- Home
- Modbus register maps
- INVT
- Goodrive35 (GD35) closed-loop vector VFD
Variable frequency drive · Modbus register map
INVT Goodrive35 (GD35) closed-loop vector VFD Modbus register map
Updated 19 November 2026
INVT's closed-loop vector drive for high-performance machinery, with encoder feedback support. The built-in RS-485 port speaks Modbus RTU. Commands and setpoints go to the 2000H block, status and fault words sit at 2100H-2103H, monitors at 3000H onwards, and each function parameter has its own hex address. This map covers that block plus the run-source, P14 serial and fault parameters.
This page lists 49 Modbus registers for the INVT Goodrive35 (GD35) closed-loop vector VFD — 25 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from INVT’s own free documentation (linked below) and checked against it.
- Manufacturer
- INVT
- Model
- Goodrive35 (GD35) closed-loop vector VFD
- Equipment type
- Variable frequency drive
- Registers
- 49 (25 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 19200 baud, 8E1
- Documented addressing
- hexadecimal, 0-based
- Also known as
- GD35, Goodrive35, GD35 vector VFD
Integration notes: INVT Goodrive35 (GD35) closed-loop vector VFD
Set P00.01 = 2 and P00.02 = 0 so run commands come from Modbus, and P00.06 = 8 so the speed reference does too. Write the frequency to 2001H in 0.01 Hz and a run/stop code to 2000H, then poll 2100H, 2102H and 3000H-3004H.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 8192 | Communication control command | UINT16 | Run / stop / fault reset command | Read/write |
| HR 8193 | Communication frequency setting | UINT16 | Speed reference in 0.01 Hz | Read/write |
| HR 8448 | VFD status word 1 | UINT16 | Running / stopped / fault state | Read |
| HR 8450 | VFD fault code | UINT16 | Active fault code | Read |
| HR 12288 | Running frequency | UINT16 | Output frequency | Read |
| HR 12292 | Output current | UINT16 | Output current | Read |
| HR 12290 | Bus voltage | UINT16 | DC bus voltage | Read |
Enable Modbus control & writes
P00.01 = 2 gives the run command to communication; P00.02 = 0 picks Modbus as that channel. P00.06 (A frequency source) = 8 makes 2001H the speed reference. P09.00 must select Modbus before 2002H/2003H act as PID reference/feedback. P14.00-P14.02 set address, baud and format.
Communication loss & watchdog
P14.04 sets a bus-silence timeout (0.0 s = off). When it runs out the drive raises CE (fault 18) and P14.05 decides whether it coasts, keeps running or stops with its stop mode.
Byte order & addressing
- Parameter Pxx.yy sits at hex register (xx << 8) | yy: P14.01 = 0E01H, P07.27 = 071BH.
- Setting the top bit of a parameter address (for example 8007H for P00.07) writes RAM only and spares the EEPROM; those aliases cannot be read.
- Scaled values follow the decimals printed in the parameter list or address table (one decimal = x10, two decimals = x100), per the manual's fieldbus-scale section. Registers with a negative printed range are typed INT16 here.
Network setup
- P14.00 slave address (default 1), P14.01 baud (default 4 = 19200 bps), P14.02 format (default 1 = E,8,1 RTU).
- Read with function 03H; write with 06H or 10H.
Watch out for
- Frequent parameter writes wear the EEPROM; use the RAM alias (address + 8000H) for values that change often.
- Some parameters cannot be changed while the drive runs; the drive answers with exception 08H.
