ||||
| HR | 16299doc 16300 | 16-30 DC link voltage | UINT32 | ABCD | V | Read | |||
| HR | 16339doc 16340 | 16-34 Heatsink temperature | Int8 in the list, carried in one register. | INT16 | °C | Read | |||
| HR | 16349doc 16350 | 16-35 Inverter thermal | UINT16 | % | Read | ||||
| HR | 16359doc 16360 | 16-36 Inverter nominal current | UINT16 | × 0.01 | A | Read | |||
| HR | 16369doc 16370 | 16-37 Inverter maximum current | UINT16 | × 0.01 | A | Read | |||
| HR | 16499doc 16500 | 16-50 External reference | INT16 | × 0.1 | % | Read | |||
| HR | 16519doc 16520 | 16-52 Feedback [Unit] | INT32 | ABCD | × 0.001 | Read | |||
| HR | 16539doc 16540 | 16-54 Feedback 1 [Unit] | INT32 | ABCD | × 0.001 | Read | |||
| HR | 16549doc 16550 | 16-55 Feedback 2 [Unit] | INT32 | ABCD | × 0.001 | Read | |||
| HR | 16599doc 16600 | 16-60 Digital input | UINT16 | Read | |||||
| HR | 16649doc 16650 | 16-65 Analog output AO42 [mA] | UINT16 | × 0.01 | mA | Read | |||
| HR | 16709doc 16710 | 16-71 Relay output [bin] | UINT16 | Read | |||||
| HR | 16719doc 16720 | 16-72 Counter A | INT16 | Read | |||||
| HR | 16729doc 16730 | 16-73 Counter B | INT16 | Read | |||||
| HR | 16789doc 16790 | 16-79 Analog output AO45 | UINT16 | × 0.01 | mA | Read | |||
| HR | 16859doc 16860 | 16-86 FC port REF 1 | Reference received on the FC port; 4000h = 100 %. | INT16 | Read | ||||
| HR | 16899doc 16900 | 16-90 Alarm word | Bit meanings in the programming guide. | UINT32 | ABCD | Read | |||
| HR | 16909doc 16910 | 16-91 Alarm word 2 | Bit meanings in the programming guide. | UINT32 | ABCD | Read | |||
| HR | 16919doc 16920 | 16-92 Warning word | Bit meanings in the programming guide. | UINT32 | ABCD | Read | |||
| HR | 16929doc 16930 | 16-93 Warning word 2 | Bit meanings in the programming guide. | UINT32 | ABCD | Read | |||
| HR | 16939doc 16940 | 16-94 External status word | Bit meanings in the programming guide. | UINT32 | ABCD | Read | |||
| HR | 16949doc 16950 | 16-95 External status word 2 | Bit meanings in the programming guide. | UINT32 | ABCD | Read |
Notes on this map
- 32-bit values are high word first: the design guide's example reads 3-03 at registers 3030/3031 and gets 0x0016 0xE360, and its preset-multiple example writes 1-24 = 738 (7.38 A) as 0x0000 0x02E2.
- Scale comes from each parameter's conversion index in the programming guide (-1 = x0.1, -2 = x0.01, -3 = x0.001, 0 = x1). Indices 74, 75 and 100 have factors 3600, 3600000 and 1 relative to SI units, so 15-00/15-01 arrive in hours, 15-02 in kWh and 16-34 in °C (scale 1).
- The design guide's read example prints the start address bytes as 0B 05 while naming register address 3029 (0x0BD5); 0x0BD5 is what the x10 rule gives.
- Left out: 16-05 Main Actual Value [%] (normalised N2), 16-09 Custom Readout, 16-62/16-64 analog inputs (unit not given), 16-66 Digital Output (text), 16-67 pulse input, text and array parameters. The FC 101 parameter list has no 8-10 Control Word Profile; the FC profile is used.
- The design guide for this drive lists no 50000/50200 control registers; bus control uses coils 1-16 (control word), 17-32 (16-bit speed reference, 4000h = 100 %, negative in two's complement), 33-48 (status word) and 49-64 (output frequency, or feedback in closed loop).
- Uint8 parameters are read and written as one 16-bit register.
- Bit-by-bit coil names follow the FC profile tables; coil 15 has no function and STW coils 37-39 and 45 are unused.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Danfoss VLT HVAC Basic Drive FC 101 (Modbus RTU)
What Modbus registers does the Danfoss VLT HVAC Basic Drive FC 101 (Modbus RTU) have?
