Energy meter (DIN-rail, single-phase) · Modbus register map
IME Conto D1 single-phase energy meter (CE111) Modbus register map
Updated 17 November 2026
The Conto D1 is a one-module single-phase energy meter with an RS-485 Modbus/JBUS port. Its map is short: voltage, current, frequency and powers as scaled 16-bit words, two 32-bit energy totals, and the baud rate and node address.
This page lists 10 Modbus registers for the IME Conto D1 single-phase energy meter (CE111) — 2 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from IME’s own free documentation (linked below) and checked against it.
- Manufacturer
- IME
- Model
- Conto D1 single-phase energy meter (CE111)
- Equipment type
- Energy meter (DIN-rail, single-phase)
- Registers
- 10 (2 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- hexadecimal, 0-based
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- CE111, Conto D1
Integration notes: IME Conto D1 single-phase energy meter (CE111)
Read 6 holding registers from 0x00 (function 03) for V, A, Hz and powers, then 2 from 0x07 for active energy and 2 from 0x11 for reactive energy.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 0 | Voltage | UINT16 | Voltage | Read |
| HR 1 | Current | UINT16 | Current | Read |
| HR 3 | Active power | UINT16 | Active power | Read |
| HR 7 | Total active energy | UINT32 ABCD | Active energy | Read |
| HR 17 | Total reactive energy | UINT32 ABCD | Reactive energy | Read |
Enable Modbus control & writes
Set node address and baud rate on the meter or through 0x2A/0x2B.
Byte order & addressing
- A request may ask for at most 14 bytes of data (7 registers).
- Only functions 03 and 0x10 are supported.
Network setup
- Baud rate choices are 1200, 2400, 4800 and 9600; slave response time is at least 20 ms.
Watch out for
- Energy registers count in tens of Wh/varh.
IME Conto D1 single-phase energy meter (CE111) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 0x00 | Voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 1doc 0x01 | Current | UINT16 | × 0.1 | A | Read | |||
| HR | 2doc 0x02 | Frequency | UINT16 | × 0.01 | Hz | Read | |||
| HR | 3doc 0x03 | Active power | UINT16 | W | Read | ||||
| HR | 4doc 0x04 | Reactive power | UINT16 | var | Read | ||||
| HR | 5doc 0x05 | Apparent power | UINT16 | VA | Read | ||||
| HR | 7doc 0x07 | Total active energy | Counts in steps of 10 Wh. | UINT32 | ABCD | × 10 | Wh | Read | |
| HR | 17doc 0x11 | Total reactive energy | Counts in steps of 10 varh. | UINT32 | ABCD | × 10 | varh | Read | |
| HR | 42doc 0x2A | Baud rate | UINT16 | Read/write | 1 = 1200; 2 = 2400; 3 = 4800; 4 = 9600 | ||||
| HR | 43doc 0x2B | Node address | 1-247. | UINT16 | Read/write |
Notes on this map
- Double words are sent most significant word first, as stated in the data format section with a worked example.
- Scaling is taken from the printed formats: xxx,x V and A (tenths), xx,xx Hz (hundredths), energy 'Wh * 10' and 'varh * 10'.
- Left out: 0x06 power factor, whose unit and access columns are blank ('-').
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the IME Conto D1 single-phase energy meter (CE111)
What Modbus registers does the IME Conto D1 single-phase energy meter (CE111) have?
This map lists 10 registers: 10 holding registers. 2 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the IME Conto D1 single-phase energy meter (CE111) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Addresses are the hex word addresses sent as 'first WORD address' in the request, so 0x07 is wire address 7.
What byte order does the IME Conto D1 single-phase energy meter (CE111) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the IME Conto D1 single-phase energy meter (CE111)?
Start with HR 0 Voltage (Voltage); HR 1 Current (Current); HR 3 Active power (Active power); HR 7 Total active energy (Active energy); HR 17 Total reactive energy (Reactive energy).
How do I enable Modbus control of the IME Conto D1 single-phase energy meter (CE111)?
Set node address and baud rate on the meter or through 0x2A/0x2B.
Where is the official IME Conto D1 single-phase energy meter (CE111) Modbus documentation?
