Energy meter · Modbus register map

Eastron SDM120-Modbus Modbus register map

Updated 17 November 2026

Short answer

The SDM120-Modbus is a one-module single-phase DIN-rail kWh meter with an RS485 Modbus RTU port. All measurements are IEEE-754 floats in input register pairs read with function 04: voltage, current, powers, power factor, frequency, import/export energy and demand. A handful of holding registers set the address, baud, parity, pulse output and how total energy is summed.

This page lists 28 Modbus registers for the Eastron SDM120-Modbus — 7 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Eastron’s own free documentation (linked below) and checked against it.

Manufacturer
Eastron
Model
SDM120-Modbus
Equipment type
Energy meter
Registers
28 (7 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
2400 baud, 8N1
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
ABCD high word first (big-endian)
Also known as
SDM120M, SDM120Modbus, SDM120-M
Source document
Eastron SDM120Modbus Smart Meter Modbus Protocol Implementation V2.4 · V2.4
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Eastron SDM120-Modbus

Integration in brief

Read input registers with function 04 in two-register pairs; each value is an IEEE-754 float, high word first. Voltage is at 0x0000, current at 0x0006, active power at 0x000C and import kWh at 0x0048.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 0VoltageFLOAT32 ABCDVoltageRead
IR 6CurrentFLOAT32 ABCDCurrentRead
IR 12Active powerFLOAT32 ABCDActive powerRead
IR 30Power factorFLOAT32 ABCDPower factorRead
IR 70FrequencyFLOAT32 ABCDFrequencyRead
IR 72Import active energyFLOAT32 ABCDImport kWhRead
IR 342Total active energyFLOAT32 ABCDTotal kWhRead

Enable Modbus control & writes

Modbus RTU is always available on the RS485 terminals.

Byte order & addressing

Network setup

Watch out for

Eastron SDM120-Modbus Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

28 of 28 shown
Eastron SDM120-Modbus Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR0doc 30001VoltageFLOAT32ABCDVRead
IR6doc 30007CurrentFLOAT32ABCDARead
IR12doc 30013Active powerFLOAT32ABCDWRead
IR18doc 30019Apparent powerFLOAT32ABCDVARead
IR24doc 30025Reactive powerFLOAT32ABCDVArRead
IR30doc 30031Power factorFLOAT32ABCDRead
IR70doc 30071FrequencyFLOAT32ABCDHzRead
IR72doc 30073Import active energyFLOAT32ABCDkWhRead
IR74doc 30075Export active energyFLOAT32ABCDkWhRead
IR76doc 30077Import reactive energyFLOAT32ABCDkVArhRead
IR78doc 30079Export reactive energyFLOAT32ABCDkVArhRead
IR84doc 30085Total active power demandFLOAT32ABCDWRead
IR86doc 30087Max total active power demandFLOAT32ABCDWRead
IR88doc 30089Import active power demandFLOAT32ABCDWRead
IR90doc 30091Max import active power demandFLOAT32ABCDWRead
IR92doc 30093Export active power demandFLOAT32ABCDWRead
IR94doc 30095Max export active power demandFLOAT32ABCDWRead
IR258doc 30259Current demandFLOAT32ABCDARead
IR264doc 30265Max current demandFLOAT32ABCDARead
IR342doc 30343Total active energyPer the Measurement mode setting (default import + export).FLOAT32ABCDkWhRead
IR344doc 30345Total reactive energyFLOAT32ABCDkVArhRead
HR12doc 40013Relay pulse width60, 100 or 200 ms (default 100).FLOAT32ABCDmsRead/write
HR18doc 40019Network parity / stop bitsTakes effect after restart.FLOAT32ABCDRead/write0 = No parity, 1 stop bit (default); 1 = Even parity, 1 stop bit; 2 = Odd parity, 1 stop bit; 3 = No parity, 2 stop bits
HR20doc 40021Meter ID (Modbus address)1-247, default 1.FLOAT32ABCDRead/write
HR28doc 40029Baud rateFLOAT32ABCDRead/write0 = 2400 (default); 1 = 4800; 2 = 9600; 5 = 1200
HR86doc 40087Pulse 1 output modeEnergy quantity driving the pulse output.FLOAT32ABCDRead/write1 = Import active energy; 2 = Import + export active energy; 4 = Export active energy (default); 5 = Import reactive energy; 6 = Import + export reactive energy; 8 = Export reactive energy
HR63760doc 463761Pulse 1 output constantUINT16Read/write0 = 0.001 kWh/imp (default); 1 = 0.01 kWh/imp; 2 = 0.1 kWh/imp; 3 = 1 kWh/imp
HR63776doc 463777Measurement modeHow the total energy registers are calculated.UINT16Read/write1 = Total = import; 2 = Total = import + export (default); 3 = Total = import - export

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Eastron SDM120-Modbus

What Modbus registers does the Eastron SDM120-Modbus have?

This map lists 28 registers: 21 input registers, 7 holding registers. 7 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Eastron SDM120-Modbus Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are printed 30001/40001 style (six-digit 46xxxx for the F9xx block) next to the hex start address sent on the wire, e.g. 30007 = 0x0006 and 463777 = 0xF920. Wire address = printed number minus 30001, 40001 or 400001.

What byte order does the Eastron SDM120-Modbus use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Eastron SDM120-Modbus?

Start with IR 0 Voltage (Voltage); IR 6 Current (Current); IR 12 Active power (Active power); IR 30 Power factor (Power factor); IR 70 Frequency (Frequency); IR 72 Import active energy (Import kWh); IR 342 Total active energy (Total kWh).

How do I enable Modbus control of the Eastron SDM120-Modbus?

Modbus RTU is always available on the RS485 terminals.

Where is the official Eastron SDM120-Modbus Modbus documentation?

The source is Eastron SDM120Modbus Smart Meter Modbus Protocol Implementation V2.4 (V2.4), published free by Eastron at https://res.cloudinary.com/fastron-electronics/image/upload/v1625456706/Eastron%20Europe/SDM120-MODBUS_Protocol.pdf.

More Eastron Modbus register maps

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: Eastron SDM120Modbus Smart Meter Modbus Protocol Implementation V2.4 · V2.4. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.