Power meter (panel meter) · Modbus register map

Trumeter APM Power meter (APM-PWR) Modbus map Modbus register map

Updated 17 November 2026

Short answer

Panel-mounted power and energy meter from the Trumeter APM family. Function code 4 input registers return 44 measurements as 32-bit floats (per-phase voltages, currents, powers, angles, power factor, THD, max load, totals and energy); function code 1 coils report ten alarm states.

This page lists 54 Modbus registers for the Trumeter APM Power meter (APM-PWR) Modbus map — 0 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Trumeter’s own free documentation (linked below) and checked against it.

Manufacturer
Trumeter
Model
APM Power meter (APM-PWR) Modbus map
Equipment type
Power meter (panel meter)
Registers
54 (0 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Documented addressing
0-based (the number printed is the address on the wire)
32-bit word order
ABCD high word first (big-endian)
Also known as
APM-PWR, APM Power, Trumeter APM Power meter
Source document
Modbus Register Map - APM Power (Trumeter Knowledge Base)
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Trumeter APM Power meter (APM-PWR) Modbus map

Integration in brief

Read input registers 0-87 with FC04 as 44 big-endian floats, and coils 0-9 with FC01 for alarm states.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 0FrequencyFLOAT32 ABCDFrequencyRead
IR 4L1 to N VoltageFLOAT32 ABCDL1-N voltageRead
IR 6L1 CurrentFLOAT32 ABCDL1 currentRead
IR 80Total Active PowerFLOAT32 ABCDTotal active powerRead
IR 74Active EnergyFLOAT32 ABCDActive energyRead
IR 86All phase power factorFLOAT32 ABCDPower factorRead
CO 0Alarm 1 statusBITAlarm 1Read

Enable Modbus control & writes

Not described on the source page.

Byte order & addressing

Network setup

Watch out for

Trumeter APM Power meter (APM-PWR) Modbus map Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

