Energy meter · Modbus register map

Continental Control Systems WattNode Modbus (WNC) energy meter Modbus register map

Updated 17 November 2026

Short answer

The WattNode Modbus is a compact three-phase energy meter with external CTs and an RS-485 Modbus RTU port. Most values come both as 32-bit floats and as scaled integers; 32-bit values are sent low word first. This map covers energy (net, positive, negative, reactive, apparent), power, voltage, current, PF, frequency, demand, CT and demand configuration, communication overrides and diagnostics.

This page lists 107 Modbus registers for the Continental Control Systems WattNode Modbus (WNC) energy meter — 44 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Continental Control Systems’s own free documentation (linked below) and checked against it.

Manufacturer
Continental Control Systems
Model
WattNode Modbus (WNC) energy meter
Equipment type
Energy meter
Registers
107 (44 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
9600 baud, 8N1
Documented addressing
1-based (subtract 1 for the wire address)
32-bit word order
CDAB low word first (word-swapped)
Firmware
18-24
Also known as
WNC-3Y-208-MB, WNC-3Y-400-MB, WNC-3Y-480-MB, WNC-3Y-600-MB, WNC-3D-240-MB, WNC-3D-400-MB, WNC-3D-480-MB, RWNC-3Y-208-MB, RWNC-3Y-400-MB, RWNC-3Y-480-MB, RWNC-3Y-600-MB, RWNC-3D-240-MB, RWNC-3D-400-MB, RWNC-3D-480-MB, WattNode Revenue Modbus
Source document
WattNode Modbus Installation and Operation Manual · WNC-MB-1.18c · rev. 2015-11-03
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Continental Control Systems WattNode Modbus (WNC) energy meter

Integration in brief

Set the address and baud on the DIP switches, set CtAmps (1603), then read floats from 1001-1034 (documented numbers; wire 1000-1033) in one request, decoding each pair low word first.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 1000EnergySumFLOAT32 CDABEnergySum (kWh)Read/write
HR 1008PowerSumFLOAT32 CDABPowerSum (W)Read
HR 1016VoltAvgLNFLOAT32 CDABAverage L-N voltageRead
HR 1162CurrentAFLOAT32 CDABCurrent phase ARead
HR 1138PowerFactorAvgFLOAT32 CDABAverage power factorRead
HR 1032FreqFLOAT32 CDABFrequencyRead
HR 1602CtAmpsINT16CtAmps (must match the CTs)Read/write

Enable Modbus control & writes

Modbus RTU on RS-485 is always on. Address and baud come from the DIP switches unless overridden at 1652-1656 (write 1234 to 1651 to apply).

Byte order & addressing

Network setup

Watch out for

Continental Control Systems WattNode Modbus (WNC) energy meter Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

