Energy meter · Modbus register map
Eastron SDM120CT-M Modbus register map
Updated 17 November 2026
The SDM120CT-M is a single-phase DIN-rail kWh meter that measures through an external current transformer and reports over RS485 Modbus RTU. Readings are IEEE-754 floats in input register pairs (function 04). Holding registers set the CT primary and secondary, demand period, communication and pulse settings.
This page lists 33 Modbus registers for the Eastron SDM120CT-M — 11 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Eastron’s own free documentation (linked below) and checked against it.
- Manufacturer
- Eastron
- Model
- SDM120CT-M
- Equipment type
- Energy meter
- Registers
- 33 (11 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 2400 baud, 8N1
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- SDM120CTM, SDM120CT Modbus, SDM120CT-MV
Integration notes: Eastron SDM120CT-M
Read input registers with function 04 in two-register pairs; each value is an IEEE-754 float, high word first. Voltage is at 0x0000, current at 0x0006, active power at 0x000C and import kWh at 0x0048.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 0 | Voltage | FLOAT32 ABCD | Voltage | Read |
| IR 6 | Current | FLOAT32 ABCD | Current | Read |
| IR 12 | Active power | FLOAT32 ABCD | Active power | Read |
| IR 30 | Power factor | FLOAT32 ABCD | Power factor | Read |
| IR 70 | Frequency | FLOAT32 ABCD | Frequency | Read |
| IR 72 | Import active energy | FLOAT32 ABCD | Import kWh | Read |
| IR 342 | Total active energy | FLOAT32 ABCD | Total kWh | Read |
Enable Modbus control & writes
Modbus RTU is always available on the RS485 terminals. Set CT1/CT2 to match the installed transformer before trusting current, power or energy.
Byte order & addressing
- Settings at 40001-40087 are floats over two registers (write with function 16); the F9xx registers are single 16-bit hex values.
- The parity/stop setting only takes effect after a restart.
Network setup
- Default: Modbus address 1, 2400 baud, no parity, 1 stop bit (data bits not stated in this document).
- Baud rates 1200, 2400, 4800 and 9600 are selectable.
Watch out for
- The factory default baud rate is 2400, not 9600; set the master accordingly before the first read.
Eastron SDM120CT-M Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 0doc 30001 | Voltage | FLOAT32 | ABCD | V | Read | |||
| IR | 6doc 30007 | Current | FLOAT32 | ABCD | A | Read | |||
| IR | 12doc 30013 | Active power | FLOAT32 | ABCD | W | Read | |||
| IR | 18doc 30019 | Apparent power | FLOAT32 | ABCD | VA | Read | |||
| IR | 24doc 30025 | Reactive power | FLOAT32 | ABCD | VAr | Read | |||
| IR | 30doc 30031 | Power factor | FLOAT32 | ABCD | Read | ||||
| IR | 70doc 30071 | Frequency | FLOAT32 | ABCD | Hz | Read | |||
| IR | 72doc 30073 | Import active energy | FLOAT32 | ABCD | kWh | Read | |||
| IR | 74doc 30075 | Export active energy | FLOAT32 | ABCD | kWh | Read | |||
| IR | 76doc 30077 | Import reactive energy | FLOAT32 | ABCD | kVArh | Read | |||
| IR | 78doc 30079 | Export reactive energy | FLOAT32 | ABCD | kVArh | Read | |||
| IR | 84doc 30085 | Total active power demand | FLOAT32 | ABCD | W | Read | |||
| IR | 86doc 30087 | Max total active power demand | FLOAT32 | ABCD | W | Read | |||
| IR | 88doc 30089 | Import active power demand | FLOAT32 | ABCD | W | Read | |||
| IR | 90doc 30091 | Max import active power demand | FLOAT32 | ABCD | W | Read | |||
| IR | 92doc 30093 | Export active power demand | FLOAT32 | ABCD | W | Read | |||
| IR | 94doc 30095 | Max export active power demand | FLOAT32 | ABCD | W | Read | |||
| IR | 258doc 30259 | Current demand | FLOAT32 | ABCD | A | Read | |||
| IR | 264doc 30265 | Max current demand | FLOAT32 | ABCD | A | Read | |||
| IR | 342doc 30343 | Total active energy | Per the Measurement mode setting (default import + export). | FLOAT32 | ABCD | kWh | Read | ||
