Energy meter · Modbus register map
Eastron SDM120-Modbus Modbus register map
Updated 17 November 2026
The SDM120-Modbus is a one-module single-phase DIN-rail kWh meter with an RS485 Modbus RTU port. All measurements are IEEE-754 floats in input register pairs read with function 04: voltage, current, powers, power factor, frequency, import/export energy and demand. A handful of holding registers set the address, baud, parity, pulse output and how total energy is summed.
This page lists 28 Modbus registers for the Eastron SDM120-Modbus — 7 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Eastron’s own free documentation (linked below) and checked against it.
- Manufacturer
- Eastron
- Model
- SDM120-Modbus
- Equipment type
- Energy meter
- Registers
- 28 (7 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 2400 baud, 8N1
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- SDM120M, SDM120Modbus, SDM120-M
Integration notes: Eastron SDM120-Modbus
Read input registers with function 04 in two-register pairs; each value is an IEEE-754 float, high word first. Voltage is at 0x0000, current at 0x0006, active power at 0x000C and import kWh at 0x0048.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 0 | Voltage | FLOAT32 ABCD | Voltage | Read |
| IR 6 | Current | FLOAT32 ABCD | Current | Read |
| IR 12 | Active power | FLOAT32 ABCD | Active power | Read |
| IR 30 | Power factor | FLOAT32 ABCD | Power factor | Read |
| IR 70 | Frequency | FLOAT32 ABCD | Frequency | Read |
| IR 72 | Import active energy | FLOAT32 ABCD | Import kWh | Read |
| IR 342 | Total active energy | FLOAT32 ABCD | Total kWh | Read |
Enable Modbus control & writes
Modbus RTU is always available on the RS485 terminals.
Byte order & addressing
- Settings at 40001-40087 are floats over two registers (write with function 16); the F9xx registers are single 16-bit hex values.
- The parity/stop setting only takes effect after a restart.
Network setup
- Default: Modbus address 1, 2400 baud, no parity, 1 stop bit (data bits not stated in this document).
- Baud rates 1200, 2400, 4800 and 9600 are selectable.
Watch out for
- The factory default baud rate is 2400, not 9600; set the master accordingly before the first read.
Eastron SDM120-Modbus Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 0doc 30001 | Voltage | FLOAT32 | ABCD | V | Read | |||
| IR | 6doc 30007 | Current | FLOAT32 | ABCD | A | Read | |||
| IR | 12doc 30013 | Active power | FLOAT32 | ABCD | W | Read | |||
| IR | 18doc 30019 | Apparent power | FLOAT32 | ABCD | VA | Read | |||
| IR | 24doc 30025 | Reactive power | FLOAT32 | ABCD | VAr | Read | |||
| IR | 30doc 30031 | Power factor | FLOAT32 | ABCD | Read | ||||
| IR | 70doc 30071 | Frequency | FLOAT32 | ABCD | Hz | Read | |||
| IR | 72doc 30073 | Import active energy | FLOAT32 | ABCD | kWh | Read | |||
| IR | 74doc 30075 | Export active energy | FLOAT32 | ABCD | kWh | Read | |||
| IR | 76doc 30077 | Import reactive energy | FLOAT32 | ABCD | kVArh | Read | |||
| IR | 78doc 30079 | Export reactive energy | FLOAT32 | ABCD | kVArh | Read | |||
| IR | 84doc 30085 | Total active power demand | FLOAT32 | ABCD | W | Read | |||
| IR | 86doc 30087 | Max total active power demand | FLOAT32 | ABCD | W | Read | |||
| IR | 88doc 30089 | Import active power demand | FLOAT32 | ABCD | W | Read | |||
| IR | 90doc 30091 | Max import active power demand | FLOAT32 | ABCD | W | Read | |||
| IR | 92doc 30093 | Export active power demand | FLOAT32 | ABCD | W | Read | |||
| IR | 94doc 30095 | Max export active power demand | FLOAT32 | ABCD | W | Read | |||
| IR | 258doc 30259 | Current demand | FLOAT32 | ABCD | A | Read | |||
