Variable frequency drive · Modbus register map
Schneider Electric Altivar Machine ATV340 (embedded Modbus serial / Modbus TCP) Modbus register map
Updated 17 November 2026
Schneider Electric's high-performance machine drive with Modbus RTU on the built-in serial port, plus embedded Ethernet on the N4E versions. Each parameter has a fixed decimal logical address sent as the holding-register address. This map covers the CiA402 command and status words, frequency and speed references, the main monitors, energy counters, fault and warning codes, I/O states and the Modbus and channel settings needed for network control.
This page lists 73 Modbus registers for the Schneider Electric Altivar Machine ATV340 (embedded Modbus serial / Modbus TCP) — 41 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Schneider Electric’s own free documentation (linked below) and checked against it.
- Manufacturer
- Schneider Electric
- Model
- Altivar Machine ATV340 (embedded Modbus serial / Modbus TCP)
- Equipment type
- Variable frequency drive
- Registers
- 73 (41 writable)
- Transport
- Modbus RTU, Modbus TCP
- Default unit ID
- Not stated
- Default serial
- 19200 baud, 8E1
- Documented addressing
- 0-based (the number printed is the address on the wire)
- Also known as
- ATV340, Altivar 340, Altivar Machine ATV340, ATV340U, ATV340D, ATV340...N4E
- Source document
- ATV340 - Communication Parameters (Excel) · NVE61728 V4.6
Integration notes: Schneider Electric Altivar Machine ATV340 (embedded Modbus serial / Modbus TCP)
Set Add (6001) to 1-247 and power-cycle, keep CHCF = SIM and set FR1 to Modbus (164), then write CMD (8501) = 0006h followed by 000Fh with a non-zero LFR (8502, 0.1 Hz) or LFRD (8602, rpm). Poll ETA (3201), RFR (3202), HMIS (3240) and LFT (7121).
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 8501 | CMD - Command register | BITMAP16 | CMD: CiA402 run/stop/reset | Read/write |
| HR 8502 | LFR - Reference frequency | INT16 | LFR: frequency reference, 0.1 Hz | Read/write |
| HR 3201 | ETA - Status Register | BITMAP16 | ETA: CiA402 status word | Read |
| HR 3202 | RFR - Motor frequency | INT16 | RFR: output frequency, 0.1 Hz | Read |
| HR 3204 | LCR - Motor current | UINT16 | LCR: motor current (raw) | Read |
| HR 3240 | HMIS - Device state | UINT16 | HMIS: drive state code | Read |
| HR 7121 | LFT - Last error occurred | UINT16 | LFT: last fault code | Read |
| HR 3209 | THD - Drive thermal state | UINT16 | THD: drive thermal state | Read |
Enable Modbus control & writes
Set [Modbus Address] Add (logical 6001) to 1-247; the factory value 0 (OFF) means the drive does not answer. Speed and format default to 19200 baud, 8-E-1 (tbr 6003, tFO 6004). Communication changes take effect after a power cycle. For combined CiA402 control keep [Control Mode] CHCF = [Not separ.] SIM and set [Ref Freq 1 Config] FR1 = Modbus (164); for separate mode use CHCF = SEP with Cd1 = Modbus.
Communication loss & watchdog
[ModbusTimeout] ttO (6005), 0.1-30 s, factory 10 s. If no valid Modbus frame arrives within ttO on a monitored channel, the drive raises [Modbus Com Interruption] SLF1 and reacts per SLL (7010): factory freewheel stop, or ignore, configured stop, fallback speed LFF (7080), speed maintained, ramp stop, fast stop or DC injection.
Byte order & addressing
- Addresses are decimal logical numbers sent as-is (3201 = 0x0C81); do not subtract 1 or add 40001.
- CiA402 sequence: 0006h (shutdown) -> Ready to switch on, then 000Fh (enable operation) to run; 0007h disables operation, 0000h disables voltage, 0002h quick stop, 0080h rising edge resets a fault.
- Mask ETA with 006Fh to read the state: 0040h switch on disabled, 0021h ready to switch on, 0023h switched on, 0027h operation enabled, 0007h quick stop active, 0008h/0028h fault.
- CMD bit 11 is reverse direction by default ([Reverse Assign] rrS = C111); bits 12-15 can be assigned to functions (C112-C115).
Network setup
- Set Add, tbr and tFO in the [Communication] COM- / [Modbus SL] menu, then power-cycle the drive.
- RS-485 trunk: shielded twisted pair plus a common conductor; each line terminator is 120 ohm in series with 1 nF; the master supplies bus polarization.
- Write CMD and the reference at least once so the Modbus channel becomes active and monitored.
Watch out for
- Factory Add = OFF: a brand-new drive is silent on the bus.
- Configuration parameters (R/WS) are refused while the motor is running.
- CMI bit 1 (save to EEPROM) clears itself, but if CMI is written cyclically the master must write it back to 0; EEPROM life is about 100,000 writes.
Schneider Electric Altivar Machine ATV340 (embedded Modbus serial / Modbus TCP) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 3102 | SFR - Switching frequency | Range 2.0 kHz to 16.0 kHz. | UINT16 | × 0.1 | kHz | Read/write | ||
| HR | 3103 | TFR - Max frequency | Range 10.0 Hz to 599.0 Hz. Write only when stopped. | UINT16 | × 0.1 | Hz | Read/write | ||
| HR | 3104 | HSP - High speed | Range 0.0 Hz to 599.0 Hz. | UINT16 | × 0.1 | Hz | Read/write | ||
| HR | 3105 | LSP - Low speed | Range 0.0 Hz to 599.0 Hz. | UINT16 | × 0.1 | Hz | Read/write | ||
| HR | 3201 | ETA - Status Register | CiA402 status word. | BITMAP16 | Read | bit 0 = Ready to switch on; bit 1 = Switched on; bit 2 = Operation enabled (running); bit 3 = Fault; bit 4 = Voltage enabled (power stage supplied); bit 5 = Quick stop (0 = quick stop active); bit 6 = Switch on disabled; bit 7 = Warning active; bit 9 = Remote: command or reference via network; bit 10 = Target reference reached; bit 11 = Reference outside LSP/HSP limits; bit 14 = Stop via STOP key; bit 15 = Reverse rotation at output | |||
| HR | 3202 | RFR - Motor frequency | Signed; 0.1 Hz while CMI bit 9 = 0. | INT16 | × 0.1 | Hz | Read | ||
| HR | 3203 | FRH - Reference frequency before ramp | Range -599.0 Hz to 599.0 Hz. | INT16 | × 0.1 | Hz | Read | ||
| HR | 3204 | LCR - Motor current | Raw; resolution depends on drive rating (see notes). | UINT16 | Read | ||||
| HR | 3205 | OTR - Motor torque | Range -3276.7 % to 3276.7 %. | INT16 | × 0.1 | % | Read | ||
| HR | 3206 | ETI - Internal State register | BITMAP16 | Read | bit 0 = Access to the EEPROM non-volatile memory in progress | ||||
| HR | 3207 | ULN - Mains voltage | Range 0.0 V to 6553.5 V. | UINT16 | × 0.1 | V | Read | ||
| HR | 3208 | UOP - Motor voltage | Range 0 V to 65535 V. | UINT16 | V | Read | |||
| HR | 3209 | THD - Drive thermal state | Range 0 % to 200 %. | UINT16 | % | Read | |||
| HR | 3211 | OPR - Motor power in % | Range -32767 % to 32767 %. | INT16 | % | Read | |||
| HR | 3240 | HMIS - Device state | UINT16 | Read | 0 = Drive automatic tuning (TUN); 1 = DC injection (DCB); 2 = Ready (RDY); 3 = Freewheel stop (NST); 4 = Running (RUN); 5 = Accelerating (ACC); 6 = Decelerating (DEC); 7 = In current limitation (CLI); 8 = Fast stop (FST); 9 = Motor fluxing (FLU); 11 = No mains voltage (NLP); 13 = Control stopping (CTL); 14 = Dec ramp adaptation (OBR); 15 = Output cut (SOC); 17 = Undervoltage warning (USA); 18 = TC mode active (TC); 19 = In autotest (ST); 20 = Autotest error (FA); 21 = Autotest OK (OK); 22 = EEprom test (EP); 23 = Operating state "Fault" (FLT); 25 = DCP Flashing mode (DCP); 28 = SS1 active (SS1); 29 = SLS active (SLS); 30 = STO active (STO); 36 = Firmware Update (FWUP); 38 = Angle test (ASA); 40 = SOS active (SOS); 41 = SS2 active (SS2); 42 = SMS active (SMS); 43 = Safety configuration test (SCTP); 44 = Safety function (SFTY) | ||||
