- MC Series drives MC1000 / MC3000 (Modbus RTU)
Variable frequency drive · Modbus register map
Lenze MC Series drives MC1000 / MC3000 (Modbus RTU) Modbus register map
Updated 17 November 2026
The MC1000/MC3000 are Lenze AC Tech drives with a Modbus RTU slave at a fixed 9600 baud. Registers #1-#50 hold the control word, keypad speed command, status bytes (load, run status, direction, source, fault), motor voltage, run time and PID values; programming parameter n sits at register n + 51.
This page lists 20 Modbus registers for the Lenze MC Series drives MC1000 / MC3000 (Modbus RTU) — 8 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Lenze’s own free documentation (linked below) and checked against it.
- Manufacturer
- Lenze
- Model
- MC Series drives MC1000 / MC3000 (Modbus RTU)
- Equipment type
- Variable frequency drive
- Registers
- 20 (8 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 9600 baud, 8N2
- Documented addressing
- derived from parameter numbers
- Firmware
- MC software 213-083 revision 13 (register #50 = 188, 189 or 190)
- Also known as
- MC1000, MC3000, MC Series, Lenze AC Tech MC, RG-MCMOD
Integration notes: Lenze MC Series drives MC1000 / MC3000 (Modbus RTU)
Set P57 and P58 on the keypad. Read #26-#29 (or the 6-register block at #24) for load, status, mode, source and fault. To control: write the password (default 19) to #48, send 0200h to #1 for manual mode, start/stop via #1 and write the speed to #40.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 48 | Unlock commands | UINT16 | Unlock control | Write |
| HR 1 | Drive control | BITMAP16 | Start / stop / direction | Write |
| HR 40 | Keypad speed command | UINT16 | Keypad speed command | Read/write |
| HR 27 | Actual direction (high) / control mode (low) | UINT16 | Control mode (low byte) and direction | Read |
| HR 26 | Load (high byte) / operational status (low byte) | UINT16 | Load and status | Read |
| HR 29 | Present fault (high) / commanded direction (low) | UINT16 | Present fault | Read |
Enable Modbus control & writes
P57 SERIAL LINK = 01 (with 10 s watchdog) or 02 (without); P58 = address; P30 CONTROL usually LOCAL on MC1000 and SERIAL on MC3000 for serial use.
Communication loss & watchdog
Fixed 10 s once #48 or #49 has unlocked the drive and P57 = with timer; in LOCAL/KEYPAD 2 control the drive stops on time-out (no fault is logged).
Byte order & addressing
- Read one register at a time except the #24 six-word block.
- FC16 accepts a single register only; FC03 and FC04 are identical.
- No broadcast support.
Network setup
- Fixed 9600 baud, 8 data bits, no parity, 2 stop bits.
Watch out for
- Changing CONTROL from LOCAL to REMOTE stops the drive immediately.
- End a session by writing 2 to #1 (lock security).
Lenze MC Series drives MC1000 / MC3000 (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 1doc #1 (4X 40002) | Drive control | One bit per write: 0004h stop, 0008h start, 0200h manual mode, 0002h lock. | BITMAP16 | Write | bit 0 = Update buffers; bit 1 = Lock security; bit 2 = Stop drive; bit 3 = Start drive; bit 6 = Set reverse; bit 7 = Set forward; bit 8 = Auto mode; bit 9 = Manual mode | |||
| HR | 19doc #19 (4X 40020) | Drive family | Reads 65 (41h) for MC Series. | UINT16 | Read | ||||
| HR | 21doc #21 (4X 40022) | Drive size code | HP / voltage code (table 9 of the guide). | UINT16 | Read | ||||
| HR | 26doc #26 (4X 40027) | Load (high byte) / operational status (low byte) | High byte = % of full load. Low byte = status code, see notes. | UINT16 | Read | ||||
| HR | 27doc #27 (4X 40028) | Actual direction (high) / control mode (low) | High: 0 fwd, 1 rev. Low: 0 local, 1 remote, 2 serial. | UINT16 | Read | ||||
| HR | 28doc #28 (4X 40029) | Speed source (high) / speed reference (low) | High: speed source code (notes). Low: 0 auto, 1 manual. | UINT16 | Read | ||||
| HR | 29doc #29 (4X 40030) | Present fault (high) / commanded direction (low) | High byte = fault code. Low: 0 fwd, 1 rev. | UINT16 | Read | ||||
| HR | 30doc #30 (4X 40031) | Motor voltage | Effective output voltage to the motor, 0-999 V. | UINT16 | V | Read | |||
| HR | 36doc #36 (4X 40037) | Total run time, hours | MC3000 only. | UINT16 | h | Read | |||
| HR | 37doc #37 (4X 40038) | Total run time, minutes | MC3000 only. | UINT16 | min | Read | |||
