- PowerTag Energy wireless sensors via PowerTag Link gateway (Modbus TCP)
Energy meter (wireless sensors through an Ethernet gateway) · Modbus register map
Schneider Electric PowerTag Energy wireless sensors via PowerTag Link gateway (Modbus TCP) Modbus register map
Updated 19 November 2026
PowerTag Energy sensors clip onto breakers and report over radio to a PowerTag Link gateway, which serves each sensor as its own Modbus TCP server address (1-247). Every sensor exposes the same register block: currents, voltages, power and power factor as big-endian floats, and energy counters as 64-bit integers in Wh. Which registers a sensor fills depends on its type (63 A, M250/M630, F160/Rope).
This page lists 83 Modbus registers for the Schneider Electric PowerTag Energy wireless sensors via PowerTag Link gateway (Modbus TCP) — 20 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Schneider Electric’s own free documentation (linked below) and checked against it.
- Manufacturer
- Schneider Electric
- Model
- PowerTag Energy wireless sensors via PowerTag Link gateway (Modbus TCP)
- Registers
- 83 (20 writable)
- Transport
- Modbus TCP
- Default unit ID
- Not stated
- TCP port
- 502
- Documented addressing
- 1-based (subtract 1 for the wire address)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- PowerTag Link, PowerTag Link HD, A9XMWD20, A9XMWD100, PowerTag Energy 63, A9MEM1520, A9MEM1540, A9MEM1560, A9MEM1570, PowerTag M250, PowerTag M630, LV434020, PowerTag F160, A9MEM1580, PowerTag Rope, A9MEM1590
Integration notes: Schneider Electric PowerTag Energy wireless sensors via PowerTag Link gateway (Modbus TCP)
Connect to the gateway on TCP port 502, use each sensor's Modbus address as the unit ID, and read 3000-3110 (floats) plus the 64-bit energy registers 3204-3212.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 2999 | RMS current on phase A | FLOAT32 ABCD | Phase A current | Read |
| HR 3027 | RMS phase-to-neutral voltage A-N | FLOAT32 ABCD | Phase A-N voltage | Read |
| HR 3059 | Total active power | FLOAT32 ABCD | Total active power | Read |
| HR 3083 | Total power factor | FLOAT32 ABCD | Total power factor | Read |
| HR 3203 | Total active energy delivered + received (non-resettable) | INT64 ABCD | Total active energy (not resettable) | Read |
| HR 3211 | Total active energy received (non-resettable) | INT64 ABCD | Total active energy received | Read |
Enable Modbus control & writes
Modbus TCP is on by default on the gateway. The gateway gives each paired wireless device a Modbus address (1-247), which can be changed on its web pages.
Byte order & addressing
- Unit ID selects the sensor, not the gateway; 255 addresses the gateway itself.
- Energy is in Wh/VARh/VAh as signed 64-bit integers.
- Not every register is filled by every sensor type.
Network setup
- The gateway takes its IP address by DHCP by default; a static IPv4 address can be set on its web pages.
- Check or edit each wireless device's Modbus address in that device's parameters on the web pages.
Watch out for
- The gateway flags a communication-loss alarm when it hears nothing from a device for 6 times that device's communication period.
- The guide lists two misprinted hex addresses; trust the decimal register numbers.
