Energy meter · Modbus register map
Continental Control Systems WattNode Modbus (WNC) energy meter Modbus register map
Updated 17 November 2026
The WattNode Modbus is a compact three-phase energy meter with external CTs and an RS-485 Modbus RTU port. Most values come both as 32-bit floats and as scaled integers; 32-bit values are sent low word first. This map covers energy (net, positive, negative, reactive, apparent), power, voltage, current, PF, frequency, demand, CT and demand configuration, communication overrides and diagnostics.
This page lists 107 Modbus registers for the Continental Control Systems WattNode Modbus (WNC) energy meter — 44 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Continental Control Systems’s own free documentation (linked below) and checked against it.
- Manufacturer
- Continental Control Systems
- Model
- WattNode Modbus (WNC) energy meter
- Equipment type
- Energy meter
- Registers
- 107 (44 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 9600 baud, 8N1
- Documented addressing
- 1-based (subtract 1 for the wire address)
- 32-bit word order
- CDAB low word first (word-swapped)
- Firmware
- 18-24
- Also known as
- WNC-3Y-208-MB, WNC-3Y-400-MB, WNC-3Y-480-MB, WNC-3Y-600-MB, WNC-3D-240-MB, WNC-3D-400-MB, WNC-3D-480-MB, RWNC-3Y-208-MB, RWNC-3Y-400-MB, RWNC-3Y-480-MB, RWNC-3Y-600-MB, RWNC-3D-240-MB, RWNC-3D-400-MB, RWNC-3D-480-MB, WattNode Revenue Modbus
Integration notes: Continental Control Systems WattNode Modbus (WNC) energy meter
Set the address and baud on the DIP switches, set CtAmps (1603), then read floats from 1001-1034 (documented numbers; wire 1000-1033) in one request, decoding each pair low word first.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 1000 | EnergySum | FLOAT32 CDAB | EnergySum (kWh) | Read/write |
| HR 1008 | PowerSum | FLOAT32 CDAB | PowerSum (W) | Read |
| HR 1016 | VoltAvgLN | FLOAT32 CDAB | Average L-N voltage | Read |
| HR 1162 | CurrentA | FLOAT32 CDAB | Current phase A | Read |
| HR 1138 | PowerFactorAvg | FLOAT32 CDAB | Average power factor | Read |
| HR 1032 | Freq | FLOAT32 CDAB | Frequency | Read |
| HR 1602 | CtAmps | INT16 | CtAmps (must match the CTs) | Read/write |
Enable Modbus control & writes
Modbus RTU on RS-485 is always on. Address and baud come from the DIP switches unless overridden at 1652-1656 (write 1234 to 1651 to apply).
Byte order & addressing
- 32-bit values are low word first (CDAB).
- Documented numbers are one-based; subtract 1 on the wire.
- Float energy loses resolution above 100,000 kWh; the integer energy registers keep 0.1 kWh.
Network setup
- Default 9600 baud (DIP switch 8 down), N81.
- Set CtAmps (1603) to the CT rating before reading power.
Watch out for
- A configuration passcode (1601) blocks writes if one was set.
- Writing a 32-bit register with two single writes must happen within 30 s with nothing else in between.