| HR | 38doc #38 (4X 40039) | PID setpoint | MC1000 with PID and MC3000. Internal units 0-32736 over the feedback range. | UINT16 | Read | ||||
| HR | 39doc #39 (4X 40040) | PID feedback | MC1000 with PID and MC3000. Internal units 0-32736 over the feedback range. | UINT16 | Read | ||||
| HR | 40doc #40 (4X 40041) | Keypad speed command | 0-65000; drive must be in manual mode (0200h to #1). | UINT16 | × 0.01 | Hz | Read/write | ||
| HR | 41doc #41 (4X 40042) | Local PID command | MC1000 with PID and MC3000. Internal units 0-32736 over the feedback range. | UINT16 | Read/write | ||||
| HR | 48doc #48 (4X 40049) | Unlock commands | 0 unlocks control; the password (default 19) also unlocks parameters. | UINT16 | Write | ||||
| HR | 49doc #49 (4X 40050) | Unlock parameters | Password unlocks parameter writes only. | UINT16 | Write | ||||
| HR | 50doc #50 (4X 40051) | Register version | Parameter configuration 188, 189 or 190 for software 213-083 rev 13. | UINT16 | Read | ||||
| HR | 81doc #81 (4X 40082) | P30 control | MC1000: 0 local, 1 remote, 2 both. MC3000 adds 2 serial, 3-5 (see notes). | UINT16 | Read/write | ||||
| HR | 108doc #108 (4X 40109) | P57 serial link | UINT16 | Read/write | 0 = Disable; 1 = With timer; 2 = Without timer | ||||
| HR | 109doc #109 (4X 40110) | P58 serial address | 1-247 (default 30). Set before using the serial link; avoid address 1. | UINT16 | Read/write |
Notes on this map
- Host: copy hosted by Precision Electric (a Lenze AC Tech distributor); no copy was found on lenze.com.
- Left out: command speed #24 and actual speed #25. Table 6 prints 0.1 Hz (0-2400), while the data-type table and notes 3a/3b say hundredths of a Hz (0x0201 = 5.13 Hz); the guide contradicts itself. #24 can still be read as a 6-register block starting at address 24.
- Operational status (low byte #26): 0 fault lockout, 1 fault, 2 start pending, 3 stop, 4 DC brake, 5 run at 0 Hz, 6 run, 7 accel, 8 decel, 9 current limit, 10 decel override, 11 lower transistors switching on, 12 sleep.
- Speed source (high byte #28): 0 keypad, 1 0-10 VDC, 2 4-20 mA, 3-6 preset 1-4, 7 MOP, 8 reserved, 9 keypad speed (PID enabled), 10 PID keypad setpoint, 11 0-10 VDC PID setpoint, 12 4-20 mA PID setpoint.
- No kWh registers are listed for the MC Series. Only the control registers and serial-setup parameters are included here.
- Present fault (high byte #29): 0 none, 1 output transistor, 3 high DC bus, 4 high drive temperature, 5 thermal overload, 7 low DC bus, 9 DC brake error, 10 follower loss, 11 dynamic brake overload, 12 power sag, 13 control, 14 language, 15 external, 16 internal 16, 17 power transient, 18-23 internal errors (2, 6 and 8 reserved).
- P30 CONTROL: MC1000 0 local (default), 1 remote, 2 both; MC3000 0 local (default), 1 remote, 2 serial, 3 keypad, 4 TB strip, 5 keypad 2.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Lenze MC Series drives MC1000 / MC3000 (Modbus RTU)
What Modbus registers does the Lenze MC Series drives MC1000 / MC3000 (Modbus RTU) have?
This map lists 20 registers: 20 holding registers. 8 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Lenze MC Series drives MC1000 / MC3000 (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers derived from parameter numbers. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Lenze numbers by AC Tech register #, which is the address sent on the wire (Modbus 4X/3X numbers are one larger). The frame examples confirm it: #24 is read at start address 0x0018. Programming parameter n = register n + 51.
What are the minimum Modbus registers to integrate the Lenze MC Series drives MC1000 / MC3000 (Modbus RTU)?
Start with HR 48 Unlock commands (Unlock control); HR 1 Drive control (Start / stop / direction); HR 40 Keypad speed command (Keypad speed command); HR 27 Actual direction (high) / control mode (low) (Control mode (low byte) and direction); HR 26 Load (high byte) / operational status (low byte) (Load and status); HR 29 Present fault (high) / commanded direction (low) (Present fault).
How do I enable Modbus control of the Lenze MC Series drives MC1000 / MC3000 (Modbus RTU)?
P57 SERIAL LINK = 01 (with 10 s watchdog) or 02 (without); P58 = address; P30 CONTROL usually LOCAL on MC1000 and SERIAL on MC3000 for serial use.
What happens when the Lenze MC Series drives MC1000 / MC3000 (Modbus RTU) loses Modbus communication?
