Energy meter (wireless sensors through an Ethernet gateway) · Modbus register map

Schneider Electric PowerTag Energy wireless sensors via PowerTag Link gateway (Modbus TCP) Modbus register map

Updated 19 November 2026

Short answer

PowerTag Energy sensors clip onto breakers and report over radio to a PowerTag Link gateway, which serves each sensor as its own Modbus TCP server address (1-247). Every sensor exposes the same register block: currents, voltages, power and power factor as big-endian floats, and energy counters as 64-bit integers in Wh. Which registers a sensor fills depends on its type (63 A, M250/M630, F160/Rope).

This page lists 83 Modbus registers for the Schneider Electric PowerTag Energy wireless sensors via PowerTag Link gateway (Modbus TCP) — 20 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Schneider Electric’s own free documentation (linked below) and checked against it.

Manufacturer
Schneider Electric
Model
PowerTag Energy wireless sensors via PowerTag Link gateway (Modbus TCP)
Equipment type
Energy meter (wireless sensors through an Ethernet gateway)
Registers
83 (20 writable)
Transport
Modbus TCP
Default unit ID
Not stated
TCP port
502
Documented addressing
1-based (subtract 1 for the wire address)
32-bit word order
ABCD high word first (big-endian)
Also known as
PowerTag Link, PowerTag Link HD, A9XMWD20, A9XMWD100, PowerTag Energy 63, A9MEM1520, A9MEM1540, A9MEM1560, A9MEM1570, PowerTag M250, PowerTag M630, LV434020, PowerTag F160, A9MEM1580, PowerTag Rope, A9MEM1590
Source document
PowerTag Link Gateway User Guide · DOCA0157EN-09 · rev. 2025-10
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Schneider Electric PowerTag Energy wireless sensors via PowerTag Link gateway (Modbus TCP)

Integration in brief

Connect to the gateway on TCP port 502, use each sensor's Modbus address as the unit ID, and read 3000-3110 (floats) plus the 64-bit energy registers 3204-3212.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 2999RMS current on phase AFLOAT32 ABCDPhase A currentRead
HR 3027RMS phase-to-neutral voltage A-NFLOAT32 ABCDPhase A-N voltageRead
HR 3059Total active powerFLOAT32 ABCDTotal active powerRead
HR 3083Total power factorFLOAT32 ABCDTotal power factorRead
HR 3203Total active energy delivered + received (non-resettable)INT64 ABCDTotal active energy (not resettable)Read
HR 3211Total active energy received (non-resettable)INT64 ABCDTotal active energy receivedRead

Enable Modbus control & writes

Modbus TCP is on by default on the gateway. The gateway gives each paired wireless device a Modbus address (1-247), which can be changed on its web pages.

Byte order & addressing

Network setup

Watch out for

Schneider Electric PowerTag Energy wireless sensors via PowerTag Link gateway (Modbus TCP) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