54 of 54 shown
Trumeter APM Power meter (APM-PWR) Modbus map Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
CO0Alarm 1 statusBITRead0 = Alarm inactive; 1 = Alarm active
CO1Alarm 2 statusBITRead0 = Alarm inactive; 1 = Alarm active
CO2Alarm 3 statusBITRead0 = Alarm inactive; 1 = Alarm active
CO3Alarm 4 statusBITRead0 = Alarm inactive; 1 = Alarm active
CO4Alarm 5 statusBITRead0 = Alarm inactive; 1 = Alarm active
CO5Alarm 6 statusBITRead0 = Alarm inactive; 1 = Alarm active
CO6Alarm 7 statusBITRead0 = Alarm inactive; 1 = Alarm active
CO7Alarm 8 statusBITRead0 = Alarm inactive; 1 = Alarm active
CO8Alarm 9 statusBITRead0 = Alarm inactive; 1 = Alarm active
CO9Alarm 10 statusBITRead0 = Alarm inactive; 1 = Alarm active
IR0FrequencyParameter 0. Value as shown on the display, in the configured unit.FLOAT32ABCDRead
IR2L1 to L2 VoltageParameter 1. Value as shown on the display, in the configured unit.FLOAT32ABCDRead
IR4L1 to N VoltageParameter 2. Value as shown on the display, in the configured unit.FLOAT32ABCDRead
IR6L1 CurrentParameter 3. Value as shown on the display, in the configured unit.FLOAT32ABCDRead
IR8L1 Active PowerParameter 4. Value as shown on the display, in the configured unit.FLOAT32ABCDRead
IR10L1 Apparent PowerParameter 5. Value as shown on the display, in the configured unit.FLOAT32ABCDRead
IR12L1 Reactive PowerParameter 6. Value as shown on the display, in the configured unit.FLOAT32ABCDRead
IR14L1 Current Phase AngleParameter 7. Value as shown on the display, in the configured unit.FLOAT32ABCDRead
IR16L1 Power FactorParameter 8. Value as shown on the display, in the configured unit.FLOAT32ABCDRead
IR18L1 Voltage THDParameter 9. Value as shown on the display, in the configured unit.FLOAT32ABCDRead
IR20L1 Current THDParameter 10. Value as shown on the display, in the configured unit.FLOAT32ABCDRead
IR22L1 Max LoadParameter 11. Value as shown on the display, in the configured unit.FLOAT32ABCDRead
IR24L1 to L2 Voltage Phase AngleParameter 12. Value as shown on the display, in the configured unit.FLOAT32ABCDRead
IR26L2 to L3 VoltageParameter 13. Value as shown on the display, in the configured unit.FLOAT32ABCDRead
IR28L2 to N VoltageParameter 14. Value as shown on the display, in the configured unit.FLOAT32ABCDRead
IR30L2 CurrentParameter 15. Value as shown on the display, in the configured unit.FLOAT32ABCDRead
IR32L2 Active PowerParameter 16. Value as shown on the display, in the configured unit.FLOAT32ABCDRead
IR34L2 Apparent PowerParameter 17. Value as shown on the display, in the configured unit.FLOAT32ABCDRead
IR36L2 Reactive PowerParameter 18. Value as shown on the display, in the configured unit.FLOAT32ABCDRead
IR38L2 Current Phase AngleParameter 19. Value as shown on the display, in the configured unit.FLOAT32ABCDRead
IR40L2 Power FactorParameter 20. Value as shown on the display, in the configured unit.FLOAT32ABCDRead
IR42L2 Voltage THDParameter 21. Value as shown on the display, in the configured unit.FLOAT32ABCDRead
IR44L2 Current THDParameter 22. Value as shown on the display, in the configured unit.FLOAT32ABCDRead
IR46L2 Max LoadParameter 23. Value as shown on the display, in the configured unit.FLOAT32ABCDRead
IR48L1 to L3 Voltage Phase AngleParameter 24. Value as shown on the display, in the configured unit.FLOAT32ABCDRead
IR50L3 to L1 VoltageParameter 25. Value as shown on the display, in the configured unit.FLOAT32ABCDRead
IR52L3 to N VoltageParameter 26. Value as shown on the display, in the configured unit.FLOAT32ABCDRead
IR54L3 CurrentParameter 27. Value as shown on the display, in the configured unit.FLOAT32ABCDRead
IR56L3 Active PowerParameter 28. Value as shown on the display, in the configured unit.FLOAT32ABCDRead
IR58L3 Apparent PowerParameter 29. Value as shown on the display, in the configured unit.FLOAT32ABCDRead
IR60L3 Reactive PowerParameter 30. Value as shown on the display, in the configured unit.FLOAT32ABCDRead
IR62L3 Current Phase AngleParameter 31. Value as shown on the display, in the configured unit.FLOAT32ABCDRead
IR64L3 Power FactorParameter 32. Value as shown on the display, in the configured unit.FLOAT32ABCDRead
IR66L3 Voltage THDParameter 33. Value as shown on the display, in the configured unit.FLOAT32ABCDRead
IR68L3 Current THDParameter 34. Value as shown on the display, in the configured unit.FLOAT32ABCDRead
IR70L3 Max LoadParameter 35. Value as shown on the display, in the configured unit.FLOAT32ABCDRead
IR72Internal TemperatureParameter 36. Value as shown on the display, in the configured unit.FLOAT32ABCDRead
IR74Active EnergyParameter 37. Value as shown on the display, in the configured unit.FLOAT32ABCDRead
IR76Apparent EnergyParameter 38. Value as shown on the display, in the configured unit.FLOAT32ABCDRead
IR78Reactive EnergyParameter 39. Value as shown on the display, in the configured unit.FLOAT32ABCDRead
IR80Total Active PowerParameter 40. Value as shown on the display, in the configured unit.FLOAT32ABCDRead
IR82Total Apparent PowerParameter 41. Value as shown on the display, in the configured unit.FLOAT32ABCDRead
IR84Total Reactive PowerParameter 42. Value as shown on the display, in the configured unit.FLOAT32ABCDRead
IR86All phase power factorParameter 43. Value as shown on the display, in the configured unit.FLOAT32ABCDRead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Trumeter APM Power meter (APM-PWR) Modbus map

What Modbus registers does the Trumeter APM Power meter (APM-PWR) Modbus map have?

This map lists 54 registers: 10 coils, 44 input registers. 0 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Trumeter APM Power meter (APM-PWR) Modbus map Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The table lists a parameter number and an 'Address' that starts at 0 (frequency at address 0, L1-L2 voltage at 2); the address column is used directly as the wire address.

What byte order does the Trumeter APM Power meter (APM-PWR) Modbus map use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Trumeter APM Power meter (APM-PWR) Modbus map?

Start with IR 0 Frequency (Frequency); IR 4 L1 to N Voltage (L1-N voltage); IR 6 L1 Current (L1 current); IR 80 Total Active Power (Total active power); IR 74 Active Energy (Active energy); IR 86 All phase power factor (Power factor); CO 0 Alarm 1 status (Alarm 1).

How do I enable Modbus control of the Trumeter APM Power meter (APM-PWR) Modbus map?

Not described on the source page.

Where is the official Trumeter APM Power meter (APM-PWR) Modbus map Modbus documentation?

The source is Modbus Register Map - APM Power (Trumeter Knowledge Base), published free by Trumeter at https://help.trumeter.com/modbus-register-map-apm-power.

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: Modbus Register Map - APM Power (Trumeter Knowledge Base). Register numbers, types, scaling and units are reproduced as published; descriptions are our own.