Variable frequency drive · Modbus register map

Lenze MCH Series HVAC drive (Modbus RTU) Modbus register map

Updated 17 November 2026

Short answer

The MCH is a Lenze AC Tech drive family that acts as a Modbus RTU slave at a fixed 9600 baud. Registers #1-#50 hold the control word, speed commands, status bytes, fault code, kWh and run-time counters and PID values; programming parameter n sits at register n + 51.

This page lists 24 Modbus registers for the Lenze MCH Series HVAC drive (Modbus RTU) — 10 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Lenze’s own free documentation (linked below) and checked against it.

Manufacturer
Lenze
Model
MCH Series HVAC drive (Modbus RTU)
Equipment type
Variable frequency drive
Registers
24 (10 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
9600 baud, 8N2
Documented addressing
derived from parameter numbers
Firmware
MCH software 213-070 revision 00 (register #50 = 148)
Also known as
MCH, Lenze AC Tech MCH, RG-MHMOD
Source document
MCH Series Drives Modbus Communications Reference Guide · RG-MHMOD · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Lenze MCH Series HVAC drive (Modbus RTU)

Integration in brief

Set P57 (serial link) and P58 (address) on the keypad. Read #26-#29 for load, status, mode, source and fault. To control: write 0 to #48 to unlock #1, or the password (default 19) to also unlock #40/#42; start/stop via #1 and write speed to #40, or set serial select (0200h on #1) and write #42.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 48Unlock commandsUINT16Unlock controlWrite
HR 1Drive controlBITMAP16Start / stop / serial selectWrite
HR 40Keypad speed commandUINT16Keypad speed commandRead/write
HR 27Actual direction (high) / control mode (low)UINT16Control mode (low byte) and directionRead
HR 26Load (high byte) / operational status (low byte)UINT16Load and statusRead
HR 29Present fault (high) / commanded direction (low)UINT16Present faultRead

Enable Modbus control & writes

P57 SERIAL LINK = 01 (with 10 s watchdog) or 02 (without); P58 = address; P30 CONTROL sets how much the serial link may command (serial speed/auto modes). TB1 must be closed to unlock serial control.

Communication loss & watchdog

Fixed 10 s once #48 or #49 has unlocked the drive and P57 = with timer. Action depends on P30: normal modes drop out of serial control, serial speed modes follow P56 SERIAL LOSS, serial auto modes trip FLWR/SER fault.

Byte order & addressing

Network setup

Watch out for

Lenze MCH Series HVAC drive (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