Schneider Electric PowerTag Energy wireless sensors via PowerTag Link gateway (Modbus TCP) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 2999doc 3000 (0x0BB7) | RMS current on phase A | Sensors: PowerTag 63, M250, M630, F160, Rope | FLOAT32 | ABCD | A | Read | ||
| HR | 3001doc 3002 (0x0BB9) | RMS current on phase B | Sensors: PowerTag 63, M250, M630, F160, Rope | FLOAT32 | ABCD | A | Read | ||
| HR | 3003doc 3004 (0x0BBB) | RMS current on phase C | Sensors: PowerTag 63, M250, M630, F160, Rope | FLOAT32 | ABCD | A | Read | ||
| HR | 3005doc 3006 (0x0BBD) | RMS current on neutral | Sensors: F160, Rope | FLOAT32 | ABCD | A | Read | ||
| HR | 3019doc 3020 (0x0BCB) | RMS phase-to-phase voltage A-B | Sensors: PowerTag 63, M250, M630, F160, Rope | FLOAT32 | ABCD | V | Read | ||
| HR | 3021doc 3022 (0x0BCD) | RMS phase-to-phase voltage B-C | Sensors: PowerTag 63, M250, M630, F160, Rope | FLOAT32 | ABCD | V | Read | ||
| HR | 3023doc 3024 (0x0BCF) | RMS phase-to-phase voltage C-A | Sensors: PowerTag 63, M250, M630, F160, Rope | FLOAT32 | ABCD | V | Read | ||
| HR | 3027doc 3028 (0x0BD3) | RMS phase-to-neutral voltage A-N | Sensors: PowerTag 63, M250, M630, F160, Rope | FLOAT32 | ABCD | V | Read | ||
| HR | 3029doc 3030 (0x0BD5) | RMS phase-to-neutral voltage B-N | Sensors: PowerTag 63, M250, M630, F160, Rope | FLOAT32 | ABCD | V | Read | ||
| HR | 3031doc 3032 (0x0BD7) | RMS phase-to-neutral voltage C-N | Sensors: PowerTag 63, M250, M630, F160, Rope | FLOAT32 | ABCD | V | Read | ||
| HR | 3053doc 3054 (0x0BED) | Active power on phase A | Sensors: PowerTag 63, M250, M630, F160, Rope | FLOAT32 | ABCD | W | Read | ||
| HR | 3055doc 3056 (0x0BEF) | Active power on phase B | Sensors: PowerTag 63, M250, M630, F160, Rope | FLOAT32 | ABCD | W | Read | ||
| HR | 3057doc 3058 (0x0BF1) | Active power on phase C | Sensors: PowerTag 63, M250, M630, F160, Rope | FLOAT32 | ABCD | W | Read | ||
| HR | 3059doc 3060 (0x0BF3) | Total active power | Sensors: PowerTag 63, M250, M630, F160, Rope | FLOAT32 | ABCD | W | Read | ||
| HR | 3061doc 3062 (0x0BF5) | Reactive power on phase A | Sensors: F160, Rope | FLOAT32 | ABCD | VAR | Read | ||
| HR | 3063doc 3064 (0x0BF7) | Reactive power on phase B | Sensors: F160, Rope | FLOAT32 | ABCD | VAR | Read | ||
| HR | 3065doc 3066 (0x0BF9) | Reactive power on phase C | Sensors: F160, Rope | FLOAT32 | ABCD | VAR | Read | ||
| HR | 3067doc 3068 (0x0BFB) | Total reactive power | Sensors: M250, M630, F160, Rope | FLOAT32 | ABCD | VAR | Read | ||
| HR | 3069doc 3070 (0x0BFD) | Apparent power on phase A | Sensors: F160, Rope | FLOAT32 | ABCD | VA | Read | ||
| HR | 3071doc 3072 (0x0BFF) | Apparent power on phase B | Sensors: F160, Rope | FLOAT32 | ABCD | VA | Read | ||
| HR | 3073doc 3074 (0x0C01) | Apparent power on phase C | Sensors: F160, Rope | FLOAT32 | ABCD | VA | Read | ||
| HR | 3075doc 3076 (0x0C03) | Total apparent power (arithmetic) | Sensors: PowerTag 63, M250, M630, F160, Rope | FLOAT32 | ABCD | VA | Read | ||
| HR | 3077doc 3078 (0x0C05) | Power factor on phase A | Sensors: F160, Rope | FLOAT32 | ABCD | Read | |||
| HR | 3079doc 3080 (0x0C07) | Power factor on phase B | Sensors: F160, Rope | FLOAT32 | ABCD | Read | |||
| HR | 3081doc 3082 (0x0C09) | Power factor on phase C | Sensors: F160, Rope | FLOAT32 | ABCD | Read | |||
| HR | 3083doc 3084 (0x0C0B) | Total power factor | Sensors: PowerTag 63, M250, M630, F160, Rope | FLOAT32 | ABCD | Read | |||
| HR | 3085doc 3086 (0x0C0D) | Power factor sign convention | Sensors: F160, Rope | UINT16 | Read | 0 = IEC; 1 = IEEE | |||