INVT Goodrive35 (GD35) closed-loop vector VFD Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 1doc P00.01 (0001H) | P00.01 Run command channel | Set 2 so run/stop comes from 2000H. | UINT16 | Read/write | 0 = Keypad; 1 = Terminal; 2 = Communication | |||
| HR | 2doc P00.02 (0002H) | P00.02 Communication run command channel | Which bus carries run commands when P00.01 = 2. | UINT16 | Read/write | 0 = Modbus communication channel | |||
| HR | 3doc P00.03 (0003H) | P00.03 Max. output frequency | Fmax; ceiling for 2001H. | UINT16 | × 0.01 | Hz | Read/write | ||
| HR | 6doc P00.06 (0006H) | P00.06 A frequency command channel | Set to the Modbus option so 2001H sets the speed; other values pick local sources. | UINT16 | Read/write | 8 = Modbus communication setting | |||
| HR | 1819doc P07.27 (071BH) | P07.27 Present fault type | Same codes as 2102H. | UINT16 | Read | 0 = No fault; 1 = Inverter unit phase protection (OUt1); 2 = Inverter unit V phase protection (OUt2); 3 = Inverter unit W phase protection (OUt3); 4 = ACC overcurrent (OC1); 5 = DEC overcurrent (OC2); 6 = Constant-speed overcurrent (OC3); 7 = ACC overvoltage (OV1); 8 = DEC overvoltage (OV2); 9 = Constant-speed overvoltage (OV3); 10 = Bus undervoltage (UV); 11 = Motor overload (OL1); 12 = VFD overload (OL2); 13 = Input side phase loss (SPI); 14 = Output side phase loss (SPO); 15 = Overheat of the rectifier module (OH1); 16 = Overheat fault of the inverter module (OH2); 17 = External fault (EF); 18 = 485 communication fault (CE); 19 = Current detection fault (ItE); 20 = Motor autotune fault (tE); 21 = EEPROM operation fault (EEP); 22 = PID response offline fault (PIDE); 23 = Braking unit fault (bCE); 24 = Running time arrival (END); 25 = Electrical overload (OL3); 26 = Panel communication fault (PCE); 27 = Parameter uploading fault (UPE); 28 = Parameter downloading fault (DNE); 29 = PROFIBUS communication fault (E-DP); 30 = Ethernet communication fault (E-NET); 31 = CANopen communication fault (E-CAN); 32 = Grounding short circuit fault 1 (ETH1); 33 = Grounding short circuit fault 2 (ETH2); 34 = Speed deviation fault (dEu); 35 = Maladjustment (STu); 36 = Undervoltage fault (LL); 37 = Encoder offline fault (ENC1o); 38 = Encoder reverse fault (ENC1d); 39 = Encoder pulse Z offline fault (ENC1Z); 43 = Motor overtemperature fault (OT) | |||
| HR | 3584doc P14.00 (0E00H) | P14.00 Local communication address | 1-247; 0 is broadcast. | UINT16 | Read/write | ||||
| HR | 3585doc P14.01 (0E01H) | P14.01 Baud rate | UINT16 | Read/write | 0 = 1200 bps; 1 = 2400 bps; 2 = 4800 bps; 3 = 9600 bps; 4 = 19200 bps; 5 = 38400 bps; 6 = 57600 bps; 7 = 115200 bps | ||||
| HR | 3586doc P14.02 (0E02H) | P14.02 Data bit check | UINT16 | Read/write | 0 = N,8,1 RTU; 1 = E,8,1 RTU; 2 = O,8,1 RTU; 3 = N,8,2 RTU; 4 = E,8,2 RTU; 5 = O,8,2 RTU | ||||
| HR | 3587doc P14.03 (0E03H) | P14.03 Communication response delay | 0-200 ms extra delay before replying. | UINT16 | ms | Read/write | |||
| HR | 3588doc P14.04 (0E04H) | P14.04 Communication timeout | 0.0 = off; otherwise CE fault after this much bus silence. | UINT16 | × 0.1 | s | Read/write | ||
| HR | 3589doc P14.05 (0E05H) | P14.05 Transmission fault processing | UINT16 | Read/write | 0 = Alarm and coast to stop; 1 = Keep running, no alarm; 2 = Stop by stop mode, no alarm (communication mode only); 3 = Stop by stop mode, no alarm (any mode) | ||||
| HR | 8192doc 2000H | Communication control command | Needs P00.01 = 2. | UINT16 | Read/write | 1 = Forward running; 2 = Reverse running; 3 = Forward jogging; 4 = Reverse jogging; 5 = Stop; 6 = Coast to stop; 7 = Fault reset; 8 = Jogging stop | |||
| HR | 8193doc 2001H | Communication frequency setting | 0 to Fmax. | UINT16 | × 0.01 | Hz | Read/write | ||
| HR | 8194doc 2002H | PID reference | 0-1000 = 0-100.0 %. | UINT16 | × 0.1 | % | Read/write | ||
| HR | 8195doc 2003H | PID feedback | 0-1000 = 0-100.0 %. | UINT16 | × 0.1 | % | Read/write | ||