| HR | 3243 | VBUS - DC bus voltage | Range 0.0 V to 6553.5 V. | UINT16 | × 0.1 | V | Read | ||
| HR | 3263 | FSPD - Fan speed | Range 0 rpm to 65535 rpm. | UINT16 | rpm | Read | |||
| HR | 3297 | EPR - Active Electrical output power in % | Range -300 % to 300 %. | INT16 | % | Read | |||
| HR | 5202 | IL1R - Logic inputs states | BITMAP16 | Read | bit 0 = LI1 input state; bit 1 = LI2 input state; bit 2 = LI3 input state; bit 3 = LI4 input state; bit 4 = LI5 input state; bit 5 = LI6 input state; bit 6 = LI7 input state; bit 7 = LI8 input state; bit 10 = LI11 input state; bit 11 = LI12 input state; bit 12 = LI13 input state; bit 13 = LI14 input state; bit 14 = LI15 input state; bit 15 = LI16 input state | ||||
| HR | 5212 | OL1R - Logic outputs states | BITMAP16 | Read/write | bit 0 = R1 relay state; bit 1 = R2 relay state; bit 2 = R3 relay state; bit 3 = R4 relay state; bit 4 = R5 relay state; bit 5 = R6 relay state; bit 8 = DO1 output state; bit 9 = DO2 output state; bit 12 = DO11 output state; bit 13 = DO12 output state | ||||
| HR | 6001 | ADD - Device modbus address | Range 0 to 247. Factory 0. Write only when stopped. | UINT16 | Read/write | ||||
| HR | 6003 | TBR - Modbus baud rate | Factory [19200 bps]. Write only when stopped. | UINT16 | Read/write | 4 = Automatic (AUTO); 8 = 300 bps (300); 12 = 600 bps (600); 16 = 1.2 Kbps (1200); 20 = 2.4 Kbps (2400); 24 = 4800 bps (4800); 28 = 9600 bps (9600); 30 = 10 Kbps (10000); 32 = 19200 bps (19200); 34 = 20 Kbps (20000); 35 = 28.8 Kbps (28800); 36 = 38.4 Kbps (38400); 37 = 45.45 Kbps (45450); 38 = 50 Kbps (50000); 40 = 57.6 Kbps (57600); 41 = 76.8 Kbps (76800); 42 = 93.75 Kbps (93750); 44 = 100 Kbps (100K); 48 = 115.2 Kbps (115K2); 52 = 125 Kbps (125K); 53 = 156 Kbps (156K); 54 = 187.5 Kbps (187K5); 56 = 230.4 Kbps (230K4); 60 = 250 Kbps (250K); 64 = 460.8 Kbps (460K8); 68 = 500 Kbps (500K); 69 = 625 Kbps (625K); 70 = 800 Kbps (800K); 72 = 921.6 Kbps (921K6); 76 = 1 Mbps (1M); 80 = 1.5 Mbps (1M5); 81 = 2.5 Mbps (2M5); 82 = 3 Mbps (3M); 83 = 6 Mbps (6M); 84 = 10 Mbps (10M); 86 = 5 Mbps (5M); 88 = 12 Mbps (12M); 92 = 100 Mbps (100M) | |||
| HR | 6004 | TFO - Modbus format | Factory [8 bits even parity 1 stop bit]. Write only when stopped. | UINT16 | Read/write | 2 = 8bit odd parity 1stop bit (8O1); 3 = 8 bits even parity 1 stop bit (8E1); 4 = 8bit no parity 1stop bit (8N1); 5 = 8bit no parity 2stop bits (8N2) | |||
| HR | 6005 | TTO - Modbus timeout | Range 0.1 s to 30.0 s. Factory 10.0 s. Write only when stopped. | UINT16 | × 0.1 | s | Read/write | ||
| HR | 6010 | M1EC - Mdb CRC errors | Range 0 to 65535. | UINT16 | Read | ||||
| HR | 6011 | M1CT - Mdb frame number | Range 0 to 65535. | UINT16 | Read | ||||
| HR | 7010 | SLL - Response to Modbus interruption | Factory [Freewheel stop]. Write only when stopped. | UINT16 | Read/write | 0 = Ignore (NO); 1 = Freewheel stop (YES); 2 = Configured stop [STT] parameter (STT); 4 = Fallback speed (LFF); 5 = Speed maintained (RLS); 6 = Ramp stop (RMP); 7 = Fast stop (FST); 8 = DC injection (DCI) | |||
| HR | 7021 | ETHL - Ethernet error response | Factory [Freewheel stop]. Write only when stopped. | UINT16 | Read/write | 0 = Ignore (NO); 1 = Freewheel stop (YES); 2 = Configured stop [STT] parameter (STT); 4 = Fallback speed (LFF); 5 = Speed maintained (RLS); 6 = Ramp stop (RMP); 7 = Fast stop (FST); 8 = DC injection (DCI) | |||
| HR | 7080 | LFF - Fall back speed | Range 0.0 Hz to 599.0 Hz. Factory 0.0 Hz. Write only when stopped. | UINT16 | × 0.1 | Hz | Read/write | ||
| HR | 7121 | LFT - Last error occurred | UINT16 | Read | 0 = No error detected (NOF); 2 = Control memory error (EEF1); 3 = Incorrect configuration (CFF); 4 = Invalid configuration (CFI); 5 = Modbus communication interruption (SLF1); 6 = Internal communication interruption with option module (ILF); 7 = Fieldbus communication interruption (CNF); 8 = External detected error (EPF1); 9 = Overcurrent (OCF); 10 = Precharge capacitor (CRF1); 11 = Encoder feedback loss (SPF); 12 = Load slipping (ANF); 15 = Input Overheating (IHF); 16 = Device overheating (OHF); 17 = Motor overload (OLF); 18 = DC bus overvoltage (OBF); 19 = Supply mains overvoltage (OSF); 20 = Single output phase loss (OPF1); 21 = Input phase loss (PHF); 22 = Supply mains undervoltage (USF); 23 = Motor short circuit (SCF1); 24 = Motor overspeed (SOF); 25 = Autotuning detected error (TNF); 26 = Internal error 1 (Rating) (INF1); 27 = Internal error 2 (Soft) (INF2); 28 = Internal error 3 (Intern Comm) (INF3); 29 = Internal error 4 (Manufacturing) (INF4); 30 = Power memory error (EEF2); 32 = Ground short circuit (SCF3); 33 = Output phase loss (OPF2); 34 = CANopen communication interruption (COF); 35 = Brake control (BLF); 37 = Internal error 7 (Init) (INF7); 38 = External error detected by Fieldbus (EPF2); 40 = Internal error 8 (Switching Supply) (INF8); 41 = Brake feedback (BRF); 42 = PC communication interruption (SLF2); 43 = Encoder coupling (ECF); 44 = Torque limitation error (SSF); 45 = HMI communication interruption (SLF3); 51 = Internal error 9 (Measure) (INF9); 52 = Internal error 10 (Mains) (INFA); 53 = Internal error 11 (Temperature) (INFB); 54 = Device overheating (TJF); 55 = IGBT short circuit (SCF4); 56 = Motor short circuit (SCF5); 57 = Torque timeout (SRF); 58 = Output contactor closed error (FCF1); 59 = Output contactor opened error (FCF2); 60 = Internal error 12 (Internal current supply) (INFC); 62 = Encoder (ENF); 64 = input contactor (LCF); 65 = DB unit sh. circuit (BUF); 68 = Internal error 6 (Option) (INF6); 69 = Internal error 14 (CPU) (INFE); 70 = Braking resistor overload (BOF); 71 = AI3 4-20mA loss (LFF3); 72 = AI4 4-20mA loss (LFF4); 73 = Boards compatibility (HCF); 76 = Dynamic load detected error (DLF); 77 = Configuration transfer error (CFI2); 79 = AI5 4-20 mA loss (LFF5); 82 = ON lock error (LKON); 99 = Channel switching detected error (CSF); 100 = Process underload (ULF); 101 = Process overload (OLC); 105 = Angle error (ASF); 106 = AI1 4-20 mA loss (LFF1); 107 = Safety function detected error (SAFF); 112 = AI3 thermal level error (TH3F); 113 = Thermal sensor error on AI3 (T3CF); 120 = AI4 thermal level error (TH4F); 121 = Thermal sensor error on AI4 (T4CF); 122 = AI5 thermal level error (TH5F); 123 = Thermal sensor error on AI5 (T5CF); 128 = Program loading detected error (PGLF); 129 = Program running detected error (PGRF); 133 = Safety violation (SAVF); 134 = Safety configuration error (SCFF); 135 = Safety IO error (SIOF); 142 = Internal error 16 (IO module - relay) (INFG); 143 = Internal error 17 (IO module - Standard) (INFH); 144 = Internal error 0 (IPC) (INF0); 146 = Internal error 13 (Diff current) (INFD); 147 = Internal error 18 (Safety function module) (INFI); 148 = Motor stall detected error (STF); 149 = Internal error 21 (RTC) (INFL); 150 = Embedded Ethernet communication interruption (ETHF); 151 = Internal error 15 (Flash) (INFF); 152 = Firmware Update error (FWER); 153 = Internal error 22 (Embedded Ethernet) (INFM); 154 = Internal error 25 (Incompatibility CB & SW) (INFP); 155 = Internal error 20 (option interface PCBA) (INFK); 156 = Internal error 19 (Encoder module) (INFJ); 157 = Internal error 27 (Diagnostics CPLD) (INFR); 158 = Internal error 23 (Module link) (INFN); 159 = AFE ShortCircuit error (SCF6); 160 = AFE Bus unbalancing (OBF2); 161 = Internal error 28 (AFE) (INFS); 162 = Monitoring circuit A error (IFA); 163 = Monitoring circuit B error (IFB); 164 = Monitoring circuit C error (IFC); 165 = Monitoring circuit D error (IFD); 173 = Cabinet overheat error (CHF); 175 = Internal error 31 (Missing brick) (INFV); 176 = Internal error 29 (Inverter) (INFT); 177 = Internal error 30 (Rectifier) (INFU); 179 = AFE IGBT over-heat error (TJF2); 180 = AFE contactor feedback error (CRF3); 181 = Pre-settings transfer error (CFI3); 182 = Circuit breaker error (CBF); 184 = DB unit open circuit (BUFO); 185 = Drive overload (TLOF); 186 = MultiDrive Link error (MDLF); 187 = AI1 thermal level error (TH1F); 188 = Thermal sensor error on AI1 (T1CF); 189 = Backlash error (BSQF); 190 = M/S device error (MSDF); 194 = Encoder module thermal level error (THEF); 195 = Thermal sensor error on encoder module (TECF); 196 = Empty configuration (CFI4); 200 = FDR Eth embedded error (FDR1); 201 = FDR Eth module error (FDR2); 206 = DC Bus ripple error (DCRE); 208 = Idle mode exit error (IDLF); 209 = Load movement error (MDCF); 211 = Security files corrupt (SPFC) | ||||
| HR | 7200 | DP0 - Fault code on last fault | UINT16 | Read | 0 = No error detected (NOF); 2 = Control memory error (EEF1); 3 = Incorrect configuration (CFF); 4 = Invalid configuration (CFI); 5 = Modbus communication interruption (SLF1); 6 = Internal communication interruption with option module (ILF); 7 = Fieldbus communication interruption (CNF); 8 = External detected error (EPF1); 9 = Overcurrent (OCF); 10 = Precharge capacitor (CRF1); 11 = Encoder feedback loss (SPF); 12 = Load slipping (ANF); 15 = Input Overheating (IHF); 16 = Device overheating (OHF); 17 = Motor overload (OLF); 18 = DC bus overvoltage (OBF); 19 = Supply mains overvoltage (OSF); 20 = Single output phase loss (OPF1); 21 = Input phase loss (PHF); 22 = Supply mains undervoltage (USF); 23 = Motor short circuit (SCF1); 24 = Motor overspeed (SOF); 25 = Autotuning detected error (TNF); 26 = Internal error 1 (Rating) (INF1); 27 = Internal error 2 (Soft) (INF2); 28 = Internal error 3 (Intern Comm) (INF3); 29 = Internal error 4 (Manufacturing) (INF4); 30 = Power memory error (EEF2); 32 = Ground short circuit (SCF3); 33 = Output phase loss (OPF2); 34 = CANopen communication interruption (COF); 35 = Brake control (BLF); 37 = Internal error 7 (Init) (INF7); 38 = External error detected by Fieldbus (EPF2); 40 = Internal error 8 (Switching Supply) (INF8); 41 = Brake feedback (BRF); 42 = PC communication interruption (SLF2); 43 = Encoder coupling (ECF); 44 = Torque limitation error (SSF); 45 = HMI communication interruption (SLF3); 51 = Internal error 9 (Measure) (INF9); 52 = Internal error 10 (Mains) (INFA); 53 = Internal error 11 (Temperature) (INFB); 54 = Device overheating (TJF); 55 = IGBT short circuit (SCF4); 56 = Motor short circuit (SCF5); 57 = Torque timeout (SRF); 58 = Output contactor closed error (FCF1); 59 = Output contactor opened error (FCF2); 60 = Internal error 12 (Internal current supply) (INFC); 62 = Encoder (ENF); 64 = input contactor (LCF); 65 = DB unit sh. circuit (BUF); 68 = Internal error 6 (Option) (INF6); 69 = Internal error 14 (CPU) (INFE); 70 = Braking resistor overload (BOF); 71 = AI3 4-20mA loss (LFF3); 72 = AI4 4-20mA loss (LFF4); 73 = Boards compatibility (HCF); 76 = Dynamic load detected error (DLF); 77 = Configuration transfer error (CFI2); 79 = AI5 4-20 mA loss (LFF5); 82 = ON lock error (LKON); 99 = Channel switching detected error (CSF); 100 = Process underload (ULF); 101 = Process overload (OLC); 105 = Angle error (ASF); 106 = AI1 4-20 mA loss (LFF1); 107 = Safety function detected error (SAFF); 112 = AI3 thermal level error (TH3F); 113 = Thermal sensor error on AI3 (T3CF); 120 = AI4 thermal level error (TH4F); 121 = Thermal sensor error on AI4 (T4CF); 122 = AI5 thermal level error (TH5F); 123 = Thermal sensor error on AI5 (T5CF); 128 = Program loading detected error (PGLF); 129 = Program running detected error (PGRF); 133 = Safety violation (SAVF); 134 = Safety configuration error (SCFF); 135 = Safety IO error (SIOF); 142 = Internal error 16 (IO module - relay) (INFG); 143 = Internal error 17 (IO module - Standard) (INFH); 144 = Internal error 0 (IPC) (INF0); 146 = Internal error 13 (Diff current) (INFD); 147 = Internal error 18 (Safety function module) (INFI); 148 = Motor stall detected error (STF); 149 = Internal error 21 (RTC) (INFL); 150 = Embedded Ethernet communication interruption (ETHF); 151 = Internal error 15 (Flash) (INFF); 152 = Firmware Update error (FWER); 153 = Internal error 22 (Embedded Ethernet) (INFM); 154 = Internal error 25 (Incompatibility CB & SW) (INFP); 155 = Internal error 20 (option interface PCBA) (INFK); 156 = Internal error 19 (Encoder module) (INFJ); 157 = Internal error 27 (Diagnostics CPLD) (INFR); 158 = Internal error 23 (Module link) (INFN); 159 = AFE ShortCircuit error (SCF6); 160 = AFE Bus unbalancing (OBF2); 161 = Internal error 28 (AFE) (INFS); 162 = Monitoring circuit A error (IFA); 163 = Monitoring circuit B error (IFB); 164 = Monitoring circuit C error (IFC); 165 = Monitoring circuit D error (IFD); 173 = Cabinet overheat error (CHF); 175 = Internal error 31 (Missing brick) (INFV); 176 = Internal error 29 (Inverter) (INFT); 177 = Internal error 30 (Rectifier) (INFU); 179 = AFE IGBT over-heat error (TJF2); 180 = AFE contactor feedback error (CRF3); 181 = Pre-settings transfer error (CFI3); 182 = Circuit breaker error (CBF); 184 = DB unit open circuit (BUFO); 185 = Drive overload (TLOF); 186 = MultiDrive Link error (MDLF); 187 = AI1 thermal level error (TH1F); 188 = Thermal sensor error on AI1 (T1CF); 189 = Backlash error (BSQF); 190 = M/S device error (MSDF); 194 = Encoder module thermal level error (THEF); 195 = Thermal sensor error on encoder module (TECF); 196 = Empty configuration (CFI4); 200 = FDR Eth embedded error (FDR1); 201 = FDR Eth module error (FDR2); 206 = DC Bus ripple error (DCRE); 208 = Idle mode exit error (IDLF); 209 = Load movement error (MDCF); 211 = Security files corrupt (SPFC) | ||||
