Easy Modbus
  1. Home
  2. Modbus register maps
  3. INVT
  4. Goodrive300 (GD300) vector VFD

Variable frequency drive · Modbus register map

INVT Goodrive300 (GD300) vector VFD Modbus register map

Updated 19 November 2026

Short answer

INVT's open-loop vector drive for induction and permanent-magnet motors. The built-in RS-485 port speaks Modbus RTU. Commands and setpoints go to the 2000H block, status and fault words sit at 2100H-2103H, monitors at 3000H onwards, and each function parameter has its own hex address. This map covers that block plus the run-source, P14 serial and fault parameters.

This page lists 48 Modbus registers for the INVT Goodrive300 (GD300) vector VFD — 25 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from INVT’s own free documentation (linked below) and checked against it.

Manufacturer
INVT
Model
Goodrive300 (GD300) vector VFD
Equipment type
Variable frequency drive
Registers
48 (25 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
19200 baud, 8E1
Documented addressing
hexadecimal, 0-based
Also known as
GD300, Goodrive300, GD300 vector VFD
Source document
Goodrive300 Series VFD Operation Manual · V3.6 · rev. 2021-10
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: INVT Goodrive300 (GD300) vector VFD

Integration in brief

Set P00.01 = 2 and P00.02 = 0 so run commands come from Modbus, and P00.06 = 8 so the speed reference does too. Write the frequency to 2001H in 0.01 Hz and a run/stop code to 2000H, then poll 2100H, 2102H and 3000H-3004H.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 8192Communication control commandUINT16Run / stop / fault reset commandRead/write
HR 8193Communication frequency settingUINT16Speed reference in 0.01 HzRead/write
HR 8448VFD status word 1UINT16Running / stopped / fault stateRead
HR 8450VFD fault codeUINT16Active fault codeRead
HR 12288Running frequencyUINT16Output frequencyRead
HR 12292Output currentUINT16Output currentRead
HR 12290Bus voltageUINT16DC bus voltageRead

Enable Modbus control & writes

P00.01 = 2 gives the run command to communication; P00.02 = 0 picks Modbus as that channel. P00.06 (A frequency source) = 8 makes 2001H the speed reference. P09.00 must select Modbus before 2002H/2003H act as PID reference/feedback. P14.00-P14.02 set address, baud and format.

Communication loss & watchdog

P14.04 sets a bus-silence timeout (0.0 s = off). When it runs out the drive raises CE (fault 18) and P14.05 decides whether it coasts, keeps running or stops with its stop mode.

Byte order & addressing

Network setup

Watch out for

INVT Goodrive300 (GD300) vector VFD Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