The source is Communication Modbus protocol PR133 - CE111 Conto D1 (PR133), revision 2025-02-24, published free by IME at https://assets.legrand.com/pim/NP-FT-GT/PR133FR.pdf.
More IME Modbus register maps
- Power meter
IME Nemo 72Le multifunction meter (MF724)
IME Nemo 72Le 72x72 panel meter MF724 with RS-485, per protocol PR141 (software 1.04).
Also known as: MF724, Nemo 72Le - Power meter
IME Nemo 96HD multifunction meter (MF96001 / MF96021)
IME Nemo 96HD panel meters MF96001 and MF96021 with an RS-485 module, per protocol PR106 (software 3.18).
Also known as: MF96001, MF96021, Nemo 96HD - Power meter
IME Nemo 96HDe multifunction meter (MF96E06)
IME Nemo 96HDe panel meter MF96E06 with RS-485, per protocol PR145.
Also known as: MF96E06, Nemo 96HDe - Power meter
IME Nemo 96HDLe multifunction meter (MF964)
IME Nemo 96HDLe panel meter MF964 with RS-485, per protocol PR130 (software 5.08).
Also known as: MF964, Nemo 96HDLe - Power meter
IME Nemo 96HDLe with Rogowski coil input (KRNEMOHD)
IME Nemo 96HDLe for Rogowski coils, code KRNEMOHD, per protocol PR139 (software 1.03).
Also known as: KRNEMOHD - Power meter (DIN-rail)
IME Nemo D4-Le multifunction meter (MFD44)
IME Nemo D4-Le DIN-rail meter MFD44 with RS-485, per protocol PR129 (software 2.05).
Also known as: MFD44, Nemo D4-Le - Power meter (DIN-rail)
IME Nemo D4-Le with Rogowski coil input (KRNEMOD4)
IME Nemo D4-Le for Rogowski coils, code KRNEMOD4, per protocol PR140 (software 1.01).
Also known as: KRNEMOD4
Other power & energy meters register maps
- Energy meter
inepro Metering PRO380-Eichrecht three-phase energy meter
PRO380-Eichrecht direct-connected 3x230/400 V, 40 A meter (MID + German MessEV calibration law, for EV chargers), user manual version 1.45, September 2025.
Also known as: PRO380 Eichrecht, PRO380-E, inepro PRO380 Eichrecht - Power meter (power quality analyser)
Janitza UMG 512-PRO power quality analyser (Modbus RTU / Modbus TCP)
UMG 512-PRO power quality analyser, per address list 1.054.016.3.k (08/2023).
Also known as: UMG512-PRO, UMG 512, UMG512, UMG 512 PRO, Janitza UMG512-PRO - Power meter (power analyser)
Janitza UMG 96RM-E power analyser (Ethernet, Modbus TCP / RTU)
UMG 96RM-E from firmware 3.01 / hardware release 104, per address list 1.040.085.8.n (06/2024).
Also known as: UMG96RM-E, UMG 96 RM-E, UMG96RME, Janitza UMG96RM-E - Energy meter
Legrand Energy meter 046 77 / 046 79 (2-module, RS485 Modbus)
Legrand 2-module DIN energy meters cat. no. 046 77 and 046 79 with RS485 (Modbus/JBUS), per the 'Communication protocol' sheet dated 01/07/2011.
Also known as: 04677, 04679, 046 77, 046 79, Legrand 4 677, Legrand 4 679 - Power meter (panel network parameter meter)
Lumel ND31LITE network parameter meter
Lumel ND31LITE panel meter with RS-485 Modbus RTU, per user manual ND31LITE-09.
Also known as: ND31LITE - Power meter
Northern Design Cube & Rail IP Meter (Ethernet, Modbus TCP)
V2 Ethernet versions of the Cube 350I, Cube 350V, Cube 400I and Cube 400V (label 'IP.Ver: V2') and the Rail 350V, per manual revision 1.07p (December 2013).
Also known as: Cube 350I IP, Cube 350V IP, Cube 400I IP, Cube 400V IP, Rail 350V IP, Cube IP meter V2
All power & energy meters Modbus register maps →
Source: Communication Modbus protocol PR133 - CE111 Conto D1 · PR133 · rev. 2025-02-24. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.