Power meter (panel meter) · Modbus register map
Trumeter APM Power meter (APM-PWR) Modbus map Modbus register map
Updated 17 November 2026
Panel-mounted power and energy meter from the Trumeter APM family. Function code 4 input registers return 44 measurements as 32-bit floats (per-phase voltages, currents, powers, angles, power factor, THD, max load, totals and energy); function code 1 coils report ten alarm states.
This page lists 54 Modbus registers for the Trumeter APM Power meter (APM-PWR) Modbus map — 0 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Trumeter’s own free documentation (linked below) and checked against it.
- Manufacturer
- Trumeter
- Model
- APM Power meter (APM-PWR) Modbus map
- Equipment type
- Power meter (panel meter)
- Registers
- 54 (0 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- 0-based (the number printed is the address on the wire)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- APM-PWR, APM Power, Trumeter APM Power meter
- Source document
- Modbus Register Map - APM Power (Trumeter Knowledge Base)
Integration notes: Trumeter APM Power meter (APM-PWR) Modbus map
Read input registers 0-87 with FC04 as 44 big-endian floats, and coils 0-9 with FC01 for alarm states.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 0 | Frequency | FLOAT32 ABCD | Frequency | Read |
| IR 4 | L1 to N Voltage | FLOAT32 ABCD | L1-N voltage | Read |
| IR 6 | L1 Current | FLOAT32 ABCD | L1 current | Read |
| IR 80 | Total Active Power | FLOAT32 ABCD | Total active power | Read |
| IR 74 | Active Energy | FLOAT32 ABCD | Active energy | Read |
| IR 86 | All phase power factor | FLOAT32 ABCD | Power factor | Read |
| CO 0 | Alarm 1 status | BIT | Alarm 1 | Read |
Enable Modbus control & writes
Not described on the source page.
Byte order & addressing
- Readings follow the configured display unit (V vs kV, kVA etc.).
- Floats are high word first.
Network setup
- Set address and serial settings on the meter; they are not listed in the register map.
Watch out for
- The table spells parameter 39 'Reative Energy'; it is reactive energy.
Trumeter APM Power meter (APM-PWR) Modbus map Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 0 | Alarm 1 status | BIT | Read | 0 = Alarm inactive; 1 = Alarm active | ||||
| CO | 1 | Alarm 2 status | BIT | Read | 0 = Alarm inactive; 1 = Alarm active | ||||
| CO | 2 | Alarm 3 status | BIT | Read | 0 = Alarm inactive; 1 = Alarm active | ||||
| CO | 3 | Alarm 4 status | BIT | Read | 0 = Alarm inactive; 1 = Alarm active | ||||
| CO | 4 | Alarm 5 status | BIT | Read | 0 = Alarm inactive; 1 = Alarm active | ||||
| CO | 5 | Alarm 6 status | BIT | Read | 0 = Alarm inactive; 1 = Alarm active | ||||
| CO | 6 | Alarm 7 status | BIT | Read | 0 = Alarm inactive; 1 = Alarm active | ||||
| CO | 7 | Alarm 8 status | BIT | Read | 0 = Alarm inactive; 1 = Alarm active | ||||
| CO | 8 | Alarm 9 status | BIT | Read | 0 = Alarm inactive; 1 = Alarm active | ||||
| CO | 9 | Alarm 10 status | BIT | Read | 0 = Alarm inactive; 1 = Alarm active | ||||
| IR | 0 | Frequency | Parameter 0. Value as shown on the display, in the configured unit. | FLOAT32 | ABCD | Read | |||
| IR | 2 | L1 to L2 Voltage | Parameter 1. Value as shown on the display, in the configured unit. | FLOAT32 | ABCD | Read | |||
| IR | 4 | L1 to N Voltage | Parameter 2. Value as shown on the display, in the configured unit. | FLOAT32 | ABCD | Read | |||
| IR | 6 | L1 Current | Parameter 3. Value as shown on the display, in the configured unit. | FLOAT32 | ABCD | Read | |||
| IR | 8 | L1 Active Power | Parameter 4. Value as shown on the display, in the configured unit. | FLOAT32 | ABCD | Read | |||
| IR | 10 | L1 Apparent Power | Parameter 5. Value as shown on the display, in the configured unit. | FLOAT32 | ABCD | Read | |||
| IR | 12 | L1 Reactive Power | Parameter 6. Value as shown on the display, in the configured unit. | FLOAT32 | ABCD | Read | |||
| IR | 14 | L1 Current Phase Angle | Parameter 7. Value as shown on the display, in the configured unit. | FLOAT32 | ABCD | Read | |||
| IR | 16 | L1 Power Factor | Parameter 8. Value as shown on the display, in the configured unit. | FLOAT32 | ABCD | Read | |||
| IR | 18 | L1 Voltage THD | Parameter 9. Value as shown on the display, in the configured unit. | FLOAT32 | ABCD | Read | |||
| IR | 20 | L1 Current THD | Parameter 10. Value as shown on the display, in the configured unit. | FLOAT32 | ABCD | Read | |||
