  4. NR10PLUS single-phase energy meter

Energy meter (DIN-rail, single-phase) · Modbus register map

Lumel NR10PLUS single-phase energy meter Modbus register map

Updated 17 November 2026

Short answer

Single-phase DIN-rail energy counter with pulse outputs and an RS-485 Modbus RTU port. Values are IEEE-754 floats in two registers, high word first, readable as input registers (3X) and mirrored as holding registers (4X). The map covers instantaneous values, demands, import/export, tariff and partial energies, run hours and status values.

This page lists 102 Modbus registers for the Lumel NR10PLUS single-phase energy meter — 0 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Lumel’s own free documentation (linked below) and checked against it.

Manufacturer
Lumel
Model
NR10PLUS single-phase energy meter
Equipment type
Energy meter (DIN-rail, single-phase)
Registers
102 (0 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
9600 baud, 8N1
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
ABCD high word first (big-endian)
Also known as
NR10PLUS
Source document
NR10PLUS Single Phase AC Energy Meter - User Manual
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Lumel NR10PLUS single-phase energy meter

Integration in brief

Poll input registers 0x00-0x1F with function 04 for voltage, current, powers and power factor, then 0x6C and 0x70 for import/export energy. Each value is a float in two registers, high word first.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 0VoltageFLOAT32 ABCDVoltageRead
IR 6CurrentFLOAT32 ABCDCurrentRead
IR 12Active PowerFLOAT32 ABCDActive powerRead
IR 30Power FactorFLOAT32 ABCDPower factorRead
IR 70FrequencyFLOAT32 ABCDFrequencyRead
IR 108Active Import EnergyFLOAT32 ABCDActive import energyRead
IR 112Active Export EnergyFLOAT32 ABCDActive export energyRead

Enable Modbus control & writes

Modbus is always on in the Modbus versions; set address, baud rate and parity/stop bits in the front-panel setup menu.

Byte order & addressing

Network setup

Watch out for

Lumel NR10PLUS single-phase energy meter Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