| IR | 344doc 30345 | Total reactive energy | FLOAT32 | ABCD | kVArh | Read | |||
| HR | 0doc 40001 | Demand time | Minutes into the first demand period; demand values valid once it reaches the period. | FLOAT32 | ABCD | min | Read | ||
| HR | 2doc 40003 | Demand period | 0-60 minutes, default 60; 0 turns demand off. | FLOAT32 | ABCD | min | Read/write | ||
| HR | 12doc 40013 | Relay pulse width | 60, 100 or 200 ms (default 100). | FLOAT32 | ABCD | ms | Read/write | ||
| HR | 18doc 40019 | Network parity / stop bits | Takes effect after restart. | FLOAT32 | ABCD | Read/write | 0 = No parity, 1 stop bit (default); 1 = Even parity, 1 stop bit; 2 = Odd parity, 1 stop bit; 3 = No parity, 2 stop bits | ||
| HR | 20doc 40021 | Meter ID (Modbus address) | 1-247, default 1. | FLOAT32 | ABCD | Read/write | |||
| HR | 28doc 40029 | Baud rate | FLOAT32 | ABCD | Read/write | 0 = 2400 (default); 1 = 4800; 2 = 9600; 5 = 1200 | |||
| HR | 50doc 40051 | CT1 primary current | CT primary rating, 5-9999 (default 5). | FLOAT32 | ABCD | A | Read/write | ||
| HR | 52doc 40053 | CT2 secondary current | CT secondary: 1 A or 5 A (default 5 A). | FLOAT32 | ABCD | A | Read/write | ||
| HR | 86doc 40087 | Pulse 1 output mode | Energy quantity driving the pulse output. | FLOAT32 | ABCD | Read/write | 1 = Import active energy; 2 = Import + export active energy; 4 = Export active energy (default); 5 = Import reactive energy; 6 = Import + export reactive energy; 8 = Export reactive energy | ||
| HR | 61456doc 461457 | Reset historical data | Write 0x0000 to reset demand values. | UINT16 | Write | 0 = Reset demand | |||
| HR | 63760doc 463761 | Pulse 1 output constant | UINT16 | Read/write | 0 = 0.001 kWh/imp; 1 = 0.01 kWh/imp (default); 2 = 0.1 kWh/imp; 3 = 1 kWh/imp; 4 = 10 kWh/imp; 5 = 100 kWh/imp; 6 = 1000 kWh/imp | ||||
| HR | 63776doc 463777 | Measurement mode | How the total energy registers are calculated. | UINT16 | Read/write | 1 = Total = import; 2 = Total = import + export (default); 3 = Total = import - export |
Notes on this map
- Word order: the document's read example returns 43 66 33 34 (high register first) for 230.2 V, so all floats here are ABCD.
- Floats must be read in register pairs starting on an even address; odd counts or starts return an exception.
- Left out: the serial number (464513), an unsigned 32-bit integer whose word order the document does not state, and the scroll-display time register (463745), whose format is given as BCD without an encoding rule.
- Source host: the PDF is served from the media store used by Eastron Europe (Fastron Electronics, Eastron's UK distributor) for its product pages.
- This is the 1 A / 5 A CT version; the SDM120CT-40mA has its own map in this library.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Eastron SDM120CT-M
What Modbus registers does the Eastron SDM120CT-M have?
This map lists 33 registers: 21 input registers, 12 holding registers. 11 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Eastron SDM120CT-M Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are printed 30001/40001 style (six-digit 46xxxx for the F0xx/F9xx block) next to the hex start address sent on the wire, e.g. 30007 = 0x0006 and 463777 = 0xF920. Wire address = printed number minus 30001, 40001 or 400001.
What byte order does the Eastron SDM120CT-M use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Eastron SDM120CT-M?
Start with IR 0 Voltage (Voltage); IR 6 Current (Current); IR 12 Active power (Active power); IR 30 Power factor (Power factor); IR 70 Frequency (Frequency); IR 72 Import active energy (Import kWh); IR 342 Total active energy (Total kWh).
How do I enable Modbus control of the Eastron SDM120CT-M?
Modbus RTU is always available on the RS485 terminals. Set CT1/CT2 to match the installed transformer before trusting current, power or energy.
Where is the official Eastron SDM120CT-M Modbus documentation?