| HR | 3109doc 3110 (0x0C25) | AC frequency | Sensors: M250, M630, F160, Rope | FLOAT32 | ABCD | Hz | Read | ||
| HR | 3131doc 3132 (0x0C3B) | Device internal temperature | Sensors: M250, M630, F160, Rope | FLOAT32 | ABCD | °C | Read | ||
| HR | 3203doc 3204 (0x0C83) | Total active energy delivered + received (non-resettable) | Sensors: PowerTag 63, M250, M630, F160, Rope | INT64 | ABCD | Wh | Read | ||
| HR | 3207doc 3208 (0x0C87) | Total active energy delivered count positively (non-resettable) | Sensors: PowerTag 63, M250, M630, F160, Rope | INT64 | ABCD | Wh | Read | ||
| HR | 3211doc 3212 (0x0C8B) | Total active energy received (non-resettable) | Sensors: PowerTag 63, M250, M630, F160, Rope | INT64 | ABCD | Wh | Read | ||
| HR | 3215doc 3216 (0x0C8F) | Phase A active energy delivered - received (non-resettable) | Sensors: M250, M630 | INT64 | ABCD | Wh | Read | ||
| HR | 3219doc 3220 (0x0C93) | Phase B active energy delivered - received (non-resettable) | Sensors: M250, M630 | INT64 | ABCD | Wh | Read | ||
| HR | 3223doc 3224 (0x0C97) | Phase C active energy delivered - received (non-resettable) | Sensors: M250, M630 | INT64 | ABCD | Wh | Read | ||
| HR | 3255doc 3256 (0x0CB7) | Partial active energy delivered + received (resettable) | Sensors: PowerTag 63, M250, M630, F160, Rope | INT64 | ABCD | Wh | Read | ||
| HR | 3263doc 3264 (0x0CBF) | Partial active energy delivered (resettable) | Sensors: PowerTag 63, M250, M630, F160, Rope | INT64 | ABCD | Wh | Read | ||
| HR | 3271doc 3272 (0x0CC7) | Partial active energy received (resettable) | Sensors: PowerTag 63, M250, M630, F160, Rope | INT64 | ABCD | Wh | Read | ||
| HR | 3279doc 3280 (0x0CCF) | Partial reactive energy delivered (resettable) | Sensors: M250, M630, F160, Rope | INT64 | ABCD | VARh | Read | ||
| HR | 3287doc 3288 (0x0CD7) | Partial reactive energy received (resettable) | Sensors: M250, M630, F160, Rope | INT64 | ABCD | VARh | Read | ||
| HR | 3765doc 3766 (0x0EB5) | Demand total active power | Sensors: PowerTag 63, F160, Rope | FLOAT32 | ABCD | W | Read | ||
| HR | 3769doc 3770 (0x0EB9) | Maximum Demand total active power | Sensors: PowerTag 63, F160, Rope | FLOAT32 | ABCD | W | Read | ||
| HR | 5008doc 5009 (0x1390) | Active energy delivered (resettable) | Sensors: PowerTag 63, F160, Rope | INT64 | ABCD | Wh | Read/write | ||
| HR | 5012doc 5013 (0x1394) | Active energy delivered count positively (non-resettable) | Sensors: PowerTag 63, F160, Rope | INT64 | ABCD | Wh | Read | ||
| HR | 5016doc 5017 (0x1398) | Active energy received (resettable) | Sensors: PowerTag 63, F160, Rope | INT64 | ABCD | Wh | Read/write | ||
| HR | 5020doc 5021 (0x139C) | Active energy received count negatively (non-resettable) | Sensors: PowerTag 63, F160, Rope | INT64 | ABCD | Wh | Read | ||
| HR | 5048doc 5049 (0x13B8) | Phase A active energy delivered (resettable) | Sensors: F160, Rope | INT64 | ABCD | Wh | Read/write | ||
| HR | 5052doc 5053 (0x13BC) | Phase A active energy delivered (non-resettable) | Sensors: F160, Rope | INT64 | ABCD | Wh | Read | ||
| HR | 5056doc 5057 (0x13C0) | Phase A active energy received (resettable) | Sensors: F160, Rope | INT64 | ABCD | Wh | Read/write | ||
| HR | 5060doc 5061 (0x13C4) | Phase A active energy received (non-resettable) | Sensors: F160, Rope | INT64 | ABCD | Wh | Read | ||
| HR | 5076doc 5077 (0x13D4) | Phase A active energy delivered + received (non-resettable) | Sensors: F160, Rope | INT64 | ABCD | Wh | Read | ||