102 of 102 shown
Lumel NR10PLUS single-phase energy meter Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR0doc 30001 (0x0000)VoltageFLOAT32ABCDVRead
IR6doc 30007 (0x0006)CurrentFLOAT32ABCDARead
IR12doc 30013 (0x000C)Active PowerFLOAT32ABCDWRead
IR18doc 30019 (0x0012)Apparent PowerFLOAT32ABCDVARead
IR24doc 30025 (0x0018)Reactive PowerFLOAT32ABCDVArRead
IR30doc 30031 (0x001E)Power FactorFLOAT32ABCDRead
IR36doc 30037 (0x0024)AngleFLOAT32ABCD°Read
IR70doc 30071 (0x0046)FrequencyFLOAT32ABCDHzRead
IR72doc 30073 (0x0048)W Import DemandFLOAT32ABCDWRead
IR74doc 30075 (0x004A)W Import Max DemandFLOAT32ABCDWRead
IR76doc 30077 (0x004C)W Export DemandFLOAT32ABCDWRead
IR78doc 30079 (0x004E)W Exp. Max DemandFLOAT32ABCDWRead
IR80doc 30081 (0x0050)var Imp. DemandFLOAT32ABCDVArRead
IR82doc 30083 (0x0052)var Imp. Max DemandFLOAT32ABCDVArRead
IR86doc 30087 (0x0056)var Exp. Max DemandFLOAT32ABCDVArRead
IR88doc 30089 (0x0058)va Imp. DemandFLOAT32ABCDVARead
IR90doc 30091 (0x005A)va Imp. Max DemandFLOAT32ABCDVARead
IR92doc 30093 (0x005C)va Exp. DemandFLOAT32ABCDVARead
IR94doc 30095 (0x005E)va Exp. Max DemandFLOAT32ABCDVARead
IR96doc 30097 (0x0060)Current Imp. DemandFLOAT32ABCDARead
IR98doc 30099 (0x0062)Current Imp Max. DemandFLOAT32ABCDARead
IR100doc 30101 (0x0064)Current Exp. DemandFLOAT32ABCDARead
IR102doc 30103 (0x0066)Current Exp. Max DemandFLOAT32ABCDARead
IR104doc 30105 (0x0068)Watt R FundamentalFLOAT32ABCDWRead
IR106doc 30107 (0x006A)Active Import Energy Overflow CountTimes the matching energy register rolled past 99999.999.FLOAT32ABCDRead
IR108doc 30109 (0x006C)Active Import EnergyFLOAT32ABCDkWhRead
IR110doc 30111 (0x006E)Active Export Energy Overflow CountTimes the matching energy register rolled past 99999.999.FLOAT32ABCDRead
IR112doc 30113 (0x0070)Active Export EnergyFLOAT32ABCDkWhRead
IR114doc 30115 (0x0072)Reactive Import Energy Overflow CountTimes the matching energy register rolled past 99999.999.FLOAT32ABCDRead
IR116doc 30117 (0x0074)Reactive Import EnergyFLOAT32ABCDkVArhRead
IR118doc 30119 (0x0076)Reactive Export Energy Overflow CountTimes the matching energy register rolled past 99999.999.FLOAT32ABCDRead
IR120doc 30121 (0x0078)Reactive Export EnergyFLOAT32ABCDkVArhRead
IR122doc 30123 (0x007A)Apparent Import Energy Overflow CountTimes the matching energy register rolled past 99999.999.FLOAT32ABCDRead
IR124doc 30125 (0x007C)Apparent Import EnergyFLOAT32ABCDkVAhRead
IR126doc 30127 (0x007E)Apparent Export Energy Overflow CountTimes the matching energy register rolled past 99999.999.FLOAT32ABCDRead
IR128doc 30129 (0x0080)Apparent Export EnergyFLOAT32ABCDkVAhRead
IR130doc 30131 (0x0082)Active Energy Overflow CountTimes the matching energy register rolled past 99999.999.FLOAT32ABCDRead
IR132doc 30133 (0x0084)Active EnergyFLOAT32ABCDkWhRead
IR134doc 30135 (0x0086)Reactive Energy Overflow CountTimes the matching energy register rolled past 99999.999.FLOAT32ABCDRead
IR136doc 30137 (0x0088)Reactive EnergyFLOAT32ABCDkVArhRead
IR138doc 30139 (0x008A)Apparent Energy Overflow CountTimes the matching energy register rolled past 99999.999.FLOAT32ABCDRead
IR140doc 30141 (0x008C)Apparent EnergyFLOAT32ABCDkVAhRead
IR142doc 30143 (0x008E)T1 Active Import Energy Overflow CountTimes the matching energy register rolled past 99999.999.FLOAT32ABCDRead
IR144doc 30145 (0x0090)T1 Active Import EnergyFLOAT32ABCDkWhRead
IR146doc 30147 (0x0092)T1 Active Export Energy Overflow CountTimes the matching energy register rolled past 99999.999.FLOAT32ABCDRead