| HR | 7201 | DP1 - Fault code on fault n-1 | UINT16 | Read | 0 = No error detected (NOF); 2 = Control memory error (EEF1); 3 = Incorrect configuration (CFF); 4 = Invalid configuration (CFI); 5 = Modbus communication interruption (SLF1); 6 = Internal communication interruption with option module (ILF); 7 = Fieldbus communication interruption (CNF); 8 = External detected error (EPF1); 9 = Overcurrent (OCF); 10 = Precharge capacitor (CRF1); 11 = Encoder feedback loss (SPF); 12 = Load slipping (ANF); 15 = Input Overheating (IHF); 16 = Device overheating (OHF); 17 = Motor overload (OLF); 18 = DC bus overvoltage (OBF); 19 = Supply mains overvoltage (OSF); 20 = Single output phase loss (OPF1); 21 = Input phase loss (PHF); 22 = Supply mains undervoltage (USF); 23 = Motor short circuit (SCF1); 24 = Motor overspeed (SOF); 25 = Autotuning detected error (TNF); 26 = Internal error 1 (Rating) (INF1); 27 = Internal error 2 (Soft) (INF2); 28 = Internal error 3 (Intern Comm) (INF3); 29 = Internal error 4 (Manufacturing) (INF4); 30 = Power memory error (EEF2); 32 = Ground short circuit (SCF3); 33 = Output phase loss (OPF2); 34 = CANopen communication interruption (COF); 35 = Brake control (BLF); 37 = Internal error 7 (Init) (INF7); 38 = External error detected by Fieldbus (EPF2); 40 = Internal error 8 (Switching Supply) (INF8); 41 = Brake feedback (BRF); 42 = PC communication interruption (SLF2); 43 = Encoder coupling (ECF); 44 = Torque limitation error (SSF); 45 = HMI communication interruption (SLF3); 51 = Internal error 9 (Measure) (INF9); 52 = Internal error 10 (Mains) (INFA); 53 = Internal error 11 (Temperature) (INFB); 54 = Device overheating (TJF); 55 = IGBT short circuit (SCF4); 56 = Motor short circuit (SCF5); 57 = Torque timeout (SRF); 58 = Output contactor closed error (FCF1); 59 = Output contactor opened error (FCF2); 60 = Internal error 12 (Internal current supply) (INFC); 62 = Encoder (ENF); 64 = input contactor (LCF); 65 = DB unit sh. circuit (BUF); 68 = Internal error 6 (Option) (INF6); 69 = Internal error 14 (CPU) (INFE); 70 = Braking resistor overload (BOF); 71 = AI3 4-20mA loss (LFF3); 72 = AI4 4-20mA loss (LFF4); 73 = Boards compatibility (HCF); 76 = Dynamic load detected error (DLF); 77 = Configuration transfer error (CFI2); 79 = AI5 4-20 mA loss (LFF5); 82 = ON lock error (LKON); 99 = Channel switching detected error (CSF); 100 = Process underload (ULF); 101 = Process overload (OLC); 105 = Angle error (ASF); 106 = AI1 4-20 mA loss (LFF1); 107 = Safety function detected error (SAFF); 112 = AI3 thermal level error (TH3F); 113 = Thermal sensor error on AI3 (T3CF); 120 = AI4 thermal level error (TH4F); 121 = Thermal sensor error on AI4 (T4CF); 122 = AI5 thermal level error (TH5F); 123 = Thermal sensor error on AI5 (T5CF); 128 = Program loading detected error (PGLF); 129 = Program running detected error (PGRF); 133 = Safety violation (SAVF); 134 = Safety configuration error (SCFF); 135 = Safety IO error (SIOF); 142 = Internal error 16 (IO module - relay) (INFG); 143 = Internal error 17 (IO module - Standard) (INFH); 144 = Internal error 0 (IPC) (INF0); 146 = Internal error 13 (Diff current) (INFD); 147 = Internal error 18 (Safety function module) (INFI); 148 = Motor stall detected error (STF); 149 = Internal error 21 (RTC) (INFL); 150 = Embedded Ethernet communication interruption (ETHF); 151 = Internal error 15 (Flash) (INFF); 152 = Firmware Update error (FWER); 153 = Internal error 22 (Embedded Ethernet) (INFM); 154 = Internal error 25 (Incompatibility CB & SW) (INFP); 155 = Internal error 20 (option interface PCBA) (INFK); 156 = Internal error 19 (Encoder module) (INFJ); 157 = Internal error 27 (Diagnostics CPLD) (INFR); 158 = Internal error 23 (Module link) (INFN); 159 = AFE ShortCircuit error (SCF6); 160 = AFE Bus unbalancing (OBF2); 161 = Internal error 28 (AFE) (INFS); 162 = Monitoring circuit A error (IFA); 163 = Monitoring circuit B error (IFB); 164 = Monitoring circuit C error (IFC); 165 = Monitoring circuit D error (IFD); 173 = Cabinet overheat error (CHF); 175 = Internal error 31 (Missing brick) (INFV); 176 = Internal error 29 (Inverter) (INFT); 177 = Internal error 30 (Rectifier) (INFU); 179 = AFE IGBT over-heat error (TJF2); 180 = AFE contactor feedback error (CRF3); 181 = Pre-settings transfer error (CFI3); 182 = Circuit breaker error (CBF); 184 = DB unit open circuit (BUFO); 185 = Drive overload (TLOF); 186 = MultiDrive Link error (MDLF); 187 = AI1 thermal level error (TH1F); 188 = Thermal sensor error on AI1 (T1CF); 189 = Backlash error (BSQF); 190 = M/S device error (MSDF); 194 = Encoder module thermal level error (THEF); 195 = Thermal sensor error on encoder module (TECF); 196 = Empty configuration (CFI4); 200 = FDR Eth embedded error (FDR1); 201 = FDR Eth module error (FDR2); 206 = DC Bus ripple error (DCRE); 208 = Idle mode exit error (IDLF); 209 = Load movement error (MDCF); 211 = Security files corrupt (SPFC) | ||||
| HR | 7202 | DP2 - Fault code on fault n-2 | UINT16 | Read | 0 = No error detected (NOF); 2 = Control memory error (EEF1); 3 = Incorrect configuration (CFF); 4 = Invalid configuration (CFI); 5 = Modbus communication interruption (SLF1); 6 = Internal communication interruption with option module (ILF); 7 = Fieldbus communication interruption (CNF); 8 = External detected error (EPF1); 9 = Overcurrent (OCF); 10 = Precharge capacitor (CRF1); 11 = Encoder feedback loss (SPF); 12 = Load slipping (ANF); 15 = Input Overheating (IHF); 16 = Device overheating (OHF); 17 = Motor overload (OLF); 18 = DC bus overvoltage (OBF); 19 = Supply mains overvoltage (OSF); 20 = Single output phase loss (OPF1); 21 = Input phase loss (PHF); 22 = Supply mains undervoltage (USF); 23 = Motor short circuit (SCF1); 24 = Motor overspeed (SOF); 25 = Autotuning detected error (TNF); 26 = Internal error 1 (Rating) (INF1); 27 = Internal error 2 (Soft) (INF2); 28 = Internal error 3 (Intern Comm) (INF3); 29 = Internal error 4 (Manufacturing) (INF4); 30 = Power memory error (EEF2); 32 = Ground short circuit (SCF3); 33 = Output phase loss (OPF2); 34 = CANopen communication interruption (COF); 35 = Brake control (BLF); 37 = Internal error 7 (Init) (INF7); 38 = External error detected by Fieldbus (EPF2); 40 = Internal error 8 (Switching Supply) (INF8); 41 = Brake feedback (BRF); 42 = PC communication interruption (SLF2); 43 = Encoder coupling (ECF); 44 = Torque limitation error (SSF); 45 = HMI communication interruption (SLF3); 51 = Internal error 9 (Measure) (INF9); 52 = Internal error 10 (Mains) (INFA); 53 = Internal error 11 (Temperature) (INFB); 54 = Device overheating (TJF); 55 = IGBT short circuit (SCF4); 56 = Motor short circuit (SCF5); 57 = Torque timeout (SRF); 58 = Output contactor closed error (FCF1); 59 = Output contactor opened error (FCF2); 60 = Internal error 12 (Internal current supply) (INFC); 62 = Encoder (ENF); 64 = input contactor (LCF); 65 = DB unit sh. circuit (BUF); 68 = Internal error 6 (Option) (INF6); 69 = Internal error 14 (CPU) (INFE); 70 = Braking resistor overload (BOF); 71 = AI3 4-20mA loss (LFF3); 72 = AI4 4-20mA loss (LFF4); 73 = Boards compatibility (HCF); 76 = Dynamic load detected error (DLF); 77 = Configuration transfer error (CFI2); 79 = AI5 4-20 mA loss (LFF5); 82 = ON lock error (LKON); 99 = Channel switching detected error (CSF); 100 = Process underload (ULF); 101 = Process overload (OLC); 105 = Angle error (ASF); 106 = AI1 4-20 mA loss (LFF1); 107 = Safety function detected error (SAFF); 112 = AI3 thermal level error (TH3F); 113 = Thermal sensor error on AI3 (T3CF); 120 = AI4 thermal level error (TH4F); 121 = Thermal sensor error on AI4 (T4CF); 122 = AI5 thermal level error (TH5F); 123 = Thermal sensor error on AI5 (T5CF); 128 = Program loading detected error (PGLF); 129 = Program running detected error (PGRF); 133 = Safety violation (SAVF); 134 = Safety configuration error (SCFF); 135 = Safety IO error (SIOF); 142 = Internal error 16 (IO module - relay) (INFG); 143 = Internal error 17 (IO module - Standard) (INFH); 144 = Internal error 0 (IPC) (INF0); 146 = Internal error 13 (Diff current) (INFD); 147 = Internal error 18 (Safety function