Continental Control Systems WattNode Modbus (WNC) energy meter Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 1000doc 1001, 1002 | EnergySum | Net (bidirectional) energy. Kept through power loss; can be reset or preset. | FLOAT32 | CDAB | kWh | Read/write | ||
| HR | 1002doc 1003, 1004 | EnergyPosSum | Positive energy. Kept through power loss; can be reset or preset. | FLOAT32 | CDAB | kWh | Read/write | ||
| HR | 1004doc 1005, 1006 | EnergySumNR | Net energy, non-resettable. | FLOAT32 | CDAB | kWh | Read | ||
| HR | 1006doc 1007, 1008 | EnergyPosSumNR | Positive energy, non-resettable. | FLOAT32 | CDAB | kWh | Read | ||
| HR | 1008doc 1009, 1010 | PowerSum | Real power, sum of active phases. | FLOAT32 | CDAB | W | Read | ||
| HR | 1010doc 1011, 1012 | PowerA | FLOAT32 | CDAB | W | Read | |||
| HR | 1012doc 1013, 1014 | PowerB | FLOAT32 | CDAB | W | Read | |||
| HR | 1014doc 1015, 1016 | PowerC | FLOAT32 | CDAB | W | Read | |||
| HR | 1016doc 1017, 1018 | VoltAvgLN | Average line-to-neutral voltage. | FLOAT32 | CDAB | V | Read | ||
| HR | 1018doc 1019, 1020 | VoltA | FLOAT32 | CDAB | V | Read | |||
| HR | 1020doc 1021, 1022 | VoltB | FLOAT32 | CDAB | V | Read | |||
| HR | 1022doc 1023, 1024 | VoltC | FLOAT32 | CDAB | V | Read | |||
| HR | 1024doc 1025, 1026 | VoltAvgLL | Average line-to-line voltage. | FLOAT32 | CDAB | V | Read | ||
| HR | 1026doc 1027, 1028 | VoltAB | FLOAT32 | CDAB | V | Read | |||
| HR | 1028doc 1029, 1030 | VoltBC | FLOAT32 | CDAB | V | Read | |||
| HR | 1030doc 1031, 1032 | VoltAC | FLOAT32 | CDAB | V | Read | |||
| HR | 1032doc 1033, 1034 | Freq | Line frequency. | FLOAT32 | CDAB | Hz | Read | ||
| HR | 1100doc 1101, 1102 | EnergyA | Resettable/presettable. | FLOAT32 | CDAB | kWh | Read/write | ||
| HR | 1102doc 1103, 1104 | EnergyB | Resettable/presettable. | FLOAT32 | CDAB | kWh | Read/write | ||
| HR | 1104doc 1105, 1106 | EnergyC | Resettable/presettable. | FLOAT32 | CDAB | kWh | Read/write | ||
| HR | 1106doc 1107, 1108 | EnergyPosA | Resettable/presettable. | FLOAT32 | CDAB | kWh | Read/write | ||
| HR | 1108doc 1109, 1110 | EnergyPosB | Resettable/presettable. | FLOAT32 | CDAB | kWh | Read/write | ||
| HR | 1110doc 1111, 1112 | EnergyPosC | Resettable/presettable. | FLOAT32 | CDAB | kWh | Read/write | ||
| HR | 1112doc 1113, 1114 | EnergyNegSum | Resettable/presettable. | FLOAT32 | CDAB | kWh | Read/write | ||
| HR | 1114doc 1115, 1116 | EnergyNegSumNR | FLOAT32 | CDAB | kWh | Read | |||
| HR | 1116doc 1117, 1118 | EnergyNegA | Resettable/presettable. | FLOAT32 | CDAB | kWh | Read/write | ||
| HR | 1118doc 1119, 1120 | EnergyNegB | Resettable/presettable. | FLOAT32 | CDAB | kWh | Read/write | ||
| HR | 1120doc 1121, 1122 | EnergyNegC | Resettable/presettable. | FLOAT32 | CDAB | kWh | Read/write | ||
| HR | 1122doc 1123, 1124 | EnergyReacSum | Resettable/presettable. | FLOAT32 | CDAB | kVARh | Read/write | ||
| HR | 1124doc 1125, 1126 | EnergyReacA | Resettable/presettable. | FLOAT32 | CDAB | kVARh | Read/write | ||
| HR | 1126doc 1127, 1128 | EnergyReacB | Resettable/presettable. | FLOAT32 | CDAB | kVARh | Read/write | ||
| HR | 1128doc 1129, 1130 | EnergyReacC | Resettable/presettable. | FLOAT32 | CDAB | kVARh | Read/write | ||
| HR | 1130doc 1131, 1132 | EnergyAppSum | Resettable/presettable. | FLOAT32 | CDAB | kVAh | Read/write | ||
| HR | 1132doc 1133, 1134 | EnergyAppA | Resettable/presettable. | FLOAT32 | CDAB | kVAh | Read/write | ||