This map lists 86 registers: 28 coils, 58 holding registers. 30 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Danfoss VLT HVAC Basic Drive FC 101 (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers derived from parameter numbers. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Coils and registers are numbered from 1 and sent minus 1 (coil 65 = address 64, register 40001 = address 0). A parameter's register is 10 x its parameter number (16-13 -> 16130) and the request uses that minus 1; the design guide reads 3-03 (register 3030) at register address 3029.
What byte order does the Danfoss VLT HVAC Basic Drive FC 101 (Modbus RTU) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Danfoss VLT HVAC Basic Drive FC 101 (Modbus RTU)?
Start with CO 6 CTW bit 6 (coil 7) (CTW bit 6: start / ramp stop); CO 10 CTW bit 10 (coil 11) (CTW bit 10: data valid); CO 43 STW bit 11 (coil 44) (Running); CO 35 STW bit 3 (coil 36) (Alarm); HR 16129 16-13 Frequency (16-13 Frequency); HR 16139 16-14 Motor current (16-14 Motor current); HR 16899 16-90 Alarm word (16-90 Alarm word).
How do I enable Modbus control of the Danfoss VLT HVAC Basic Drive FC 101 (Modbus RTU)?
8-30 Protocol = [2] Modbus RTU, 8-31 Address 1-247, 8-32 Baud Rate (2400-115200; 19200 is the Modbus RTU default), 8-33 Parity/Stop Bits. 8-02 Control Source must be [1] FC port (the default) and 8-01 Control Site decides whether digital inputs, the control word or both are used.
What happens when the Danfoss VLT HVAC Basic Drive FC 101 (Modbus RTU) loses Modbus communication?
8-03 Control Timeout Time (0.1-6500 s) and 8-04 Control Timeout Function (default Off; Freeze output, Stop, Jogging, Max. speed, Stop and trip, N2 override release) act when the control word stops being updated.
Where is the official Danfoss VLT HVAC Basic Drive FC 101 (Modbus RTU) Modbus documentation?
The source is VLT HVAC Basic Drive FC 101 Design Guide (chapter 7 RS-485 Installation and Set-up, Modbus RTU) (MG18C502), revision 2013-09-06, published free by Danfoss at https://files.danfoss.com/download/Drives/MG18C502.pdf.
More Danfoss Modbus register maps
- Thermostat / heating controller (district heating and HVAC)
Danfoss ECL Comfort 210 / 296 / 310 heating controller (Modbus RTU / TCP)
ECL Comfort 210, 296 and 310 controllers (and B versions) with any application key; many parameters depend on the loaded application.
Also known as: ECL Comfort 210, ECL Comfort 296, ECL Comfort 310, ECL Comfort 210B, ECL Comfort 310B, 087H3020, 087H3024, 087H3030, 087H3034, 087H3040, 087H3044, 087H3050, 087H3054 - Sensor (refrigerant / toxic gas detector)
Danfoss Gas Detection Units GD Basic / Premium / Heavy Duty (Modbus RTU)
Danfoss GD Basic, Premium and Heavy Duty gas detection units on their own RS-485 Modbus port (Part 2 of the guide). The gas detection controller's X-bus map in Part 1 is not included.
Also known as: GDA, GDC, GDHC, GDHF, GDH, GD Basic, GD Premium, GD Heavy Duty - Variable frequency drive
Danfoss iC2-Micro frequency converter (Modbus RTU)
Danfoss iC2-Micro frequency converters using the built-in RS-485 port with P 10.1.1 Protocol = [2] Modbus RTU and the FC control profile; Application Guide AB413939445838en-000401.
Also known as: iC2-Micro, iC2 Micro, Danfoss iC2 - Sensor / controller (CO2 condensing unit gateway)
Danfoss Optyma iCO2 gateway (OP-MPAM015 / OP-MPAM005)
Danfoss Optyma iCO2 CO2 condensing units (4.6 kW MT and 20 kW MT / 10 kW LT) through their Modbus gateway, software 1.0x.
Also known as: OP-MPAM015, OP-MPAM005, Optyma iCO2 4.6 kW MT, Optyma iCO2 20 kW MT / 10 kW LT - Variable frequency drive
Danfoss VLT AQUA Drive FC 202 (Modbus RTU)
VLT AQUA Drive FC 202 using the built-in RS-485 (FC) port with 8-30 Protocol = Modbus RTU and the FC control profile; parameter data checked against the software 5.4X programming guide.