| HR | 8196doc 2004H | Torque setting | -3000 to 3000; 1000 = 100.0 % of motor rated current. | INT16 | × 0.1 | % | Read/write | ||
| HR | 8197doc 2005H | Forward upper frequency limit | 0 to Fmax. | UINT16 | × 0.01 | Hz | Read/write | ||
| HR | 8198doc 2006H | Reverse upper frequency limit | 0 to Fmax. | UINT16 | × 0.01 | Hz | Read/write | ||
| HR | 8199doc 2007H | Motoring torque upper limit | 0-3000; 1000 = 100.0 % of the VFD rated current. | UINT16 | × 0.1 | % | Read/write | ||
| HR | 8200doc 2008H | Braking torque upper limit | 0-3000; 1000 = 100.0 % of motor rated current. | UINT16 | × 0.1 | % | Read/write | ||
| HR | 8201doc 2009H | Special control command word | Bits 0-1 select the motor (00 = motor 1, 01 = motor 2, 10 = motor 3, 11 = motor 4). | BITMAP16 | Read/write | bit 2 = 1 = torque control disabled; bit 3 = 1 = reset power consumption to 0; bit 4 = 1 = pre-excitation; bit 5 = 1 = DC braking | |||
| HR | 8202doc 200AH | Virtual input terminal command | Range 0x000-0x1FF. | BITMAP16 | Read/write | ||||
| HR | 8203doc 200BH | Virtual output terminal command | Range 0x00-0x0F. | BITMAP16 | Read/write | ||||
| HR | 8204doc 200CH | Voltage setting (V/F separation) | 0-1000 = 0-100.0 % of motor rated voltage. | UINT16 | × 0.1 | % | Read/write | ||
| HR | 8205doc 200DH | AO output setting 1 | -1000 to 1000 = -100.0 to 100.0 %. | INT16 | × 0.1 | % | Read/write | ||
| HR | 8206doc 200EH | AO output setting 2 | -1000 to 1000 = -100.0 to 100.0 %. | INT16 | × 0.1 | % | Read/write | ||
| HR | 8448doc 2100H | VFD status word 1 | UINT16 | Read | 1 = Forward running; 2 = Reverse running; 3 = Stopped; 4 = Faulty; 5 = POFF; 6 = Pre-excited | ||||
| HR | 8449doc 2101H | VFD status word 2 | BITMAP16 | Read | bit 0 = 1 = ready to run; bit 1 = Motor select bit 0 (bits 1-2: 00 motor 1 .. 11 motor 4); bit 2 = Motor select bit 1; bit 3 = 1 = synchronous motor, 0 = asynchronous; bit 4 = 1 = overload pre-alarm; bit 5 = Control source bit 0 (bits 5-6: 00 keypad, 01 terminal, 10 communication); bit 6 = Control source bit 1 | ||||
| HR | 8450doc 2102H | VFD fault code | Codes match P07.27. | UINT16 | Read | 0 = No fault; 1 = Inverter unit phase protection (OUt1); 2 = Inverter unit V phase protection (OUt2); 3 = Inverter unit W phase protection (OUt3); 4 = ACC overcurrent (OC1); 5 = DEC overcurrent (OC2); 6 = Constant-speed overcurrent (OC3); 7 = ACC overvoltage (OV1); 8 = DEC overvoltage (OV2); 9 = Constant-speed overvoltage (OV3); 10 = Bus undervoltage (UV); 11 = Motor overload (OL1); 12 = VFD overload (OL2); 13 = Input side phase loss (SPI); 14 = Output side phase loss (SPO); 15 = Overheat of the rectifier module (OH1); 16 = Overheat fault of the inverter module (OH2); 17 = External fault (EF); 18 = 485 communication fault (CE); 19 = Current detection fault (ItE); 20 = Motor autotune fault (tE); 21 = EEPROM operation fault (EEP); 22 = PID response offline fault (PIDE); 23 = Braking unit fault (bCE); 24 = Running time arrival (END); 25 = Electrical overload (OL3); 26 = Panel communication fault (PCE); 27 = Parameter uploading fault (UPE); 28 = Parameter downloading fault (DNE); 29 = PROFIBUS communication fault (E-DP); 30 = Ethernet communication fault (E-NET); 31 = CANopen communication fault (E-CAN); 32 = Grounding short circuit fault 1 (ETH1); 33 = Grounding short circuit fault 2 (ETH2); 34 = Speed deviation fault (dEu); 35 = Maladjustment (STu); 36 = Undervoltage fault (LL); 37 = Encoder offline fault (ENC1o); 38 = Encoder reverse fault (ENC1d); 39 = Encoder pulse Z offline fault (ENC1Z); 43 = Motor overtemperature fault (OT) | |||
| HR | 8451doc 2103H | VFD identification code | 0x0109 = GD35 (high byte 0x01 Goodrive series). | UINT16 | Read | ||||
| HR | 12288doc 3000H | Running frequency | UINT16 | × 0.01 | Hz | Read | |||
| HR | 12289doc 3001H | Set frequency | UINT16 | × 0.01 | Hz | Read | |||
| HR | 12290doc 3002H | Bus voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 12291doc 3003H | Output voltage | UINT16 | V | Read | ||||