| HR | 1134doc 1135, 1136 | EnergyAppB | Resettable/presettable. | FLOAT32 | CDAB | kVAh | Read/write | ||
| HR | 1136doc 1137, 1138 | EnergyAppC | Resettable/presettable. | FLOAT32 | CDAB | kVAh | Read/write | ||
| HR | 1138doc 1139, 1140 | PowerFactorAvg | FLOAT32 | CDAB | Read | ||||
| HR | 1140doc 1141, 1142 | PowerFactorA | FLOAT32 | CDAB | Read | ||||
| HR | 1142doc 1143, 1144 | PowerFactorB | FLOAT32 | CDAB | Read | ||||
| HR | 1144doc 1145, 1146 | PowerFactorC | FLOAT32 | CDAB | Read | ||||
| HR | 1146doc 1147, 1148 | PowerReacSum | FLOAT32 | CDAB | VAR | Read | |||
| HR | 1148doc 1149, 1150 | PowerReacA | FLOAT32 | CDAB | VAR | Read | |||
| HR | 1150doc 1151, 1152 | PowerReacB | FLOAT32 | CDAB | VAR | Read | |||
| HR | 1152doc 1153, 1154 | PowerReacC | FLOAT32 | CDAB | VAR | Read | |||
| HR | 1154doc 1155, 1156 | PowerAppSum | FLOAT32 | CDAB | VA | Read | |||
| HR | 1156doc 1157, 1158 | PowerAppA | FLOAT32 | CDAB | VA | Read | |||
| HR | 1158doc 1159, 1160 | PowerAppB | FLOAT32 | CDAB | VA | Read | |||
| HR | 1160doc 1161, 1162 | PowerAppC | FLOAT32 | CDAB | VA | Read | |||
| HR | 1162doc 1163, 1164 | CurrentA | FLOAT32 | CDAB | A | Read | |||
| HR | 1164doc 1165, 1166 | CurrentB | FLOAT32 | CDAB | A | Read | |||
| HR | 1166doc 1167, 1168 | CurrentC | FLOAT32 | CDAB | A | Read | |||
| HR | 1168doc 1169, 1170 | Demand | Real power demand over the demand period. | FLOAT32 | CDAB | W | Read | ||
| HR | 1170doc 1171, 1172 | DemandMin | FLOAT32 | CDAB | W | Read | |||
| HR | 1172doc 1173, 1174 | DemandMax | FLOAT32 | CDAB | W | Read | |||
| HR | 1174doc 1175, 1176 | DemandApp | Apparent power demand (unit printed as W). | FLOAT32 | CDAB | W | Read | ||
| HR | 1176doc 1177, 1178 | DemandA | FLOAT32 | CDAB | W | Read | |||
| HR | 1178doc 1179, 1180 | DemandB | FLOAT32 | CDAB | W | Read | |||
| HR | 1180doc 1181, 1182 | DemandC | FLOAT32 | CDAB | W | Read | |||
| HR | 1200doc 1201, 1202 | EnergySum (integer) | Constant 0.1 kWh resolution. | INT32 | CDAB | × 0.1 | kWh | Read/write | |
| HR | 1202doc 1203, 1204 | EnergyPosSum (integer) | Constant 0.1 kWh resolution. | INT32 | CDAB | × 0.1 | kWh | Read/write | |
| HR | 1204doc 1205, 1206 | EnergySumNR (integer) | Constant 0.1 kWh resolution. | INT32 | CDAB | × 0.1 | kWh | Read | |
| HR | 1206doc 1207, 1208 | EnergyPosSumNR (integer) | Constant 0.1 kWh resolution. | INT32 | CDAB | × 0.1 | kWh | Read | |
| HR | 1212doc 1213 | VoltAvgLN (integer) | INT16 | × 0.1 | V | Read | |||
| HR | 1213doc 1214 | VoltA (integer) | INT16 | × 0.1 | V | Read | |||
| HR | 1214doc 1215 | VoltB (integer) | INT16 | × 0.1 | V | Read | |||
| HR | 1215doc 1216 | VoltC (integer) | INT16 | × 0.1 | V | Read | |||
| HR | 1216doc 1217 | VoltAvgLL (integer) | INT16 | × 0.1 | V | Read | |||
| HR | 1217doc 1218 | VoltAB (integer) | INT16 | × 0.1 | V | Read | |||
| HR | 1218doc 1219 | VoltBC (integer) | INT16 | × 0.1 | V | Read | |||
| HR | 1219doc 1220 | VoltAC (integer) | INT16 | × 0.1 | V | Read | |||
| HR | 1220doc 1221 | Freq (integer) | INT16 | × 0.1 | Hz | Read | |||
| HR | 1312doc 1313, 1314 | EnergyNegSum (integer) | INT32 | CDAB | × 0.1 | kWh | Read/write | ||
| HR | 1314doc 1315, 1316 | EnergyNegSumNR (integer) | INT32 | CDAB | × 0.1 | kWh | Read | ||
| HR | 1322doc 1323, 1324 | EnergyReacSum (integer) | INT32 | CDAB | × 0.1 | kVARh | Read/write | ||
| HR | 1330doc 1331, 1332 | EnergyAppSum (integer) | INT32 | CDAB | × 0.1 | kVAh | Read/write | ||
| HR | 1338doc 1339 | PowerFactorAvg (integer) | INT16 | × 0.01 | Read | ||||