Also known as: VLT AQUA Drive, FC202, FC-202, AQUA Drive FC 202 - Variable frequency drive
Danfoss VLT AutomationDrive FC 301/302 (Modbus RTU)
VLT AutomationDrive FC 301 and FC 302 (0.25-75 kW design guide; same scheme across sizes) using the built-in RS-485 (FC) port with 8-30 Protocol = Modbus RTU and the FC control profile; parameter data checked against the software 9.5x / 48.96 programming guide.
Also known as: VLT AutomationDrive, FC 301, FC301, FC302, FC-302, FC-301, FC 300 - Variable frequency drive
Danfoss VLT AutomationDrive FC 360 (Modbus RTU)
VLT AutomationDrive FC 360 on its built-in RS-485 port with 8-30 Protocol = Modbus RTU and the FC control profile.
Also known as: FC360, FC-360, VLT AutomationDrive FC 360 - Variable frequency drive
Danfoss VLT Compressor Drive CDS 803 (Modbus RTU)
VLT Compressor Drive CDS 803 (variable-speed compressor drive for HVAC/R) using the built-in RS-485 port with 8-30 Protocol = Modbus RTU; Modbus rules from Design Guide MG18N202 (software 1.20), parameter data from Programming Guide MG18P202 (software 2.0).
Also known as: CDS803, CDS-803, VLT Compressor Drive CDS 803 - Variable frequency drive
Danfoss VLT HVAC Drive FC 102 (Modbus RTU)
VLT HVAC Drive FC 102 using the built-in RS-485 (FC) port with 8-30 Protocol = Modbus RTU and the FC control profile; parameter scaling checked against the software 7.61 programming guide.
Also known as: VLT HVAC Drive, FC102, FC-102 - Variable frequency drive
Danfoss VLT Micro Drive FC 51 (Modbus RTU)
VLT Micro Drive FC 51 on the built-in RS-485 port with 8-30 = Modbus, software 3.1x; registers per design guide MG02K402 and parameter data per programming guide MG02C702.
Also known as: FC 51, FC51, VLT Micro Drive, VLT Micro Drive FC 51 - Variable frequency drive
Danfoss VLT Midi Drive FC 280 (Modbus RTU)
VLT Midi Drive FC 280 on its built-in RS-485 port with 8-30 Protocol = Modbus RTU and the FC control profile.
Also known as: FC280, FC-280, VLT Midi Drive FC 280, VLT Midi Drive
Other variable frequency drives register maps
- Variable frequency drive
Eaton PowerXL DB1 compact drive (Modbus RTU)
Eaton PowerXL DB1 per the Modbus RTU communication manual MN040018EN, edition 12/22.
Also known as: DB1, PowerXL DB1, DB1-12, DB1-32, DB1-34 - Variable frequency drive
Hitachi SJ700-2 series inverter (Modbus RTU)
Hitachi SJ700-2 series inverters using the built-in RS485 port (TM2) in Modbus-RTU mode (C079), per instruction manual NT204DX.
Also known as: SJ700, SJ700-2, SJ700 series - Variable frequency drive
Invertek Drives Optidrive Elevator Core (built-in Modbus RTU)
Invertek Elevator Core lift drives on the RJ45 Modbus RTU port, per the online Elevator Core user guide (support.invertekdrives.com).
Also known as: Elevator Core, Optidrive Elevator Core - Variable frequency drive
INVT Goodrive35 (GD35) closed-loop vector VFD
INVT Goodrive35 closed-loop vector drives using the built-in RS-485 Modbus RTU port, per the GD35 VFD manual V4.0 (communication protocol chapter).
Also known as: GD35, Goodrive35, GD35 vector VFD - Variable frequency drive
Lenze SCF Series drive with Modbus module (basic network control)
Lenze AC Tech SCF Series drives with the optional Modbus RTU communication module; application note AN0028/A1 (January 2008).
Also known as: SCF, Lenze AC Tech SCF, AN0028 - Variable frequency drive
Mitsubishi Electric FR-E700 compact inverter (PU connector, Modbus RTU)
FR-E700 series (FR-E720/E740/E720S/E710W, incl. SC safety-stop models) using the PU connector with Pr.549 = 1; Instruction Manual (Applied) revision G.
Also known as: FR-E720, FR-E740, FR-E720S, FR-E710W, FR-E700-SC
All variable frequency drives Modbus register maps →
Source: VLT HVAC Basic Drive FC 101 Design Guide (chapter 7 RS-485 Installation and Set-up, Modbus RTU) · MG18C502 · rev. 2013-09-06. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.