Fixed 10 s once #48 or #49 has unlocked the drive and P57 = with timer; in LOCAL/KEYPAD 2 control the drive stops on time-out (no fault is logged).
Where is the official Lenze MC Series drives MC1000 / MC3000 (Modbus RTU) Modbus documentation?
The source is MC Series Drives Modbus Communications Reference Guide (RG-MCMOD). Lenze doesn't publish it on its own website, so this map was re-typed from a free copy at https://www.precision-elec.com/wp-content/uploads/2014/08/lenze-ac-tech-mc-series-modbus-communications-reference.pdf. It may be an older revision, so check it against the live unit.
More Lenze Modbus register maps
- Variable frequency drive
Lenze i510 cabinet inverter 0.25-2.2 kW (Modbus RTU)
Lenze i510 cabinet inverters 0.25-2.2 kW with the Modbus/CANopen control unit, selector set to Modbus, firmware 01.01.01.00 as documented in the commissioning manual.
Also known as: i500 series, i510 Cabinet, I51AE - Variable frequency drive
Lenze MCH Series HVAC drive (Modbus RTU)
Lenze AC Tech MCH Series drives, software 213-070 rev 00 (parameter configuration 148); reference guide RG-MHMOD.
Also known as: MCH, Lenze AC Tech MCH, RG-MHMOD - Variable frequency drive
Lenze SCF Series drive with Modbus module (basic network control)
Lenze AC Tech SCF Series drives with the optional Modbus RTU communication module; application note AN0028/A1 (January 2008).
Also known as: SCF, Lenze AC Tech SCF, AN0028 - Variable frequency drive
Lenze SMVector drive with ESVZAR0 RS-485 Modbus module
Lenze AC Tech SMVector drives up to 10 HP with the ESVZAR0 RS-485 Modbus module, module software 1.01 / 1.10 / 1.30 (guide CMVMB401C).
Also known as: SMVector, SMV, ESVZAR0, Lenze AC Tech SMV, CMVMB401C
Other variable frequency drives register maps
- Variable frequency drive
Mitsubishi Electric FR-A800 inverter (RS-485 terminals, Modbus RTU)
FR-A800 series inverters (FR-A820/A840/A842/A846, incl. -GF) using the built-in RS-485 terminals with Pr.549 = 1 (MODBUS RTU); Instruction Manual (Detailed) revision P.
Also known as: FR-A820, FR-A840, FR-A842, FR-A846, FR-A800-GF, FR-A800 series - Variable frequency drive
Schneider Electric Altivar Machine ATV340 (embedded Modbus serial / Modbus TCP)
ATV340 drives on the built-in Modbus serial port; Ethernet versions (ATV340...N4E) expose the same addresses on embedded Modbus TCP. Per Communication Parameters file NVE61728 V4.6.
Also known as: ATV340, Altivar 340, Altivar Machine ATV340, ATV340U, ATV340D, ATV340...N4E - Variable frequency drive
Siemens SINAMICS G120 / G120C (Modbus RTU)
SINAMICS G120 with an RS485 Control Unit (CU230P-2 HVAC/BT, CU240B-2, CU240E-2 / -2 F, CU250S-2), G120C USS/MB and G110M CU240M USS, firmware V4.7, per Fieldbuses function manual A5E34229197B AA. Not SINAMICS G120X, which has its own documentation.
Also known as: G120C USS/MB, CU230P-2 HVAC, CU230P-2 BT, CU240B-2, CU240E-2, CU240E-2 F, CU250S-2, G110M CU240M USS, G120P - Variable frequency drive (HVAC fan / pump)
TECO-Westinghouse F510 HVAC fan/pump inverter (Modbus RTU/ASCII)
TECO-Westinghouse F510 HVAC inverters using the built-in RS-485 port (CN6) in Modbus mode, per communication addendum DOCUMENT-TECO-F510-AC001 Ver01 (2015-03).
Also known as: TECO F510, F510 HVAC drive - Variable frequency drive
Yaskawa A1000 AC drive (MEMOBUS/Modbus RTU)
Yaskawa A1000 drives (CIMR-AU; 200 V, 400 V and 600 V classes) using the built-in RS-422/485 MEMOBUS/Modbus terminals (TB5), per Technical Manual SIEP C710616 41H.
Also known as: CIMR-AU, CIMR-AUA, A1000 High Performance Vector Control Drive - Variable frequency drive
Yaskawa GA800 AC drive (MEMOBUS/Modbus RTU)
Yaskawa GA800 drives using the built-in RS-485 MEMOBUS/Modbus port, per technical reference SIEPC71061737 revision G.
Also known as: CIPR-GA80, GA800 Industrial AC Microdrive
All variable frequency drives Modbus register maps →
Source: MC Series Drives Modbus Communications Reference Guide · RG-MCMOD · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.