83 of 83 shown
Schneider Electric PowerTag Energy wireless sensors via PowerTag Link gateway (Modbus TCP) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR2999doc 3000 (0x0BB7)RMS current on phase ASensors: PowerTag 63, M250, M630, F160, RopeFLOAT32ABCDARead
HR3001doc 3002 (0x0BB9)RMS current on phase BSensors: PowerTag 63, M250, M630, F160, RopeFLOAT32ABCDARead
HR3003doc 3004 (0x0BBB)RMS current on phase CSensors: PowerTag 63, M250, M630, F160, RopeFLOAT32ABCDARead
HR3005doc 3006 (0x0BBD)RMS current on neutralSensors: F160, RopeFLOAT32ABCDARead
HR3019doc 3020 (0x0BCB)RMS phase-to-phase voltage A-BSensors: PowerTag 63, M250, M630, F160, RopeFLOAT32ABCDVRead
HR3021doc 3022 (0x0BCD)RMS phase-to-phase voltage B-CSensors: PowerTag 63, M250, M630, F160, RopeFLOAT32ABCDVRead
HR3023doc 3024 (0x0BCF)RMS phase-to-phase voltage C-ASensors: PowerTag 63, M250, M630, F160, RopeFLOAT32ABCDVRead
HR3027doc 3028 (0x0BD3)RMS phase-to-neutral voltage A-NSensors: PowerTag 63, M250, M630, F160, RopeFLOAT32ABCDVRead
HR3029doc 3030 (0x0BD5)RMS phase-to-neutral voltage B-NSensors: PowerTag 63, M250, M630, F160, RopeFLOAT32ABCDVRead
HR3031doc 3032 (0x0BD7)RMS phase-to-neutral voltage C-NSensors: PowerTag 63, M250, M630, F160, RopeFLOAT32ABCDVRead
HR3053doc 3054 (0x0BED)Active power on phase ASensors: PowerTag 63, M250, M630, F160, RopeFLOAT32ABCDWRead
HR3055doc 3056 (0x0BEF)Active power on phase BSensors: PowerTag 63, M250, M630, F160, RopeFLOAT32ABCDWRead
HR3057doc 3058 (0x0BF1)Active power on phase CSensors: PowerTag 63, M250, M630, F160, RopeFLOAT32ABCDWRead
HR3059doc 3060 (0x0BF3)Total active powerSensors: PowerTag 63, M250, M630, F160, RopeFLOAT32ABCDWRead
HR3061doc 3062 (0x0BF5)Reactive power on phase ASensors: F160, RopeFLOAT32ABCDVARRead
HR3063doc 3064 (0x0BF7)Reactive power on phase BSensors: F160, RopeFLOAT32ABCDVARRead
HR3065doc 3066 (0x0BF9)Reactive power on phase CSensors: F160, RopeFLOAT32ABCDVARRead
HR3067doc 3068 (0x0BFB)Total reactive powerSensors: M250, M630, F160, RopeFLOAT32ABCDVARRead
HR3069doc 3070 (0x0BFD)Apparent power on phase ASensors: F160, RopeFLOAT32ABCDVARead
HR3071doc 3072 (0x0BFF)Apparent power on phase BSensors: F160, RopeFLOAT32ABCDVARead
HR3073doc 3074 (0x0C01)Apparent power on phase CSensors: F160, RopeFLOAT32ABCDVARead
HR3075doc 3076 (0x0C03)Total apparent power (arithmetic)Sensors: PowerTag 63, M250, M630, F160, RopeFLOAT32ABCDVARead
HR3077doc 3078 (0x0C05)Power factor on phase ASensors: F160, RopeFLOAT32ABCDRead
HR3079doc 3080 (0x0C07)Power factor on phase BSensors: F160, RopeFLOAT32ABCDRead
HR3081doc 3082 (0x0C09)Power factor on phase CSensors: F160, RopeFLOAT32ABCDRead
HR3083doc 3084 (0x0C0B)Total power factorSensors: PowerTag 63, M250, M630, F160, RopeFLOAT32ABCDRead
HR3085doc 3086 (0x0C0D)Power factor sign conventionSensors: F160, RopeUINT16Read0 = IEC; 1 = IEEE
HR3109doc 3110 (0x0C25)AC frequencySensors: M250, M630, F160, RopeFLOAT32ABCDHzRead
HR3131doc 3132 (0x0C3B)Device internal temperatureSensors: M250, M630, F160, RopeFLOAT32ABCD°CRead
HR3203doc 3204 (0x0C83)Total active energy delivered + received (non-resettable)Sensors: PowerTag 63, M250, M630, F160, RopeINT64ABCDWhRead
HR3207doc 3208 (0x0C87)Total active energy delivered count positively (non-resettable)Sensors: PowerTag 63, M250, M630, F160, RopeINT64ABCDWhRead
HR3211doc 3212 (0x0C8B)Total active energy received (non-resettable)Sensors: PowerTag 63, M250, M630, F160, RopeINT64ABCDWhRead
HR3215doc 3216 (0x0C8F)Phase A active energy delivered - received (non-resettable)Sensors: M250, M630INT64ABCDWhRead
HR3219doc 3220 (0x0C93)Phase B active energy delivered - received (non-resettable)Sensors: M250, M630INT64ABCDWhRead
HR3223doc 3224 (0x0C97)Phase C active energy delivered - received (non-resettable)Sensors: M250, M630INT64ABCDWhRead
HR3255doc 3256 (0x0CB7)Partial active energy delivered + received (resettable)Sensors: PowerTag 63, M250, M630, F160, RopeINT64ABCDWhRead
HR3263doc 3264 (0x0CBF)Partial active energy delivered (resettable)Sensors: PowerTag 63, M250, M630, F160, RopeINT64ABCDWhRead
HR3271doc 3272 (0x0CC7)Partial active energy received (resettable)Sensors: PowerTag 63, M250, M630, F160, RopeINT64ABCDWhRead
HR3279doc 3280 (0x0CCF)Partial reactive energy delivered (resettable)Sensors: M250, M630, F160, RopeINT64ABCDVARhRead
HR3287doc 3288 (0x0CD7)Partial reactive energy received (resettable)Sensors: M250, M630, F160, RopeINT64ABCDVARhRead
HR3765doc 3766 (0x0EB5)Demand total active powerSensors: PowerTag 63, F160, RopeFLOAT32ABCDWRead
HR3769doc 3770 (0x0EB9)Maximum Demand total active powerSensors: PowerTag 63, F160, RopeFLOAT32ABCDWRead
