Power meter (panel network parameter meter) · Modbus register map
Lumel ND31LITE network parameter meter Modbus register map
Updated 17 November 2026
The ND31LITE is a 96x96 panel meter for 3- and 1-phase networks with RS-485 Modbus RTU. Its fixed measurement list is offered as floats in several areas; this map uses the 8000 area (two registers per value, high word first), plus comms settings, status words and the 32-bit energy counters from the 4000/4400 areas.
This page lists 66 Modbus registers for the Lumel ND31LITE network parameter meter — 4 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Lumel’s own free documentation (linked below) and checked against it.
- Manufacturer
- Lumel
- Model
- ND31LITE network parameter meter
- Equipment type
- Power meter (panel network parameter meter)
- Registers
- 66 (4 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 9600 baud, 8N2
- Documented addressing
- 0-based (the number printed is the address on the wire)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- ND31LITE
- Source document
- ND31LITE Network parameter meter - User manual · ND31LITE-09
Integration notes: Lumel ND31LITE network parameter meter
Read holding registers from 8000 (function 03 or 04): 3 x 9 per-phase values, then 3-phase totals at 8054-8066, frequency at 8072 and energies from 8090. Floats are high word first in the 8000 area.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 8000 | L1 phase voltage | FLOAT32 ABCD | L1 voltage | Read |
| HR 8002 | L1 phase current | FLOAT32 ABCD | L1 current | Read |
| HR 8058 | 3-phase active power (P1+P2+P3) | FLOAT32 ABCD | 3-phase active power | Read |
| HR 8064 | 3-phase power factor (P/S) | FLOAT32 ABCD | 3-phase power factor | Read |
| HR 8072 | Frequency | FLOAT32 ABCD | Frequency | Read |
| HR 4426 | Active import energy (counter) | UINT32 ABCD | Active import energy counter | Read |
| HR 4415 | Status 1 | BITMAP16 | Status 1 | Read |
Enable Modbus control & writes
Modbus RTU is always on; set address, mode and baud from the menu or registers 4100-4102, then write 1 to 4104.
Byte order & addressing
- The 6000 area is low word first and the 8000 area high word first.
- Powers are in W, var and VA.
Network setup
- Factory settings: address 1, 9600 baud, RTU 8N2.
Watch out for
- 7000-7118 is not a fixed map on this meter: it returns whatever was programmed in 4200-4259.
Lumel ND31LITE network parameter meter Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 4100 | Modbus address | UINT16 | Read/write | |||||
| HR | 4101 | Transmission mode | UINT16 | Read/write | 0 = 8N2; 1 = 8E1; 2 = 8O1; 3 = 8N1 | ||||
| HR | 4102 | Baud rate | UINT16 | Read/write | 0 = 4800; 1 = 9600; 2 = 19200; 3 = 38400; 4 = 57600; 5 = 115200 | ||||
| HR | 4104 | Apply transmission settings | Write 1 to make new address/mode/baud take effect. | UINT16 | Read/write | ||||
| HR | 4403 | Program version | UINT16 | × 0.01 | Read | ||||
| HR | 4415 | Status 1 | BITMAP16 | Read | bit 1 = RTC battery used up; bit 5 = Supervisory relay register error; bit 7 = Phase sequence error; bit 8 = Energy value error; bit 9 = Programmable readout group register error; bit 10 = Display screen register error; bit 11 = Configuration register error; bit 13 = Output not calibrated; bit 14 = Input not calibrated; bit 15 = FRAM memory damage | ||||
| HR | 4416 | Status 2 (alarms) | BITMAP16 | Read | bit 0 = Alarm 1 active; bit 4 = Alarm 1 signalled; bit 8 = Alarm 2 active; bit 12 = Alarm 2 signalled | ||||
| HR | 4426doc 4426-4427 | Active import energy (counter) | High register x 65536 + low register, in 0.01 units. | UINT32 | ABCD | × 0.01 | kWh | Read | |
| HR | 4428doc 4428-4429 | Active export energy (counter) | High register x 65536 + low register, in 0.01 units. | UINT32 | ABCD | × 0.01 | kWh | Read | |