48 of 48 shown
INVT Goodrive300 (GD300) vector VFD Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR1doc P00.01 (0001H)P00.01 Run command channelSet 2 so run/stop comes from 2000H.UINT16Read/write0 = Keypad; 1 = Terminal; 2 = Communication
HR2doc P00.02 (0002H)P00.02 Communication run command channelWhich bus carries run commands when P00.01 = 2.UINT16Read/write0 = Modbus communication channel
HR3doc P00.03 (0003H)P00.03 Max. output frequencyFmax; ceiling for 2001H.UINT16× 0.01HzRead/write
HR6doc P00.06 (0006H)P00.06 A frequency command channelSet to the Modbus option so 2001H sets the speed; other values pick local sources.UINT16Read/write8 = Modbus communication setting
HR1819doc P07.27 (071BH)P07.27 Present fault typeSame codes as 2102H.UINT16Read0 = No fault; 1 = Inverter unit U phase protection (OUt1); 2 = Inverter unit V phase protection (OUt2); 3 = Inverter unit W phase protection (OUt3); 4 = ACC overcurrent (OC1); 5 = DEC overcurrent (OC2); 6 = Constant-speed overcurrent (OC3); 7 = ACC overvoltage (OV1); 8 = DEC overvoltage (OV2); 9 = Constant-speed overvoltage (OV3); 10 = Bus undervoltage (UV); 11 = Motor overload (OL1); 12 = The VFD overload (OL2); 13 = Input side phase loss (SPI); 14 = Output side phase loss (SPO); 15 = Overheat of the rectifier module (OH1); 16 = Overheat fault of the inverter module (OH2); 17 = External fault (EF); 18 = 485 communication fault (CE); 19 = Current detection fault (ItE); 20 = Motor antotune fault (tE); 21 = EEPROM operation fault (EEP); 22 = PID response offline fault (PIDE); 23 = Braking unit fault (bCE); 24 = Running time arrival (END); 25 = Electrical overload (OL3); 26 = Panel communication fault (PCE); 27 = Parameter uploading fault (UPE); 28 = Parameter downloading fault (DNE); 29 = PROFIBUS communication fault (E-DP); 30 = Ethernet communication fault (E-NET); 31 = CANopen communication fault (E-CAN); 32 = Grounding short circuit fault 1 (ETH1); 33 = Grounding short circuit fault 2 (ETH2); 34 = Speed deviation fault (dEu); 35 = Maladjustment (STo); 36 = Undervoltage fault (LL)
HR3584doc P14.00 (0E00H)P14.00 Local communication address1-247; 0 is broadcast.UINT16Read/write
HR3585doc P14.01 (0E01H)P14.01 Baud rateUINT16Read/write0 = 1200 bps; 1 = 2400 bps; 2 = 4800 bps; 3 = 9600 bps; 4 = 19200 bps; 5 = 38400 bps; 6 = 57600 bps; 7 = 115200 bps
HR3586doc P14.02 (0E02H)P14.02 Data bit checkUINT16Read/write0 = N,8,1 RTU; 1 = E,8,1 RTU; 2 = O,8,1 RTU; 3 = N,8,2 RTU; 4 = E,8,2 RTU; 5 = O,8,2 RTU
HR3587doc P14.03 (0E03H)P14.03 Communication response delay0-200 ms extra delay before replying.UINT16msRead/write
HR3588doc P14.04 (0E04H)P14.04 Communication timeout0.0 = off; otherwise CE fault after this much bus silence.UINT16× 0.1sRead/write
HR3589doc P14.05 (0E05H)P14.05 Transmission fault processingUINT16Read/write0 = Alarm and coast to stop; 1 = Keep running, no alarm; 2 = Stop by stop mode, no alarm (communication mode only); 3 = Stop by stop mode, no alarm (any mode)
HR8192doc 2000HCommunication control commandNeeds P00.01 = 2.UINT16Read/write1 = Forward running; 2 = Reverse running; 3 = Forward jogging; 4 = Reverse jogging; 5 = Stop; 6 = Coast to stop; 7 = Fault reset; 8 = Jogging stop
HR8193doc 2001HCommunication frequency setting0 to Fmax.UINT16× 0.01HzRead/write
HR8194doc 2002HPID reference0-1000 = 0-100.0 %.UINT16× 0.1%Read/write
HR8195doc 2003HPID feedback0-1000 = 0-100.0 %.UINT16× 0.1%Read/write
HR8196doc 2004HTorque setting-3000 to 3000; 1000 = 100.0 % of motor rated current.INT16× 0.1%Read/write
HR8197doc 2005HForward upper frequency limit0 to Fmax.UINT16× 0.01HzRead/write
HR8198doc 2006HReverse upper frequency limit0 to Fmax.UINT16× 0.01HzRead/write
HR8199doc 2007HMotoring torque upper limit0-3000; 1000 = 100.0 % of motor rated current.UINT16× 0.1%Read/write
HR8200doc 2008HBraking torque upper limit0-3000; 1000 = 100.0 % of motor rated current.UINT16× 0.1%Read/write
HR8201doc 2009HSpecial control command wordBits 0-1 select the motor (00 = motor 1, 01 = motor 2, 10 = motor 3, 11 = motor 4).BITMAP16Read/writebit 2 = 1 = torque control prohibited; bit 3 = 1 = clear power consumption; bit 4 = 1 = pre-exciting enabled; bit 5 = 1 = DC braking enabled
HR8202doc 200AHVirtual input terminal commandRange 0x000-0x1FF.BITMAP16Read/write
HR8203doc 200BHVirtual output terminal commandRange 0x00-0x0F.BITMAP16Read/write
HR8204doc 200CHVoltage setting (V/F separation)0-1000 = 0-100.0 %.UINT16× 0.1%Read/write
HR8205doc 200DHAO output setting 1-1000 to 1000 = -100.0 to 100.0 %.INT16× 0.1%Read/write
HR8206doc 200EHAO output setting 2-1000 to 1000 = -100.0 to 100.0 %.INT16× 0.1%Read/write
HR8448doc 2100HVFD status word 1UINT16Read1 = Forward running; 2 = Running (printed as forward running twice); 3 = Stop; 4 = Fault; 5 = POFF state; 6 = Pre-exciting state
HR8449doc 2101HVFD status word 2BITMAP16Readbit 0 = 1 = ready to run; bit 1 = Motor select bit 0 (bits 1-2: 00 motor 1 .. 11 motor 4); bit 2 = Motor select bit 1; bit 3 = 1 = synchronous motor, 0 = asynchronous; bit 4 = 1 = overload pre-alarm; bit 5 = Control source bit 0 (bits 5-6: 00 keypad, 01 terminal, 10 communication); bit 6 = Control source bit 1
HR8450doc 2102HVFD fault codeCodes match P07.27.UINT16Read0 = No fault; 1 = Inverter unit U phase protection (OUt1); 2 = Inverter unit V phase protection (OUt2); 3 = Inverter unit W phase protection (OUt3); 4 = ACC overcurrent (OC1); 5 = DEC overcurrent (OC2); 6 = Constant-speed overcurrent (OC3); 7 = ACC overvoltage (OV1); 8 = DEC overvoltage (OV2); 9 = Constant-speed overvoltage (OV3); 10 = Bus undervoltage (UV); 11 = Motor overload (OL1); 12 = The VFD overload (OL2); 13 = Input side phase loss (SPI); 14 = Output side phase loss (SPO); 15 = Overheat of the rectifier module (OH1); 16 = Overheat fault of the inverter module (OH2); 17 = External fault (EF); 18 = 485 communication fault (CE); 19 = Current detection fault (ItE); 20 = Motor antotune fault (tE); 21 = EEPROM operation fault (EEP); 22 = PID response offline fault (PIDE); 23 = Braking unit fault (bCE); 24 = Running time arrival (END); 25 = Electrical overload (OL3); 26 = Panel communication fault (PCE); 27 = Parameter uploading fault (UPE); 28 = Parameter downloading fault (DNE); 29 = PROFIBUS communication fault (E-DP); 30 = Ethernet communication fault (E-NET); 31 = CANopen communication fault (E-CAN); 32 = Grounding short circuit fault 1 (ETH1); 33 = Grounding short circuit fault 2 (ETH2); 34 = Speed deviation fault (dEu); 35 = Maladjustment (STo); 36 = Undervoltage fault (LL)
HR8451doc 2103HVFD identification code0x010A = GD300 (high byte 0x01 Goodrive series).UINT16Read
HR12288doc 3000HRunning frequencyUINT16× 0.01HzRead
HR12289doc 3001HSet frequencyUINT16× 0.01HzRead
HR12290doc 3002HBus voltageUINT16× 0.1VRead
HR12291doc 3003HOutput voltageUINT16VRead
HR12292doc 3004HOutput currentUINT16× 0.1ARead
HR12293doc 3005HRotating speedUINT16rpmRead
HR12294doc 3006HOutput power-300.0 to 300.0 %.INT16× 0.1%Read
HR12295doc 3007HOutput torque-250.0 to 250.0 %.INT16× 0.1%Read
HR12296doc 3008HClosed-loop setting-100.0 to 100.0 %.INT16× 0.1%Read
HR12297doc 3009HClosed-loop feedback-100.0 to 100.0 %.INT16× 0.1%Read
HR12298doc 300AHInput terminal stateRange 000-1FF.BITMAP16Read
HR12299doc 300BHOutput terminal stateRange 000-1FF.BITMAP16Read
HR12300doc 300CHAnalog input 10.00-10.00 V.UINT16× 0.01VRead
HR12301doc 300DHAnalog input 20.00-10.00 V.UINT16× 0.01VRead
HR12306doc 3012HCurrent step of multi-step speed0-15.UINT16Read
HR12307doc 3013HExternal length valueUINT16Read
HR12308doc 3014HExternal count valueUINT16Read
HR12309doc 3015HTorque setting-300.0 to 300.0 %.INT16× 0.1%Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the INVT Goodrive300 (GD300) vector VFD

