- Home
- Modbus register maps
- Lenze
- MCH Series HVAC drive (Modbus RTU)
Variable frequency drive · Modbus register map
Lenze MCH Series HVAC drive (Modbus RTU) Modbus register map
Updated 17 November 2026
The MCH is a Lenze AC Tech drive family that acts as a Modbus RTU slave at a fixed 9600 baud. Registers #1-#50 hold the control word, speed commands, status bytes, fault code, kWh and run-time counters and PID values; programming parameter n sits at register n + 51.
This page lists 24 Modbus registers for the Lenze MCH Series HVAC drive (Modbus RTU) — 10 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Lenze’s own free documentation (linked below) and checked against it.
- Manufacturer
- Lenze
- Model
- MCH Series HVAC drive (Modbus RTU)
- Equipment type
- Variable frequency drive
- Registers
- 24 (10 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 9600 baud, 8N2
- Documented addressing
- derived from parameter numbers
- Firmware
- MCH software 213-070 revision 00 (register #50 = 148)
- Also known as
- MCH, Lenze AC Tech MCH, RG-MHMOD
Integration notes: Lenze MCH Series HVAC drive (Modbus RTU)
Set P57 (serial link) and P58 (address) on the keypad. Read #26-#29 for load, status, mode, source and fault. To control: write 0 to #48 to unlock #1, or the password (default 19) to also unlock #40/#42; start/stop via #1 and write speed to #40, or set serial select (0200h on #1) and write #42.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 48 | Unlock commands | UINT16 | Unlock control | Write |
| HR 1 | Drive control | BITMAP16 | Start / stop / serial select | Write |
| HR 40 | Keypad speed command | UINT16 | Keypad speed command | Read/write |
| HR 27 | Actual direction (high) / control mode (low) | UINT16 | Control mode (low byte) and direction | Read |
| HR 26 | Load (high byte) / operational status (low byte) | UINT16 | Load and status | Read |
| HR 29 | Present fault (high) / commanded direction (low) | UINT16 | Present fault | Read |
Enable Modbus control & writes
P57 SERIAL LINK = 01 (with 10 s watchdog) or 02 (without); P58 = address; P30 CONTROL sets how much the serial link may command (serial speed/auto modes). TB1 must be closed to unlock serial control.
Communication loss & watchdog
Fixed 10 s once #48 or #49 has unlocked the drive and P57 = with timer. Action depends on P30: normal modes drop out of serial control, serial speed modes follow P56 SERIAL LOSS, serial auto modes trip FLWR/SER fault.
Byte order & addressing
- Read one register at a time except the #24 six-word block (and 4-word #100/#101).
- FC16 accepts a single register only; FC03 and FC04 are identical.
- No broadcast support.
Network setup
- Fixed 9600 baud, 8 data bits, no parity, 2 stop bits.
Watch out for
- If register #50 is not 148, do not write registers with this map.
- End a session by writing 2 to #1 (lock security).
Lenze MCH Series HVAC drive (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 1doc #1 (4X 40002) | Drive control | One bit per write: 0004h stop, 0008h start, 0200h serial select, 0002h lock. | BITMAP16 | Write | bit 0 = Update buffers; bit 1 = Lock security; bit 2 = Stop drive; bit 3 = Start drive; bit 8 = Clear serial select flag; bit 9 = Set serial select flag | |||
| HR | 19doc #19 (4X 40020) | Drive family | Reads 68 (44h) for MCH. | UINT16 | Read | ||||
| HR | 21doc #21 (4X 40022) | Drive size code | HP / voltage code (table 9 of the guide). | UINT16 | Read | ||||
| HR | 26doc #26 (4X 40027) | Load (high byte) / operational status (low byte) | High byte = % of full load. Low byte = status code, see notes. | UINT16 | Read | ||||
| HR | 27doc #27 (4X 40028) | Actual direction (high) / control mode (low) | High: 0 fwd, 1 rev. Low: 0 off, 1 hand, 2 auto, 3 serial. | UINT16 | Read | ||||
| HR | 28doc #28 (4X 40029) | Speed source (high) / auto-hand (low) | High: speed source code (notes). Low: 0 hand, 1 auto. | UINT16 | Read | ||||
| HR | 29doc #29 (4X 40030) | Present fault (high) / commanded direction (low) | High byte = fault code (notes). Low: 0 fwd, 1 rev. | UINT16 | Read | ||||
| HR | 30doc #30 (4X 40031) | Motor voltage | Effective output voltage to the motor, 0-999 V. | UINT16 | V | Read | |||
| HR | 32doc #32 (4X 40033) | Kilowatt hours, low word | Read separately; total kWh = #33 x 65536 + #32. | UINT16 | Read | ||||
| HR | 33doc #33 (4X 40034) | Kilowatt hours, high word | Read separately; total kWh = #33 x 65536 + #32. | UINT16 | Read | ||||