| IR | 264doc 30265 | Max current demand | FLOAT32 | ABCD | A | Read | |||
| IR | 342doc 30343 | Total active energy | Per the Measurement mode setting (default import + export). | FLOAT32 | ABCD | kWh | Read | ||
| IR | 344doc 30345 | Total reactive energy | FLOAT32 | ABCD | kVArh | Read | |||
| HR | 12doc 40013 | Relay pulse width | 60, 100 or 200 ms (default 100). | FLOAT32 | ABCD | ms | Read/write | ||
| HR | 18doc 40019 | Network parity / stop bits | Takes effect after restart. | FLOAT32 | ABCD | Read/write | 0 = No parity, 1 stop bit (default); 1 = Even parity, 1 stop bit; 2 = Odd parity, 1 stop bit; 3 = No parity, 2 stop bits | ||
| HR | 20doc 40021 | Meter ID (Modbus address) | 1-247, default 1. | FLOAT32 | ABCD | Read/write | |||
| HR | 28doc 40029 | Baud rate | FLOAT32 | ABCD | Read/write | 0 = 2400 (default); 1 = 4800; 2 = 9600; 5 = 1200 | |||
| HR | 86doc 40087 | Pulse 1 output mode | Energy quantity driving the pulse output. | FLOAT32 | ABCD | Read/write | 1 = Import active energy; 2 = Import + export active energy; 4 = Export active energy (default); 5 = Import reactive energy; 6 = Import + export reactive energy; 8 = Export reactive energy | ||
| HR | 63760doc 463761 | Pulse 1 output constant | UINT16 | Read/write | 0 = 0.001 kWh/imp (default); 1 = 0.01 kWh/imp; 2 = 0.1 kWh/imp; 3 = 1 kWh/imp | ||||
| HR | 63776doc 463777 | Measurement mode | How the total energy registers are calculated. | UINT16 | Read/write | 1 = Total = import; 2 = Total = import + export (default); 3 = Total = import - export |
Notes on this map
- Word order: the document's read example returns 43 66 33 34 (high register first) for 230.2 V, so all floats here are ABCD.
- Floats must be read in register pairs starting on an even address; odd counts or starts return an exception.
- Left out: the serial number (464513), an unsigned 32-bit integer whose word order the document does not state, and the scroll-display time register (463745), whose format is given only as HEX without an encoding rule.
- Source host: the PDF is served from the media store used by Eastron Europe (Fastron Electronics, Eastron's UK distributor) for its product pages.
- Left out: meter code (464515) and software version (464516) because the document gives only a 'Hex' format with no layout beyond the SDM120 code 00 20.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Eastron SDM120-Modbus
What Modbus registers does the Eastron SDM120-Modbus have?
This map lists 28 registers: 21 input registers, 7 holding registers. 7 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Eastron SDM120-Modbus Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are printed 30001/40001 style (six-digit 46xxxx for the F9xx block) next to the hex start address sent on the wire, e.g. 30007 = 0x0006 and 463777 = 0xF920. Wire address = printed number minus 30001, 40001 or 400001.
What byte order does the Eastron SDM120-Modbus use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Eastron SDM120-Modbus?
Start with IR 0 Voltage (Voltage); IR 6 Current (Current); IR 12 Active power (Active power); IR 30 Power factor (Power factor); IR 70 Frequency (Frequency); IR 72 Import active energy (Import kWh); IR 342 Total active energy (Total kWh).
How do I enable Modbus control of the Eastron SDM120-Modbus?
Modbus RTU is always available on the RS485 terminals.
Where is the official Eastron SDM120-Modbus Modbus documentation?
The source is Eastron SDM120Modbus Smart Meter Modbus Protocol Implementation V2.4 (V2.4), published free by Eastron at https://res.cloudinary.com/fastron-electronics/image/upload/v1625456706/Eastron%20Europe/SDM120-MODBUS_Protocol.pdf.