The source is Eastron SDM120CTM Smart Meter Modbus Protocol Implementation V1.3 (V1.3), published free by Eastron at https://res.cloudinary.com/fastron-electronics/image/upload/v1619064123/Eastron%20Europe/SDM120CT_Modbus_protocol.pdf.
More Eastron Modbus register maps
- Energy meter
Eastron SDM120-Modbus
Eastron SDM120Modbus single-phase DIN-rail meter (direct connected), protocol implementation V2.4.
Also known as: SDM120M, SDM120Modbus, SDM120-M - Energy meter
Eastron SDM120CT-40mA
Eastron SDM120CT-40mA single-phase CT-connected DIN-rail meter with RS485 Modbus RTU, user manual V1.0 (2026-07-16).
Also known as: SDM120CT-M-40mA, SDM120CT-M 40mA - Energy meter
Eastron SDM230-DI
Eastron SDM230-DI single-phase 100 A DIN-rail meter with two digital inputs and RS485 Modbus RTU, manual 2025 V1.00.
Also known as: SDM230 DI - Energy meter
Eastron SDM230-Modbus
Eastron SDM230-Modbus (two-tariff SDM230-2T protocol) single-phase two-module DIN-rail meter, protocol V1.1.
Also known as: SDM230Modbus, SDM230-2T, SDM230-M - Energy meter
Eastron SDM630-DI
Eastron SDM630-DI three-phase DIN-rail meter (100 A direct, two digital inputs, RS485 Modbus RTU), manual V1.02.
Also known as: SDM630 DI - Energy meter
Eastron SDM630-Modbus
Eastron SDM630Modbus three-phase DIN-rail meter, protocol implementation V1.8 as published by Eastron Europe.
Also known as: SDM630Modbus, SDM630 Modbus V2, SDM630-Modbus V2 - Energy meter
Eastron SDM630MCT
Eastron SDM630MCT three-phase CT-connected DIN-rail meter with RS485 Modbus RTU, protocol implementation V1.7.
Also known as: SDM630 MCT
Other power & energy meters register maps
- Power meter
Eaton Power Xpert Meter 1000 Series (PXM 1000/1100/1200/1300)
Eaton PXM 1000 series meters on the built-in RS-485 Modbus RTU port, per user manual MN150009EN (October 2018).
Also known as: PXM 1000, PXM 1100, PXM 1200, PXM 1300, PXM1000, PXM1100, PXM1200, PXM1300, Power Xpert Meter 1000 - Energy meter
Finder 7M.24 single-phase energy meter (Modbus RS485)
Finder 7M.24 single-phase meters with RS485 communication, per the 7M24 section of 'Modbus Communication Protocol 7M24 - 7M38' v2.
Also known as: 7M.24, 7M24, Finder 7M24 Modbus - Power meter
IME Nemo 96HD multifunction meter (MF96001 / MF96021)
IME Nemo 96HD panel meters MF96001 and MF96021 with an RS-485 module, per protocol PR106 (software 3.18).
Also known as: MF96001, MF96021, Nemo 96HD - Energy meter
inepro Metering PRO1 single-phase energy meter (2026 PRO line)
PRO1-Mod (art. 1101) and PRO1-Mod-Ba (art. 1102, with RTC tariffs) from the 2026 PRO1 user manual version 1.3; the PRO1-S has no Modbus.
Also known as: PRO1-Mod, PRO1-Mod-Ba, PRO1 1U AC 45A Mo T MID, PRO1 1U AC 45A Mo T Ba MID, 1101, 1102 - Power meter (power analyser)
Janitza UMG 104 power analyser (RS-485 Modbus RTU)
UMG 104 DIN-rail power analyser, firmware 1.268, per address list 1.041.006.1.e (01/2023).
Also known as: UMG104, UMG 104, Janitza UMG104 - Power meter (power quality analyser)
Janitza UMG 604-PRO power analyser (Modbus RTU / Modbus TCP)
UMG 604-PRO from firmware release 5.028, per address list 1.033.034.e (08/2023).
Also known as: UMG604-PRO, UMG 604PRO, UMG604PRO, UMG 604-EP PRO, Janitza UMG 604
All power & energy meters Modbus register maps →
Source: Eastron SDM120CTM Smart Meter Modbus Protocol Implementation V1.3 · V1.3. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.