module) (INFI); 148 = Motor stall detected error (STF); 149 = Internal error 21 (RTC) (INFL); 150 = Embedded Ethernet communication interruption (ETHF); 151 = Internal error 15 (Flash) (INFF); 152 = Firmware Update error (FWER); 153 = Internal error 22 (Embedded Ethernet) (INFM); 154 = Internal error 25 (Incompatibility CB & SW) (INFP); 155 = Internal error 20 (option interface PCBA) (INFK); 156 = Internal error 19 (Encoder module) (INFJ); 157 = Internal error 27 (Diagnostics CPLD) (INFR); 158 = Internal error 23 (Module link) (INFN); 159 = AFE ShortCircuit error (SCF6); 160 = AFE Bus unbalancing (OBF2); 161 = Internal error 28 (AFE) (INFS); 162 = Monitoring circuit A error (IFA); 163 = Monitoring circuit B error (IFB); 164 = Monitoring circuit C error (IFC); 165 = Monitoring circuit D error (IFD); 173 = Cabinet overheat error (CHF); 175 = Internal error 31 (Missing brick) (INFV); 176 = Internal error 29 (Inverter) (INFT); 177 = Internal error 30 (Rectifier) (INFU); 179 = AFE IGBT over-heat error (TJF2); 180 = AFE contactor feedback error (CRF3); 181 = Pre-settings transfer error (CFI3); 182 = Circuit breaker error (CBF); 184 = DB unit open circuit (BUFO); 185 = Drive overload (TLOF); 186 = MultiDrive Link error (MDLF); 187 = AI1 thermal level error (TH1F); 188 = Thermal sensor error on AI1 (T1CF); 189 = Backlash error (BSQF); 190 = M/S device error (MSDF); 194 = Encoder module thermal level error (THEF); 195 = Thermal sensor error on encoder module (TECF); 196 = Empty configuration (CFI4); 200 = FDR Eth embedded error (FDR1); 201 = FDR Eth module error (FDR2); 206 = DC Bus ripple error (DCRE); 208 = Idle mode exit error (IDLF); 209 = Load movement error (MDCF); 211 = Security files corrupt (SPFC) | ||||
| HR | 7203 | DP3 - Fault code on fault n-3 | UINT16 | Read | 0 = No error detected (NOF); 2 = Control memory error (EEF1); 3 = Incorrect configuration (CFF); 4 = Invalid configuration (CFI); 5 = Modbus communication interruption (SLF1); 6 = Internal communication interruption with option module (ILF); 7 = Fieldbus communication interruption (CNF); 8 = External detected error (EPF1); 9 = Overcurrent (OCF); 10 = Precharge capacitor (CRF1); 11 = Encoder feedback loss (SPF); 12 = Load slipping (ANF); 15 = Input Overheating (IHF); 16 = Device overheating (OHF); 17 = Motor overload (OLF); 18 = DC bus overvoltage (OBF); 19 = Supply mains overvoltage (OSF); 20 = Single output phase loss (OPF1); 21 = Input phase loss (PHF); 22 = Supply mains undervoltage (USF); 23 = Motor short circuit (SCF1); 24 = Motor overspeed (SOF); 25 = Autotuning detected error (TNF); 26 = Internal error 1 (Rating) (INF1); 27 = Internal error 2 (Soft) (INF2); 28 = Internal error 3 (Intern Comm) (INF3); 29 = Internal error 4 (Manufacturing) (INF4); 30 = Power memory error (EEF2); 32 = Ground short circuit (SCF3); 33 = Output phase loss (OPF2); 34 = CANopen communication interruption (COF); 35 = Brake control (BLF); 37 = Internal error 7 (Init) (INF7); 38 = External error detected by Fieldbus (EPF2); 40 = Internal error 8 (Switching Supply) (INF8); 41 = Brake feedback (BRF); 42 = PC communication interruption (SLF2); 43 = Encoder coupling (ECF); 44 = Torque limitation error (SSF); 45 = HMI communication interruption (SLF3); 51 = Internal error 9 (Measure) (INF9); 52 = Internal error 10 (Mains) (INFA); 53 = Internal error 11 (Temperature) (INFB); 54 = Device overheating (TJF); 55 = IGBT short circuit (SCF4); 56 = Motor short circuit (SCF5); 57 = Torque timeout (SRF); 58 = Output contactor closed error (FCF1); 59 = Output contactor opened error (FCF2); 60 = Internal error 12 (Internal current supply) (INFC); 62 = Encoder (ENF); 64 = input contactor (LCF); 65 = DB unit sh. circuit (BUF); 68 = Internal error 6 (Option) (INF6); 69 = Internal error 14 (CPU) (INFE); 70 = Braking resistor overload (BOF); 71 = AI3 4-20mA loss (LFF3); 72 = AI4 4-20mA loss (LFF4); 73 = Boards compatibility (HCF); 76 = Dynamic load detected error (DLF); 77 = Configuration transfer error (CFI2); 79 = AI5 4-20 mA loss (LFF5); 82 = ON lock error (LKON); 99 = Channel switching detected error (CSF); 100 = Process underload (ULF); 101 = Process overload (OLC); 105 = Angle error (ASF); 106 = AI1 4-20 mA loss (LFF1); 107 = Safety function detected error (SAFF); 112 = AI3 thermal level error (TH3F); 113 = Thermal sensor error on AI3 (T3CF); 120 = AI4 thermal level error (TH4F); 121 = Thermal sensor error on AI4 (T4CF); 122 = AI5 thermal level error (TH5F); 123 = Thermal sensor error on AI5 (T5CF); 128 = Program loading detected error (PGLF); 129 = Program running detected error (PGRF); 133 = Safety violation (SAVF); 134 = Safety configuration error (SCFF); 135 = Safety IO error (SIOF); 142 = Internal error 16 (IO module - relay) (INFG); 143 = Internal error 17 (IO module - Standard) (INFH); 144 = Internal error 0 (IPC) (INF0); 146 = Internal error 13 (Diff current) (INFD); 147 = Internal error 18 (Safety function module) (INFI); 148 = Motor stall detected error (STF); 149 = Internal error 21 (RTC) (INFL); 150 = Embedded Ethernet communication interruption (ETHF); 151 = Internal error 15 (Flash) (INFF); 152 = Firmware Update error (FWER); 153 = Internal error 22 (Embedded Ethernet) (INFM); 154 = Internal error 25 (Incompatibility CB & SW) (INFP); 155 = Internal error 20 (option interface PCBA) (INFK); 156 = Internal error 19 (Encoder module) (INFJ); 157 = Internal error 27 (Diagnostics CPLD) (INFR); 158 = Internal error 23 (Module link) (INFN); 159 = AFE ShortCircuit error (SCF6); 160 = AFE Bus unbalancing (OBF2); 161 = Internal error 28 (AFE) (INFS); 162 = Monitoring circuit A error (IFA); 163 = Monitoring circuit B error (IFB); 164 = Monitoring circuit C error (IFC); 165 = Monitoring circuit D error (IFD); 173 = Cabinet overheat error (CHF); 175 = Internal error 31 (Missing brick) (INFV); 176 = Internal error 29 (Inverter) (INFT); 177 = Internal error 30 (Rectifier) (INFU); 179 = AFE IGBT over-heat error (TJF2); 180 = AFE contactor feedback error (CRF3); 181 = Pre-settings transfer error (CFI3); 182 = Circuit breaker error (CBF); 184 = DB unit open circuit (BUFO); 185 = Drive overload (TLOF); 186 = MultiDrive Link error (MDLF); 187 = AI1 thermal level error (TH1F); 188 = Thermal sensor error on AI1 (T1CF); 189 = Backlash error (BSQF); 190 = M/S device error (MSDF); 194 = Encoder module thermal level error (THEF); 195 = Thermal sensor error on encoder module (TECF); 196 = Empty configuration (CFI4); 200 = FDR Eth embedded error (FDR1); 201 = FDR Eth module error (FDR2); 206 = DC Bus ripple error (DCRE); 208 = Idle mode exit error (IDLF); 209 = Load movement error (MDCF); 211 = Security files corrupt (SPFC) | ||||
| HR | 7393 | FNB - Fault counter | Range 0 to 65535. | UINT16 | Read | ||||
| HR | 8401 | CHCF - Control mode configuration | Factory [Combined channel mode]. Write only when stopped. | UINT16 | Read/write | 1 = Combined channel mode (SIM); 2 = Separated channel mode (SEP); 3 = I/O mode (IO) | |||