| HR | 36doc #36 (4X 40037) | Total run time, hours | UINT16 | h | Read | ||||
| HR | 37doc #37 (4X 40038) | Total run time, minutes | UINT16 | min | Read | ||||
| HR | 38doc #38 (4X 40039) | PID setpoint | Internal units 0-32736 over the feedback device range. | UINT16 | Read | ||||
| HR | 39doc #39 (4X 40040) | PID feedback | Internal units 0-32736 over the feedback device range. | UINT16 | Read | ||||
| HR | 40doc #40 (4X 40041) | Keypad speed command | 0-65000; writable after unlocking control. | UINT16 | × 0.01 | Hz | Read/write | ||
| HR | 41doc #41 (4X 40042) | Local PID command | Internal units 0-32736. | UINT16 | Read/write | ||||
| HR | 42doc #42 (4X 40043) | Serial speed command | Followed when the serial select flag is set. | UINT16 | × 0.01 | Hz | Read/write | ||
| HR | 43doc #43 (4X 40044) | Serial PID command | Internal units 0-32736. | UINT16 | Read/write | ||||
| HR | 48doc #48 (4X 40049) | Unlock commands | 0 unlocks control; the password (default 19) also unlocks parameters. | UINT16 | Write | ||||
| HR | 49doc #49 (4X 40050) | Unlock parameters | Password unlocks parameter writes only. | UINT16 | Write | ||||
| HR | 50doc #50 (4X 40051) | Register version | Parameter configuration number; 148 for software 213-070 rev 00. | UINT16 | Read | ||||
| HR | 81doc #81 (4X 40082) | P30 control | UINT16 | Read/write | 0 = Normal (default); 1 = Norm no hand; 2 = Serial speed; 3 = S spd / no hand; 4 = Serial auto; 5 = S auto / no hand | ||||
| HR | 108doc #108 (4X 40109) | P57 serial link | UINT16 | Read/write | 0 = Disable (default); 1 = With timer; 2 = Without timer | ||||
| HR | 109doc #109 (4X 40110) | P58 serial address | 1-247 (default 30). Must be set before using the serial link. | UINT16 | Read/write |
Notes on this map
- Host: copy hosted by Precision Electric (a Lenze AC Tech distributor); no copy was found on lenze.com.
- Left out: command speed #24 and actual speed #25. Table 6 prints 0.1 Hz (0-2400), while the data-type table and notes 3a/3b say hundredths of a Hz (0x0201 = 5.13 Hz); the guide contradicts itself. #24 can still be read as a 6-register block starting at address 24.
- kWh: #32 is the low word and #33 the high word; total = high x 65536 + low. The guide reads one register at a time (only #24 and #100/#101 allow multi-word reads), so they are listed as two separate words.
- Operational status (low byte #26): 0 fault lockout, 1 fault, 2 start pending, 3 stop, 4 DC brake, 5 run at 0 Hz, 6 run, 7 accel, 8 decel, 9 current limit, 10 decel override.
- Speed source (high byte #28): 0 keypad, 1 0-10 VDC, 2 4-20 mA, 3-6 preset 1-4, 7 MOP, 8 keypad speed, 9 keypad/serial PID setpoint, 10 0-10 VDC PID setpoint, 11 4-20 mA PID setpoint, 12 serial speed, 13 serial PID setpoint, 14 sleep.
- Present fault (high byte #29): 0 none, 1 output transistor, 3 high DC bus, 4 high drive temperature, 5 thermal overload, 7 low DC bus, 9 DC brake error, 10 serial/follower loss, 11 dynamic brake overload, 12 power sag, 13 control, 14 language, 15 external, 16 internal 16, 17 power transient, 18-23 internal errors.
- Only the control registers and the three serial-setup parameters are listed; the full parameter list (#51 onward, one or two implied decimals) applies to software 213-070 rev 00 only.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Lenze MCH Series HVAC drive (Modbus RTU)
What Modbus registers does the Lenze MCH Series HVAC drive (Modbus RTU) have?
This map lists 24 registers: 24 holding registers. 10 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Lenze MCH Series HVAC drive (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers derived from parameter numbers. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Lenze numbers by AC Tech register #, which is exactly the address sent on the wire (Modbus 4X/3X register numbers are one larger). The guide's frames confirm it: #24 is read with start address 0x0018. Programming parameter n = AC Tech register n + 51.
What are the minimum Modbus registers to integrate the Lenze MCH Series HVAC drive (Modbus RTU)?
Start with HR 48 Unlock commands (Unlock control); HR 1 Drive control (Start / stop / serial select); HR 40 Keypad speed command (Keypad speed command); HR 27 Actual direction (high) / control mode (low) (Control mode (low byte) and direction); HR 26 Load (high byte) / operational status (low byte) (Load and status); HR 29 Present fault (high) / commanded direction (low) (Present fault).
How do I enable Modbus control of the Lenze MCH Series HVAC drive (Modbus RTU)?