| HR | 12292doc 3004H | Output current | UINT16 | × 0.1 | A | Read | |||
| HR | 12293doc 3005H | Rotating speed | UINT16 | rpm | Read | ||||
| HR | 12294doc 3006H | Output power | -300.0 to 300.0 %. | INT16 | × 0.1 | % | Read | ||
| HR | 12295doc 3007H | Output torque | -250.0 to 250.0 %. | INT16 | × 0.1 | % | Read | ||
| HR | 12296doc 3008H | Closed-loop setting | -100.0 to 100.0 %. | INT16 | × 0.1 | % | Read | ||
| HR | 12297doc 3009H | Closed-loop feedback | -100.0 to 100.0 %. | INT16 | × 0.1 | % | Read | ||
| HR | 12298doc 300AH | Input terminal state | Range 000-1FF. | BITMAP16 | Read | ||||
| HR | 12299doc 300BH | Output terminal state | Range 000-1FF. | BITMAP16 | Read | ||||
| HR | 12300doc 300CH | Analog input 1 | 0.00-10.00 V. | UINT16 | × 0.01 | V | Read | ||
| HR | 12301doc 300DH | Analog input 2 | 0.00-10.00 V. | UINT16 | × 0.01 | V | Read | ||
| HR | 12302doc 300EH | Analog input 3 | -10.00 to 10.00 V. | INT16 | × 0.01 | V | Read | ||
| HR | 12306doc 3012H | Current step of multi-step speed | 0-15. | UINT16 | Read | ||||
| HR | 12307doc 3013H | External length value | UINT16 | Read | |||||
| HR | 12308doc 3014H | External count value | UINT16 | Read | |||||
| HR | 12309doc 3015H | Torque setting | -300.0 to 300.0 %. | INT16 | × 0.1 | % | Read |
Notes on this map
- Every register is a single 16-bit word; there are no 32-bit values in this map.
- Any function parameter can be read or written at (group << 8) | index; only the parameters an integrator needs most are listed here.
- 3016H (identification code) and 5000H (fault code) are printed without range or unit, so they are left out; 2102H and 2103H carry the same information.
- 300FH, 3010H (pulse input printed with a mixed kHz/0.01 Hz unit) and 3011H are left out.
- P00.02 values other than 0 select option cards; only 0 (Modbus) is listed.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the INVT Goodrive35 (GD35) closed-loop vector VFD
What Modbus registers does the INVT Goodrive35 (GD35) closed-loop vector VFD have?
This map lists 49 registers: 49 holding registers. 25 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the INVT Goodrive35 (GD35) closed-loop vector VFD Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Addresses are printed in hex and go on the wire unchanged. Parameter P00.00 sits at 0000H and the manual's example frames carry the address bytes directly (setting P01.20 is sent as 01 06 01 14 00 32, and the multi-register write starts at 20 00).
What are the minimum Modbus registers to integrate the INVT Goodrive35 (GD35) closed-loop vector VFD?
Start with HR 8192 Communication control command (Run / stop / fault reset command); HR 8193 Communication frequency setting (Speed reference in 0.01 Hz); HR 8448 VFD status word 1 (Running / stopped / fault state); HR 8450 VFD fault code (Active fault code); HR 12288 Running frequency (Output frequency); HR 12292 Output current (Output current); HR 12290 Bus voltage (DC bus voltage).
How do I enable Modbus control of the INVT Goodrive35 (GD35) closed-loop vector VFD?
P00.01 = 2 gives the run command to communication; P00.02 = 0 picks Modbus as that channel. P00.06 (A frequency source) = 8 makes 2001H the speed reference. P09.00 must select Modbus before 2002H/2003H act as PID reference/feedback. P14.00-P14.02 set address, baud and format.
What happens when the INVT Goodrive35 (GD35) closed-loop vector VFD loses Modbus communication?
P14.04 sets a bus-silence timeout (0.0 s = off). When it runs out the drive raises CE (fault 18) and P14.05 decides whether it coasts, keeps running or stops with its stop mode.
Where is the official INVT Goodrive35 (GD35) closed-loop vector VFD Modbus documentation?
The source is Goodrive35 Series Closed-loop Vector Control VFD Operation Manual (V4.0), revision 2022-05, published free by INVT at https://www.invt.com/uploads/file1/20220622/GD35-Series-VFD-Manual_V4.0.pdf.