| HR | 8413 | FR1 - Configuration reference frequency 1 | Write only when stopped. | UINT16 | Read/write | 0 = Not configured (NO); 1 = AI1 Analog input (AI1); 2 = AI2 Analog input (AI2); 3 = AI3 Analog input (AI3); 4 = AI4 Analog input (AI4); 5 = AI5 Analog input (AI5); 129 = Motor current (OCR); 130 = Motor frequency (OFR); 131 = Ramp output (ORP); 132 = Motor torque (TRQ); 133 = Signed torque (STQ); 134 = Signed ramp (ORS); 135 = PID reference (OPS); 136 = PID feedback (OPF); 137 = PID error (OPE); 138 = PID output (OPI); 139 = Motor power in % (OPR); 140 = Motor thermal state (THR); 141 = Drive thermal state (THD); 142 = Torque 4Q (TR4Q); 143 = Measured motor frequency (OFRR); 145 = Motor frequency without filter (OFR1); 160 = Reference frequency via DI (UPDT); 163 = Local HMI (LCC); 164 = Reference frequency via Modbus (MDB); 167 = Reference frequency via CANopen (CAN); 169 = Reference frequency via Com module (NET); 171 = Embedded Ethernet (ETH); 173 = Signed output frequency (OFS); 174 = Motor thermal 2 state (THR2); 175 = Motor thermal 3 state (THR3); 176 = Motor thermal 4 state (THR4); 177 = Unsigned torque reference (UTR); 178 = Signed torque reference (STR); 179 = Torque limit (TQL); 180 = Motor voltage (UOP); 181 = Pulse input (PI); 182 = Encoder reference (PG); 183 = AI Virtual 1 (AIV1); 184 = Digital output 1 (DO1); 188 = DI7 pulseInput (PI7); 189 = DI8 pulseInput (PI8); 344 = M/S output speed reference (MSSO); 345 = M/S output torque reference (MSTO) | |||
| HR | 8423 | CD1 - Command channel 1 assign | Factory [Terminal block]. Write only when stopped. | UINT16 | Read/write | 1 = Terminal block (TER); 3 = Local HMI (LCC); 10 = Modbus communication (MDB); 20 = CANopen communication (CAN); 30 = Ext. communication module (NET); 40 = Ethernet Embedded (ETH) | |||
| HR | 8441 | CRC - Channel for reference frequency | BITMAP16 | Read | bit 0 = Terminals; bit 1 = Local keypad; bit 2 = Remote keypad; bit 3 = Modbus; bit 6 = CANopen; bit 7 = Terminal up-Down speed; bit 8 = Remote keypad up-down speed; bit 9 = COM option board; bit 11 = Embedded Ethernet; bit 14 = Indus; bit 15 = PowerSuite | ||||
| HR | 8442 | CCC - Active command channel | BITMAP16 | Read | bit 0 = Terminals; bit 1 = Local keypad; bit 2 = Remote keypad; bit 3 = Modbus; bit 6 = CANopen; bit 7 = Terminal up-Down speed; bit 8 = Remote keypad up-down speed; bit 9 = COM option board; bit 11 = Embedded Ethernet; bit 14 = Indus; bit 15 = PowerSuite | ||||
| HR | 8501 | CMD - Command register | CiA402 control word (I/O-profile bits when CHCF = IO). | BITMAP16 | Read/write | bit 0 = CiA402: Switch on; bit 1 = CiA402: Enable voltage; bit 2 = CiA402: Quick stop (0 = quick stop active); bit 3 = CiA402: Enable operation (run); bit 7 = CiA402: Fault reset on 0->1 edge; bit 8 = CiA402: Halt (stop per Stt, stays in Operation enabled); bit 11 = CiA402: assignable, default reverse direction (rrS = C111); bit 12 = Assignable (C112); bit 13 = Assignable (C113); bit 14 = Assignable (C114); bit 15 = Assignable (C115) | |||
| HR | 8502 | LFR - Reference frequency | Signed; 0.1 Hz while CMI bit 9 = 0. | INT16 | × 0.1 | Hz | Read/write | ||
| HR | 8503 | PISP - PIDSet point | Range 0 to 1000. | UINT16 | Read/write | ||||
| HR | 8504 | CMI - Extended control word | Save to EEPROM, factory reset, LFR unit select. | BITMAP16 | Read/write | bit 0 = Restore factory settings (drive stopped); bit 1 = Save configuration to EEPROM (drive stopped); bit 9 = LFR/RFR unit: 0 = 0.1 Hz, 1 = signed value where 32767 = tFr; bit 15 = 1 = parameter consistency check off (drive locked in stop) | |||
| HR | 8602 | LFRD - Speed setpoint | Signed speed reference in rpm. | INT16 | rpm | Read/write | |||
| HR | 8604 | RFRD - Output velocity | Range -32767 rpm to 32767 rpm. | INT16 | rpm | Read | |||
| HR | 8605 | FRHD - Speed reference before ramp | Range -32767 rpm to 32767 rpm. | INT16 | rpm | Read | |||
| HR | 9001 | ACC - Acceleration ramp time | Raw; resolution set by INR (factory 0.1 s). | UINT16 | Read/write | ||||
| HR | 9002 | DEC - Deceleration ramp time | Raw; resolution set by INR (factory 0.1 s). | UINT16 | Read/write | ||||
| HR | 9020 | INR - Ramp increment | Factory [Tenths of seconds]. | UINT16 | Read/write | 0 = hundredths of seconds (001); 1 = Tenths of seconds (01); 2 = seconds (1) | |||
| HR | 9601 | UNS - Nominal motor voltage | Range 100 V to 690 V. Write only when stopped. | UINT16 | V | Read/write | |||
| HR | 9602 | FRS - Nominal motor frequency | Range 10.0 Hz to 599.0 Hz. Write only when stopped. | UINT16 | × 0.1 | Hz | Read/write | ||
| HR | 9604 | NSP - Nominal motor speed | Range 0 rpm to 65535 rpm. Write only when stopped. | UINT16 | rpm | Read/write | |||
| HR | 9630 | THR - Motor thermal state | Range 0 % to 200 %. | UINT16 | % | Read | |||
| HR | 10606 | OC0 - Electrical energy consumed by the motor (Wh) | Range 0 Wh to 999 Wh. Write only when stopped. | UINT16 | Wh | Read/write | |||
| HR | 10607 | OC1 - Electrical energy consumed by the motor (KWh) | Range 0 kWh to 999 kWh. Write only when stopped. | UINT16 | kWh | Read/write | |||
| HR | 10608 | OC2 - Electrical energy consumed by the motor (MWh) | Range 0 MWh to 999 MWh. Write only when stopped. | UINT16 | MWh | Read/write | |||
| HR | 10609 | OC3 - Electrical energy consumed by the motor (GWh) | Range 0 GWh to 999 GWh. Write only when stopped. | UINT16 | GWh | Read/write | |||
| HR | 10610 | OC4 - Electrical energy consumed by the motor (TWh) | Range 0 TWh to 999 TWh. Write only when stopped. | UINT16 | TWh | Read/write | |||
| HR | 10626 | IC0 - Input Energy (Wh) | Range 0 Wh to 999 Wh. Write only when stopped. | UINT16 | Wh | Read/write | |||
| HR | 10627 | IC1 - Input Energy (kWh) | Range 0 kWh to 999 kWh. Write only when stopped. | UINT16 | kWh | Read/write | |||
| HR | 10628 | IC2 - Input Energy (MWh) | Range 0 MWh to 999 MWh. Write only when stopped. | UINT16 | MWh | Read/write | |||
| HR | 10629 | IC3 - Input Energy (GWh) | Range 0 GWh to 999 GWh. Write only when stopped. | UINT16 | GWh | Read/write | |||
| HR | 10630 | IC4 - Input Energy (TWh) | Range 0 TWh to 999 TWh. Write only when stopped. | UINT16 | TWh | Read/write | |||
| HR | 11201 | STT - Type of stop | Write only when stopped. | UINT16 | Read/write | 0 = On ramp (RMP); 1 = Fast stop (FST); 2 = Freewheel stop (NST); 3 = DC injection (DCI) | |||
| HR | 11983 | RPO - PID output | Range -3276.7 Hz to 3276.7 Hz. | INT16 | × 0.1 | Hz | Read | ||
| HR | 12701 | NMA1 - Scan input 1 address | Range 0 to 65535. Factory 3201. Write only when stopped. | UINT16 | Read/write | ||||
| HR | 12721 | NCA1 - Scan output 1 address | Range 0 to 65535. Factory 8501. Write only when stopped. | UINT16 | Read/write | ||||
| HR | 12741 | NM1 - Com scan input 1 value | Range 0 to 65535. | UINT16 | Read | ||||
| HR | 12761 | NC1 - Com scan output 1 value | Range 0 to 65535. | UINT16 | Read | ||||