107 of 107 shown
Continental Control Systems WattNode Modbus (WNC) energy meter Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR1000doc 1001, 1002EnergySumNet (bidirectional) energy. Kept through power loss; can be reset or preset.FLOAT32CDABkWhRead/write
HR1002doc 1003, 1004EnergyPosSumPositive energy. Kept through power loss; can be reset or preset.FLOAT32CDABkWhRead/write
HR1004doc 1005, 1006EnergySumNRNet energy, non-resettable.FLOAT32CDABkWhRead
HR1006doc 1007, 1008EnergyPosSumNRPositive energy, non-resettable.FLOAT32CDABkWhRead
HR1008doc 1009, 1010PowerSumReal power, sum of active phases.FLOAT32CDABWRead
HR1010doc 1011, 1012PowerAFLOAT32CDABWRead
HR1012doc 1013, 1014PowerBFLOAT32CDABWRead
HR1014doc 1015, 1016PowerCFLOAT32CDABWRead
HR1016doc 1017, 1018VoltAvgLNAverage line-to-neutral voltage.FLOAT32CDABVRead
HR1018doc 1019, 1020VoltAFLOAT32CDABVRead
HR1020doc 1021, 1022VoltBFLOAT32CDABVRead
HR1022doc 1023, 1024VoltCFLOAT32CDABVRead
HR1024doc 1025, 1026VoltAvgLLAverage line-to-line voltage.FLOAT32CDABVRead
HR1026doc 1027, 1028VoltABFLOAT32CDABVRead
HR1028doc 1029, 1030VoltBCFLOAT32CDABVRead
HR1030doc 1031, 1032VoltACFLOAT32CDABVRead
HR1032doc 1033, 1034FreqLine frequency.FLOAT32CDABHzRead
HR1100doc 1101, 1102EnergyAResettable/presettable.FLOAT32CDABkWhRead/write
HR1102doc 1103, 1104EnergyBResettable/presettable.FLOAT32CDABkWhRead/write
HR1104doc 1105, 1106EnergyCResettable/presettable.FLOAT32CDABkWhRead/write
HR1106doc 1107, 1108EnergyPosAResettable/presettable.FLOAT32CDABkWhRead/write
HR1108doc 1109, 1110EnergyPosBResettable/presettable.FLOAT32CDABkWhRead/write
HR1110doc 1111, 1112EnergyPosCResettable/presettable.FLOAT32CDABkWhRead/write
HR1112doc 1113, 1114EnergyNegSumResettable/presettable.FLOAT32CDABkWhRead/write
HR1114doc 1115, 1116EnergyNegSumNRFLOAT32CDABkWhRead
HR1116doc 1117, 1118EnergyNegAResettable/presettable.FLOAT32CDABkWhRead/write
HR1118doc 1119, 1120EnergyNegBResettable/presettable.FLOAT32CDABkWhRead/write
HR1120doc 1121, 1122EnergyNegCResettable/presettable.FLOAT32CDABkWhRead/write
HR1122doc 1123, 1124EnergyReacSumResettable/presettable.FLOAT32CDABkVARhRead/write
HR1124doc 1125, 1126EnergyReacAResettable/presettable.FLOAT32CDABkVARhRead/write
HR1126doc 1127, 1128EnergyReacBResettable/presettable.FLOAT32CDABkVARhRead/write
HR1128doc 1129, 1130EnergyReacCResettable/presettable.FLOAT32CDABkVARhRead/write
HR1130doc 1131, 1132EnergyAppSumResettable/presettable.FLOAT32CDABkVAhRead/write
HR1132doc 1133, 1134EnergyAppAResettable/presettable.FLOAT32CDABkVAhRead/write
HR1134doc 1135, 1136EnergyAppBResettable/presettable.FLOAT32CDABkVAhRead/write
HR1136doc 1137, 1138EnergyAppCResettable/presettable.FLOAT32CDABkVAhRead/write
HR1138doc 1139, 1140PowerFactorAvgFLOAT32CDABRead
HR1140doc 1141, 1142PowerFactorAFLOAT32CDABRead
HR1142doc 1143, 1144PowerFactorBFLOAT32CDABRead
HR1144doc 1145, 1146PowerFactorCFLOAT32CDABRead
HR1146doc 1147, 1148PowerReacSumFLOAT32CDABVARRead
HR1148doc 1149, 1150PowerReacAFLOAT32CDABVARRead
HR1150doc 1151, 1152PowerReacBFLOAT32CDABVARRead
HR1152doc 1153, 1154PowerReacCFLOAT32CDABVARRead
HR1154doc 1155, 1156PowerAppSumFLOAT32CDABVARead
HR1156doc 1157, 1158PowerAppAFLOAT32CDABVARead
HR1158doc 1159, 1160PowerAppBFLOAT32CDABVARead
HR1160doc 1161, 1162PowerAppCFLOAT32CDABVARead
HR1162doc 1163, 1164CurrentAFLOAT32CDABARead
HR1164doc 1165, 1166CurrentBFLOAT32CDABARead
HR1166doc 1167, 1168CurrentCFLOAT32CDABARead
HR1168doc 1169, 1170DemandReal power demand over the demand period.FLOAT32CDABWRead
HR1170doc 1171, 1172DemandMinFLOAT32CDABWRead
HR1172doc 1173, 1174DemandMaxFLOAT32CDABWRead
HR1174doc 1175, 1176DemandAppApparent power demand (unit printed as W).FLOAT32CDABWRead
HR1176doc 1177, 1178DemandAFLOAT32CDABWRead
HR1178doc 1179, 1180DemandBFLOAT32CDABWRead
HR1180doc 1181, 1182DemandCFLOAT32CDABWRead
HR1200doc 1201, 1202EnergySum (integer)Constant 0.1 kWh resolution.INT32CDAB× 0.1kWhRead/write
HR1202doc 1203, 1204EnergyPosSum (integer)Constant 0.1 kWh resolution.INT32CDAB× 0.1kWhRead/write
HR1204doc 1205, 1206EnergySumNR (integer)Constant 0.1 kWh resolution.INT32CDAB× 0.1kWhRead
HR1206doc 1207, 1208EnergyPosSumNR (integer)Constant 0.1 kWh resolution.INT32CDAB× 0.1kWhRead
HR1212doc 1213VoltAvgLN (integer)INT16× 0.1VRead
HR1213doc 1214VoltA (integer)INT16× 0.1VRead
HR1214doc 1215VoltB (integer)INT16× 0.1VRead
HR1215doc 1216VoltC (integer)INT16× 0.1VRead
HR1216doc 1217VoltAvgLL (integer)INT16× 0.1VRead
HR1217doc 1218VoltAB (integer)INT16× 0.1VRead
HR1218doc 1219VoltBC (integer)INT16× 0.1VRead
HR1219doc 1220VoltAC (integer)INT16× 0.1VRead
HR1220doc 1221Freq (integer)INT16× 0.1HzRead
HR1312doc 1313, 1314EnergyNegSum (integer)INT32CDAB× 0.1kWhRead/write
HR1314doc 1315, 1316EnergyNegSumNR (integer)INT32CDAB× 0.1kWhRead
HR1322doc 1323, 1324EnergyReacSum (integer)INT32CDAB× 0.1kVARhRead/write
HR1330doc 1331, 1332EnergyAppSum (integer)INT32CDAB× 0.1kVAhRead/write
HR1338doc 1339PowerFactorAvg (integer)INT16× 0.01Read
HR1339doc 1340PowerFactorA (integer)INT16× 0.01Read
HR1340doc 1341PowerFactorB (integer)INT16× 0.01Read
HR1341doc 1342PowerFactorC (integer)INT16× 0.01Read
HR1360doc 1361IoPinStateI/O pin digital input or output state (I/O option).INT16Read
HR1361doc 1362PulseCountI/O pin pulse count (I/O option).INT16Read
HR1602doc 1603CtAmpsSets all three CT ratings at once; default 5.INT16ARead/write
HR1603doc 1604CtAmpsAPhase A CT rated current, 0-6000.INT16ARead/write
HR1604doc 1605CtAmpsB0-6000.INT16ARead/write
HR1605doc 1606CtAmpsC0-6000.INT16ARead/write
HR1606doc 1607CtDirectionsInvert CT orientations, 0-7.INT16Read/write
HR1607doc 1608AveragingMeasurement averaging 0-3; default 1 (fast).INT16Read/write
HR1608doc 1609PowerIntScaleScale for integer power registers, 0 = auto (default).INT16WRead/write
HR1609doc 1610DemPerMinsDemand period 1-720, default 15.INT16minRead/write
HR1610doc 1611DemSubintsDemand subintervals 1-10.INT16Read/write
HR1618doc 1619PhaseOffsetNominal angle between voltage phases; default 120.INT16degRead/write
HR1619doc 1620ZeroEnergyWrite 1 to zero all resettable energy registers.INT16Read/write
HR1620doc 1621ZeroDemandWrite 1 to zero all demand values.INT16Read/write
HR1621doc 1622CurrentIntScaleScale factor for integer currents, default 20000.INT16Read/write
HR1650doc 1651ApplyComConfigWrite 1234 to apply 1652-1656; reads 1 if changes are pending.INT16Read/write
HR1651doc 1652Address (Modbus address override)Modbus address; non-zero overrides the DIP switches.INT16Read/write
HR1652doc 1653BaudRateINT16Read/write0 = DIP switch assigned; 1 = 1200; 2 = 2400; 3 = 4800; 4 = 9600; 5 = 19200; 6 = 38400
HR1653doc 1654ParityModeINT16Read/write0 = N81 - no parity, 1 stop bit; 1 = E81 - even parity, 1 stop bit
HR1654doc 1655ModbusModeINT16Read/write0 = RTU; 1 = TCP-RTU
HR1655doc 1656ReplyDelayMinimum reply delay 5-180 ms, default 5.INT16msRead/write
HR1700doc 1701, 1702SerialNumberINT32CDABRead
HR1702doc 1703, 1704UptimeSecsSeconds since last power on.INT32CDABsRead
HR1704doc 1705, 1706TotalSecsTotal seconds of operation.INT32CDABsRead
HR1706doc 1707ModelINT16Read201 = WNC-3Y-208-MB; 202 = WNC-3Y-400-MB; 203 = WNC-3Y-480-MB; 204 = WNC-3Y-600-MB; 205 = WNC-3D-240-MB; 206 = WNC-3D-400-MB; 207 = WNC-3D-480-MB
HR1707doc 1708VersionFirmware version.INT16Read
HR1709doc 1710ErrorStatusRecent error/event code; see the manual's error list.INT16Read
HR1710doc 1711PowerFailCountPower cycles, up to 32767.INT16Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Continental Control Systems WattNode Modbus (WNC) energy meter