| HR | 1339doc 1340 | PowerFactorA (integer) | INT16 | × 0.01 | Read | ||||
| HR | 1340doc 1341 | PowerFactorB (integer) | INT16 | × 0.01 | Read | ||||
| HR | 1341doc 1342 | PowerFactorC (integer) | INT16 | × 0.01 | Read | ||||
| HR | 1360doc 1361 | IoPinState | I/O pin digital input or output state (I/O option). | INT16 | Read | ||||
| HR | 1361doc 1362 | PulseCount | I/O pin pulse count (I/O option). | INT16 | Read | ||||
| HR | 1602doc 1603 | CtAmps | Sets all three CT ratings at once; default 5. | INT16 | A | Read/write | |||
| HR | 1603doc 1604 | CtAmpsA | Phase A CT rated current, 0-6000. | INT16 | A | Read/write | |||
| HR | 1604doc 1605 | CtAmpsB | 0-6000. | INT16 | A | Read/write | |||
| HR | 1605doc 1606 | CtAmpsC | 0-6000. | INT16 | A | Read/write | |||
| HR | 1606doc 1607 | CtDirections | Invert CT orientations, 0-7. | INT16 | Read/write | ||||
| HR | 1607doc 1608 | Averaging | Measurement averaging 0-3; default 1 (fast). | INT16 | Read/write | ||||
| HR | 1608doc 1609 | PowerIntScale | Scale for integer power registers, 0 = auto (default). | INT16 | W | Read/write | |||
| HR | 1609doc 1610 | DemPerMins | Demand period 1-720, default 15. | INT16 | min | Read/write | |||
| HR | 1610doc 1611 | DemSubints | Demand subintervals 1-10. | INT16 | Read/write | ||||
| HR | 1618doc 1619 | PhaseOffset | Nominal angle between voltage phases; default 120. | INT16 | deg | Read/write | |||
| HR | 1619doc 1620 | ZeroEnergy | Write 1 to zero all resettable energy registers. | INT16 | Read/write | ||||
| HR | 1620doc 1621 | ZeroDemand | Write 1 to zero all demand values. | INT16 | Read/write | ||||
| HR | 1621doc 1622 | CurrentIntScale | Scale factor for integer currents, default 20000. | INT16 | Read/write | ||||
| HR | 1650doc 1651 | ApplyComConfig | Write 1234 to apply 1652-1656; reads 1 if changes are pending. | INT16 | Read/write | ||||
| HR | 1651doc 1652 | Address (Modbus address override) | Modbus address; non-zero overrides the DIP switches. | INT16 | Read/write | ||||
| HR | 1652doc 1653 | BaudRate | INT16 | Read/write | 0 = DIP switch assigned; 1 = 1200; 2 = 2400; 3 = 4800; 4 = 9600; 5 = 19200; 6 = 38400 | ||||
| HR | 1653doc 1654 | ParityMode | INT16 | Read/write | 0 = N81 - no parity, 1 stop bit; 1 = E81 - even parity, 1 stop bit | ||||
| HR | 1654doc 1655 | ModbusMode | INT16 | Read/write | 0 = RTU; 1 = TCP-RTU | ||||
| HR | 1655doc 1656 | ReplyDelay | Minimum reply delay 5-180 ms, default 5. | INT16 | ms | Read/write | |||
| HR | 1700doc 1701, 1702 | SerialNumber | INT32 | CDAB | Read | ||||
| HR | 1702doc 1703, 1704 | UptimeSecs | Seconds since last power on. | INT32 | CDAB | s | Read | ||
| HR | 1704doc 1705, 1706 | TotalSecs | Total seconds of operation. | INT32 | CDAB | s | Read | ||
| HR | 1706doc 1707 | Model | INT16 | Read | 201 = WNC-3Y-208-MB; 202 = WNC-3Y-400-MB; 203 = WNC-3Y-480-MB; 204 = WNC-3Y-600-MB; 205 = WNC-3D-240-MB; 206 = WNC-3D-400-MB; 207 = WNC-3D-480-MB | ||||
| HR | 1707doc 1708 | Version | Firmware version. | INT16 | Read | ||||
| HR | 1709doc 1710 | ErrorStatus | Recent error/event code; see the manual's error list. | INT16 | Read | ||||
| HR | 1710doc 1711 | PowerFailCount | Power cycles, up to 32767. | INT16 | Read |
Notes on this map
- Word order: the manual says the first (lower) register of a float or 32-bit integer holds the least significant 16 bits (little-endian, 'byte order 1032' on Tridium), so 32-bit values are CDAB.