| IR | 22 | L1 Max Load | Parameter 11. Value as shown on the display, in the configured unit. | FLOAT32 | ABCD | Read | |||
| IR | 24 | L1 to L2 Voltage Phase Angle | Parameter 12. Value as shown on the display, in the configured unit. | FLOAT32 | ABCD | Read | |||
| IR | 26 | L2 to L3 Voltage | Parameter 13. Value as shown on the display, in the configured unit. | FLOAT32 | ABCD | Read | |||
| IR | 28 | L2 to N Voltage | Parameter 14. Value as shown on the display, in the configured unit. | FLOAT32 | ABCD | Read | |||
| IR | 30 | L2 Current | Parameter 15. Value as shown on the display, in the configured unit. | FLOAT32 | ABCD | Read | |||
| IR | 32 | L2 Active Power | Parameter 16. Value as shown on the display, in the configured unit. | FLOAT32 | ABCD | Read | |||
| IR | 34 | L2 Apparent Power | Parameter 17. Value as shown on the display, in the configured unit. | FLOAT32 | ABCD | Read | |||
| IR | 36 | L2 Reactive Power | Parameter 18. Value as shown on the display, in the configured unit. | FLOAT32 | ABCD | Read | |||
| IR | 38 | L2 Current Phase Angle | Parameter 19. Value as shown on the display, in the configured unit. | FLOAT32 | ABCD | Read | |||
| IR | 40 | L2 Power Factor | Parameter 20. Value as shown on the display, in the configured unit. | FLOAT32 | ABCD | Read | |||
| IR | 42 | L2 Voltage THD | Parameter 21. Value as shown on the display, in the configured unit. | FLOAT32 | ABCD | Read | |||
| IR | 44 | L2 Current THD | Parameter 22. Value as shown on the display, in the configured unit. | FLOAT32 | ABCD | Read | |||
| IR | 46 | L2 Max Load | Parameter 23. Value as shown on the display, in the configured unit. | FLOAT32 | ABCD | Read | |||
| IR | 48 | L1 to L3 Voltage Phase Angle | Parameter 24. Value as shown on the display, in the configured unit. | FLOAT32 | ABCD | Read | |||
| IR | 50 | L3 to L1 Voltage | Parameter 25. Value as shown on the display, in the configured unit. | FLOAT32 | ABCD | Read | |||
| IR | 52 | L3 to N Voltage | Parameter 26. Value as shown on the display, in the configured unit. | FLOAT32 | ABCD | Read | |||
| IR | 54 | L3 Current | Parameter 27. Value as shown on the display, in the configured unit. | FLOAT32 | ABCD | Read | |||
| IR | 56 | L3 Active Power | Parameter 28. Value as shown on the display, in the configured unit. | FLOAT32 | ABCD | Read | |||
| IR | 58 | L3 Apparent Power | Parameter 29. Value as shown on the display, in the configured unit. | FLOAT32 | ABCD | Read | |||
| IR | 60 | L3 Reactive Power | Parameter 30. Value as shown on the display, in the configured unit. | FLOAT32 | ABCD | Read | |||
| IR | 62 | L3 Current Phase Angle | Parameter 31. Value as shown on the display, in the configured unit. | FLOAT32 | ABCD | Read | |||
| IR | 64 | L3 Power Factor | Parameter 32. Value as shown on the display, in the configured unit. | FLOAT32 | ABCD | Read | |||
| IR | 66 | L3 Voltage THD | Parameter 33. Value as shown on the display, in the configured unit. | FLOAT32 | ABCD | Read | |||
| IR | 68 | L3 Current THD | Parameter 34. Value as shown on the display, in the configured unit. | FLOAT32 | ABCD | Read | |||
| IR | 70 | L3 Max Load | Parameter 35. Value as shown on the display, in the configured unit. | FLOAT32 | ABCD | Read | |||
| IR | 72 | Internal Temperature | Parameter 36. Value as shown on the display, in the configured unit. | FLOAT32 | ABCD | Read | |||
| IR | 74 | Active Energy | Parameter 37. Value as shown on the display, in the configured unit. | FLOAT32 | ABCD | Read | |||
| IR | 76 | Apparent Energy | Parameter 38. Value as shown on the display, in the configured unit. | FLOAT32 | ABCD | Read | |||
| IR | 78 | Reactive Energy | Parameter 39. Value as shown on the display, in the configured unit. | FLOAT32 | ABCD | Read | |||
| IR | 80 | Total Active Power | Parameter 40. Value as shown on the display, in the configured unit. | FLOAT32 | ABCD | Read | |||
| IR | 82 | Total Apparent Power | Parameter 41. Value as shown on the display, in the configured unit. | FLOAT32 | ABCD | Read | |||
| IR | 84 | Total Reactive Power | Parameter 42. Value as shown on the display, in the configured unit. | FLOAT32 | ABCD | Read | |||
| IR | 86 | All phase power factor | Parameter 43. Value as shown on the display, in the configured unit. | FLOAT32 | ABCD | Read |
Notes on this map
- Word order: the page states the floats use two 16-bit words with the most significant word sent first, and each word high byte first (ABCD).