What Modbus registers does the Continental Control Systems WattNode Modbus (WNC) energy meter have?

This map lists 107 registers: 107 holding registers. 44 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Continental Control Systems WattNode Modbus (WNC) energy meter Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual documents registers one-based and says they are sent zero-based: EnergySum is documented at 1001 and appears on the bus as 1000 (0x03E8). Wire address = documented number - 1.

What byte order does the Continental Control Systems WattNode Modbus (WNC) energy meter use for 32-bit values?

Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Continental Control Systems WattNode Modbus (WNC) energy meter?

Start with HR 1000 EnergySum (EnergySum (kWh)); HR 1008 PowerSum (PowerSum (W)); HR 1016 VoltAvgLN (Average L-N voltage); HR 1162 CurrentA (Current phase A); HR 1138 PowerFactorAvg (Average power factor); HR 1032 Freq (Frequency); HR 1602 CtAmps (CtAmps (must match the CTs)).

How do I enable Modbus control of the Continental Control Systems WattNode Modbus (WNC) energy meter?

Modbus RTU on RS-485 is always on. Address and baud come from the DIP switches unless overridden at 1652-1656 (write 1234 to 1651 to apply).

Where is the official Continental Control Systems WattNode Modbus (WNC) energy meter Modbus documentation?

The source is WattNode Modbus Installation and Operation Manual (WNC-MB-1.18c), revision 2015-11-03, published free by Continental Control Systems at https://ctlsys.com/m/WNC-MB-Ref-Manual.pdf.

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: WattNode Modbus Installation and Operation Manual · WNC-MB-1.18c · rev. 2015-11-03. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.