| HR | 5088doc 5089 (0x13E0) | Phase B active energy delivered (resettable) | Sensors: F160, Rope | INT64 | ABCD | Wh | Read/write | ||
| HR | 5092doc 5093 (0x13E4) | Phase B active energy delivered (non-resettable) | Sensors: F160, Rope | INT64 | ABCD | Wh | Read | ||
| HR | 5096doc 5097 (0x13E8) | Phase B active energy received (resettable) | Sensors: F160, Rope | INT64 | ABCD | Wh | Read/write | ||
| HR | 5100doc 5101 (0x13EC) | Phase B active energy received (non-resettable) | Sensors: F160, Rope | INT64 | ABCD | Wh | Read | ||
| HR | 5128doc 5129 (0x1408) | Phase C active energy delivered (resettable) | Sensors: F160, Rope | INT64 | ABCD | Wh | Read/write | ||
| HR | 5132doc 5133 (0x140C) | Phase C active energy delivered (non-resettable) | Sensors: F160, Rope | INT64 | ABCD | Wh | Read | ||
| HR | 5136doc 5137 (0x1410) | Phase C active energy received (resettable) | Sensors: F160, Rope | INT64 | ABCD | Wh | Read/write | ||
| HR | 5140doc 5141 (0x1414) | Phase C active energy received (non-resettable) | Sensors: F160, Rope | INT64 | ABCD | Wh | Read | ||
| HR | 5176doc 5177 (0x1438) | Reactive energy delivered (resettable) | Sensors: F160, Rope | INT64 | ABCD | VARh | Read/write | ||
| HR | 5180doc 5181 (0x143C) | Reactive energy delivered count positively (non-resettable) | Sensors: F160, Rope | INT64 | ABCD | VARh | Read | ||
| HR | 5192doc 5193 (0x1488) | Reactive energy received (resettable) | Sensors: F160, Rope | INT64 | ABCD | VARh | Read/write | ||
| HR | 5196doc 5197 (0x144C) | Reactive energy received count negatively (non-resettable) | Sensors: F160, Rope | INT64 | ABCD | VARh | Read | ||
| HR | 5232doc 5233 (0x1470) | Phase A reactive energy delivered (resettable) | Sensors: F160, Rope | INT64 | ABCD | VARh | Read/write | ||
| HR | 5236doc 5237 (0x1474) | Phase A reactive energy delivered (non-resettable) | Sensors: F160, Rope | INT64 | ABCD | VARh | Read | ||
| HR | 5240doc 5241 (0x1478) | Phase A reactive energy received (resettable) | Sensors: F160, Rope | INT64 | ABCD | VARh | Read/write | ||
| HR | 5244doc 5245 (0x147C) | Phase A reactive energy received (non-resettable) | Sensors: F160, Rope | INT64 | ABCD | VARh | Read | ||
| HR | 5272doc 5273 (0x1498) | Phase B reactive energy delivered (resettable) | Sensors: F160, Rope | INT64 | ABCD | VARh | Read/write | ||
| HR | 5276doc 5277 (0x149C) | Phase B reactive energy delivered (non-resettable) | Sensors: F160, Rope | INT64 | ABCD | VARh | Read | ||
| HR | 5280doc 5281 (0x14A0) | Phase B reactive energy received (resettable) | Sensors: F160, Rope | INT64 | ABCD | VARh | Read/write | ||
| HR | 5284doc 5285 (0x14A4) | Phase B reactive energy received (non-resettable) | Sensors: F160, Rope | INT64 | ABCD | VARh | Read | ||
| HR | 5312doc 5313 (0x14C0) | Phase C reactive energy delivered (resettable) | Sensors: F160, Rope | INT64 | ABCD | VARh | Read/write | ||
| HR | 5316doc 5317 (0x14C4) | Phase C reactive energy delivered (non-resettable) | Sensors: F160, Rope | INT64 | ABCD | VARh | Read | ||
| HR | 5320doc 5321 (0x14C8) | Phase C reactive energy received (resettable) | Sensors: F160, Rope | INT64 | ABCD | VARh | Read/write | ||
| HR | 5324doc 5325 (0x14CC) | Phase C reactive energy received (non-resettable) | Sensors: F160, Rope | INT64 | ABCD | VARh | Read | ||
| HR | 5364doc 5365 (0x14F4) | Apparent energy delivered + received (resettable) | Sensors: F160, Rope | INT64 | ABCD | VAh | Read/write | ||
| HR | 5368doc 5369 (0x14F8) | Apparent energy delivered + received (non-resettable) | Sensors: F160, Rope | INT64 | ABCD | VAh | Read | ||