| HR | 12890 | LALR - Last warning | UINT16 | Read | 0 = No warning stored (NOA); 1 = Fallback frequency reaction (FRF); 2 = Speed maintained (RLS); 3 = Type of stop (STT); 4 = Reference frequency warning (SRA); 18 = PID error warning (PEE); 19 = PID feedback warning (PFA); 20 = PID high feedback warning (PFAH); 21 = PID low feedback warning (PFAL); 22 = Regulation warning (PISH); 23 = Limit switch reached (LSA); 24 = Slack rope warning (RSDA); 25 = Dynamic load warning (DLDA); 27 = AI3 thermal sensor warning (TP3A); 28 = AI4 thermal sensor warning (TP4A); 29 = AI5 thermal sensor warning (TP5A); 30 = AI1 4-20 loss warning (AP1); 32 = AI3 4-20 loss warning (AP3); 33 = AI4 4-20 loss warning (AP4); 34 = AI5 4-20 loss warning (AP5); 35 = Device thermal state warning (THA); 36 = Thermal junction warning (TJA); 37 = Fan counter warning (FCTA); 39 = Braking resistor thermal warning (BOA); 40 = External error warning (EFA); 41 = Undervoltage warning (USA); 42 = Preventive undervoltage active (UPA); 44 = Motor frequency high threshold reached (FTA); 45 = Motor frequency low threshold reached (FTAL); 46 = Pulse warning threshold reached (FQLA); 47 = Motor frequency low threshold 2 reached (F2AL); 48 = High speed reached (FLA); 49 = Reference frequency high threshold reached (RTAH); 50 = Reference frequency low threshold reached (RTAL); 51 = 2nd frequency threshold reached (F2A); 52 = Current threshold reached (CTA); 53 = Low current threshold reached (CTAL); 54 = High torque warning (TTHA); 55 = Low torque warning (TTLA); 56 = Process underload warning (ULA); 57 = Process overload warning (OLA); 58 = Torque limit reached (SSA); 59 = Torque control warning (RTA); 60 = Device thermal threshold reached (TAD); 61 = Motor thermal threshold reached (TSA); 62 = Motor 2 thermal threshold reached (TS2); 63 = Motor 3 thermal threshold reached (TS3); 64 = Motor 4 thermal threshold reached (TS4); 65 = Power high threshold reached (PTHA); 66 = Power low threshold reached (PTHL); 67 = Customer warning 1 (CAS1); 68 = Customer warning 2 (CAS2); 69 = Customer warning 3 (CAS3); 70 = Customer warning 4 (CAS4); 71 = Customer warning 5 (CAS5); 73 = Power Consumption warning (POWD); 83 = Slipping warning (ANA); 85 = Load movement warning (BSA); 86 = Brake contact warning (BCA); 87 = AI1 thermal sensor warning (TP1A); 89 = Current reduction warning (TLOW); 97 = Monitoring circuit A warning (IWA); 98 = Monitoring circuit B warning (IWB); 99 = Monitoring circuit C warning (IWC); 100 = Monitoring circuit D warning (IWD); 110 = Fieldbus communication loss fallback channel is active (AFFL); 124 = M/S device warning (MSDA); 125 = Backlash warning (BSQA); 126 = Encoder module thermal warning (TPEA); 133 = Temperature sensor AI1 warning (TS1A); 135 = Temperature sensor AI3 warning (TS3A); 136 = Temperature sensor AI4 warning (TS4A); 137 = Temperature sensor AI5 warning (TS5A); 138 = DC bus ripple warning (DCRW); 143 = ON lock warning (LKON); 144 = Power backup mode warning (RFTA); 145 = Internal error 22 (Embedded Ethernet) (INFM); 146 = Modbus communication interruption warning (SLF1) | ||||
| HR | 64400 | IM00 - IP mode Ethernet Embd | Factory [DHCP]. | UINT16 | Read/write | 0 = Fixed address (MANU); 1 = BOOTP (BOOTP); 2 = DHCP (DHCP); 3 = DCP (DCP) | |||
| HR | 64415 | TTOB - Ethernet embedded : time-out | Range 0.1 s to 30.0 s. Factory 10.0 s. Write only when stopped. | UINT16 | × 0.1 | s | Read/write |
Notes on this map
- Second source: Altivar Machine ATV340 Modbus Serial Line Manual NVE61654 (06/2016), https://download.schneider-electric.com/files?p_Doc_Ref=NVE61654 - addressing examples, function codes, settings, the CiA402 sequence and the CMD/ETA bit layout (the parameter file does not break these two words out bit by bit).
- Every register in this map is a single 16-bit word. 32-bit values (RTH motor run time 3244, PTH power-on time 3246, both UINT32 in seconds) are left out because neither document states their word order.
- LFR (8502) and RFR (3202) are 0.1 Hz only while CMI bit 9 = 0; with bit 9 = 1 they become a signed value where 32767 = tFr. The parameter file states this in the CMI bit 9 description.
- LCR (3204) is left unscaled: the parameter file says 'refer to programming manual' and the programming manual (NVE61643) only says the unit follows the drive rating.
- ACC/DEC (9001/9002) are raw values; their resolution follows INR (9020): 0 = 0.01 s, 1 = 0.1 s (factory), 2 = 1 s.
- Energy is split into 0-999 registers per decade: motor energy = OC4 TWh + OC3 GWh + OC2 MWh + OC1 kWh + OC0 Wh; input energy likewise with IC0-IC4.
- Value lists for HMIS, LFT/DP0-DP3, LALR, FR1 (PSA list), CD1, TBR and the stop/fault reactions are copied from the Enumerations sheet.
- Registers shown as RW that the file lists as R/WS can only be written while the drive is not running.
- Left out: NCR, ITH, AI physical values, PID feedback/reference and SPD because their unit is 'refer to programming manual'; option-card, safety and function-block parameters.
- ETHL, IM00 and TTOB only apply to the Ethernet versions (ATV340...N4E). Neither source states the Modbus TCP port, so tcp_port is left null.
- Ethernet manual NVE61653 (12/2018, https://download.schneider-electric.com/files?p_Doc_Ref=NVE61653): on Modbus TCP, Unit ID 0 or 248 reaches the drive parameters at the same logical addresses; Unit ID 255 is the I/O scanner.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Schneider Electric Altivar Machine ATV340 (embedded Modbus serial / Modbus TCP)
What Modbus registers does the Schneider Electric Altivar Machine ATV340 (embedded Modbus serial / Modbus TCP) have?
This map lists 73 registers: 73 holding registers. 41 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Schneider Electric Altivar Machine ATV340 (embedded Modbus serial / Modbus TCP) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The parameter file gives each logical address in hex and decimal (16#0C81 = 3201); the decimal value goes into the request unchanged. The Modbus serial manual's example reads W3102-W3105 by sending start address 0C1E hex (= 3102) and writes W9001 at 2329 hex, so there is no 40001 offset and no minus 1.
What are the minimum Modbus registers to integrate the Schneider Electric Altivar Machine ATV340 (embedded Modbus serial / Modbus TCP)?
Start with HR 8501 CMD - Command register (CMD: CiA402 run/stop/reset); HR 8502 LFR - Reference frequency (LFR: frequency reference, 0.1 Hz); HR 3201 ETA - Status Register (ETA: CiA402 status word); HR 3202 RFR - Motor frequency (RFR: output frequency, 0.1 Hz); HR 3204 LCR - Motor current (LCR: motor current (raw)); HR 3240 HMIS - Device state (HMIS: drive state code); HR 7121 LFT - Last error occurred (LFT: last fault code); HR 3209 THD - Drive thermal state (THD: drive thermal state).
How do I enable Modbus control of the Schneider Electric Altivar Machine ATV340 (embedded Modbus serial / Modbus TCP)?
Set [Modbus Address] Add (logical 6001) to 1-247; the factory value 0 (OFF) means the drive does not answer. Speed and format default to 19200 baud, 8-E-1 (tbr 6003, tFO 6004). Communication changes take effect after a power cycle. For combined CiA402 control keep [Control Mode] CHCF = [Not separ.] SIM and set [Ref Freq 1 Config] FR1 = Modbus (164); for separate mode use CHCF = SEP with Cd1 = Modbus.
What happens when the Schneider Electric Altivar Machine ATV340 (embedded Modbus serial / Modbus TCP) loses Modbus communication?
[ModbusTimeout] ttO (6005), 0.1-30 s, factory 10 s. If no valid Modbus frame arrives within ttO on a monitored channel, the drive raises [Modbus Com Interruption] SLF1 and reacts per SLL (7010): factory freewheel stop, or ignore, configured stop, fallback speed LFF (7080), speed maintained, ramp stop, fast stop or DC injection.
Where is the official Schneider Electric Altivar Machine ATV340 (embedded Modbus serial / Modbus TCP) Modbus documentation?