More Eastron Modbus register maps
- Energy meter
Eastron SDM120CT-40mA
Eastron SDM120CT-40mA single-phase CT-connected DIN-rail meter with RS485 Modbus RTU, user manual V1.0 (2026-07-16).
Also known as: SDM120CT-M-40mA, SDM120CT-M 40mA - Energy meter
Eastron SDM120CT-M
Eastron SDM120CTM single-phase CT-operated DIN-rail meter (1 A / 5 A CT secondary), protocol implementation V1.3. Not the SDM120CT-40mA.
Also known as: SDM120CTM, SDM120CT Modbus, SDM120CT-MV - Energy meter
Eastron SDM230-DI
Eastron SDM230-DI single-phase 100 A DIN-rail meter with two digital inputs and RS485 Modbus RTU, manual 2025 V1.00.
Also known as: SDM230 DI - Energy meter
Eastron SDM230-Modbus
Eastron SDM230-Modbus (two-tariff SDM230-2T protocol) single-phase two-module DIN-rail meter, protocol V1.1.
Also known as: SDM230Modbus, SDM230-2T, SDM230-M - Energy meter
Eastron SDM630-DI
Eastron SDM630-DI three-phase DIN-rail meter (100 A direct, two digital inputs, RS485 Modbus RTU), manual V1.02.
Also known as: SDM630 DI - Energy meter
Eastron SDM630-Modbus
Eastron SDM630Modbus three-phase DIN-rail meter, protocol implementation V1.8 as published by Eastron Europe.
Also known as: SDM630Modbus, SDM630 Modbus V2, SDM630-Modbus V2 - Energy meter
Eastron SDM630MCT
Eastron SDM630MCT three-phase CT-connected DIN-rail meter with RS485 Modbus RTU, protocol implementation V1.7.
Also known as: SDM630 MCT
Other power & energy meters register maps
- Sensor (ultrasonic gas flowmeter)
Endress+Hauser Proline Prosonic Flow G 500 ultrasonic gas flowmeter (Modbus RS485)
Prosonic Flow G 500 with the Modbus RS485 communication option, parameter description GP01133D/06/EN/02.24-00.
Also known as: Prosonic Flow G 500 - Energy meter (DIN-rail, single-phase)
IME Conto D1 single-phase energy meter (CE111)
IME Conto D1 single-phase meter, code CE111, per protocol PR133 (2025-02-24).
Also known as: CE111, Conto D1 - Power meter (DIN-rail)
IME Nemo D4-Le with Rogowski coil input (KRNEMOD4)
IME Nemo D4-Le for Rogowski coils, code KRNEMOD4, per protocol PR140 (software 1.01).
Also known as: KRNEMOD4 - Energy meter
inepro Metering PRO380-Eichrecht three-phase energy meter
PRO380-Eichrecht direct-connected 3x230/400 V, 40 A meter (MID + German MessEV calibration law, for EV chargers), user manual version 1.45, September 2025.
Also known as: PRO380 Eichrecht, PRO380-E, inepro PRO380 Eichrecht - Power meter (power quality analyser)
Janitza UMG 512-PRO power quality analyser (Modbus RTU / Modbus TCP)
UMG 512-PRO power quality analyser, per address list 1.054.016.3.k (08/2023).
Also known as: UMG512-PRO, UMG 512, UMG512, UMG 512 PRO, Janitza UMG512-PRO - Power meter (power analyser)
Janitza UMG 96RM-E power analyser (Ethernet, Modbus TCP / RTU)
UMG 96RM-E from firmware 3.01 / hardware release 104, per address list 1.040.085.8.n (06/2024).
Also known as: UMG96RM-E, UMG 96 RM-E, UMG96RME, Janitza UMG96RM-E
All power & energy meters Modbus register maps →
Source: Eastron SDM120Modbus Smart Meter Modbus Protocol Implementation V2.4 · V2.4. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.