| HR | 5388doc 5389 (0x150C) | Phase A apparent energy (resettable) | Sensors: F160, Rope | INT64 | ABCD | VAh | Read/write | ||
| HR | 5392doc 5393 (0x1510) | Phase A apparent energy (non-resettable) | Sensors: F160, Rope | INT64 | ABCD | VAh | Read | ||
| HR | 5428doc 5429 (0x1534) | Phase B apparent energy (resettable) | Sensors: F160, Rope | INT64 | ABCD | VAh | Read/write | ||
| HR | 5432doc 5433 (0x1538) | Phase B apparent energy (non-resettable) | Sensors: F160, Rope | INT64 | ABCD | VAh | Read | ||
| HR | 5468doc 5469 (0x155C) | Phase C apparent energy (resettable) | Sensors: F160, Rope | INT64 | ABCD | VAh | Read/write | ||
| HR | 5472doc 5473 (0x1560) | Phase C apparent energy (non-resettable) | Sensors: F160, Rope | INT64 | ABCD | VAh | Read |
Notes on this map
- The guide says 32-bit and 64-bit values are big-endian: most significant word first.
- Read a sensor by using its Modbus server address (set per wireless device on the gateway web pages, 1-247). The gateway's own identification registers answer on server address 255.
- Invalid or unavailable values read 0xFFC00000 (floats) or 0x8000000000000000 (64-bit energy).
- Each register's description says which sensor types fill it: PowerTag 63 = A9MEM152x/154x/156x/157x, M250/M630 = LV43402x, F160/Rope = A9MEM1580/A9MEM159x.
- Left out: the 'set partial counter' write registers (3260, 3268, 3276, 3284, 3292), demand timestamps (DATETIME), the PowerTag control-module, HeatTag, load-monitoring, configuration, diagnostic and synthesis-table registers.
- Schneider's function code 100-4 (read scattered registers) is also accepted for most float registers; this map uses plain function 03.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Schneider Electric PowerTag Energy wireless sensors via PowerTag Link gateway (Modbus TCP)
What Modbus registers does the Schneider Electric PowerTag Energy wireless sensors via PowerTag Link gateway (Modbus TCP) have?
This map lists 83 registers: 83 holding registers. 20 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Schneider Electric PowerTag Energy wireless sensors via PowerTag Link gateway (Modbus TCP) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide prints register numbers in decimal and addresses in hex, with address = register - 1 (register 3000 is address 0x0BB7). Two hex cells in the table are misprinted (register 3228 shown as 0x09CB, register 5193 as 0x1488); wire addresses here follow the register-minus-one rule.
What byte order does the Schneider Electric PowerTag Energy wireless sensors via PowerTag Link gateway (Modbus TCP) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Schneider Electric PowerTag Energy wireless sensors via PowerTag Link gateway (Modbus TCP)?
Start with HR 2999 RMS current on phase A (Phase A current); HR 3027 RMS phase-to-neutral voltage A-N (Phase A-N voltage); HR 3059 Total active power (Total active power); HR 3083 Total power factor (Total power factor); HR 3203 Total active energy delivered + received (non-resettable) (Total active energy (not resettable)); HR 3211 Total active energy received (non-resettable) (Total active energy received).
How do I enable Modbus control of the Schneider Electric PowerTag Energy wireless sensors via PowerTag Link gateway (Modbus TCP)?
Modbus TCP is on by default on the gateway. The gateway gives each paired wireless device a Modbus address (1-247), which can be changed on its web pages.
Where is the official Schneider Electric PowerTag Energy wireless sensors via PowerTag Link gateway (Modbus TCP) Modbus documentation?