HR5008doc 5009 (0x1390)Active energy delivered (resettable)Sensors: PowerTag 63, F160, RopeINT64ABCDWhRead/write
HR5012doc 5013 (0x1394)Active energy delivered count positively (non-resettable)Sensors: PowerTag 63, F160, RopeINT64ABCDWhRead
HR5016doc 5017 (0x1398)Active energy received (resettable)Sensors: PowerTag 63, F160, RopeINT64ABCDWhRead/write
HR5020doc 5021 (0x139C)Active energy received count negatively (non-resettable)Sensors: PowerTag 63, F160, RopeINT64ABCDWhRead
HR5048doc 5049 (0x13B8)Phase A active energy delivered (resettable)Sensors: F160, RopeINT64ABCDWhRead/write
HR5052doc 5053 (0x13BC)Phase A active energy delivered (non-resettable)Sensors: F160, RopeINT64ABCDWhRead
HR5056doc 5057 (0x13C0)Phase A active energy received (resettable)Sensors: F160, RopeINT64ABCDWhRead/write
HR5060doc 5061 (0x13C4)Phase A active energy received (non-resettable)Sensors: F160, RopeINT64ABCDWhRead
HR5076doc 5077 (0x13D4)Phase A active energy delivered + received (non-resettable)Sensors: F160, RopeINT64ABCDWhRead
HR5088doc 5089 (0x13E0)Phase B active energy delivered (resettable)Sensors: F160, RopeINT64ABCDWhRead/write
HR5092doc 5093 (0x13E4)Phase B active energy delivered (non-resettable)Sensors: F160, RopeINT64ABCDWhRead
HR5096doc 5097 (0x13E8)Phase B active energy received (resettable)Sensors: F160, RopeINT64ABCDWhRead/write
HR5100doc 5101 (0x13EC)Phase B active energy received (non-resettable)Sensors: F160, RopeINT64ABCDWhRead
HR5128doc 5129 (0x1408)Phase C active energy delivered (resettable)Sensors: F160, RopeINT64ABCDWhRead/write
HR5132doc 5133 (0x140C)Phase C active energy delivered (non-resettable)Sensors: F160, RopeINT64ABCDWhRead
HR5136doc 5137 (0x1410)Phase C active energy received (resettable)Sensors: F160, RopeINT64ABCDWhRead/write
HR5140doc 5141 (0x1414)Phase C active energy received (non-resettable)Sensors: F160, RopeINT64ABCDWhRead
HR5176doc 5177 (0x1438)Reactive energy delivered (resettable)Sensors: F160, RopeINT64ABCDVARhRead/write
HR5180doc 5181 (0x143C)Reactive energy delivered count positively (non-resettable)Sensors: F160, RopeINT64ABCDVARhRead
HR5192doc 5193 (0x1488)Reactive energy received (resettable)Sensors: F160, RopeINT64ABCDVARhRead/write
HR5196doc 5197 (0x144C)Reactive energy received count negatively (non-resettable)Sensors: F160, RopeINT64ABCDVARhRead
HR5232doc 5233 (0x1470)Phase A reactive energy delivered (resettable)Sensors: F160, RopeINT64ABCDVARhRead/write
HR5236doc 5237 (0x1474)Phase A reactive energy delivered (non-resettable)Sensors: F160, RopeINT64ABCDVARhRead
HR5240doc 5241 (0x1478)Phase A reactive energy received (resettable)Sensors: F160, RopeINT64ABCDVARhRead/write
HR5244doc 5245 (0x147C)Phase A reactive energy received (non-resettable)Sensors: F160, RopeINT64ABCDVARhRead
HR5272doc 5273 (0x1498)Phase B reactive energy delivered (resettable)Sensors: F160, RopeINT64ABCDVARhRead/write
HR5276doc 5277 (0x149C)Phase B reactive energy delivered (non-resettable)Sensors: F160, RopeINT64ABCDVARhRead
HR5280doc 5281 (0x14A0)Phase B reactive energy received (resettable)Sensors: F160, RopeINT64ABCDVARhRead/write
HR5284doc 5285 (0x14A4)Phase B reactive energy received (non-resettable)Sensors: F160, RopeINT64ABCDVARhRead
HR5312doc 5313 (0x14C0)Phase C reactive energy delivered (resettable)Sensors: F160, RopeINT64ABCDVARhRead/write
HR5316doc 5317 (0x14C4)Phase C reactive energy delivered (non-resettable)Sensors: F160, RopeINT64ABCDVARhRead
HR5320doc 5321 (0x14C8)Phase C reactive energy received (resettable)Sensors: F160, RopeINT64ABCDVARhRead/write
HR5324doc 5325 (0x14CC)Phase C reactive energy received (non-resettable)Sensors: F160, RopeINT64ABCDVARhRead
HR5364doc 5365 (0x14F4)Apparent energy delivered + received (resettable)Sensors: F160, RopeINT64ABCDVAhRead/write
HR5368doc 5369 (0x14F8)Apparent energy delivered + received (non-resettable)Sensors: F160, RopeINT64ABCDVAhRead
HR5388doc 5389 (0x150C)Phase A apparent energy (resettable)Sensors: F160, RopeINT64ABCDVAhRead/write
HR5392doc 5393 (0x1510)Phase A apparent energy (non-resettable)Sensors: F160, RopeINT64ABCDVAhRead
HR5428doc 5429 (0x1534)Phase B apparent energy (resettable)Sensors: F160, RopeINT64ABCDVAhRead/write
HR5432doc 5433 (0x1538)Phase B apparent energy (non-resettable)Sensors: F160, RopeINT64ABCDVAhRead
HR5468doc 5469 (0x155C)Phase C apparent energy (resettable)Sensors: F160, RopeINT64ABCDVAhRead/write
HR5472doc 5473 (0x1560)Phase C apparent energy (non-resettable)Sensors: F160, RopeINT64ABCDVAhRead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Schneider Electric PowerTag Energy wireless sensors via PowerTag Link gateway (Modbus TCP)