The source is ATV340 - Communication Parameters (Excel) (NVE61728 V4.6), published free by Schneider Electric at https://download.schneider-electric.com/files?p_Doc_Ref=NVE61728.
More Schneider Electric Modbus register maps
- Energy meter (pulse and status concentrator)
Schneider Electric Acti 9 Smartlink Modbus (A9XMSB11) 11-channel I/O and pulse concentrator
Acti 9 Smartlink Modbus RS-485 module A9XMSB11, per user manual DOCA0004EN-06 (04/2016).
Also known as: Acti 9 Smartlink, Smartlink Modbus, A9XMSB11, Acti9 Smartlink - Variable frequency drive (HVAC fans and pumps)
Schneider Electric Altivar 212 (embedded Modbus RTU)
ATV212H (IP21) and ATV212W (IP55) drives on the built-in Modbus RTU ports (RJ45 and open-style terminal), per Modbus manual S1A53844.
Also known as: ATV212, Altivar 212, ATV212H, ATV212W, ATV212HU15N4, ATV212WD11N4 - Variable frequency drive
Schneider Electric Altivar Machine ATV320 (embedded Modbus RTU)
ATV320 Book (ATV320...B) and Compact (ATV320...C) drives on the built-in RJ45 Modbus serial port; register map per Communication Parameters file NVE41316 V3.5.
Also known as: ATV320, Altivar 320, ATV320U, ATV320D, ATV320 Book, ATV320 Compact - Variable frequency drive
Schneider Electric Altivar Process ATV630 / ATV600 family (Modbus serial and Modbus TCP)
Altivar Process ATV600 drives (ATV630, ATV650 and other ATV6x0 models) on the embedded RJ45 Modbus serial port or the embedded Ethernet Modbus TCP server; register map per Communication Parameters file EAV64332 V4.6.
Also known as: ATV600, ATV630, ATV650, ATV660, ATV680, Altivar Process 600, ATV630U, ATV630D - Variable frequency drive
Schneider Electric Altivar Process ATV900 (ATV930/ATV950, embedded Modbus serial / Modbus TCP)
Altivar Process ATV900 drives (ATV930, ATV950) on the built-in Modbus serial port and the embedded Ethernet port (Modbus TCP). Per Communication Parameters file NHA80944 V4.6.
Also known as: ATV900, ATV930, ATV950, Altivar Process 900, Altivar 930, Altivar 950, ATV930U, ATV930D, ATV950U - Power meter (circuit breaker trip unit)
Schneider Electric ComPact NSX MicroLogic trip unit, standard dataset (IFM / IFE interface)
Standard dataset registers 32000-32341 served by the IFM (Modbus RTU) or IFE (Modbus TCP) interface for ComPact NSX; the same table lists availability for ComPact NS / MasterPact NT/NW and MasterPact MTZ. Per DOCA0091EN-09 (07/2022).
Also known as: ComPact NSX, Compact NSX, MicroLogic 5.2 E, MicroLogic 6.2 E, MicroLogic 7.2 E, MicroLogic 5.3 A, MicroLogic 6.3 E, IFM LV434000, IFE LV434001, IFE LV434002, ComPact NS, MasterPact NT, MasterPact NW, MasterPact MTZ - Solar inverter
Schneider Electric Conext CL three-phase PV inverter 18/20/25 kVA
Conext CL (IEC, PVSCL20E/25E) and Conext CL-NA (PVSCL18NA/25NA) three-phase string inverters, map revision 1.5.
Also known as: Conext CL-NA, Conext CL-E, PVSCL18NA, PVSCL20E, PVSCL25E, PVSCL25NA - Solar inverter
Schneider Electric Conext Core XC Series grid-tie PV inverter (0G-XC-BB)
Conext Core XC Series grid-tied PV inverters (540/630/680 kW ratings, 0G-XC-BB) with firmware v1.07 and later; some registers need newer firmware as noted.
Also known as: 0G-XC-BB, XC-AIC15P - Variable frequency drive
Schneider Electric Easy Altivar ATV610 (embedded Modbus serial)
Easy Altivar ATV610 drives on the built-in Modbus serial port, per Communication Parameters file EAV64394 V1.6.
Also known as: ATV610, Altivar 610, Easy Altivar 610, Altivar Easy 610, ATV610U, ATV610D - EV charger
Schneider Electric EVlink Pro AC charging station (Modbus TCP)
EVlink Pro AC charging stations (T2S socket, attached cable, and T2S plus domestic socket versions), software 1.1.6 to 1.4.0.
Also known as: EVlink Pro AC - Energy meter (wireless sensors through an Ethernet gateway)
Schneider Electric PowerTag Energy wireless sensors via PowerTag Link gateway (Modbus TCP)
PowerTag Energy 63, M250/M630, F160 and Rope sensors read through a PowerTag Link or PowerTag Link HD gateway, per DOCA0157EN-09 (10/2025).
Also known as: PowerTag Link, PowerTag Link HD, A9XMWD20, A9XMWD100, PowerTag Energy 63, A9MEM1520, A9MEM1540, A9MEM1560, A9MEM1570, PowerTag M250, PowerTag M630, LV434020, PowerTag F160, A9MEM1580, PowerTag Rope, A9MEM1590 - Motor management and protection relay
Schneider Electric TeSys T LTMR motor management controller (Modbus RTU)
TeSys T LTMR Modbus controllers (LTMR..M..), with or without the LTMEV40 expansion module, per DOCA0130EN-03 (02/2024).
Also known as: TeSys T, LTMR, LTMR08MBD, LTMR27MBD, LTMR100MBD, LTMR08MFM, LTMR27MFM, LTMR100MFM, LTMR..M, LTMEV40 - Air handler (rack-mounted room cooling unit, split DX)
Schneider Electric Uniflair Rack Mounted Room Cooling ACRMD4K
Schneider Electric Uniflair Rack Mounted Room Cooling units ACRMD4Kxxx (indoor rack unit with matching outdoor unit), register map part number 990-91589.
Also known as: ACRMD4K, ACRMD4Kxxx, Uniflair rack mounted room cooling, 990-91589
Other variable frequency drives register maps
- Variable frequency drive
Siemens SINAMICS G120 / G120C (Modbus RTU)
SINAMICS G120 with an RS485 Control Unit (CU230P-2 HVAC/BT, CU240B-2, CU240E-2 / -2 F, CU250S-2), G120C USS/MB and G110M CU240M USS, firmware V4.7, per Fieldbuses function manual A5E34229197B AA. Not SINAMICS G120X, which has its own documentation.
Also known as: G120C USS/MB, CU230P-2 HVAC, CU230P-2 BT, CU240B-2, CU240E-2, CU240E-2 F, CU250S-2, G110M CU240M USS, G120P - Variable frequency drive (HVAC fan / pump)
TECO-Westinghouse F510 HVAC fan/pump inverter (Modbus RTU/ASCII)
TECO-Westinghouse F510 HVAC inverters using the built-in RS-485 port (CN6) in Modbus mode, per communication addendum DOCUMENT-TECO-F510-AC001 Ver01 (2015-03).
Also known as: TECO F510, F510 HVAC drive - Variable frequency drive
Yaskawa A1000 AC drive (MEMOBUS/Modbus RTU)
Yaskawa A1000 drives (CIMR-AU; 200 V, 400 V and 600 V classes) using the built-in RS-422/485 MEMOBUS/Modbus terminals (TB5), per Technical Manual SIEP C710616 41H.
Also known as: CIMR-AU, CIMR-AUA, A1000 High Performance Vector Control Drive - Variable frequency drive
Yaskawa GA800 AC drive (MEMOBUS/Modbus RTU)
Yaskawa GA800 drives using the built-in RS-485 MEMOBUS/Modbus port, per technical reference SIEPC71061737 revision G.
Also known as: CIPR-GA80, GA800 Industrial AC Microdrive - Variable frequency drive
Yaskawa iQpump605 intelligent pump controller (MEMOBUS/Modbus RTU)
Yaskawa iQpump605 drives using the built-in RS-485 port (MEMOBUS/Modbus RTU), per user manual SIEPYAIWM6502D.
Also known as: WM65W, iQpump605 drive, iQpump605 Intelligent Pump Controller - Variable frequency drive
Yaskawa V1000 AC drive (MEMOBUS/Modbus RTU)
Yaskawa V1000 drives (CIMR-VU; 200 V single/three-phase and 400 V three-phase, 0.1-18.5 kW) using the built-in RS-422/485 MEMOBUS/Modbus terminals, per Technical Manual SIEP C710606 18F.
Also known as: CIMR-VU, V1000 Compact Vector Control Drive
All variable frequency drives Modbus register maps →
Source: ATV340 - Communication Parameters (Excel) · NVE61728 V4.6. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.