24 of 24 shown
Lenze MCH Series HVAC drive (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR1doc #1 (4X 40002)Drive controlOne bit per write: 0004h stop, 0008h start, 0200h serial select, 0002h lock.BITMAP16Writebit 0 = Update buffers; bit 1 = Lock security; bit 2 = Stop drive; bit 3 = Start drive; bit 8 = Clear serial select flag; bit 9 = Set serial select flag
HR19doc #19 (4X 40020)Drive familyReads 68 (44h) for MCH.UINT16Read
HR21doc #21 (4X 40022)Drive size codeHP / voltage code (table 9 of the guide).UINT16Read
HR26doc #26 (4X 40027)Load (high byte) / operational status (low byte)High byte = % of full load. Low byte = status code, see notes.UINT16Read
HR27doc #27 (4X 40028)Actual direction (high) / control mode (low)High: 0 fwd, 1 rev. Low: 0 off, 1 hand, 2 auto, 3 serial.UINT16Read
HR28doc #28 (4X 40029)Speed source (high) / auto-hand (low)High: speed source code (notes). Low: 0 hand, 1 auto.UINT16Read
HR29doc #29 (4X 40030)Present fault (high) / commanded direction (low)High byte = fault code (notes). Low: 0 fwd, 1 rev.UINT16Read
HR30doc #30 (4X 40031)Motor voltageEffective output voltage to the motor, 0-999 V.UINT16VRead
HR32doc #32 (4X 40033)Kilowatt hours, low wordRead separately; total kWh = #33 x 65536 + #32.UINT16Read
HR33doc #33 (4X 40034)Kilowatt hours, high wordRead separately; total kWh = #33 x 65536 + #32.UINT16Read
HR36doc #36 (4X 40037)Total run time, hoursUINT16hRead
HR37doc #37 (4X 40038)Total run time, minutesUINT16minRead
HR38doc #38 (4X 40039)PID setpointInternal units 0-32736 over the feedback device range.UINT16Read
HR39doc #39 (4X 40040)PID feedbackInternal units 0-32736 over the feedback device range.UINT16Read
HR40doc #40 (4X 40041)Keypad speed command0-65000; writable after unlocking control.UINT16× 0.01HzRead/write
HR41doc #41 (4X 40042)Local PID commandInternal units 0-32736.UINT16Read/write
HR42doc #42 (4X 40043)Serial speed commandFollowed when the serial select flag is set.UINT16× 0.01HzRead/write
HR43doc #43 (4X 40044)Serial PID commandInternal units 0-32736.UINT16Read/write
HR48doc #48 (4X 40049)Unlock commands0 unlocks control; the password (default 19) also unlocks parameters.UINT16Write
HR49doc #49 (4X 40050)Unlock parametersPassword unlocks parameter writes only.UINT16Write
HR50doc #50 (4X 40051)Register versionParameter configuration number; 148 for software 213-070 rev 00.UINT16Read
HR81doc #81 (4X 40082)P30 controlUINT16Read/write0 = Normal (default); 1 = Norm no hand; 2 = Serial speed; 3 = S spd / no hand; 4 = Serial auto; 5 = S auto / no hand
HR108doc #108 (4X 40109)P57 serial linkUINT16Read/write0 = Disable (default); 1 = With timer; 2 = Without timer
HR109doc #109 (4X 40110)P58 serial address1-247 (default 30). Must be set before using the serial link.UINT16Read/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Lenze MCH Series HVAC drive (Modbus RTU)

What Modbus registers does the Lenze MCH Series HVAC drive (Modbus RTU) have?

This map lists 24 registers: 24 holding registers. 10 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Lenze MCH Series HVAC drive (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers derived from parameter numbers. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Lenze numbers by AC Tech register #, which is exactly the address sent on the wire (Modbus 4X/3X register numbers are one larger). The guide's frames confirm it: #24 is read with start address 0x0018. Programming parameter n = AC Tech register n + 51.

What are the minimum Modbus registers to integrate the Lenze MCH Series HVAC drive (Modbus RTU)?

Start with HR 48 Unlock commands (Unlock control); HR 1 Drive control (Start / stop / serial select); HR 40 Keypad speed command (Keypad speed command); HR 27 Actual direction (high) / control mode (low) (Control mode (low byte) and direction); HR 26 Load (high byte) / operational status (low byte) (Load and status); HR 29 Present fault (high) / commanded direction (low) (Present fault).

How do I enable Modbus control of the Lenze MCH Series HVAC drive (Modbus RTU)?

P57 SERIAL LINK = 01 (with 10 s watchdog) or 02 (without); P58 = address; P30 CONTROL sets how much the serial link may command (serial speed/auto modes). TB1 must be closed to unlock serial control.

What happens when the Lenze MCH Series HVAC drive (Modbus RTU) loses Modbus communication?

Fixed 10 s once #48 or #49 has unlocked the drive and P57 = with timer. Action depends on P30: normal modes drop out of serial control, serial speed modes follow P56 SERIAL LOSS, serial auto modes trip FLWR/SER fault.

Where is the official Lenze MCH Series HVAC drive (Modbus RTU) Modbus documentation?

The source is MCH Series Drives Modbus Communications Reference Guide (RG-MHMOD). Lenze doesn't publish it on its own website, so this map was re-typed from a free copy at https://www.precision-elec.com/wp-content/uploads/2014/08/lenze-ac-tech-mch-series-modbus-communications-reference.pdf. It may be an older revision, so check it against the live unit.