- Values are the displayed values in whatever unit the meter is configured for (e.g. 415 for V or 8.7 for kVA), so units are not fixed here; check the meter's unit configuration.
- Serial settings and default address are not given on this page; set them in the meter's configuration menu.
- Transport is listed as RTU on the basis that the APM is an RS-485 panel meter; the page itself does not name the physical layer.
- Unsupported functions return exception 1 and unknown addresses exception 2.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Trumeter APM Power meter (APM-PWR) Modbus map
What Modbus registers does the Trumeter APM Power meter (APM-PWR) Modbus map have?
This map lists 54 registers: 10 coils, 44 input registers. 0 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Trumeter APM Power meter (APM-PWR) Modbus map Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The table lists a parameter number and an 'Address' that starts at 0 (frequency at address 0, L1-L2 voltage at 2); the address column is used directly as the wire address.
What byte order does the Trumeter APM Power meter (APM-PWR) Modbus map use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Trumeter APM Power meter (APM-PWR) Modbus map?
Start with IR 0 Frequency (Frequency); IR 4 L1 to N Voltage (L1-N voltage); IR 6 L1 Current (L1 current); IR 80 Total Active Power (Total active power); IR 74 Active Energy (Active energy); IR 86 All phase power factor (Power factor); CO 0 Alarm 1 status (Alarm 1).
How do I enable Modbus control of the Trumeter APM Power meter (APM-PWR) Modbus map?
Not described on the source page.
Where is the official Trumeter APM Power meter (APM-PWR) Modbus map Modbus documentation?
The source is Modbus Register Map - APM Power (Trumeter Knowledge Base), published free by Trumeter at https://help.trumeter.com/modbus-register-map-apm-power.
Other power & energy meters register maps
- Power meter (network analyzer)
ABB M4M 20 / M4M 30 network analyzer
ABB M4M 20 and M4M 30 network analyzers, Modbus RTU and Modbus TCP versions, map v1.3O; items marked M4M 30 only are absent on M4M 20.
Also known as: M4M 20, M4M 30, M4M 20 Modbus, M4M 30 Modbus, M4M 20 Ethernet, M4M 30 Ethernet, M4M 20 I/O, M4M 30 I/O, M4M 2X, M4M 30-M, M4M 32 - Power meter (metered/switched rack PDU)
Bachmann BlueNet BN PRO intelligent PDU (Modbus TCP)
Bachmann BlueNet BN PRO rack PDUs with Modbus TCP, protocol v1.00 REV00 register list.
Also known as: BlueNet BN PRO, BN PRO PDU, BlueNet 2 BN PRO - Energy meter
Carlo Gavazzi EM100 / ET100 series (EM111, EM112, ET112)
Single-phase EM111, EM112 energy meters and ET112 bidirectional meter with the S1 (RS485 Modbus RTU) port, protocol version 2 revision 14.
Also known as: EM111, EM112, ET112, EM110, EM111-DIN, EM112-DIN, ET112-DIN, EM111DINAV81XS1X, EM112DINAV01XS1X, ET112DINAV01XS1X - Energy meter
Carlo Gavazzi EM300 / ET300 series (EM330, EM340, ET330, ET340)
EM330, EM331, EM340, EM341 energy meters and ET330/ET340 bidirectional meters with the S1 (RS485 Modbus RTU) port, protocol version 2 revision 17.
Also known as: EM330, EM340, ET330, ET340, EM331, EM341, EM330-DIN, EM340-DIN, ET340-DIN, EM340DINAV23XS1X, EM340DINAV23XS1PFA, EM340DINAV23XS1PFB - Power meter (power analyzer)
Carlo Gavazzi WM50 power analyzer with TCD branch channels
WM50 base unit (firmware X0, i.e. all A and B versions) with an MC485232 or MCETH communication module, plus TCD branch channels, per communication protocol user version rev. 1.0.0 (2017-09-27).
Also known as: WM50, WM50AV5, WM50-96, WM50 AV5 - Energy meter
Continental Control Systems WattNode Modbus (WNC) energy meter
WattNode Modbus WNC and revenue RWNC models, firmware 18-24, per manual WNC-MB-1.18c (2015-11-03).
Also known as: WNC-3Y-208-MB, WNC-3Y-400-MB, WNC-3Y-480-MB, WNC-3Y-600-MB, WNC-3D-240-MB, WNC-3D-400-MB, WNC-3D-480-MB, RWNC-3Y-208-MB, RWNC-3Y-400-MB, RWNC-3Y-480-MB, RWNC-3Y-600-MB, RWNC-3D-240-MB, RWNC-3D-400-MB, RWNC-3D-480-MB, WattNode Revenue Modbus
All power & energy meters Modbus register maps →
Source: Modbus Register Map - APM Power (Trumeter Knowledge Base). Register numbers, types, scaling and units are reproduced as published; descriptions are our own.