- Holding and input registers are interchangeable (functions 03 and 04 return the same data).
- Left out: ConfigPasscode (1601-1602, signedness not stated); integer power, current and demand registers (1209-1212, 1343-1360), which use the configurable PowerIntScale/CurrentIntScale factors; integer per-phase energies; gain/phase adjustment, creep and I/O mode settings; option information and custom register map registers.
- Read both halves of a 32-bit value in one request; the meter only guarantees a consistent pair within a single read.
- The Model register lists codes only for WNC models; revenue RWNC codes are not given.
- SerialNumber, UptimeSecs and TotalSecs are described as 32-bit long integers, which the manual defines as signed, so they are INT32.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Continental Control Systems WattNode Modbus (WNC) energy meter
What Modbus registers does the Continental Control Systems WattNode Modbus (WNC) energy meter have?
This map lists 107 registers: 107 holding registers. 44 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Continental Control Systems WattNode Modbus (WNC) energy meter Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual documents registers one-based and says they are sent zero-based: EnergySum is documented at 1001 and appears on the bus as 1000 (0x03E8). Wire address = documented number - 1.
What byte order does the Continental Control Systems WattNode Modbus (WNC) energy meter use for 32-bit values?
Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Continental Control Systems WattNode Modbus (WNC) energy meter?
Start with HR 1000 EnergySum (EnergySum (kWh)); HR 1008 PowerSum (PowerSum (W)); HR 1016 VoltAvgLN (Average L-N voltage); HR 1162 CurrentA (Current phase A); HR 1138 PowerFactorAvg (Average power factor); HR 1032 Freq (Frequency); HR 1602 CtAmps (CtAmps (must match the CTs)).
How do I enable Modbus control of the Continental Control Systems WattNode Modbus (WNC) energy meter?
Modbus RTU on RS-485 is always on. Address and baud come from the DIP switches unless overridden at 1652-1656 (write 1234 to 1651 to apply).
Where is the official Continental Control Systems WattNode Modbus (WNC) energy meter Modbus documentation?
The source is WattNode Modbus Installation and Operation Manual (WNC-MB-1.18c), revision 2015-11-03, published free by Continental Control Systems at https://ctlsys.com/m/WNC-MB-Ref-Manual.pdf.
Other power & energy meters register maps
- Energy meter
Eastron SDM120CT-M
Eastron SDM120CTM single-phase CT-operated DIN-rail meter (1 A / 5 A CT secondary), protocol implementation V1.3. Not the SDM120CT-40mA.
Also known as: SDM120CTM, SDM120CT Modbus, SDM120CT-MV - Power meter
Eaton Power Xpert Meter 1000 Series (PXM 1000/1100/1200/1300)
Eaton PXM 1000 series meters on the built-in RS-485 Modbus RTU port, per user manual MN150009EN (October 2018).
Also known as: PXM 1000, PXM 1100, PXM 1200, PXM 1300, PXM1000, PXM1100, PXM1200, PXM1300, Power Xpert Meter 1000 - Energy meter
Finder 7M.24 single-phase energy meter (Modbus RS485)
Finder 7M.24 single-phase meters with RS485 communication, per the 7M24 section of 'Modbus Communication Protocol 7M24 - 7M38' v2.
Also known as: 7M.24, 7M24, Finder 7M24 Modbus - Power meter
IME Nemo 96HD multifunction meter (MF96001 / MF96021)
IME Nemo 96HD panel meters MF96001 and MF96021 with an RS-485 module, per protocol PR106 (software 3.18).
Also known as: MF96001, MF96021, Nemo 96HD - Energy meter
inepro Metering PRO1 single-phase energy meter (2026 PRO line)
PRO1-Mod (art. 1101) and PRO1-Mod-Ba (art. 1102, with RTC tariffs) from the 2026 PRO1 user manual version 1.3; the PRO1-S has no Modbus.
Also known as: PRO1-Mod, PRO1-Mod-Ba, PRO1 1U AC 45A Mo T MID, PRO1 1U AC 45A Mo T Ba MID, 1101, 1102 - Power meter (power analyser)
Janitza UMG 104 power analyser (RS-485 Modbus RTU)
UMG 104 DIN-rail power analyser, firmware 1.268, per address list 1.041.006.1.e (01/2023).
Also known as: UMG104, UMG 104, Janitza UMG104
All power & energy meters Modbus register maps →
Source: WattNode Modbus Installation and Operation Manual · WNC-MB-1.18c · rev. 2015-11-03. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.