| HR | 4430doc 4430-4431 | Reactive inductive energy (counter) | High register x 65536 + low register, in 0.01 units. | UINT32 | ABCD | × 0.01 | kvarh | Read | |
| HR | 4432doc 4432-4433 | Reactive capacitive energy (counter) | High register x 65536 + low register, in 0.01 units. | UINT32 | ABCD | × 0.01 | kvarh | Read | |
| HR | 4434doc 4434-4435 | Apparent energy (counter) | High register x 65536 + low register, in 0.01 units. | UINT32 | ABCD | × 0.01 | kVAh | Read | |
| HR | 8000doc 6000/8000 | L1 phase voltage | FLOAT32 | ABCD | V | Read | |||
| HR | 8002doc 6002/8002 | L1 phase current | FLOAT32 | ABCD | A | Read | |||
| HR | 8004doc 6004/8004 | L1 phase active power | FLOAT32 | ABCD | W | Read | |||
| HR | 8006doc 6006/8006 | L1 phase reactive power | FLOAT32 | ABCD | var | Read | |||
| HR | 8008doc 6008/8008 | L1 phase apparent power | FLOAT32 | ABCD | VA | Read | |||
| HR | 8010doc 6010/8010 | L1 power factor (P1/S1) | FLOAT32 | ABCD | Read | ||||
| HR | 8012doc 6012/8012 | L1 tg phi (Q1/P1) | FLOAT32 | ABCD | Read | ||||
| HR | 8014doc 6014/8014 | THD U1 | FLOAT32 | ABCD | % | Read | |||
| HR | 8016doc 6016/8016 | THD I1 | FLOAT32 | ABCD | % | Read | |||
| HR | 8018doc 6018/8018 | L2 phase voltage | FLOAT32 | ABCD | V | Read | |||
| HR | 8020doc 6020/8020 | L2 phase current | FLOAT32 | ABCD | A | Read | |||
| HR | 8022doc 6022/8022 | L2 phase active power | FLOAT32 | ABCD | W | Read | |||
| HR | 8024doc 6024/8024 | L2 phase reactive power | FLOAT32 | ABCD | var | Read | |||
| HR | 8026doc 6026/8026 | L2 phase apparent power | FLOAT32 | ABCD | VA | Read | |||
| HR | 8028doc 6028/8028 | L2 power factor (P2/S2) | FLOAT32 | ABCD | Read | ||||
| HR | 8030doc 6030/8030 | L2 tg phi (Q2/P2) | FLOAT32 | ABCD | Read | ||||
| HR | 8032doc 6032/8032 | THD U2 | FLOAT32 | ABCD | % | Read | |||
| HR | 8034doc 6034/8034 | THD I2 | FLOAT32 | ABCD | % | Read | |||
| HR | 8036doc 6036/8036 | L3 phase voltage | FLOAT32 | ABCD | V | Read | |||
| HR | 8038doc 6038/8038 | L3 phase current | FLOAT32 | ABCD | A | Read | |||
| HR | 8040doc 6040/8040 | L3 phase active power | FLOAT32 | ABCD | W | Read | |||
| HR | 8042doc 6042/8042 | L3 phase reactive power | FLOAT32 | ABCD | var | Read | |||
| HR | 8044doc 6044/8044 | L3 phase apparent power | FLOAT32 | ABCD | VA | Read | |||
| HR | 8046doc 6046/8046 | L3 power factor (P3/S3) | FLOAT32 | ABCD | Read | ||||
| HR | 8048doc 6048/8048 | L3 tg phi (Q3/P3) | FLOAT32 | ABCD | Read | ||||
| HR | 8050doc 6050/8050 | THD U3 | FLOAT32 | ABCD | % | Read | |||
| HR | 8052doc 6052/8052 | THD I3 | FLOAT32 | ABCD | % | Read | |||
| HR | 8054doc 6054/8054 | Mean 3-phase voltage | FLOAT32 | ABCD | V | Read | |||
| HR | 8056doc 6056/8056 | Mean 3-phase current | FLOAT32 | ABCD | A | Read | |||
| HR | 8058doc 6058/8058 | 3-phase active power (P1+P2+P3) | FLOAT32 | ABCD | W | Read | |||
| HR | 8060doc 6060/8060 | 3-phase reactive power (Q1+Q2+Q3) | FLOAT32 | ABCD | var | Read | |||
| HR | 8062doc 6062/8062 | 3-phase apparent power (S1+S2+S3) | FLOAT32 | ABCD | VA | Read | |||
| HR | 8064doc 6064/8064 | 3-phase power factor (P/S) | FLOAT32 | ABCD | Read | ||||
| HR | 8066doc 6066/8066 | Mean 3-phase tg phi (Q/P) | FLOAT32 | ABCD | Read | ||||
| HR | 8068doc 6068/8068 | Mean 3-phase THD U | FLOAT32 | ABCD | % | Read | |||
| HR | 8070doc 6070/8070 | THD I mean 3-phase | FLOAT32 | ABCD | % | Read | |||
| HR | 8072doc 6072/8072 | Frequency | Unit printed as 'f' in the table. | FLOAT32 | ABCD | Hz | Read | ||
| HR | 8074doc 6074/8074 | Phase-to-phase voltage L 1-2 | FLOAT32 | ABCD | V | Read | |||
| HR | 8076doc 6076/8076 | Phase-to-phase voltage L 2-3 | FLOAT32 | ABCD | V | Read | |||
| HR | 8078doc 6078/8078 | Phase-to-phase voltage L 3-1 | FLOAT32 | ABCD | V | Read | |||
| HR | 8080doc 6080/8080 | Mean phase-to-phase voltage | FLOAT32 | ABCD | V | Read | |||
| HR | 8082doc 6082/8082 | Active power averaged (P Demand) | FLOAT32 | ABCD | W | Read | |||