P57 SERIAL LINK = 01 (with 10 s watchdog) or 02 (without); P58 = address; P30 CONTROL sets how much the serial link may command (serial speed/auto modes). TB1 must be closed to unlock serial control.
What happens when the Lenze MCH Series HVAC drive (Modbus RTU) loses Modbus communication?
Fixed 10 s once #48 or #49 has unlocked the drive and P57 = with timer. Action depends on P30: normal modes drop out of serial control, serial speed modes follow P56 SERIAL LOSS, serial auto modes trip FLWR/SER fault.
Where is the official Lenze MCH Series HVAC drive (Modbus RTU) Modbus documentation?
The source is MCH Series Drives Modbus Communications Reference Guide (RG-MHMOD). Lenze doesn't publish it on its own website, so this map was re-typed from a free copy at https://www.precision-elec.com/wp-content/uploads/2014/08/lenze-ac-tech-mch-series-modbus-communications-reference.pdf. It may be an older revision, so check it against the live unit.
More Lenze Modbus register maps
- Variable frequency drive
Lenze i510 cabinet inverter 0.25-2.2 kW (Modbus RTU)
Lenze i510 cabinet inverters 0.25-2.2 kW with the Modbus/CANopen control unit, selector set to Modbus, firmware 01.01.01.00 as documented in the commissioning manual.
Also known as: i500 series, i510 Cabinet, I51AE - Variable frequency drive
Lenze MC Series drives MC1000 / MC3000 (Modbus RTU)
Lenze AC Tech MC1000 and MC3000 Series drives, software 213-083 rev 13 (parameter configurations 188-190); reference guide RG-MCMOD.
Also known as: MC1000, MC3000, MC Series, Lenze AC Tech MC, RG-MCMOD - Variable frequency drive
Lenze SCF Series drive with Modbus module (basic network control)
Lenze AC Tech SCF Series drives with the optional Modbus RTU communication module; application note AN0028/A1 (January 2008).
Also known as: SCF, Lenze AC Tech SCF, AN0028 - Variable frequency drive
Lenze SMVector drive with ESVZAR0 RS-485 Modbus module
Lenze AC Tech SMVector drives up to 10 HP with the ESVZAR0 RS-485 Modbus module, module software 1.01 / 1.10 / 1.30 (guide CMVMB401C).
Also known as: SMVector, SMV, ESVZAR0, Lenze AC Tech SMV, CMVMB401C
Other variable frequency drives register maps
- Variable frequency drive
Mitsubishi Electric FR-D700 compact inverter (PU connector, Modbus RTU)
FR-D700 series (FR-D720/D740/D720S/D710W) using the PU connector with Pr.549 = 1; Instruction Manual (Applied) revision H.
Also known as: FR-D720, FR-D740, FR-D720S, FR-D710W - Variable frequency drive
Schneider Electric Altivar Process ATV630 / ATV600 family (Modbus serial and Modbus TCP)
Altivar Process ATV600 drives (ATV630, ATV650 and other ATV6x0 models) on the embedded RJ45 Modbus serial port or the embedded Ethernet Modbus TCP server; register map per Communication Parameters file EAV64332 V4.6.
Also known as: ATV600, ATV630, ATV650, ATV660, ATV680, Altivar Process 600, ATV630U, ATV630D - Variable frequency drive
Siemens SINAMICS V20 inverter (Modbus RTU)
SINAMICS V20 basic inverters (1AC 230 V 6SL3210-5BB.. and 3AC 400 V 6SL3210-5BE..) using the built-in RS485 port with P2023 = 2 (Modbus), per operating instructions A5E34559884-006 (11/2016).
Also known as: V20, 6SL3210-5BB, 6SL3210-5BE - Variable frequency drive
TECO-Westinghouse L510 inverter (Modbus RTU/ASCII)
TECO-Westinghouse L510 micro inverters with the RS-485 option card, per communication addendum DOCUMENT-TECO-L510-AC001 Ver01 (2015-06).
Also known as: TECO L510, L510 Communication Addendum - Variable frequency drive (HVAC)
Yaskawa E7 HVAC drive (CIMR-E7U) - Modbus RTU
Yaskawa E7 (CIMR-E7U) HVAC fan and pump drives using the built-in RS-422/485 terminals with H5-08 = 0 (Memobus/Modbus), per Parameter Access Technical Manual TM.E7.11 (rev 3016).
Also known as: CIMR-E7U, E7U, E7 Drive - Variable frequency drive
Yaskawa HV305 HVAC micro drive (MEMOBUS/Modbus RTU)
Yaskawa HV305 drives using the built-in RS-485 port with H5-08 = 0 (MEMOBUS/Modbus), per technical reference SIEPYAIHV3001B.
Also known as: HV35U, HV305 drive, HV305 Versatile Compact Drive
All variable frequency drives Modbus register maps →
Source: MCH Series Drives Modbus Communications Reference Guide · RG-MHMOD · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.