IR148doc 30149 (0x0094)T1 Active Export EnergyFLOAT32ABCDkWhRead
IR150doc 30151 (0x0096)T1 Reactive Import Energy Overflow CountTimes the matching energy register rolled past 99999.999.FLOAT32ABCDRead
IR152doc 30153 (0x0098)T1 Reactive Import EnergyFLOAT32ABCDkVArhRead
IR154doc 30155 (0x009A)T1 Reactive Export Energy Overflow CountTimes the matching energy register rolled past 99999.999.FLOAT32ABCDRead
IR156doc 30157 (0x009C)T1 Reactive Export EnergyFLOAT32ABCDkVArhRead
IR158doc 30159 (0x009E)T1 Apparent Import Energy Overflow CountTimes the matching energy register rolled past 99999.999.FLOAT32ABCDRead
IR160doc 30161 (0x00A0)T1 Apparent Import EnergyFLOAT32ABCDkVAhRead
IR162doc 30163 (0x00A2)T1 Apparent Export Energy Overflow CountTimes the matching energy register rolled past 99999.999.FLOAT32ABCDRead
IR164doc 30165 (0x00A4)T1 Apparent Export EnergyFLOAT32ABCDkVAhRead
IR166doc 30167 (0x00A6)T1 Active Energy Overflow CountTimes the matching energy register rolled past 99999.999.FLOAT32ABCDRead
IR168doc 30169 (0x00A8)T1 Active EnergyFLOAT32ABCDkWhRead
IR170doc 30171 (0x00AA)T1 Reactive Energy Overflow CountTimes the matching energy register rolled past 99999.999.FLOAT32ABCDRead
IR172doc 30173 (0x00AC)T1 Reactive EnergyFLOAT32ABCDkVArhRead
IR174doc 30175 (0x00AE)T1 Apparent Energy Overflow CountTimes the matching energy register rolled past 99999.999.FLOAT32ABCDRead
IR176doc 30177 (0x00B0)T1 Apparent EnergyFLOAT32ABCDkVAhRead
IR178doc 30179 (0x00B2)T2 Active Import Energy Overflow CountTimes the matching energy register rolled past 99999.999.FLOAT32ABCDRead
IR180doc 30181 (0x00B4)T2 Active Import EnergyFLOAT32ABCDkWhRead
IR182doc 30183 (0x00B6)T2 Active Export Energy Overflow CountTimes the matching energy register rolled past 99999.999.FLOAT32ABCDRead
IR184doc 30185 (0x00B8)T2 Active Export EnergyFLOAT32ABCDkWhRead
IR186doc 30187 (0x00BA)T2 Reactive Import Energy Overflow CountTimes the matching energy register rolled past 99999.999.FLOAT32ABCDRead
IR188doc 30189 (0x00BC)T2 Reactive Import EnergyFLOAT32ABCDkVArhRead
IR190doc 30191 (0x00BE)T2 Reactive Export Energy Overflow CountTimes the matching energy register rolled past 99999.999.FLOAT32ABCDRead
IR192doc 30193 (0x00C0)T2 Reactive Export EnergyFLOAT32ABCDkVArhRead
IR194doc 30195 (0x00C2)T2 Apparent Import Energy Overflow CountTimes the matching energy register rolled past 99999.999.FLOAT32ABCDRead
IR196doc 30197 (0x00C4)T2 Apparent Import EnergyFLOAT32ABCDkVAhRead
IR198doc 30199 (0x00C6)T2 Apparent Export Energy Overflow CountTimes the matching energy register rolled past 99999.999.FLOAT32ABCDRead
IR200doc 30201 (0x00C8)T2 Apparent Export EnergyFLOAT32ABCDkVAhRead
IR202doc 30203 (0x00CA)T2 Active Energy Overflow CountTimes the matching energy register rolled past 99999.999.FLOAT32ABCDRead
IR204doc 30205 (0x00CC)T2 Active EnergyFLOAT32ABCDkWhRead
IR206doc 30207 (0x00CE)T2 Reactive Energy Overflow CountTimes the matching energy register rolled past 99999.999.FLOAT32ABCDRead
IR208doc 30209 (0x00D0)T2 Reactive EnergyFLOAT32ABCDkVArhRead
IR210doc 30211 (0x00D2)T2 Apparent Energy Overflow CountTimes the matching energy register rolled past 99999.999.FLOAT32ABCDRead
IR212doc 30213 (0x00D4)T2 Apparent EnergyFLOAT32ABCDkVAhRead
IR214doc 30215 (0x00D6)Partial Active Import Energy Overflow CountTimes the matching energy register rolled past 99999.999.FLOAT32ABCDRead
IR216doc 30217 (0x00D8)Partial Active Import EnergyFLOAT32ABCDkWhRead