The source is PowerTag Link Gateway User Guide (DOCA0157EN-09), revision 2025-10, published free by Schneider Electric at https://download.se.com/files?p_Doc_Ref=DOCA0157EN.
More Schneider Electric Modbus register maps
- Energy meter (pulse and status concentrator)
Schneider Electric Acti 9 Smartlink Modbus (A9XMSB11) 11-channel I/O and pulse concentrator
Acti 9 Smartlink Modbus RS-485 module A9XMSB11, per user manual DOCA0004EN-06 (04/2016).
Also known as: Acti 9 Smartlink, Smartlink Modbus, A9XMSB11, Acti9 Smartlink - Variable frequency drive (HVAC fans and pumps)
Schneider Electric Altivar 212 (embedded Modbus RTU)
ATV212H (IP21) and ATV212W (IP55) drives on the built-in Modbus RTU ports (RJ45 and open-style terminal), per Modbus manual S1A53844.
Also known as: ATV212, Altivar 212, ATV212H, ATV212W, ATV212HU15N4, ATV212WD11N4 - Variable frequency drive
Schneider Electric Altivar Machine ATV320 (embedded Modbus RTU)
ATV320 Book (ATV320...B) and Compact (ATV320...C) drives on the built-in RJ45 Modbus serial port; register map per Communication Parameters file NVE41316 V3.5.
Also known as: ATV320, Altivar 320, ATV320U, ATV320D, ATV320 Book, ATV320 Compact - Variable frequency drive
Schneider Electric Altivar Machine ATV340 (embedded Modbus serial / Modbus TCP)
ATV340 drives on the built-in Modbus serial port; Ethernet versions (ATV340...N4E) expose the same addresses on embedded Modbus TCP. Per Communication Parameters file NVE61728 V4.6.
Also known as: ATV340, Altivar 340, Altivar Machine ATV340, ATV340U, ATV340D, ATV340...N4E - Variable frequency drive
Schneider Electric Altivar Process ATV630 / ATV600 family (Modbus serial and Modbus TCP)
Altivar Process ATV600 drives (ATV630, ATV650 and other ATV6x0 models) on the embedded RJ45 Modbus serial port or the embedded Ethernet Modbus TCP server; register map per Communication Parameters file EAV64332 V4.6.
Also known as: ATV600, ATV630, ATV650, ATV660, ATV680, Altivar Process 600, ATV630U, ATV630D - Variable frequency drive
Schneider Electric Altivar Process ATV900 (ATV930/ATV950, embedded Modbus serial / Modbus TCP)
Altivar Process ATV900 drives (ATV930, ATV950) on the built-in Modbus serial port and the embedded Ethernet port (Modbus TCP). Per Communication Parameters file NHA80944 V4.6.
Also known as: ATV900, ATV930, ATV950, Altivar Process 900, Altivar 930, Altivar 950, ATV930U, ATV930D, ATV950U - Power meter (circuit breaker trip unit)
Schneider Electric ComPact NSX MicroLogic trip unit, standard dataset (IFM / IFE interface)
Standard dataset registers 32000-32341 served by the IFM (Modbus RTU) or IFE (Modbus TCP) interface for ComPact NSX; the same table lists availability for ComPact NS / MasterPact NT/NW and MasterPact MTZ. Per DOCA0091EN-09 (07/2022).
Also known as: ComPact NSX, Compact NSX, MicroLogic 5.2 E, MicroLogic 6.2 E, MicroLogic 7.2 E, MicroLogic 5.3 A, MicroLogic 6.3 E, IFM LV434000, IFE LV434001, IFE LV434002, ComPact NS, MasterPact NT, MasterPact NW, MasterPact MTZ - Solar inverter
Schneider Electric Conext CL three-phase PV inverter 18/20/25 kVA
Conext CL (IEC, PVSCL20E/25E) and Conext CL-NA (PVSCL18NA/25NA) three-phase string inverters, map revision 1.5.
Also known as: Conext CL-NA, Conext CL-E, PVSCL18NA, PVSCL20E, PVSCL25E, PVSCL25NA - Solar inverter
Schneider Electric Conext Core XC Series grid-tie PV inverter (0G-XC-BB)
Conext Core XC Series grid-tied PV inverters (540/630/680 kW ratings, 0G-XC-BB) with firmware v1.07 and later; some registers need newer firmware as noted.