What Modbus registers does the Schneider Electric PowerTag Energy wireless sensors via PowerTag Link gateway (Modbus TCP) have?

This map lists 83 registers: 83 holding registers. 20 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Schneider Electric PowerTag Energy wireless sensors via PowerTag Link gateway (Modbus TCP) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide prints register numbers in decimal and addresses in hex, with address = register - 1 (register 3000 is address 0x0BB7). Two hex cells in the table are misprinted (register 3228 shown as 0x09CB, register 5193 as 0x1488); wire addresses here follow the register-minus-one rule.

What byte order does the Schneider Electric PowerTag Energy wireless sensors via PowerTag Link gateway (Modbus TCP) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Schneider Electric PowerTag Energy wireless sensors via PowerTag Link gateway (Modbus TCP)?

Start with HR 2999 RMS current on phase A (Phase A current); HR 3027 RMS phase-to-neutral voltage A-N (Phase A-N voltage); HR 3059 Total active power (Total active power); HR 3083 Total power factor (Total power factor); HR 3203 Total active energy delivered + received (non-resettable) (Total active energy (not resettable)); HR 3211 Total active energy received (non-resettable) (Total active energy received).

How do I enable Modbus control of the Schneider Electric PowerTag Energy wireless sensors via PowerTag Link gateway (Modbus TCP)?

Modbus TCP is on by default on the gateway. The gateway gives each paired wireless device a Modbus address (1-247), which can be changed on its web pages.

Where is the official Schneider Electric PowerTag Energy wireless sensors via PowerTag Link gateway (Modbus TCP) Modbus documentation?

The source is PowerTag Link Gateway User Guide (DOCA0157EN-09), revision 2025-10, published free by Schneider Electric at https://download.se.com/files?p_Doc_Ref=DOCA0157EN.

More Schneider Electric Modbus register maps

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: PowerTag Link Gateway User Guide · DOCA0157EN-09 · rev. 2025-10. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.