IR218doc 30219 (0x00DA)Partial Active Export Energy Overflow CountTimes the matching energy register rolled past 99999.999.FLOAT32ABCDRead
IR220doc 30221 (0x00DC)Partial Active Export EnergyFLOAT32ABCDkWhRead
IR222doc 30223 (0x00DE)Partial Reactive Import Energy Overflow CountTimes the matching energy register rolled past 99999.999.FLOAT32ABCDRead
IR224doc 30225 (0x00E0)Partial Reactive Import EnergyFLOAT32ABCDkVArhRead
IR226doc 30227 (0x00E2)partial Reactive Export Energy Overflow CountTimes the matching energy register rolled past 99999.999.FLOAT32ABCDRead
IR228doc 30229 (0x00E4)Partial Reactive Export EnergyFLOAT32ABCDkVArhRead
IR230doc 30231 (0x00E6)Partial Apparent Import Energy Overflow CountTimes the matching energy register rolled past 99999.999.FLOAT32ABCDRead
IR232doc 30233 (0x00E8)Partial Apparent Import EnergyFLOAT32ABCDkVAhRead
IR234doc 30235 (0x00EA)Partial Apparent Export Energy Overflow CountTimes the matching energy register rolled past 99999.999.FLOAT32ABCDRead
IR236doc 30237 (0x00EC)Partial Apparent Export EnergyFLOAT32ABCDkVAhRead
IR238doc 30239 (0x00EE)Partial Active Energy Overflow CountTimes the matching energy register rolled past 99999.999.FLOAT32ABCDRead
IR240doc 30241 (0x00F0)Partial Active EnergyFLOAT32ABCDkWhRead
IR242doc 30243 (0x00F2)Partial Reactive Energy Overflow CountTimes the matching energy register rolled past 99999.999.FLOAT32ABCDRead
IR244doc 30245 (0x00F4)Partial Reactive EnergyFLOAT32ABCDkVArhRead
IR246doc 30247 (0x00F6)Partial Apparent Energy Overflow CountTimes the matching energy register rolled past 99999.999.FLOAT32ABCDRead
IR248doc 30249 (0x00F8)Partial Apparent EnergyFLOAT32ABCDkVAhRead
IR250doc 30251 (0x00FA)Run HourFLOAT32ABCDhRead
IR252doc 30253 (0x00FC)On HourFLOAT32ABCDhRead
IR254doc 30255 (0x00FE)No of InterruptsFLOAT32ABCDRead
IR256doc 30257 (0x0100)Impulse RateFLOAT32ABCDRead
IR260doc 30261 (0x0104)Tariff StatusFLOAT32ABCDRead
IR262doc 30263 (0x0106)Current DirectionFLOAT32ABCDRead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Lumel NR10PLUS single-phase energy meter

What Modbus registers does the Lumel NR10PLUS single-phase energy meter have?

This map lists 102 registers: 102 input registers. 0 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Lumel NR10PLUS single-phase energy meter Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The measurement table prints Modicon numbers (30001) next to the hex start address (00 00). The hex column is the wire address, so 30001 is register 0 and power factor 30031 is 0x1E.

What byte order does the Lumel NR10PLUS single-phase energy meter use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Lumel NR10PLUS single-phase energy meter?

Start with IR 0 Voltage (Voltage); IR 6 Current (Current); IR 12 Active Power (Active power); IR 30 Power Factor (Power factor); IR 70 Frequency (Frequency); IR 108 Active Import Energy (Active import energy); IR 112 Active Export Energy (Active export energy).

How do I enable Modbus control of the Lumel NR10PLUS single-phase energy meter?

Modbus is always on in the Modbus versions; set address, baud rate and parity/stop bits in the front-panel setup menu.

Where is the official Lumel NR10PLUS single-phase energy meter Modbus documentation?

The source is NR10PLUS Single Phase AC Energy Meter - User Manual, published free by Lumel at https://www.lumel.com.pl/resources/Pliki%20do%20pobrania/NR10PLUS/NR10PLUS_user_manual.pdf.