More INVT Modbus register maps
- Variable frequency drive
INVT Goodrive10 (GD10) mini VFD
INVT Goodrive10 mini drives using the built-in RS-485 Modbus RTU port, per the GD10 VFD manual V2.9 (chapter 7).
Also known as: GD10, Goodrive10, GD10 mini VFD - Variable frequency drive
INVT Goodrive20 (GD20) general-purpose VFD
INVT Goodrive20 drives using the built-in RS-485 Modbus port, per the GD20 VFD manual V2.1 (chapter 7, communication protocol).
Also known as: GD20, Goodrive20, GD20-EU, GD20-UL, GD20 vector VFD - Variable frequency drive
INVT Goodrive200A (GD200A) general-purpose VFD
INVT Goodrive200A drives using the built-in RS-485 Modbus port, per the GD200A manual V3.1 (chapter 9).
Also known as: GD200A, Goodrive200A, GD200A general VFD - Variable frequency drive
INVT Goodrive270 (GD270) fan and pump VFD
INVT Goodrive270 fan and pump drives using the built-in RS-485 Modbus RTU port, per the GD270 manual V1.4 (chapter 9).
Also known as: GD270, Goodrive270, GD270 fan and pump drive, GD270 HVAC drive - Variable frequency drive
INVT Goodrive300 (GD300) vector VFD
INVT Goodrive300 open-loop vector drives using the built-in RS-485 Modbus RTU port, per the GD300 VFD manual V3.6 (chapter 10).
Also known as: GD300, Goodrive300, GD300 vector VFD - Variable frequency drive
INVT Goodrive350 (GD350) high-performance multifunction VFD
INVT Goodrive350 drives (not GD350A) using the built-in RS-485 Modbus RTU port, per the GD350 manual V1.1 (communication chapter).
Also known as: GD350, Goodrive350, GD350 series - Variable frequency drive
INVT Goodrive350A (GD350A) high-performance multifunction VFD
INVT Goodrive350A drives using the built-in RS-485 Modbus RTU port, per the GD350A manual V1.3 (chapter 9).
Also known as: GD350A, Goodrive350A, GD350A series
Other variable frequency drives register maps
- Variable frequency drive
Lenze SCF Series drive with Modbus module (basic network control)
Lenze AC Tech SCF Series drives with the optional Modbus RTU communication module; application note AN0028/A1 (January 2008).
Also known as: SCF, Lenze AC Tech SCF, AN0028 - Variable frequency drive
Mitsubishi Electric FR-E700 compact inverter (PU connector, Modbus RTU)
FR-E700 series (FR-E720/E740/E720S/E710W, incl. SC safety-stop models) using the PU connector with Pr.549 = 1; Instruction Manual (Applied) revision G.
Also known as: FR-E720, FR-E740, FR-E720S, FR-E710W, FR-E700-SC - Variable frequency drive
Schneider Electric Altivar Process ATV900 (ATV930/ATV950, embedded Modbus serial / Modbus TCP)
Altivar Process ATV900 drives (ATV930, ATV950) on the built-in Modbus serial port and the embedded Ethernet port (Modbus TCP). Per Communication Parameters file NHA80944 V4.6.
Also known as: ATV900, ATV930, ATV950, Altivar Process 900, Altivar 930, Altivar 950, ATV930U, ATV930D, ATV950U - Air handler (rotary heat exchanger drive controller)
Swegon SILVER C / SILVER RX rotary heat exchanger controller (Modbus RTU)
The rotary heat exchanger (rotor) drive controller in Swegon SILVER C RX air handling units, per sheet SILVERCModbusHX.201115.
Also known as: SILVER RX heat exchanger controller, SILVER C RX rotor drive, DRHX, SILVERCModbusHX - Variable frequency drive
Toshiba TOSVERT VF-AS3 inverter (RS485 Modbus RTU)
Toshiba TOSVERT VF-AS3 inverters on RS485 port 1 or 2 with the protocol set to MODBUS (F807/F827 = 1); RS485 Communication Function Instruction Manual E6582143.
Also known as: VF-AS3, TOSVERT VF-AS3 - Variable frequency drive
Yaskawa F7 drive (CIMR-F7U, legacy) - Modbus RTU
Yaskawa F7 (CIMR-F7U) general-purpose drives using the built-in RS-422/485 terminals R+/R-/S+/S-, per user manual TM.F7.01 Appendix D, with parameter and monitor addresses from TM.F7.11.
Also known as: CIMR-F7U, F7U, F7 Drive
All variable frequency drives Modbus register maps →
Source: Goodrive35 Series Closed-loop Vector Control VFD Operation Manual · V4.0 · rev. 2022-05. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.