What Modbus registers does the INVT Goodrive300 (GD300) vector VFD have?

This map lists 48 registers: 48 holding registers. 25 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the INVT Goodrive300 (GD300) vector VFD Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Addresses are printed in hex and go on the wire unchanged. Parameter P00.00 sits at 0000H and the manual's example frames carry the address bytes directly (writing P00.01 is sent as 01 06 00 01 00 03, and setting P01.20 as 01 06 01 14 00 32).

What are the minimum Modbus registers to integrate the INVT Goodrive300 (GD300) vector VFD?

Start with HR 8192 Communication control command (Run / stop / fault reset command); HR 8193 Communication frequency setting (Speed reference in 0.01 Hz); HR 8448 VFD status word 1 (Running / stopped / fault state); HR 8450 VFD fault code (Active fault code); HR 12288 Running frequency (Output frequency); HR 12292 Output current (Output current); HR 12290 Bus voltage (DC bus voltage).

How do I enable Modbus control of the INVT Goodrive300 (GD300) vector VFD?

P00.01 = 2 gives the run command to communication; P00.02 = 0 picks Modbus as that channel. P00.06 (A frequency source) = 8 makes 2001H the speed reference. P09.00 must select Modbus before 2002H/2003H act as PID reference/feedback. P14.00-P14.02 set address, baud and format.

What happens when the INVT Goodrive300 (GD300) vector VFD loses Modbus communication?

P14.04 sets a bus-silence timeout (0.0 s = off). When it runs out the drive raises CE (fault 18) and P14.05 decides whether it coasts, keeps running or stops with its stop mode.

Where is the official INVT Goodrive300 (GD300) vector VFD Modbus documentation?

The source is Goodrive300 Series VFD Operation Manual (V3.6), revision 2021-10, published free by INVT at https://www.invt.com/uploads/file1/20220421/GD300%20VFD%20Manual%20_V3.6.pdf.

More INVT Modbus register maps

Other variable frequency drives register maps

All variable frequency drives Modbus register maps →

Source: Goodrive300 Series VFD Operation Manual · V3.6 · rev. 2021-10. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.