Also known as: 0G-XC-BB, XC-AIC15P - Variable frequency drive
Schneider Electric Easy Altivar ATV610 (embedded Modbus serial)
Easy Altivar ATV610 drives on the built-in Modbus serial port, per Communication Parameters file EAV64394 V1.6.
Also known as: ATV610, Altivar 610, Easy Altivar 610, Altivar Easy 610, ATV610U, ATV610D - EV charger
Schneider Electric EVlink Pro AC charging station (Modbus TCP)
EVlink Pro AC charging stations (T2S socket, attached cable, and T2S plus domestic socket versions), software 1.1.6 to 1.4.0.
Also known as: EVlink Pro AC - Motor management and protection relay
Schneider Electric TeSys T LTMR motor management controller (Modbus RTU)
TeSys T LTMR Modbus controllers (LTMR..M..), with or without the LTMEV40 expansion module, per DOCA0130EN-03 (02/2024).
Also known as: TeSys T, LTMR, LTMR08MBD, LTMR27MBD, LTMR100MBD, LTMR08MFM, LTMR27MFM, LTMR100MFM, LTMR..M, LTMEV40 - Air handler (rack-mounted room cooling unit, split DX)
Schneider Electric Uniflair Rack Mounted Room Cooling ACRMD4K
Schneider Electric Uniflair Rack Mounted Room Cooling units ACRMD4Kxxx (indoor rack unit with matching outdoor unit), register map part number 990-91589.
Also known as: ACRMD4K, ACRMD4Kxxx, Uniflair rack mounted room cooling, 990-91589
Other power & energy meters register maps
- Circuit breaker trip unit (power meter)
Siemens SENTRON WL (3WL) air circuit breaker with COM16 Modbus module
Siemens SENTRON 3WL air circuit breakers with a COM16 Modbus RTU communication module and, for voltage/power/energy values, the metering function (PLUS), per system manual A5E02126891-02.
Also known as: SENTRON WL, 3WL, 3WL COM16, COM16 - Power meter (panel meter)
Trumeter APM Power meter (APM-PWR) Modbus map
Trumeter APM-PWR panel power meters with Modbus, per the Trumeter knowledge-base register map.
Also known as: APM-PWR, APM Power, Trumeter APM Power meter - Power meter (network analyzer)
ABB M4M 20 / M4M 30 network analyzer
ABB M4M 20 and M4M 30 network analyzers, Modbus RTU and Modbus TCP versions, map v1.3O; items marked M4M 30 only are absent on M4M 20.
Also known as: M4M 20, M4M 30, M4M 20 Modbus, M4M 30 Modbus, M4M 20 Ethernet, M4M 30 Ethernet, M4M 20 I/O, M4M 30 I/O, M4M 2X, M4M 30-M, M4M 32 - Power meter (metered/switched rack PDU)
Bachmann BlueNet BN PRO intelligent PDU (Modbus TCP)
Bachmann BlueNet BN PRO rack PDUs with Modbus TCP, protocol v1.00 REV00 register list.
Also known as: BlueNet BN PRO, BN PRO PDU, BlueNet 2 BN PRO - Energy meter
Carlo Gavazzi EM100 / ET100 series (EM111, EM112, ET112)
Single-phase EM111, EM112 energy meters and ET112 bidirectional meter with the S1 (RS485 Modbus RTU) port, protocol version 2 revision 14.
Also known as: EM111, EM112, ET112, EM110, EM111-DIN, EM112-DIN, ET112-DIN, EM111DINAV81XS1X, EM112DINAV01XS1X, ET112DINAV01XS1X - Energy meter
Carlo Gavazzi EM300 / ET300 series (EM330, EM340, ET330, ET340)
EM330, EM331, EM340, EM341 energy meters and ET330/ET340 bidirectional meters with the S1 (RS485 Modbus RTU) port, protocol version 2 revision 17.
Also known as: EM330, EM340, ET330, ET340, EM331, EM341, EM330-DIN, EM340-DIN, ET340-DIN, EM340DINAV23XS1X, EM340DINAV23XS1PFA, EM340DINAV23XS1PFB
All power & energy meters Modbus register maps →
Source: PowerTag Link Gateway User Guide · DOCA0157EN-09 · rev. 2025-10. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.