| HR | 8086doc 6086/8086 | Current averaged (I Demand) | FLOAT32 | ABCD | A | Read | |||
| HR | 8088doc 6088/8088 | Neutral wire current (calculated from vectors) | FLOAT32 | ABCD | A | Read | |||
| HR | 8090doc 6090/8090 | Active import energy overflows | Counts roll-overs of the next register (unit 100 MWh / 100 Mvarh / 100 MVAh). | FLOAT32 | ABCD | 100 MWh | Read | ||
| HR | 8092doc 6092/8092 | Active import energy | Counter up to 99999.99; add the overflow register for the full total. | FLOAT32 | ABCD | kWh | Read | ||
| HR | 8094doc 6094/8094 | Active export energy overflows | Counts roll-overs of the next register (unit 100 MWh / 100 Mvarh / 100 MVAh). | FLOAT32 | ABCD | 100 MWh | Read | ||
| HR | 8096doc 6096/8096 | Active export energy | Counter up to 99999.99; add the overflow register for the full total. | FLOAT32 | ABCD | kWh | Read | ||
| HR | 8098doc 6098/8098 | Reactive inductive energy overflows | Counts roll-overs of the next register (unit 100 MWh / 100 Mvarh / 100 MVAh). | FLOAT32 | ABCD | 100 Mvarh | Read | ||
| HR | 8100doc 6100/8100 | Reactive inductive energy | Counter up to 99999.99; add the overflow register for the full total. | FLOAT32 | ABCD | kvarh | Read | ||
| HR | 8102doc 6102/8102 | Reactive capacitive energy overflows | Counts roll-overs of the next register (unit 100 MWh / 100 Mvarh / 100 MVAh). | FLOAT32 | ABCD | 100 Mvarh | Read | ||
| HR | 8104doc 6104/8104 | Reactive capacitive energy | Counter up to 99999.99; add the overflow register for the full total. | FLOAT32 | ABCD | kvarh | Read | ||
| HR | 8106doc 6106/8106 | Apparent energy overflows | Counts roll-overs of the next register (unit 100 MWh / 100 Mvarh / 100 MVAh). | FLOAT32 | ABCD | 100 MVAh | Read | ||
| HR | 8108doc 6108/8108 | Apparent energy | Counter up to 99999.99; add the overflow register for the full total. | FLOAT32 | ABCD | kVAh | Read |
Notes on this map
- Byte order: the area table gives 8000-8970 as bytes 3-2-1-0 and 6000-6970 as 1-0-3-2. The example frames show that 3-2-1-0 means 41 20 00 00 for 10.0 (high word first) and 1-0-3-2 means 00 00 41 20, so the 8000 area is ABCD.
- The 7000/7200/7400 areas are a user-programmable group (set in 4200-4259) and are not listed.
- Energy counters 4426-4435 follow the manual's formula (high x 65536 + low) / 100.
- Left out: 8084 (printed as 'Reactive power averaged (S Demand)' with unit VA, which does not agree), time/date and status floats 8110-8128, the min/max area from 8136, and the alarm/display setup registers.
- Frequency (8072) is printed with unit 'f'; it is listed in Hz.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Lumel ND31LITE network parameter meter
What Modbus registers does the Lumel ND31LITE network parameter meter have?
This map lists 66 registers: 66 holding registers. 4 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Lumel ND31LITE network parameter meter Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Addresses are used as printed: the example frames read 7000 as 0x1B58, 6000 as 0x1770 and 4000 as 0x0FA0. Float registers show the table's 6xxx/8xxx pair in 'documented'; this map uses the 8xxx address.
What byte order does the Lumel ND31LITE network parameter meter use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Lumel ND31LITE network parameter meter?
Start with HR 8000 L1 phase voltage (L1 voltage); HR 8002 L1 phase current (L1 current); HR 8058 3-phase active power (P1+P2+P3) (3-phase active power); HR 8064 3-phase power factor (P/S) (3-phase power factor); HR 8072 Frequency (Frequency); HR 4426 Active import energy (counter) (Active import energy counter); HR 4415 Status 1 (Status 1).
How do I enable Modbus control of the Lumel ND31LITE network parameter meter?
Modbus RTU is always on; set address, mode and baud from the menu or registers 4100-4102, then write 1 to 4104.
Where is the official Lumel ND31LITE network parameter meter Modbus documentation?
The source is ND31LITE Network parameter meter - User manual (ND31LITE-09), published free by Lumel at https://www.lumel.com.pl/resources/Pliki%20do%20pobrania/ND31Lite/ND31LITE_user_manual.pdf.
More Lumel Modbus register maps
- Power meter (panel network parameter meter)
Lumel ND20 network parameter meter
Lumel ND20 panel meter per the ND20 user's manual; registers 4056-4061 need firmware 1.09 or later and are not listed here.
Also known as: ND20, ND20-xxxx - Power meter (panel network parameter meter)
Lumel ND20LITE network parameter meter
Lumel ND20LITE 96x96 panel meter with RS-485 Modbus RTU (not the ND20 or ND20CT, which have their own maps).
Also known as: ND20LITE - Energy meter (DIN-rail, single-phase, MID)
Lumel NMID08 / NMID09 / NMID10 single-phase energy meter
Modbus RTU versions of the NMID08 (1/5 A CT), NMID09 (100 mA CT) and NMID10 (100 A direct) meters; the LITE and MBUS versions have no Modbus port.
Also known as: NMID08, NMID09, NMID10 - Energy meter (DIN-rail, single-phase, MID)
Lumel NMID11 / NMID12 / NMID13 single-phase energy meter
Modbus RTU versions of the NMID11, NMID12 and NMID13 meters (NMID11/NMID13 are the CT-connected models); the LITE and MBUS versions have no Modbus port.
Also known as: NMID11, NMID12, NMID13 - Energy meter (DIN-rail, three-phase, MID)
Lumel NMID31 / NMID32 three-phase energy meter
Lumel NMID31 and NMID32 DIN-rail single/three-phase energy meters with RS-485 Modbus RTU, per their interface manual.
Also known as: NMID31, NMID32 - Energy meter (DIN-rail, single-phase)
Lumel NR10PLUS single-phase energy meter
Lumel NR10PLUS single-phase DIN-rail meter with RS-485 Modbus RTU, per its user manual.
Also known as: NR10PLUS - Power meter (DIN-rail network meter)
Lumel NR30 DIN-rail power network meter
Lumel NR30 rail-mounted 3-phase meter (RS-485 Modbus RTU; Ethernet versions also offer Modbus TCP), per manual NR30-09E_R1.
Also known as: NR30
Other power & energy meters register maps
- Power meter
Northern Design Cube & Rail IP Meter (Ethernet, Modbus TCP)
V2 Ethernet versions of the Cube 350I, Cube 350V, Cube 400I and Cube 400V (label 'IP.Ver: V2') and the Rail 350V, per manual revision 1.07p (December 2013).
Also known as: Cube 350I IP, Cube 350V IP, Cube 400I IP, Cube 400V IP, Rail 350V IP, Cube IP meter V2 - Energy meter
Panasonic KW8M Eco-POWER METER
Panasonic KW8M AKW8111 and AKW8111H (logging/demand version) with Modbus RTU selected, manual ARCT1F440E-8.
Also known as: AKW8111, AKW8111H - Energy meter (DC)
Rishabh Instruments RISH DC2111 MOD single-channel DC energy meter
Rishabh RISH DC2111 MOD single-channel DC energy meters with RS-485 Modbus, per interface definition DMAN-00IM-1669 Rev. D (08/25).
Also known as: RISH DC2111 MOD, DC2111 - Energy meter
Rishabh Instruments RISH ED21XX / EC21XX / ER21XX single-phase energy meters
Rishabh RISH ED21XX (direct), EC21XX (CT) and ER21XX (RJ12 CT) single-phase meters in their Modbus versions, per operating manual DMAN-00IM-1073 Rev. M.
Also known as: RISH ED21X1, RISH EC21X1, RISH ER21X1, RISH ED21XX, RISH EC21XX, RISH ER21XX - Power meter
Rishabh Instruments RISH LM 1340 multifunction meter
Rishabh RISH LM 1340 panel multifunction instruments with RS-485 Modbus, per interface definition DMAN-00IM-0923 Rev. D (03/2026).
Also known as: RISH LM 1340, LM1340 - Power meter (power factor controller)
Rishabh Instruments RISH PFC 96 / PFC 144 automatic power factor controller
Rishabh RISH PFC 96 and PFC 144 automatic power factor (APFC) controllers with RS-485 Modbus RTU, per interface definition version D (12/18).
Also known as: RISH PFC 96, RISH PFC 144, PFC96, PFC144, RISH PFC-12, APFC
All power & energy meters Modbus register maps →
Source: ND31LITE Network parameter meter - User manual · ND31LITE-09. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.